Installation of TSX ETY 4102/PORT/5102 Modules. Schneider Electric TSX 57/PCX 57 Implementation
Reklama
Reklama
11.4
TSX ETY 4102/PORT TSX ETY 5102
Installation of TSX ETY 4102/PORT/5102 Modules
At a Glance
Aim of this
Section
What's in this
Section?
This Section deals with the installation of TSX ETY 4102/PORT and TSX ETY 5102 modules in a PLC.
This section contains the following topics:
Topic
At a Glance
Selecting the Type of Processor
Wiring/Unwiring with Power Switched on
Page
TSX DM 57 xx
279
TSX ETY 4102/PORT TSX ETY 5102
At a Glance
General
TSX ETY 4102/PORT/5102 communication modules are mounted in the rack slot of a Premium/Atrium PLC station. They can be installed in any available slot (except in an offset X Bus rack), on condition that the supply constraints of the rack are observed (see
Electrical Characteristics, p. 287).
280
TSX DM 57 xx
TSX ETY 4102/PORT TSX ETY 5102
Selecting the Type of Processor
Selection Guide
Selecting the processor to control the PLC station will depend on the number of network connections required.
Processors Number of network connections
1
Number of ETY 4102/PORT/5102 per station (*)
1
TSX 57 P 1../2..
PCX 57 253
TSX P 57 3...
PCX 57 353
TSX P 57 4..
3 3
4 4
(*) on condition of a consumption report on the 5V, compatible with the supply selected.
Compatibility
Depending on the software version of the processor, all or some of the functions of the TSK-ETY 4102/PORT/5102 modules will be available. The table below gives the compatibility rules.
Software version of the processor
VL < 3.3
Supported functions
Does not accept the modules TSX
ETY4•••/5•••
-
Type to be configured in
PL7
3.3 £ VL < 5.1
TSX ETY 410 or 5101
VL 5.1
Functions limited to those of the
TSX ETY 410/5101 modules
Supports all the functions of the
TSX ETY 4102/PORT/5102 modules
TSX ETY 4102/PORT or
5102
TSX DM 57 xx
281
TSX ETY 4102/PORT TSX ETY 5102
Wiring/Unwiring with Power Switched on
The Module
The link
The TSX ETY 4102/PORT/5102 modules can be wired or unwired when switched on without disrupting the operation of the station.
The modules do not have an internal RAM backup memory function: this will be erased when power is switched off.
The modules reset when switched on. A communication break can be expected during these interventions.
The 10/100baseT interface RJ45 connector can be connected or disconnected when power is on. A communication break can therefore be expected in the application in progress.
282
TSX DM 57 xx