SM CS Series Heat
Troubleshooting | 21
Problem
INSUFFICIENT
COOLING OR
HEATING
Possible Cause
Unit undersized
Unit Troubleshooting
Checks and Correction
Recalculate heating and or cooling loads. If excessive, possibly adding insulation and shading will rectify the problem
Check for leaks in duct work or introduction of ambient air through doors or windows
Loss of conditioned air by leakage
Airflow Lack of adequate air flow or improper distribution of air. Replace dirty filter
Low on refrigerant charge causing inefficient operation Refrigerant charge
Compressor
Reversing Valve
Operating pressures
TXV
Moisture, noncondensables
Check for defective compressor. If discharge is too low and suction pressure is too high, compressor is not pumping properly. Replace compressor.
Defective reversing valve creating bypass of refrigerant from discharge of suction side of compressor. Replace reversing valve
Compare unit operation pressures to the pressure/temperature chart for the unit.
Check TXV for possible restriction or defect. Replace if necessary.
The refrigerant system may be contaminated with moisture or noncondensables. Reclaim refrigerant, replace filter dryer, evacuate the refrigerant system, and recharge with factory recommended charge.
Compressor Ohms
Model Start Winding Run Winding
SM024
SM036
SM048
SM060
1.64
1.52
1.86
1.63
1.3
0.88
0.52
0.39
SM070 1.85
0.34
Tolerance +/- 7%. All resistance values must be measured with compressor at room temperature.
UPM Board LED Indications
Indication
Color Blinks
GREEN
RED
RED
RED
RED
RED
RED
4
5
6
Solid
1
2
3
Description
18-30 VAC Power is present
High pressure lockout
Low pressure lockout
Freeze sensor lockout
Condensate overflow
Brownout
Evaporator Freeze condition
Revised 01-15 8 733 920 846 (2015/01)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Model Nomenclature
- 3 Key to Symbols
- 3 Safety Warnings
- 4 Standard SM CS package
- 4 GENERAL DESCRIPTION
- 4 MOVING AND STORAGE
- 4 INITIAL INSPECTION
- 4 LOCATION
- 4 Condensing Section
- 5 Air Handler
- 5 PIPING
- 6 ELECTRICAL
- 6 Safety Devices and the UPM Controller
- 10 OPTIONS
- 10 Heat Recovery Package (HRP)
- 10 DPS Water Flow Proving
- 10 Pump Relay
- 10 Comfort Alert Module
- 11 HEAT RECOVERY PACKAGE
- 11 Water Tank Preparation
- 11 HR Water Piping
- 12 Water Tank Refill
- 12 Initial Start-Up
- 13 SEQUENCE OF OPERATION
- 13 Cooling Mode
- 13 Heating Mode
- 15 APPLICATION CONSIDERATIONS
- 15 Well Water Systems
- 16 Cooling Tower/Boiler Systems
- 18 Geothermal Systems
- 19 SYSTEM CHECKOUT
- 19 UNIT START-UP
- 20 MAINTENANCE
- 21 UNIT CHECK-OUT SHEET
- 22 TROUBLESHOOTING
- 25 Unit Lockouts
- 26 OPERATING TEMPERATURES AND PRESSURES
- 31 WATER SIDE PRESSURE DROP TABLE
- 32 WIRING DIAGRAMS
- 33 DIMENSIONAL DRAWINGS
- 34 SPARE PARTS LIST
- 35 CS Parts List - Cabinet
- 36 CS Parts List -Refrigeration/Electrical
- 39 Notes