RGN 120-260 Manual

Add to My manuals
29 Pages

advertisement

RGN 120-260 Manual | Manualzz

Function

Compact gas units

The compact gas units for Nu-Way gas burners are preassembled and checked for leaks.

Version KE:

1-stage precision pressure regulator with high control quality and adjustable starting gas pressure.

Version KEV:

Exact pneumatic mixture control for optimum energy utilisation and combustion.

Technical data of compact gas unit

Gas types:

Inlet pressure:

Ambient temperature:

Connecting flanges:

Filter:

Natural gas, propane and butane, acc. to EN 437/EN 88 max. 100 mbar / 360 mbar (KE CG10 max. 50 mbar) min. 18 mbar

-15 °C to +60 °C

The connecting flanges are secured with 4 screws. The flanges can be turned through 90° or 180° in each case. Pressure measuring points in inlet and in outlet.

plastic gauze

Gas pressure monitor

The gas pressure monitor serves to monitor the gas inlet pressure. The burner is shut down if the gas inlet pressure drops below the set minimum value (preset at factory to 12 mbar). The burner starts up automatically when the minimum pressure is exceeded.

This setting should be retained.

p