advertisement
Installation
Typical circuits
The circuit diagrams that follow use the term zone to indicate
notification zones as defined in UL 864.
“Notification zone: An area covered by notification appliances that are activated simultaneously.”
Figure 5-1 shows a typical application of the 3-IDC8/4 module to support two notification zones. In this example, power is being supplied from the EST3 rail, and the jumpers (JP1 through
JP4) are set accordingly.
It is also possible to create a similar application that uses external power, supplied to NAC 1/2 IN and NAC 5/6 IN. Refer to the 3-IDC8/4 installation sheet for wiring details and the required jumper settings.
In Figure 5-1, both zones are configured with separate NAC circuits for audible and visible appliances. NAC 1 and NAC 5 are programmed as visible device types, and NAC 2 and NAC 6 as audible device types. This means that the signal silence function can be configured to silence only the horns.
Separating the visible and audible devices is optional and may not be required for your project. Refer to the Genesis Signal
Master installation sheet for additional configurations and wiring details.
5.8
EST3 Installation and Service Manual
1 2 3 4 5 6 7 8 9 10
1
2
3
JP1 JP2
1
2
3
1
2
3
JP3 JP4
1
2
3
Installation
NAC 1
Device type: Visible
Label: Zone_1_Strobes
NAC 2
Device type: Audible
Label: Zone_1_Horns
Normal Active
ZONE1
Temporal horn/strobe and G1M module
Temporal horn/strobe
S
H
10 k Ω
EOLR
10 k Ω
EOLR
Normal Active
ZONE 2
Temporal horn/strobe and G1M module
Temporal horn/strobe
S
H
10 k Ω
EOLR
10 k Ω
EOLR
9 8 7 6 5 4 3 2 1
NAC 5
Device type: Visible
Label: Zone_2_Strobes
NAC 6
Device type: Audible
Label: Zone_2_Horns
Figure 5-1: Typical 3-IDC8/4 card NAC wiring
EST3 Installation and Service Manual 5.9
Installation
Figure 5-2 shows a Signature circuit, wired as Class A, and using isolation modules or bases for each IDC and NAC.
Sync module
Temporal horn/strobe
Notification zone 1
SIGA B+
SIGA B–
SIGA A+
SIGA A–
IM
IPHS
AUX riser
CC1 CR 270 IPHS
Isolater base
Sync module
Temporal horn/strobe
Notification zone 2
Class A
(required)
IM
IPHS CC1 CR 270 IPHS
AUX riser
Figure 5-2: Signature wiring for notification circuit signal synchronization
Isolater base
Figure 5-3 Shows two NACs on a Signature data circuit. Each
NAC is controlled by a SIGA-CC1S module, one for audible appliances, and one for visible appliances.
As in Figure 5-1, this configuration allows the audible appliances to be silenced independently of the visible appliances. This operation is optional, and may or may not be required for your project.
The SIGA-CC1S modules provide signal synchronization for both NACs.
5.10
EST3 Installation and Service Manual
Installation
Figure 5-3: Typical SIGA-CC1S NAC wiring
EST3 Installation and Service Manual 5.11
Installation
Figure 5-4 shows a single SIGA-CC1 switching an NAC on or off. The G1M module provides signal synchronization for the temporal horn/strobe appliances.
As in earlier examples, this circuit allows for independent silencing of the audible appliances. This operation is provided by the SIGA-CR module, which opens or closes the circuit between
S+ and H+ on the G1M module. In this case, however, you must program the operation of the SIGA-CR. The project settings for signal silence operation will not determine the operation of the audible appliances in this NAC.
Note also, that this application could be implemented with a
SIGA-CC1S module. The SIGA-CC1S provides signal synchronization compatible with the operation of the G1M module.
The advantage to using a SIGA-CC1S module is that the NAC would then be synchronized with other NACs on the Signature data circuit.
5.12
EST3 Installation and Service Manual
Installation
Figure 5-4: Typical SIGA-CC1 NAC wiring
EST3 Installation and Service Manual 5.13
Installation
Figure 5-5 shows an auxiliary/booster power supply being used to power the NAC, to provide synchronization, and to provide horn silence capability. Because the auxiliary/booster supply has the ability to silence the horn circuit, this application can be created using only the Signature loop wiring.
The SIGA-CT1 module monitors the power supply for AC failure. The SIGA-CR module signals the power supply to turn the horns on or off. The SIGA-CC1 module signals the power supply when the system goes into alarm, turning the NAC on.
Note that the power supply can only synchronize the notification appliances to which it is connected. If you need to synchronize several similar NACs on the same Signature loop, you can use a
SIGA-CC1S module in place of the SIGA-CC1.
5.14
EST3 Installation and Service Manual
Installation
47 k EO
Figure 5-5: Using an auxiliary/booster supply to provide horn silence capability with two wires
EST3 Installation and Service Manual 5.15
advertisement
Related manuals
advertisement
Table of contents
- 18 System description
- 19 System features
- 20 Minimum system requirements
- 20 System construction
- 22 Audio subsystem description
- 22 Network audio riser wiring
- 23 Amplifiers
- 24 Backup amplifiers
- 25 3-ASU Audio Source Unit
- 31 Firefighter phone
- 32 Digital network subsystem
- 32 Network data riser wiring
- 32 Class B network data risers
- 33 Class A network data risers
- 34 Download connections
- 35 Downloading database files over the network
- 38 Foreign language support
- 38 Printer use with foreign languages
- 38 Bilingual language support
- 39 Display device language support
- 42 Signature series devices
- 45 Network applications
- 45 Network layout
- 46 Feature/function domain
- 49 Audio applications
- 50 Audio channels
- 54 Manual audio zone selection
- 55 Messages
- 58 Firefighter phone system
- 58 Five phone off-hook limit
- 58 One phone per circuit
- 59 Five phones per circuit
- 59 Limited number of portable telephone handsets
- 62 Security equipment
- 68 Certificate installations
- 72 Multiple 3-MODCOM modules
- 73 Multiple site security and access
- 76 Multiple tenant security
- 80 Secure access
- 82 Access control equipment
- 91 Anti-passback
- 94 Central monitoring station
- 96 Common door access
- 98 Delayed egress
- 101 Elevator control
- 104 Emergency exit door
- 106 Handicap access door
- 108 Maglock peripherals
- 110 Multiple card readers
- 112 Muster
- 115 Power for continuous locks
- 117 Power for intermittent locks
- 119 Power from an AC source
- 122 Power from a remote source
- 125 Remote controls
- 127 Two-person rule
- 132 Equipment required
- 133 ATPC Amplifier Terminal Panel Cabinet
- 133 Overview
- 133 Equipment racks
- 136 ATP Amplifier Terminal Panel
- 137 Battery backup
- 138 Audio amplifiers
- 140 URSM Universal Riser Supervisory Module
- 140 Application
- 141 Installation
- 141 Terminal connections
- 141 Operation
- 143 ATP installation
- 144 ATP wiring
- 144 ATP terminal connections
- 145 ATP jumper settings
- 145 3-ATPINT terminal connections
- 146 3-ATPINT jumper settings
- 150 ATP external battery charger
- 152 Amplifier backup
- 155 Branch speaker wiring
- 157 Troubleshooting
- 161 Installation overview
- 161 Electrostatic discharge precaution
- 161 Energized system precaution
- 161 Circuit compatibility
- 162 Recommended cable manufacturers
- 164 UL 864 NAC signal synchronization
- 164 Requirements
- 166 Typical circuits
- 174 Creating an initial startup version of the project database
- 176 System installation sequence
- 177 Preliminary field wiring testing
- 180 Chassis installation in EIA 19-inch racks
- 181 ATCK Attack Kit for cabinets
- 182 Local rail module installation
- 184 3-MODCOM Modem Communicator module
- 184 Features
- 185 Functions
- 186 Equipment
- 187 Configuration options
- 188 Failover operation
- 190 Compatibility
- 190 Transmission protocols
- 191 Transmission process
- 193 Programming considerations
- 194 Installation
- 198 3-SAC Security Access Control module
- 198 Product description
- 198 SAC bus
- 198 Recommended cabling
- 198 Additional power supply wiring
- 199 3-AADC1 Addressable Analog Driver Controller and IRC
- 200 AC power and DC battery wiring
- 202 Connecting auxiliary/booster power supplies
- 202 Installation
- 202 Configuration
- 204 Connecting the PT-1S impact printer
- 206 System printer power supply
- 207 Adjusting amplifier output levels
- 207 What you will need
- 207 Adjustment procedure
- 207 Design considerations
- 208 Connecting a CDR-3 Zone Coder for coded tone output
- 208 What you will need
- 208 Adjusting the gain on the 3-ASU auxiliary input
- 211 Diagnostics Utility
- 213 Running the RPM and distributing profiles
- 217 Cabinet power-up procedure
- 217 Initial power-up
- 218 Runtime and system errors
- 218 Introduction
- 218 Runtime errors
- 219 System errors
- 220 Initial and reacceptance test procedures
- 220 Introduction
- 221 Control and emergency communications equipment testing
- 221 Primary power supplies
- 221 Booster power supplies
- 222 CPU with LCD module
- 224 3-RS232 card installed in CPU
- 224 3-RS485 card installed in CPU, Class B configuration
- 225 3-RS485 card installed in CPU, Class A configuration
- 225 3-IDC8/4 Initiating Device Circuit module
- 225 3-SSDC(1) Signature Driver Controller module
- 226 module
- 226 3-OPS Off-premises Signaling module
- 228 3-ASU Audio Source Unit
- 228 3-FTCU Firefighter Telephone Unit
- 230 3-ZAxx Audio Amplifiers
- 230 Control/display modules
- 231 Amplifier transfer panel (ATP)
- 232 Detector, input module, and output module testing
- 232 module circuit
- 233 circuit
- 233 modules
- 233 UM modules
- 234 Signature series input modules
- 234 Signature series output modules
- 235 Initiating device testing
- 235 Manual stations
- 235 Nonrestorable heat detectors
- 235 Restorable heat detectors
- 235 Waterflow switches
- 237 Notification appliance testing
- 237 Visual devices
- 237 Speakers
- 237 Bells and horns
- 238 Record of completion
- 242 General
- 243 Preventive maintenance schedule
- 245 Signature device routine maintenance tips
- 245 Detectors
- 245 Modules
- 246 Signature detector cleaning procedure
- 247 System trouble and maintenance log
- 251 Overview
- 251 Maintenance philosophy
- 251 Problem classification
- 251 Handling static-sensitive circuit modules
- 252 Removing or replacing circuit modules
- 252 Recommended spares list
- 253 Hardware problems
- 253 Identification
- 253 Isolation
- 253 Substituting hardware
- 254 Adding hardware
- 254 Downloading problems
- 255 Modules
- 255 Rail signals
- 255 3-PPS/M Primary Power Supply module
- 257 3-BPS/M Booster Power Supply module
- 257 CPU Central Processor module
- 261 3-FIBMB fiber optic interface
- 262 Signature Controller modules
- 262 Control / display modules
- 263 Audio amplifier modules
- 264 3-OPS Off-Premises Signal module
- 264 3-IDC8/4 Initiating Device Circuit module
- 265 3-LDSM Display Support module
- 265 3-MODCOM(P) Modem Communicator module
- 266 Common causes of problems
- 268 Audio components
- 268 3-ASU Audio Source Unit
- 269 3-FTCU Firefighter Telephone Control Unit
- 269 SIGA audio amplifiers
- 272 Pseudo point descriptions
- 283 Signature data circuit (SDC) operation
- 285 Basic Signature data circuit troubleshooting
- 285 Isolating circuit and device problems
- 285 Open circuit conditions
- 286 Short circuit conditions
- 287 Ground fault conditions
- 289 Substituting known good Signature series devices
- 295 Signature controller modules
- 295 Substituting Signature controller modules
- 295 Mapping errors
- 297 Device troubleshooting
- 299 Signature diagnostic tools
- 299 Using Signature diagnostics
- 300 Signature diagnostic sequence
- 300 Displaying mapping errors
- 303 Displaying device chain errors
- 305 Using the chain lists
- 305 Displaying message counters
- 307 Displaying device trouble
- 310 Displaying trouble tables
- 313 DSDC status
- 313 Introduction
- 313 Setting up the System Definition Utility program
- 313 Using DSDC status
- 313 Displaying the current SDC status
- 315 Displaying a log of current SDC status events
- 316 Displaying the SDC in-process progress chart
- 318 Addressable analog diagnostic tools
- 318 System definition utility
- 320 Problem solving hints
- 322 3-AADC1 Addressable Analog Driver Controller
- 322 Substituting 3-AADC1 local rail modules
- 323 Addressable analog device troubleshooting
- 325 Wiring problems
- 326 Correcting addressable analog circuit wiring problems