Q Corresponding Serial Communication Module User's Manual


Add to my manuals
358 Pages

advertisement

Q Corresponding Serial Communication Module User's Manual | Manualzz

3 SPECIFICATIONS

MELSEC-Q

3.8 List of Input/Output Signals for the PLC CPU

This section describes the input/output signals of the Q series C24.

For assignments of the input/output signals shown in the table below, it is assumed that the Q series C24 is mounted in slot 0 of the basic base unit.

Device numbers starting with X indicate input signals from the Q series C24 to the PLC

CPU, and device numbers starting with Y indicate output signals from the PLC CPU to the Q series C24.

The following table lists the input/output signals for the PLC CPU.

Reference section

Device number

Signal description

X0

X1

X2

X3

X4

X5

X6

X7

X8

X9

XA

XB

XC

XD

XE

XF

X10

X11

X12

1

1

1

2

2

3

1

1

1

2

2

3

6

6

6

CH1 Transmission normal completion

ON: Normal completion

CH1 Transmission abnormal completion

ON: Abnormal completion

CH1 Transmission processing

ON: Transmission in progress

CH1 Reception data read request

ON: Requesting read

CH1 Reception abnormal detection

ON: Abnormal detection

(For system)

CH1 Mode switching

ON: Switching

CH2 Transmission normal completion

ON: Normal Completion

CH2 Transmission abnormal completion

ON: Abnormal completion

CH2 Transmission processing

ON: Transmission in progress

CH2 Reception data read request

ON: Requesting read

CH2 Reception abnormal detection

ON: Abnormal detection

(For system)

CH2 Mode switching

ON: Switching

CH1 ERR. occurrence

ON: Error occurring

CH2 ERR. occurrence

ON: Error occurring

Modem initialization completion

ON: Initialization completed

Dialing

ON: Dial in progress

Connection

ON: Connection in progress

X13

X14

X15

X16

6

6

6

6

Initialization/connection abnormal completion

ON: Initialization/ connection abnormally completed

Modem disconnection complete

ON: Disconnection completed

Notification normal completion

ON: Normal completion

Notification abnormal completion

ON: Abnormal completion

X17 1 Flash ROM read completion ON: Completed

X18 1 Flash ROM write completion ON: Completed

X19

Flash ROM system setting write completion

ON: Completed

Reference section

Section 8.6.4

Section 8.6.5

Section 8.6.6

Section 6.1

Section 7.1

Section 8.6.5

Section 8.6.6

Application,

Chapter 15

Section 8.6.4

Section 8.6.5

Section 8.6.6

Section 6.1

Section 7.1

Section 8.6.5

Section 8.6.6

Application,

Chapter 15

Section 8.6.10

Section 10.1.2

Section 8.6.2

Application,

Chapter 3

Device number

Y0

Y1

Y2

Y3

Y4

Y5

Y6

Y7

Y8

Y9

YA

YB

YC

YD

Y17

Y18

Y19

CH1 Transmission request

ON: Requesting transmission

CH1 Reception data read completion

ON: Data read completed

CH1 Mode switching request

ON: Requesting switch

CH2 Transmission request

ON: Requesting transmission

CH2 Reception data read completion

ON: Data read completed

CH2 Mode switching request

ON: Requesting switch

Flash ROM read request ON: Requesting

Flash ROM write request ON: Requesting

Flash ROM system setting write request

ON: Requesting

Signal description

Use prohibited

Use prohibited

YE

YF

Y10 6

Y11 6

Y12 6

CH1 ERR.clear request

ON: Requesting error clear

CH2 ERR. clear request

ON: Requesting error clear

Modem initialization request (standby request)

ON: Requesting initialization

Connection request

ON: Requesting connection

Modem disconnection request

ON: Requesting disconnection

Y13

Y14 6

Notification- issued request

OFF: Requesting notification issuance

Y15

Y16

Use prohibited

Use prohibited

Application,

Chapter 15

Application,

Chapter 15

Section 8.6.10

Section 10.1.2

Section 8.6.2

Application,

Chapter 3

3 - 15 3 - 15

3 SPECIFICATIONS

MELSEC-Q

Device number

X1A

X1B

X1C

Signal description

CH1 Global signal ON: Output instructed

CH2 Global signal ON: Output instructed

System setting default completion

ON: Completed

(For system) X1D

X1E 4 Q series C24 ready ON: Accessible

X1F 5

Watchdog timer error (WDT error)

ON : Module error occurred

OFF: Module being normally operated

Reference section

Section 3.10,

Reference

Section 8.4.11

Device number

Y1A

Y1B

Y1C

Y1D

Y1E

Y1F

Signal description

Use prohibited

System setting default request

ON: Requesting

Use prohibited

Reference section

Section 8.4.11

1 The device does not turn on/off by execution of a dedicated instruction when a function that corresponds to the input signal is used.

2 The device does turn on/off by execution of a dedicated instruction when a function that corresponds to the input signal is used (from ON to OFF: Data read completed).

3 The mode switching signal (X6/XD) turns ON at mode switching, receive clear, user frame receive designation or transmission sequence initialization.

While the mode switching signal (X6/XD) is ON, do not issue a communication request to the target interface.

(The communication processing of the Q series C24 is stopped while the mode switching signal (X6/XD) is ON.)

4 The Q series C24 ready signal indicates whether or not it is possible to access the

Q series C24 from the PLC CPU.

Use it as a interlock signal for a sequence program.

(It turns on about one second after turning the power ON and reset operation.)

5 Restart the PLC CPU when the watchdog timer error signal is turned on (reset the power and the CPU module).

6 QJ71C24N-R4 cannot be used. (Related to modem function signal.)

• X10 to X16: For system

• Y10 to Y16: Use prohibited

IMPORTANT

(1) Of the input/output signals to the PLC CPU, the signals marked with "Use prohibited" must not be output (ON).

If any of the "Use prohibited" signals is output, the PLC system may malfunction.

(2) When the modem function is not used or the QJ71C24N-R4 is used, X10 to

X16 are used for the system and Y10 to Y16 cannot be used.

POINT

(1) The input/output signals shown in this section are the signals used when a QnA series serial communication module program is utilized for the Q series C24

(see Section 2 in appendix).

In the QCPU, the on/off of input/output signals to intelligent function modules is executed with a dedicated instruction.

It is not necessary to turn the signals on/off by the sequence program, except for the input/output signals shown in the programming of each function reference page.

(2) When a program for a QnA series serial communication module is also utilized for the Q series C24, it is recommended to replace the instructions with the dedicated instructions shown on the corresponding function reference page of each manual for the Q series C24.

3 - 16 3 - 16