Display, Diagnostics. Schneider Electric TSX 57/PCX 57 Implementation
Iklan
Iklan
TSX ETY 4102/PORT TSX ETY 5102
11.6
Display, Diagnostics
Display panel, Diagnostics
General
The display panel conforms to the Premium standard
RUN
STS
RX
ERR
ADR
TX
l l l
The COL, RX and TX LEDs are managed by the line’s electronics; they indicate:
COL: a collision.
RX: a reception
TX: a transmission.
Diagnostics
Meaning of the diagnostics LEDs:
RUN ERR STS COL TX
O
O
O
O
P
O
O
O
P
P
O
P
O
O
P ns ns ns ns ns ns ns ns ns ns
RX
ns ns ns ns ns
Meaning
No supply to module.
Module running self-test.
Module ready.
Module not operational.
Software operation error. Temporary state causing module reinitialization.
O
P
F
O
P, F ns
P ns ns ns ns ns
Module not configured or configuration in progress.
Module configured, operational.
ns ns F ns ns ns Module configured. Diagnostics according to how the LEDs are flashing: l l
2 flashes: module has no MAC address.
3 flashes: ETHERNET cable not connected on the module or Hub side l
4 flashes: the module IP address is duplicated by another IP address on the network. Conflicting remote device flashing in the same way.
l
5 flashes: module configured as a BOOTP client and is waiting for a BOOTP server response.
P = Permanently on, F = flashing, O = Off, ns = not significant
TSX DM 57 xx
285
TSX ETY 4102/PORT TSX ETY 5102
RUN ERR STS COL TX
P
P
O
O
P
P
O
O
F
O
RX
O
F
Meaning
ETHERNET communication sending.
ETHERNET communication receiving.
P
P
O
O
P
P
O
F
F
F
F
O
ETHERNET communication sending/receiving.
Module has detected collision.
P = Permanently on, F = flashing, O = Off, ns = not significant