advertisement
FIREFINDER
TM
INSTALLATION COMMISSIONING & OPERATION
11 Occupant Warning Systems
The EV20, EV40, EV60 and EV120 are compact single zone occupant warning devices that when triggered produce Alert and Evacuation signals to meet the requirements of AS1670.4.
EV20
At the heart of an EV20 single zone occupant warning system is a microprocessor that generates the alert and evacuation signals, controls timing and the input / output.
If an FACP warning system input is received when the rotary switch is in the AUTO position the EV20 will begin to output the “Alert” signal for a duration determined by the setting of the 4 way DIL switch SW1. The set duration is termed the changeover timeout and ranges from 0 seconds to a maximum of 300 seconds.
If the time out is set to 0 seconds then the alert signal is bypassed and the evacuation signal commences immediately. The operator can manually stop the sequence by turning the rotary switch to the ISOLATE position.
IC4 performs the task of an audio amplifier with TX1 providing the impedance matching to a 100 volt speaker line. The alert and evacuation signal output Stages are set by adjusting RV1 and RV2 respectively.
Short or open circuit speaker faults are detected by the fault monitoring circuitry and will result in the illumination of the FAULT indicator mounted on the front panel control module.
Public Address
A microphone and pre-amplifier (Order Code 222-0007) is used to provide the public address capabilities.
EV20 Verbal Messaging
An optional verbal messaging PCB (Order Code 222-0026) is available and is mounted directly onto the main board.
EV40
At the heart of an EV40 single zone occupant warning system is a microprocessor that generates the alert and evacuation signals, controls timing and the input / output.
If an FACP warning system input is received when the rotary switch is in the AUTO position the EV40 will begin to output the
“Alert” signal for a duration determined by the setting of the 4 way DIL switch. The set duration is termed the changeover timeout and ranges from 0 seconds to a maximum of 540 seconds. If the time out is set to 0 seconds then the alert signal is bypassed and the evacuation signal commences immediately. The operator can manually stop the signal sequence by turning the rotary switch to the
ISOLATE position.
Amplifier 1 & 2 provides 40watts of audio output at 8 ohms which feeds TX1 to provide the impedance matching to a 100 volt speaker line. The
“ALERT” and “EVAC” Stage controls adjust the output Stage of each set of signals.
Short or open circuit speaker faults are detected by the fault monitoring circuitry and will result in the illumination of the FAULT indicator mounted on the front panel control module and “SPEAKER SHORT”
(red) or “SPEAKER OPEN” (yellow) LEDs on the main board.
Public Address
A microphone (Order Code 294-0001) is used to provide the public address capabilities.
EV40 Verbal Messaging
An optional verbal messaging PCB (Order Code 222-0013) is available and is mounted directly onto the main board.
EV20 / 40 Verbal Message
Alert / Evacuation
– “Emergency Evacuate Now”
Page 63
FIREFINDER
Control Module
TM
INSTALLATION COMMISSIONING & OPERATION
When the control switch is in;
AUTOMATIC - occupant warning signals and if applicable verbal messaging is under the control of the microprocessor and outputted to the speaker system when it receives a “warning system” signal from the
FACP.
ISOLATE
– the occupant warning system is isolated from the FACP “warning system” signal and even if the signal is present there will be no output.
PUBLIC ADDRESS
– the occupant warning system can be used locally as a PA system.
MANUAL EVACUATION
– the occupant warning signal/s will be transmitted over the system.
Indicators
LINE FAULT
- In the event of an open or short circuit speaker line the LINE FAULT indicator (yellow) will be illuminated
ISOLATED
- the LED will be illuminated (yellow) when the warning system is isolated
Signal Structures
ALERT SIGNAL
Australian AS1670.4 Alert Signal
ON
420Hz 420Hz
420Hz
AS1670.4:
420Hz pulsed on for 0.625 seconds at 1.25 second intervals
0.625
sec
0.625
sec
OFF
0 1
2
Time in seconds
3
4
EVACUATION SIGNAL
Australian AS1670.4 Evacuate Signal
1200Hz
OFF
0.5
0.5
0.5
sec sec sec
0.5
0.5
sec sec
500Hz
1.5
secs
0.5
sec
AS1670.4:
0.5 second sweep signal 500-1200
Hz for 2.5 seconds at 4 second intervals
0 1
2
Time in seconds
3
4
EVACUATE SIGNAL WITH VERBAL MESSAGE
1200Hz
"EMERGENCY
EVACUATE NOW"
500Hz
0.5
0.5
0.5
0.5
0.5
1.5
0.5
OFF sec sec sec sec sec secs sec
0 1 2
Time in seconds
3 4
Figure 74: Alert & Evacuation Signal Structures
Page 64
FIREFINDER
EV20 Cabling
TM
INSTALLATION COMMISSIONING & OPERATION
+27V
COMMON
TB2
3
4
WARNING
SYSTEM
TB5
2
1
EV20 222-0008
TB2
2
1
TB2
4
3
TB1
2
1
-
+
EV20
OUTPUT
47K IS PLACED ACROSS LAST
SPEAKER ON THE CIRCUIT
PSU
BRIGADE
MONITOR
BOARD
IF THE PA OPTION IS NOT
USED INSERT LINK ACROSS
PINS 1 & 2 OF CN3
EVACUATION
SYSTEM
CN1
5
4
COMMON 3
ISOLATE
MANUAL EVAC
2
1
CN3
302-604A
GND
OUT
IN
3
2
1
RED
PINK
BLACK
GREEN
ORANGE
3
EV20 CONTROL
1
2
3
4
5
CN3
1
CN1 2
3
CN2
302-718
MIC PRE-AMP
TB1
1 CN1
1
2
3
3
1
2
CN2 3
4
5
302-475
+27V
Figure 75: Typical EV20 & PA Wiring
Note: “WARNING SYSTEM” is a monitored O/P. The EOL is on board the EV20 and is effectively made to be O/C (at TB1) during an EV20 fault condition. This produces the fault condition at the FACP.
OCCUPANT WARNING SYSTEM
TX1
RV1
TX2
TB1
TB1 *
Shield
Signal
(Red)
RL1
LINE FAULT
AUTOMATIC
ISOLATED
PUBLIC ADDRESS
MANUAL EVACUATION
LINE FAULT
D0 9 0 PHILIPS
C N1
+
FRONT
PANEL
Shield
MIC I/P
C N3
PUBLIC ADDRESS
PRE-AMP
SHEILD
2 CORE AUDIO TERMINATED ONE END
WITH 3 WAY PANDUIT CONNECTOR
- + + -
C N2
1
4
5
6
3
B
2
1
A
12
11
C
10
9
7
8
SW1
ISOLATE
FRONT PANEL PCB
1
1
261-0005 CABLE ASSEMBLEY
2 CORE AUDIO FITTED WITH
3 WAY PANDUIT CONNECTORS
FACP CONNECTIONS
+27
VDC
RED .75mm (500mm)
BLACK .75mm (500mm)
TB2
WARNING
SYSTEM
FireFinder
BRIGADE
PSU MON
BOARD
GREY .22mm (500mm)
WHITE .22mm (500mm)
TB5
RES1093
47K
-
+27V
-0V
+
O N
EXAMPLE OF
SETTING - 30SECS
( FACTORY SETTING "0" )
AND I/P SET TO
NON-LATCHING
SW1 TIME
OUT TABLE
SW 1 2 3
1 2 3 4
4
0 ( EVAC ONLY ) LATCHING
3 0
6 0
120
180
240
N
D
S
S
E
C
O
300
ALERT ONLY NO CHANGE OVER
NON-LATCHING
SW1/4 MUST BE SET
TO NON-LATCHING.
TB1
5 WAY PANDUIT
EVAC/ALERT
CONTROL
F1 1A
C N1
+
RV 1
TONE
VOLUME
+
C N3
RV 2
+
VOICE
VOLUME
+ + +
+
AUDIO
NOTE: IF THE P.A. OPTION
IS NOT FITTED. FIT LINK ACROSS
CN3 PINS 1(IN) AND PIN 2(OUT)
+
+
TO VERBAL MESSAGE
BOARD
AMPAC
S T D MS G 3
E VACMESSAGE
C N2
5 WAY CABLE - MESSAGE
CONTROL 260-0027
OPTIONAL VERBAL
MESSAGE BOARD
ORDER No 222-0013
VERBAL MESSAGE BOARD IS
MOUNTED ON STANDOFFS
ONTO THE MAIN BOARD IN THE
POSITION INDICATED ABOVE
Figure 76: EV20 Wiring to Control Module, FACP Cabling and Time Out Table
Page 65
FIREFINDER
EV40 Cabling
TM
INSTALLATION COMMISSIONING & OPERATION
8 OHM
A B
AL
PA1
E V
TB5 o o o o o o o o o o
SPARE
JUMPERS
TB3
CCT FLT
RELAY
SPEAKER OPEN
(YELLOW)
OF F
4 3 1
COM FLT
PA2
C ON T
N OCF o o
O N
4321
ON
TIMER
MESSAGE BRD
MOUNTING SOCKETS
MICRO
EVACTRON
EV40
TB4
40W LINE
TRANSFORMER
22K
100V IN
100V IN
R E D
MONITORED SPK OUT
MONITORED SPK OUT
F USE
3A
M/MAN o o
PLUG IN VERBAL MESSAGE BOARD
( OPTIONAL ORDER SEPARATELY )
TB2
PAU P EV
AMP2
AMP1
SPEAKER SHORT (RED)
ALM
VOLUME CONTROLS P W R O U T
P W R
CN1
ALERT EVAC
IN
MIC1
TB1
MIC2
TERMINATION
BOARD
TB1
+
-
+
P W R
-
WARN
+
+ 27VDC IN
- 27VDC IN
FAULT
FAULT
AL IND (0v SWITCH)
EV IND (0v SWITCH)
OUT CON (0v SWITCH)
+ 27VDC
G N D
ALARM
AL
E V
AUTO
G N D
PA1
M 1
G N D
M2
PA2
NOTE 1: "WARNING SYSTEM" IS A MONITORED FACP O/P. THE EOL
IS ONBOARD THE EV40 AND IS EFFECTIVELY MADE TO BE O/C
(AT TB1) DURING AN EV40 FAULT CONDITION. THIS PRODUCES
THE FAULT INDICATION AT THE FACP
NOTE 2: IF NO SPEAKER MONITORING IS REQUIRED
PLACE A 22K RESISTOR ACROSS TB4
TERMINALS 1 & 2 TO DISABLE OPEN CIRCUIT LED
PINK
ORANGE
WHITE
BLACK
GREEN
BLACK
PINK
R E D
OCCUPANT WARNING SYSTEM
LINE FAULT
AUTOMATIC
ISOLATED
PUBLIC ADDRESS
MANUAL EVACUATION
FRONT PANEL
o o o o o o o o o o o
CN3
CN1
o o o o o o o o o o o
CN2
302-718
STATUS CONTROL
D090 PHILIPS
MIC - OPTIONAL
ORDER SEPARATELY
MIC
VERBAL
MESSAGE
BOARD
SYSTEM POWER
BLACK 0V
TB2
+27VDC
NOTE:
Ensure F7 is 3Amps
FireFinder
BRIGADE
PSU MON
BOARD
WARNING SYSTEM
RED +27V
GREY
-
WHITE
+
TB5
-
+
WARNING
SYSTEM
MONITORED
Figure 77: Typical EV40 Wiring to Control Module and FACP
SECONDS
TIME OUT TABLE
AND EXAMPLE OF
30SECS SETTING
(FACTORY SETTING
"0" SECONDS)
4
3
2
1
O N
O N
O N
O N
OFF
OFF
OFF
OFF
EVAC / ALERT = SEQUENCE GOES
STRAIGHT TO EVAC OR ALERT TONES
SW 1 - 4 = ON
SW 1 - 4 = OFF
Figure 78: EV40 Time Out Table
Jumper settings
PEV: - PA + Evac
– must be inserted when a selector switch is connected.
PAU: - PA in Auto
– if inserted allows Mic 1 input (hand held microphone) to be used in “Auto”
(with no FACP alarm ) and paging in “Evac” mode.
PA2 CONT: - PA2 Control
– if inserted allows the PA2 input to also switch the Control Output.
M2 1milli volt: - if inserted enables a 1mV microphone input for Mic 2, not inserted enables the input for 100mV line level ( background music etc.)
Page 66
FIREFINDER
TM
11.1 EV60 / 120
INSTALLATION COMMISSIONING & OPERATION
The EV60 & 120 are essentially an EV20 MPU and driver but with 60 and 120 watt output amplifiers powered from a Current Limit Fuse Board.
Figure 79: EV60 EV120
11.2 EV3000
Relay Board Operation
One of the relays on the 8 Way Relay Board will be programmed to operate on “Alarm”. The subsequent shorting of the 10K
Ω EOL initiates the Alert / Evac sequence
10K EOL
TO CN4
OR CN5
OR THE
1/0 BOARD
302-6720
C N1
TB1
N/0 C
N/C
O/P 2
N/0 C N/C
O/P 3
N/0 C N/C
O/P 4
N/0 C N/C
O/P 5
N/0 C N/C
O/P 6
N/0 C N/C
O/P 7
N/0 C N/C
O/P 8
N/0 C N/C
TB2
O/P 1
RL9
C
N/O
N/C
RL10
N/O
C
N/C
RL11
N/O
C
N/C
RL12
N/O
C
N/C
RL13
N/O
C
N/C
RL14
N/O
C
N/C
RL15
N/O
C
N/C
RL16
N/O
C
N/C
RL1
RL2 RL3 RL4 RL5 RL6 RL7 RL8
RL9
C
N/O
N/C
RL1
5 Amp Version
Legend
1 Amp Version
8 WAY RELAY BOARD
FIREFINDER
EV3000
F.I.P. INPUT
BOARD
TB5
INPUT
COMMON
INPUT
1 6 1 5 1 4 1 3
TB3
INPUT
1 2 11 1 0 9
TB4
TB2
IC37
IC39
8
INPUT
7 6 5
TB1
4
INPUT
3 2 1
IC38
CN1
RS485 IN
CN2
RS485 OUT
CN4 POWER OUT
SW1
IC40
IC41
IC36 IC27 IC18 IC9
Figure 80: FACP / EV3000 Cabling Using Relay1 and I/P 1
HLI Interface Operation
The EV3000 Occupant Warning and Intercommunications System ( OWIS ) main central processing unit communicates via a RS485 bus with a Controller Interface Card ( CIC ) in an FACP.
A fault in the EV3000 will be indicated by the Master Control Panel which in turn initiates, via the Common
Fault Relay Board and Brigade PSU Monitor Board, a Warning System Fault indication on the FACP.
CH15
D13
MAIN CONTROL BOARD (BRD85MBA)
CN16
CN8
MODEM
U15
CN11 a b c a b c
CN2
4
CN13
CN2
3
CN2
CN14
CN15
2
CN17
CN2
CN20
CH16
RN20 RN17
CN18
FireFinder
C N 1
CONTROLLER
I/F CARD
302-7250
CN3
OUT
TB2
TB3
+27V
0 V
C O M
T X D
RX D
RT S
CT S
T RX+
TRX-
S CRN
TB1
CN1
CN3
CN12
CN13 CN14 CN15
CN16
CN17
CN26
API-422B
CN4
U13
U14
U11
1
BRIGADE PSU
MONITOR
BOARD
CN5
CN7
CN6
OWIS EV3000 MAIN CENTRAL
PROCESSING UNIT
+
TIME OUT
SELECTION
SWITCH
CH8 CH8 CH6 CH8
U10
CN10
CN2
EXPANSION PANEL
CN3
EXPANSION LEDS
CN4
FRONT PANEL
CN6
CN1
CN5
PRINTER
CN7
CH2
TB5 1/2 (+/-)
WARN SYS
CN8
CN9
CN11
CN10
COMMON FAULT RELAY BRD
RESET
S W 2
EV3000
10K
302-673
Note: The common fault methodology shown here is only used in a combination EV3000 / FireFinder Panel.
CN18
Figure 81: HLI & Common Fault Cabling To & From the FACP and EV3000
EV3000 MASTER
CONTROL PANEL
Page 67
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 6 Non Disclosure Agreement
- 7 About This Manual
- 7 Introduction
- 7 General Requirements
- 7 References
- 7 Symbols
- 8 System Overview
- 10 Description
- 12 Placing The Basic System Into Operation
- 12 Unpacking
- 12 Anti-Static Precautions
- 12 Working On The System
- 12 The Cabinet
- 12 Mounting The Cabinet
- 13 Operational Parameters
- 13 Cabling Recommendations
- 14 Power Supplies and AC Mains Installation
- 16 Current Limiter, Fuse Board
- 17 Brigade / PSU Monitor Board
- 19 Brigade / PSU Monitor Board & Battery Connections
- 19 Brigade / PSU Monitor Board Auxiliary 27 Volt Power
- 19 Brigade / PSU Monitor Board DBA / MCP & Door Switch Connections
- 19 Brigade PSU Monitor Board ASE Fault Brigade Box Connection
- 20 Connecting a Bell / Sounder to the Brigade / PSU Monitor Board
- 20 Warning System Connections
- 20 Brigade / PSU Monitor Board Relay Output Connections
- 21 Main Board BRD85MBA
- 22 Front Panel Board
- 24 Main CPU BRD85CPU
- 25 Slave CPU
- 26 RS232 Modem / Programming / Debug Interfacing
- 26 Ancillary Services
- 27 Conventional Zone Board
- 28 Addressable Loop Termination Board
- 29 Boards
- 31 16/16 Input / Output Board
- 32 16 Way Input Board
- 32 Serial Relay Board
- 33 Fire Fan Module BRD25FCB
- 33 Fan Termination Board BRD25FTB
- 34 Zone & General Indicator Card
- 36 Printer
- 36 Indicators and Buttons
- 37 Maintenance
- 38 Printer Connections and Jumpering
- 38 Printer 5 Volt Power Supply ( 302-713 )
- 39 Expanding the System Through Networking
- 39 Communications: Controller Interface Card
- 39 Communications: Network Interface Card
- 40 Expansion Board ( 302-688 )
- 40 Expansion Controller
- 41 Networking
- 43 Liquid Crystal Display Repeater Panel
- 44 Terminal
- 44 Operation
- 44 Access levels
- 45 Specifications
- 45 Overview
- 46 Operational & Key Features
- 46 Mechanical
- 47 Installation & Cabling
- 48 Setting the Address
- 49 Terminal Controller Configuration in ConfigManager
- 49 Terminal Reporting Parameters in ConfigManager
- 50 Terminal Controls
- 52 Terminal Indicators
- 54 LCD Screen Format
- 55 Trouble Shooting Chart
- 56 Agent Release Control
- 56 Operation
- 59 Controlled Access
- 60 Local Control Station
- 63 Agent Release Termination Board BRD25ATB
- 64 Interface Wiring
- 66 Warning Signs
- 68 Occupant Warning Systems
- 73 Brigade Devices
- 73 ASE ( Vic Metro ) Brigade Box
- 73 Brigade Box ( Deltec WA, SA, TAS,QLD )
- 74 Operation
- 74 The Control Panel
- 77 Function And Menu
- 77 The Default LCD Display
- 77 Accessing Functions and Menus
- 77 Function Menu and Access Levels
- 77 Forgotten Passwords
- 78 The Main Menu
- 78 Status Menu
- 80 Testing Menu
- 80 Alarm Test
- 80 Fault Test
- 80 Lamp Test
- 81 Main Functions
- 81 Setting the Function Date Facility
- 81 Setting the Function Time Facility
- 81 Setting the Function Daynight Facility
- 81 Function Logs Facility
- 82 The Function Test Facility
- 83 Function Manual I/O Control
- 83 Function Access ( Level II ) / Passwords ( Level III )
- 84 Function Programming
- 84 Conventional Zone Programming
- 85 Device Programming
- 85 Input Programming
- 85 Output Programming
- 86 Manual Control Point ( MCP )
- 86 Sub Address
- 86 Watchdog
- 86 Self Learn
- 86 Extra Devices Detected
- 87 Mismatch Detected
- 87 Incoming Fire Alarm Signal
- 89 Accessing a Loop, Sensor or Zone
- 89 List of Compatible Devices
- 89 Short Circuit Isolation
- 90 Compatible Devices
- 92 Certification Information
- 93 Statement of Compliance
- 95 Installation Details
- 96 Commissioning Test Report
- 97 Procedure
- 97 System Information
- 101 Troubleshooting Chart
- 102 Address Setting
- 103 Battery Capacity Calculation
- 109 Glossary of Terms
- 110 Definitions
- 111 Quick Reference Guides