Greensource SM Split Heat Pump – CS Installation Manual (PDF 1.8 MB)


Add to my manuals
40 Pages

advertisement

Greensource SM Split Heat Pump – CS Installation Manual (PDF 1.8 MB) | Manualzz

SM CS Series Heat

Water Tank Refill

1. Open the cold water supply to the tank.

2. Open a hot water faucet to vent air from the system until water flows from the faucet, then close.

3. Depress the hot water tank pressure relief valve handle to ensure there is no air remaining in the tank.

4. Carefully inspect all plumbing for water leaks.

Correct as required.

5. Purge all air from HR by depressing the schrader valve on the HR Unit. Allow all air to bleed out until water appears at the valve.

All piping from HRP to domestic water tank must be copper or any metal of stronger alloy.

Heat Recovery Package | 11

Initial Start-Up

Make sure all valves in heat recovery water piping system are open. NEVER OPERATE

HR PUMP DRY.

1. Turn on the heat pump. The HR pump should not run if the compressor is not running.

2. Turn HR switch to the “ON” position. The pump will operate if entering water temperature to

HR is below 120° F.

3. The temperature difference between the water entering and leaving the heat recovery should be 5° to 15° F.

4. Allow the unit to operate for 20 to 30 minutes to ensure it is functioning properly. The pump should shut off when the water temperature entering the heat recovery reaches 120°F.

6. Before restoring the power or fuel supply to the water heater, adjust the temperature setting on the tank thermostat(s) to ensure maximum utilization of the heat available from the refrigeration system and conserve the most energy. On tanks with both upper and lower elements and thermostats, the lower element should be turned down to 100° F, while the upper element should be adjusted to 120° F.

Depending upon the specific needs of the customer, you may need to adjust the upper element differently. On tanks with a single thermostat lower the thermostat setting to

120° F or the “LOW” position. After thermostat adjustments are completed, replace access cover and restore electrical or fuel supply to water heater.

Revised 01-15 8 733 920 846 (2015/01)