INSTALLATION COMMISSIONING & OPERATION
6.5 Fire Fan Module BRD25FCB
The Fire Fan Module has four ( 4 ) separate fan controls each having an On, Auto and Off function switch and a set of three (3) monitoring LED’s. The LED’s indicate the status of the equipment eg. Run, Fault or
Stop. The two ( 2 ) arrow head keys are used to step up and / or down through the three ( 3 ) conditions. A slip in label can also be inserted into the hinged cover for identification purposes.
A loop driven version is also available (159-0105 )
Note#: As per AS 1668.1 1991, Clause 14.17.4 lettering on any of the slip in labels must be at least
5mm in height.
Quiescent Current: 13.5mA
AC
TIV
ATE
D
Module & PCB Securing Tabs
( Top & Bottom )
PCB
Cle ar P lasti c C lip In
La be l
PLA
NT
TR
IP
WINDOWS
FOR SLIP
IN LABELS
WINDOWS
In
C
N
1
C
N
2
Out
K2 Termination Link
Top Module &
PCB Securing Clips
ON
Address
Switch
Set to 1
RE
SE
T
CN1: Communications & 27V IN from CN2 off the previous
Front Panel Card or CN20 on the Main Control Board
Slip In
Label
CN2: Communications & 27V OUT to Next Front Panel Card.
If Unsed the Termination Link Must be Inserted.
Clip On
Plastic Surround
( Push down here and pull out to remove and insert labels )
Lettering on slip in labels must be at least 5mm in height.
Bottom Module &
PCB Securing Clips
Figure 32: Fire Fan Module Front Panel Figure 33: Fire Fan Module PCB Layout
6.6 Fan Termination Board BRD25FTB
The Fan Termination Board interfaces between the Fire Fan Module and the plant/equipment it controls via the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable monitoring of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop conditions of that equipment. Monitoring is programmed in the Function Menu for a 3, 4 or 5 Wire Start / Stop, Run,
Fault, Stop & Common functions. The inputs are protected by way of resetable transorbs and resistive / capacitive networks.
Connectors
CN5 Is used for factory programming only and may not be available on all boards.
Terminal Blocks
TB2
– 5 Are used to connect the fan control and monitoring wiring to the board.
RUN
FAN 1
START STOP RUN
FAN 1
FLT STOP COM
TB2
FAN 2
START STOP RUN
FAN 2
FLT STOP COM
TB3
FAN 3
START STOP RUN
FAN 3
FLT STOP COM
TB4
FAN 4
START STOP RUN
FAN 4
FLT STOP COM
TB5 RUN
FAN MONITORING
STOP
STOP
CN1
CN2
CN3
RS485 Control in from CN2 of Previous
Board or CN21 of the Main Control Board
START
FLT
COM
FAN CONTROL
SOLID STATE OR
RELAY INTERFACE
CN4
LK1
EOL Termination
RS485 Control Out to Next Board or Link 1 EOL is Applied
27V Out to Next Board if Applicable
O N
1 2 3 4
SW1
Address SW
STOP, START, RUN = 3 WIRE
STOP, START, RUN,
STOP = 4 WIRE
STOP, START, RUN, STOP,
FAULT = 5 WIRE
+24V O/Ps INPUTS 1, 2 & 3 0V
27V In from the Brigade Broard or CN4 of the Previous Board
1 2 3 4 5 6
Figure 34: Fan Termination Board Layout and Typical I/O Wiring
Cabling from FACP to Plant / Equipment
TB 2, 3, 4 or 5
Page 28
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 6 Non Disclosure Agreement
- 7 About This Manual
- 7 Introduction
- 7 General Requirements
- 7 References
- 7 Symbols
- 8 System Overview
- 10 Description
- 12 Placing The Basic System Into Operation
- 12 Unpacking
- 12 Anti-Static Precautions
- 12 Working On The System
- 12 The Cabinet
- 12 Mounting The Cabinet
- 13 Operational Parameters
- 13 Cabling Recommendations
- 14 Power Supplies and AC Mains Installation
- 16 Current Limiter, Fuse Board
- 17 Brigade / PSU Monitor Board
- 19 Brigade / PSU Monitor Board & Battery Connections
- 19 Brigade / PSU Monitor Board Auxiliary 27 Volt Power
- 19 Brigade / PSU Monitor Board DBA / MCP & Door Switch Connections
- 19 Brigade PSU Monitor Board ASE Fault Brigade Box Connection
- 20 Connecting a Bell / Sounder to the Brigade / PSU Monitor Board
- 20 Warning System Connections
- 20 Brigade / PSU Monitor Board Relay Output Connections
- 21 Main Board BRD85MBA
- 22 Front Panel Board
- 24 Main CPU BRD85CPU
- 25 Slave CPU
- 26 RS232 Modem / Programming / Debug Interfacing
- 26 Ancillary Services
- 27 Conventional Zone Board
- 28 Addressable Loop Termination Board
- 29 Boards
- 31 16/16 Input / Output Board
- 32 16 Way Input Board
- 32 Serial Relay Board
- 33 Fire Fan Module BRD25FCB
- 33 Fan Termination Board BRD25FTB
- 34 Zone & General Indicator Card
- 36 Printer
- 36 Indicators and Buttons
- 37 Maintenance
- 38 Printer Connections and Jumpering
- 38 Printer 5 Volt Power Supply ( 302-713 )
- 39 Expanding the System Through Networking
- 39 Communications: Controller Interface Card
- 39 Communications: Network Interface Card
- 40 Expansion Board ( 302-688 )
- 40 Expansion Controller
- 41 Networking
- 43 Liquid Crystal Display Repeater Panel
- 44 Terminal
- 44 Operation
- 44 Access levels
- 45 Specifications
- 45 Overview
- 46 Operational & Key Features
- 46 Mechanical
- 47 Installation & Cabling
- 48 Setting the Address
- 49 Terminal Controller Configuration in ConfigManager
- 49 Terminal Reporting Parameters in ConfigManager
- 50 Terminal Controls
- 52 Terminal Indicators
- 54 LCD Screen Format
- 55 Trouble Shooting Chart
- 56 Agent Release Control
- 56 Operation
- 59 Controlled Access
- 60 Local Control Station
- 63 Agent Release Termination Board BRD25ATB
- 64 Interface Wiring
- 66 Warning Signs
- 68 Occupant Warning Systems
- 73 Brigade Devices
- 73 ASE ( Vic Metro ) Brigade Box
- 73 Brigade Box ( Deltec WA, SA, TAS,QLD )
- 74 Operation
- 74 The Control Panel
- 77 Function And Menu
- 77 The Default LCD Display
- 77 Accessing Functions and Menus
- 77 Function Menu and Access Levels
- 77 Forgotten Passwords
- 78 The Main Menu
- 78 Status Menu
- 80 Testing Menu
- 80 Alarm Test
- 80 Fault Test
- 80 Lamp Test
- 81 Main Functions
- 81 Setting the Function Date Facility
- 81 Setting the Function Time Facility
- 81 Setting the Function Daynight Facility
- 81 Function Logs Facility
- 82 The Function Test Facility
- 83 Function Manual I/O Control
- 83 Function Access ( Level II ) / Passwords ( Level III )
- 84 Function Programming
- 84 Conventional Zone Programming
- 85 Device Programming
- 85 Input Programming
- 85 Output Programming
- 86 Manual Control Point ( MCP )
- 86 Sub Address
- 86 Watchdog
- 86 Self Learn
- 86 Extra Devices Detected
- 87 Mismatch Detected
- 87 Incoming Fire Alarm Signal
- 89 Accessing a Loop, Sensor or Zone
- 89 List of Compatible Devices
- 89 Short Circuit Isolation
- 90 Compatible Devices
- 92 Certification Information
- 93 Statement of Compliance
- 95 Installation Details
- 96 Commissioning Test Report
- 97 Procedure
- 97 System Information
- 101 Troubleshooting Chart
- 102 Address Setting
- 103 Battery Capacity Calculation
- 109 Glossary of Terms
- 110 Definitions
- 111 Quick Reference Guides