Configure Module 2 - Output Parameters (2-OP). RED LION CONTROLS P48, T48
Quảng cáo
Quảng cáo
Configure Module 2 - Output Parameters (2-OP)
Display
CYCt
OPAC
OPLO
OPHI
OPFL
OPdP
Parameter
Time
Proportioning
Cycle Time
Output Control
Action
Output Power
Lower Limit
(Not used in
Manual Control)
Output Power
Upper Limit
(Not used in
Manual Control)
Sensor Fail
Power Level
(Not used in
Manual Control)
Output Power
Dampening
(filtering) Time
Range and Units
(Factory Setting)
0 to 250 seconds
(2)
Description/
Comments
0 turns O1 off. Set to zero for Linear DC output control. Not used for ON/OFF Control.
For both PID & ON/OFF control.
drct - cooling rEv - heating
(rEv)
0% to 100%, O1
(0)
-100% to 100%,
O1 & O2
(-100)
0% to 100%, O1
(100)
-100% to 100%
O1 & O2
(100)
0% to 100%, O1
(0)
-100% to 100%
O1 & O2
(0)
0 to 250 seconds
(3) T48
(1) P48
Set OPLO < OPHI
Negative % is only valid for O2 cooling control.
Set OPHI > OPLO
Negative % is only valid for O2 cooling control.
Select a level to safely control the process in the event of input sensor failure. T48 only.
0 = off (no dampening)
Set in range of 1/50 to
1/10 of integral time.
Adjusted by Auto-Tune.
Display
CHYS tcOd
ANtP
ANAS
ANUt
ANLO
ANHI
Parameter
ON/OFF Control
Hysteresis
Auto-tune
Dampening Code
Main Linear DC
Output Range *
Main Linear DC
Output Source *
Main Linear DC
Output Update *
Main Linear DC
Output Low Scaling
Value *
Main Linear DC
Output High
Scaling Value *
Range and Units
(Factory Setting)
1 to 250
(2) T48
(0.2) P48
0 to 2
(0)
0 to 10 V
0 to 20 mA
4 to 20 mA
(4 to 20 mA)
OP
InP
SP
(OP)
0 to 250 secs
(0)
-999 to 9999
(0.0)
-999 to 9999
(100.0)
Description/
Comments
For O1 ON/OFF
Control. Change to
Factory Setting prior to Auto-Tune.
0 = fastest response
2 = slowest response
Set linear output range jumper to match.
SP = Active Setpoint
0 = Update rate of 0.1
sec.
Value depends on
ANAS assignment.
Value depends on
ANAS assignment.
* Model Number Dependent