18 | Maintenance
SM CS Series Heat Pump
2. An annual “checkup” is recommended by a licensed refrigeration mechanic. Recording the performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. This data should be compared to the information on the unit’s data plate and the data taken at the original startup of the equipment.
3. Lubrication of the blower motor is not required, however may be performed on some motors to extend motor life. Use SAE-20 nondetergent electric motor oil.
4. The condensate drain should be checked annually by cleaning and flushing to insure proper drainage.
Figure 12: Refrigerant Charge, Line Sizing and Capacity Multiplier Chart
SYSTEM
MODEL
SM024
SM036
Factory
R410A
Charge
(Oz)*
80
86
Refrigerant Line O.D. Size (Based on Equivalent Line Length)
25 FT.
35 FT.
45 FT.
50 FT.
75 FT
LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC.
3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8
Suct. Line
Riser Max.
3/4
3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8 3/4
SM048
SM060
SM070
93
115
127
3/8 7/8 3/8 7/8 3/8 7/8 3/8 7/8 3/8 7/8
3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8
3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8
7/8
7/8
7/8
CAPACITY MULTIPLIER 1.00
.995
Example 1:
Model SM036 with 45ft of equivalent length of 3/8” O.D Liquid
Line. Total system charge= Factory charge + (45ft - 25 ft) x .60 oz/ft Total System Charge =86 oz + (20ft x .60 oz/ft) = 98 oz.
Additional 12 oz of R410A refrigerant required.
Note: Charge value shown for paired SM air handler.
Unit
0.990
0.990
Charge adjustments for SM CS when paired with DX AH (oz)
DX025 DX035 DX049 DX061
0.980
Example 2:
Model SM060 with 10ft of equivalent length of 3/8” O.D
Liquid Line. Total system charge= Factory charge - (25ft -
10ft) x .60 oz/ft Total System Charge = 115 oz - (15ft x .60 oz/ ft) = 106 oz. Removal of 9oz of R410A refrigerant required.
DX071
SM024-1CSC
SM036-1CSC
SM048-1CSC
SM060-1CSC
-
-
-2
-
12
0
-
-
-
25
22
-
-
-
-
10
-
-
-
6
SM070-1CSC
0
Example 3:
Model SM036 CS paired with DX049 AH with 45ft of equivalent length of 3/8” O.D Liquid Line. Total system charge = Factory charge + (DX charge adjustments) + (45ft - 25ft) x .60 oz/ft) = 123 oz. Additional 37 oz of R410A refrigerant required.
Figure 13: Liquid Line Charge Per Linear Foot
R410A oz per foot
Liquid Line Size, O.D.
1/4
.25
5/16
.44
3/8
.60
1/2
1.15
5/8
1.95
8 733 920 846 (2015/01) Subject to change without prior notice SM CS Series Heat Pump
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Model Nomenclature
- 3 Key to Symbols
- 3 Safety Warnings
- 4 Standard SM CS package
- 4 GENERAL DESCRIPTION
- 4 MOVING AND STORAGE
- 4 INITIAL INSPECTION
- 4 LOCATION
- 4 Condensing Section
- 5 Air Handler
- 5 PIPING
- 6 ELECTRICAL
- 6 Safety Devices and the UPM Controller
- 10 OPTIONS
- 10 Heat Recovery Package (HRP)
- 10 DPS Water Flow Proving
- 10 Pump Relay
- 10 Comfort Alert Module
- 11 HEAT RECOVERY PACKAGE
- 11 Water Tank Preparation
- 11 HR Water Piping
- 12 Water Tank Refill
- 12 Initial Start-Up
- 13 SEQUENCE OF OPERATION
- 13 Cooling Mode
- 13 Heating Mode
- 15 APPLICATION CONSIDERATIONS
- 15 Well Water Systems
- 16 Cooling Tower/Boiler Systems
- 18 Geothermal Systems
- 19 SYSTEM CHECKOUT
- 19 UNIT START-UP
- 20 MAINTENANCE
- 21 UNIT CHECK-OUT SHEET
- 22 TROUBLESHOOTING
- 25 Unit Lockouts
- 26 OPERATING TEMPERATURES AND PRESSURES
- 31 WATER SIDE PRESSURE DROP TABLE
- 32 WIRING DIAGRAMS
- 33 DIMENSIONAL DRAWINGS
- 34 SPARE PARTS LIST
- 35 CS Parts List - Cabinet
- 36 CS Parts List -Refrigeration/Electrical
- 39 Notes