Via the parameter
Active data set
249 the data set currently selected can be read out.
Active data set
249 states the activated data set with the value 1, 2, 3 or 4. This is independent of whether the data set change-over has been done via control inputs or via
Data set selection
414.
10.2.2
Control via contacts
In the operation mode control via contacts (
Local/Remote
412 = 0) the frequency inverter is controlled via the contact inputs S2IND to S6IND. The meaning of these inputs can be seen from the operating instructions. The control word in PZD1 is not relevant for this operation mode.
State machine:
The values contained in the states report the feedback about the state word (Bit 0 to
Bit 6) in PZD1.
Power on
Initialisation
Ready
0x23
Quitt fault
Fault
0x08
20
Enable on
Enable off
Operation enabled
0x27
from any state
Bit No.
0
1
Control word
Name
-
-
State word
Bit No.
Name
0 Ready to switch on
1 Ready
2 Operation enabled
3
4
5
6
7
8
9
10
11
-
-
-
-
-
-
-
-
-
12
3 Fault
Voltage -inhibited
5 Quick-stop
6 Switch on inhibit
7 Warning
8 -
9 Remote
10 Reference value reached
11 Limit value reached
IW1 Î chapter 10.2.6
14
15 - 15
20
Warning 2
06/05
06/05
advertisement
Related manuals
advertisement
Table of contents
- 6 General safety and application information
- 6 General information
- 6 Proper use
- 7 Transport and storage
- 7 Handling and positioning
- 7 Electrical connection
- 7 Operation information
- 7 Maintenance and service
- 8 Introduction
- 9 Assembly of the Profibus-DP communication module CM-PDP
- 10 Socket occupancy/bus termination/line
- 11 Baud rate setting/line length
- 11 Setting station address
- 11 Setting PPO type
- 12 Configuration process on the DP master
- 13 Commands SYNC / FREEZE
- 13 Available objects / scanning times
- 15 10 Handling of the objects
- 15 Communication channel
- 16 10.1.1 Order identification
- 16 10.1.2 Reply identification
- 16 10.1.3 Fault messages
- 17 10.1.4 Parameters, data set selection and cyclic writing
- 18 10.1.5 Sequence of communication
- 19 10.1.6 Examples of communication
- 21 Process data channel PZD1/PZD
- 21 10.2.1 PZD1, control word / state word
- 22 10.2.2 Control via contacts
- 23 10.2.3 Control via state machine
- 26 Behavior in quick stop
- 26 Behavior in transition
- 27 10.2.4 Control via remote contacts
- 29 10.2.5 PZD2, reference value / actual value
- 30 10.2.6 Variable actual value reporting via PZD2 in PPO1 / PPO
- 32 10.2.7 Actual value report PZD2 to PZD6 in PPO2 / PPO
- 32 10.2.8 PPO-Out data as global sources
- 37 Actual value display of Profibus data
- 39 11 Parameter list
- 39 Actual value
- 39 Parameter
- 40 12 Annex
- 40 Warning messages
- 40 Fault messages
- 41 GSD File – VEC_0696.GSD