A7AX.book 23 ページ 2005年9月22日 木曜日 午後7時40分
PARAMETERS
4.2.5
16 bit digital torque command (FR-A700 series only)
Parameter
304
447
448
804
Name
Selection of digital input and analog input compensation enable/disable
Digital torque command bias
Digital torque command gain
Torque command source selection
Setting Range
0 to 4, 10 to 14, 9999
0 to 400%
0 to 400%, 9999
0, 1, 3 to 6
Initial Value Increments
9999
0
150%
0
1
1%
1%
1
Digital torque command can be given under torque control using the FR-A7AX .
A digital command using the FR-A7AX can be given when "4 (12 bit)" or "14 (16 bit)" is set in Pr.304 and "4" is set in Pr.804 Torque command source selection.
Pr.804
parameter setting
0
1
Description
Torque command by terminal 1 analog input
Torque command by parameter setting
Setting value of Pr.805 or Pr.806 (-400% to 400%)
Remarks
Refer to the inverter manual for details.
3
4
5
6
Torque command by CC-Link communication (FR-A7NC)
12 bit digital input (FR-A7AX)
16 bit digital input (FR-A7AX)
Refer to the inverter manual for details.
Torque command by CC-Link communication (FR-A7NC)
Refer to the instruction manual of the
FR-A7NC for details.
When "4" is set in Pr. 304
When "14" is set in Pr. 304
Refer to the instruction manual of the
FR-A7NC for details.
23
4
A7AX.book 24 ページ 2005年9月22日 木曜日 午後7時40分
PARAMETERS
The input signal uses the last 15 (11) bits as torque command and the most significant bit as sign.
When 16 bit is selected
Bit15 Bit0 sign bit
0: positive, 1: negative
0 to 7FFF
H
or 0 to 190
H
(400)
REMARKS
The digital torque command is input only by binary input.
24
A7AX.book 25 ページ 2005年9月22日 木曜日 午後7時40分
PARAMETERS
z Input method of torque command
Torque command may be input in either of the following two ways:
(1) Method to define the torque command value for the input command by setting the torque command value when the input signal is 0 and plus side torque command value when the input signal is 7FFF
H
(7FF
H
) as shown in the graph
Set the torque command value when the input signal is "0" in Pr.447 and the torque command value when the input signal is "7FFF
H
(7FF
H
) in Pr.448 .
Torque command value
Pr.448
150%
Initial value
7FFF
H
(7FF
H
)
0
Pr.447
7FFF
H
(7FF
H
)
Digital input signal
Most significant bit = 1
-150%
Most significant bit = 0
25
4
A7AX.book 26 ページ 2005年9月22日 木曜日 午後7時40分
PARAMETERS
(2) Method to directly input the torque command value as numeral value in digital
When "9999" is set in Pr.448, the input signal is considered as a torque command value.
Even if a value higher than 190H (400) is input, the torque command value is clamped at 400%.
Torque command value
400%
7FFF
H
(7FF
H
)
190
H
(400)
Most significant bit = 1
0
190
H
(400)
-400%
Most significant bit = 0
7FFF
H
(7FF
H
)
Digital input signal
26
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 Unpacking and Product Confirmation
- 5 Packing confirmation
- 6 Parts
- 7 Specifications
- 8 Pre-Installation Instructions
- 9 Installation Procedure
- 11 Wiring
- 13 Connection Diagram
- 15 Internal Block Diagram
- 16 Terminals
- 17 Code Input Example
- 18 Parameter List
- 20 Parameter Setting
- 20 Selection of input method (Pr. 304)
- 22 Data read timing signal on-off selection (Pr. 305)
- 24 Bias and gain adjustment (Pr. 300, Pr. 301, Pr. 302, Pr. 303)
- 26 Digital input increments selection (Pr. 329)
- 27 16 bit digital torque command (FR-A700 series only)
- 31 Instructions