Datasheet | Schneider Electric FX 3NET Technical data


Add to my manuals
58 Pages

advertisement

Datasheet | Schneider Electric FX 3NET Technical data | Manualzz

Installation Instruction 66571764GB3

16/2012

FX 3NET FIRE ALARM SYSTEM

Installation and commissioning manual

Fire Detection

Read this manual carefully before installation and commissioning!

Installation and commissioning must be performed according to this manual.

This Installation and Commissioning Manual is to be kept together with the control panel.

Installation Instruction 66571764GB3 Fire Detection

2

Contents

1.

About this document ...........................................................................................................................................4

2.

Typical placement of the units in a panel .........................................................................................................4

3.

Installation, FX and FXL - control panels ....................................................................................................... 10

4.

Installation, FXM - control panel ..................................................................................................................... 11

5.

Installation, FXS - control panel ...................................................................................................................... 12

6.

Connecting main power supply ...................................................................................................................... 13

7.

Commissioning ................................................................................................................................................. 14

7.1

Necessary devices and documents ....................................................................................................... 14

7.2

Order of commissioning ......................................................................................................................... 14

8.

Preliminary checks ........................................................................................................................................... 15

8.1

General ...................................................................................................................................................... 15

8.2

Preliminary checks .................................................................................................................................. 15

9.

Control panel test run: Note differences with the FXS! ................................................................................ 17

9.1

Mains connection..................................................................................................................................... 17

9.2

Battery connection .................................................................................................................................. 18

10.

Cable handling and preliminary measurements ....................................................................................... 19

10.1

Cable handling and measurements ....................................................................................................... 19

10.2

Cable table ................................................................................................................................................ 20

11.

Addressable detector loops ....................................................................................................................... 22

11.1

Measuring the Cables .............................................................................................................................. 22

11.2

Connecting the loop to the control panel ............................................................................................. 23

11.3

Functional check of the loop .................................................................................................................. 23

12.

Conventional detector lines ........................................................................................................................ 27

12.1

Measuring the Cables .............................................................................................................................. 27

12.2

Connection principles ............................................................................................................................. 28

12.2.1 Conventional line ................................................................................................................................... 28

12.2.2 Input line ................................................................................................................................................. 29

12.3

Connecting the line to the control panel ............................................................................................... 30

12.4

Functional check of the loop .................................................................................................................. 30

12.5

Compatible detectors and manual call points ...................................................................................... 31

13.

Monitored output lines ................................................................................................................................ 32

13.1

Measuring the cables and connecting the end-of-line resistors ........................................................ 32

13.2

Connecting the monitored output lines to the control panel .............................................................. 33

13.3

Functional check of monitored output lines ......................................................................................... 33

14.

Control outputs ............................................................................................................................................ 34

14.1

Clean relay outputs.................................................................................................................................. 34

14.2

Free power outputs.................................................................................................................................. 35

15.

Signal inputs ................................................................................................................................................ 36

15.1

Connecting the inputs to the control panel .......................................................................................... 36

15.2

Testing the inputs .................................................................................................................................... 36

16.

Info-line devices / connections .................................................................................................................. 37

16.1

INFO-fault messages ............................................................................................................................... 37

16.2

FMPX ......................................................................................................................................................... 37

16.3

DAPX ......................................................................................................................................................... 38

16.4

REPX and REPX-OB ................................................................................................................................ 38

16.5

MCOX and MCOX-OB .............................................................................................................................. 39

16.6

CODI / Codinet .......................................................................................................................................... 39

17.

Configuration ............................................................................................................................................... 40

18.

Serial communication ports ....................................................................................................................... 41

18.1

FX 3NET communication network.......................................................................................................... 42

18.2

Communication grounding ..................................................................................................................... 42

18.3

Modem connections in the communication network ........................................................................... 43

19.

Alarm routing equipment ............................................................................................................................ 44

19.1

Connecting the alarm routing equipment to the control panel ........................................................... 44

20.

FX, FXL and FXM connections ................................................................................................................... 45

20.1

FX and FXL panel external connections, SLC ...................................................................................... 45

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

3

20.2

FX and FXL panel external connections, ALC ...................................................................................... 46

20.3

FXM panel external connections, SLC .................................................................................................. 47

20.4

FXM panel external connections, ALC .................................................................................................. 48

20.5

FXS panel external connections, SLC ................................................................................................... 49

20.6

FXS panel external connections, ALC ................................................................................................... 50

20.7

Connectors on the MC2 board ............................................................................................................... 51

20.8

Connectors on the PSA and PSB - board ............................................................................................. 52

20.9

Connectors on each SLC board ............................................................................................................. 52

20.10

Connectors on each CLC board ......................................................................................................... 53

20.11

Connectors on each IOC board .......................................................................................................... 53

20.12

Connectors on each OCA-board ........................................................................................................ 54

20.13

Connectors on each ALCA- board ..................................................................................................... 55

20.14

Connectors on each ALCB- board ..................................................................................................... 55

20.15

Connectors on FMPX, DAPX, REPX and REPX-OB- board and MCOX and MCOX-OB- board .... 56

20.16

Connectors on CODINET modem adapter ........................................................................................ 57

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

4

10

11

12

13

14

15

16

6

7

8

9

2

3

4

5

1. About this document

For non-experienced installers this document provides sufficient information to install the FX_ panel (FX, FXL;

FXM, FXS) and to commission the whole system successfully.

Experienced installers may select to connect all loops and IO connections at once without testing the connections in between.

However, it is strongly recommended always to do the preliminary checks and an initial test run before any cables

(except the necessary main supply) are connected to the panel.

This document uses the following acronyms for the various units (component boards) in the panel:

1 MC2 – Master Controller

PS – Power Supply

UI2 – User Interface

SLC – Loop Controller

CLC – Conventional Line Controller

ALC - Loop Controller

IOC - IO Controller

OCA – Output Controller

LB2-32 – Panel LED Board 2: 32 LED indications

LB80 – Zone LED Board: 80 LED indications

REPX and REPX-OB protocol repeater

MCOX and MCOX-OB logical controller

ZLPX and ZLOX-IC Zone Led control unit

CODI – Communication adapter

FMPX – Fireman panel

DAPX – Delay alarm panel

NOTE: If SLC loop controller is configured to LC protocol, please read document.O1771GB0

2. Typical placement of the units in a panel

FX cabinet

The FX cabinet has space for the following

- 1 x UI2

- 1 x MC2

- 1 x PSB (4.0 A)

- 2 x Battery (B) 12 V / 17 Ah

- Option board (OP) total 5 pcs:

SLC/ALC/CLC, max. 4 pcs

IOC, max. 4 pcs

OCA, max. 4 pcs

MCOX-OB, max. 1 pcs

REPX-OB, max. 1 pcs

ZLPX-IC, max. 1 pcs

MC2

PSB

OP

OP

B B

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

FXL cabinet

The FXL cabinet has space for the following

- 1 x UI2

- 1 x MC2

- 1 x PSB (4.0 A)

- Option board (OP) total 9 pcs:

SLC/ALC/CLC, max. 4 pcs

IOC, max. 4 pcs

OCA, max. 4 pcs

MCOX-OB, max. 1 pcs

REPX-OB, max. 1 pcs

ZLPX-IC, max. 1 pcs

MC2

OP

Fire Detection

OP

OP

5

PSB

OP

FXM cabinet

The FX battery cabinet has space for the following

- 1 x UI2

- 1 x MC2

- 1 x PSA (2.2 A)

- 2 x Battery (B) 12 V / 12 Ah

- Option board (OP) total 2 pcs:

SLC/ALC/CLC, max. 2 pcs

IOC, max. 2 pcs

OCA, max. 2 pcs

MCOX-OB, max. 1 pcs

REPX-OB, max. 1 pcs

ZLPX-IC, max. 1 pcs

MC2

PSA

B

OP

B

FXS cabinet

The FXS cabinet has space for the following

- 1 x UI2

- 1 x MC2

- Option board (OP) total 1 pcs:

SLC/ALC/CLC, max. 1 pcs

IOC, max. 1 pcs

OCA, max. 1 pcs

MCOX-OB, max. 1 pcs

REPX-OB, max. 1 pcs

ZLPX-IC, max. 1 pcs

Note! Power supply feed has to be brought from an

FX, FXL or FXM panel.

MC2

OP

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

AX/FX/IX-BAT battery cabinet

The FX battery cabinet has space for the following

- 4 x battery 12 V / 17 Ah

- Fire alarm and Fault warning router

Fire Detection

6

B B

B B

FXM-BAT battery cabinet

The FXM battery cabinet has space for the following

- 4 x battery 12 V / 12 Ah

B

B B

B

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

FX-CAB mounting cabinet

Fire Detection

7

FXM-CAB mounting cabinet

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

FXM-RMFW mounting frame

Fire Detection

8

FXM-RMFW

FXM/

FXM-RMFW

FXM + FX-MAP/

FXM-RMFW + FX-RMFW

FXM + FXM-BAT +FX-MAP/

2 x FXM-RMFW + FX-RMFW

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

FX-RMFW mounting frame

Fire Detection

9

FX-RMFW

FX/

FX-RMFW

FX + FX-MAP/

2 x FX-RMFW

FX + FX-MAP +FX-BAT/

3 x FX-RMFW

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

3. Installation, FX and FXL - control panels

The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet.

The weight of the control panel excl. batteries is 11 kg and incl. batteries (2 x 17 Ah) 23 kg. The weight of the chart file cabinet is 9 kg.

The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.

The weight of the battery cabinet excl. batteries is 7 kg and incl. batteries (4 x 17 Ah) 31 kg.

FX control panel

Chart cabinet

Battery cabinet

Fire Detection

10

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

4. Installation, FXM - control panel

The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet.

The weight of the control panel is exl. batteries is 8 kg and incl. batteries 20 kg.

The weight of the battery cabinet is exl. batteries is 4 kg and incl. batteries 28 kg. The weight of the chart file cabinet is 9 kg.

The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.

FXM control panel

Battery cabinet

Chart cabinet

7

6

Fire Detection

370

370

11

424

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

5. Installation, FXS - control panel

The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet.

The weight of the control panel is 4.4 kg.

The weight of the chart file cabinet is 9 kg.

The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.

FXS control panel

Chart cabinet

Fire Detection

12

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

6. Connecting main power supply

Connect the mains supply (230 VAC)

There must be a separate fuse (10 A) for the control panel power supply.

Cable 3 x 1.5 mm².

Fire Detection

13

Note!

FXS has not any built-in power supply. The power is fed to the FXS panel from FX or FXM power supply unit using 2 power lines. The power supply PI1 and PI2 inputs in FXS are on the MC2 board. Both must be connected and the “PI in use”- jumper on MC2 must be set.

FXS panel: MC2 board

PO 2

+24V-

PO 1

+24V-

FX or FXM panel:

PSA or PSB board

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

14

7. Commissioning

7.1 Necessary devices and documents

Devices

• A universal measuring instrument (voltage, current, resistance, diode).

• A PC and the configuration tool, if the configuration is done when commissioning.

Documents

• This Installation and Commissioning manual.

• Operation manual.

• Planning and installation documents for the project.

• Client/project configuration data if the configuration is done when commissioning.

7.2 Order of commissioning

1. Check that the installation has been done correctly according to the plans.

2. Make preliminary checks on the control panel.

3. Test run the control panel.

4. Connect detector loops.

5. Connect monitored output lines.

6. Make site specific settings.

7. Connect the outputs.

8. Connect the inputs.

9. Connect the serial communication ports.

10. Configure the system if required according to the plan or site specific features.

11. Connect the router to the defined control panel.

WARNING!

Do not use an isolation resistance meter for measuring resistance!

Note!

The system does not require configuration in order to function.

On the other hand, client specific features may require configuration.

Note!

For SLC only (System Sensor devices).

If the system is not configured and a loop has the same addresses for both detectors and I/O-modules, the detectors will be assigned addresses from the low range

(01…159) and the I/O-modules from the high range (201 and 359).

Usually it is easier to start up loops, if the control panel is not configured.

Note!

On ALCA / ALCB - loop (Intellia devices) all detectors and modules must have individual addresses from 1 to 126.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

15

8.

8.1

Preliminary checks

General

The aim of the preliminary checks is to assure that the settings are correct and that the control panel has not suffered any defects during transportation or installation. This is obviously most easy to do when no external cables are connected, except for the necessary power supply connection.

8.2 Preliminary checks

1. Check that all power is disconnected from the control panel.

The cable from the transformer to the power supply component board is disconnected from the terminal 30VAC on the component board.

The battery cable is disconnected from the battery terminal BATT on the component board.

FXS: PI1 and PI2 are disconnected.

2. Check that the mains cable is connected to the mains terminal.

3. Check that the separate fuse reserved for the control panel is in its place.

MC2 jumper settings

Side CPU not in use’ jumper should not be in place in FX

NET systems in seeing panels provided with a fire routing equipment. In case of a system fault the assistant processor takes care of the system communication. If there is a fire alarm in one of the system panels the assistant processor controls: o the fire routing output CO1 of the MC2 unit

(independent of the configuration of the CO1) o the fire alarm device output of the MC2 unit

(independent of the configuration of the output) o the general fire alarm LED o the panel specific fire alarm LED (LB2-32) o the buzzer of the panel

1. Check the following settings:

The “CONF” jumper is not in place.

The “PULSED” jumper is not in place (for continuous alarm device signal) or in place (for pulsing alarm device signal).

The “PROG” jumper is not in place.

The “PI IN USE” jumper is not in place.

FXS: PI IN USE in place!

The “IOC’S” jumper is correctly set for the number of

IOC’s and OCA’s in the panel.

The “LC’S” jumper is correctly set for the number of

SLC’s, ALC’s and CLC’s in the panel.

2. Check also that there is a 4.7 k

Ω end-of-line resistor in the terminals for the monitored output line.

3. Check also that there is a 4.7 k

Ω end-of-line resistor in the terminals for the monitored input lines.

CONFIG

PULSED

PROG UPD

PI IN USE

IOC’S LC’S

RS485

Gnd - +

SYS 1

Gnd - +

RS232

Tx Rx Gnd

SYS 2

Gnd - +

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

SLC jumper settings

1. Check the following settings:

“Prog Update” jumper is not in place.

“Dev LED” jumper is in place if you want the detector leds to flash when communicating with the panel or not in place otherwise.

Set the right ID. The range is 1…4/panel and is common to SLC, ALC and CLC units.

2. Check also that there is a wire between A+ and B+ as well as between A- and B- in the terminals for both loops.

Fire Detection

16

CLC jumper settings

1. Check the following settings:

Set the right ID. The range is 1…4/panel and is common to

SLC ALC and CLC units.

Check also that all conventional line terminals have their

EOL resistors connected to the terminals.

ALC jumper settings

1. Check the following settings:

“Prog Update” jumper is not in place.

“Dev LED” jumper is in place if you want the detector leds to flash when communicating with the panel or not in place otherwise.

Set the right ID. The range is 1…4/panel and is common to

SLC, ALC and CLC units.

2. Check also that there is a wire between A+ and B+ as well as between A- and B- in the terminals for both loops.

IOC jumper settings

1. Check the following settings:

Set the right ID. The range is 1…4/FX and FXL panel. The

ID must be different for each IOC and OCA.

The monitored output line configuration jumpers are set for desired operation (pulsed or continuous signal).

Check also that there are 4.7k

Ω end-of-line resistors in the terminals for each monitored output line.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

OCA jumper settings

1. Check the following settings:

Set the right ID. The range is 1…4/FX and FXL panel. The

ID must be different for each IOC and OCA.

Fire Detection

17

2. Press the “BUZZER SILENCE”- button.

9. Control panel test run: Note differences with the FXS!

9.1 Mains connection

Note! The panel is in access level 2 when the cover is removed.

1. Switch the panel on by connecting the cable between the transformer and the terminal 30VAC on the power supply component board.

FXS: Connect power supply cables “P1” and “P2” to the

MC2 PI1 and PI2 terminals.

The backlight of the display flashes for about 20 s.

The display will show the text:

The text “Panel starting up” will disappear from the display when all addresses are scanned for presence.

After approximately one minute from start the panel will indicate a fault alarm due to the missing battery:

Note: FXS does not give any fault alarm, because there in

FXS is not built-in power supply and battery.

LCD display shows:

13:36 14.09.2007

FX

Fire Panel

Activate menu by pressing wheel

Panel starting up

Buzzer beeps continuously.

FAULT-led blinks.

FAULT 1/1

PS battery fault

Panel starting up

The audible signal is silenced.

The “FAULT”- led becomes fixed.

The LCD remains the same.

The panel will also indicate a fault alarm for missing. configuration data if the panel is not configured.

This fault alarm can be reset and will not appear again.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

9.2 Battery connection

1. Install the batteries in the cabinet. Check that the battery cable is disconnected from the battery terminal BATT.

Fire Detection

18

2. Check battery polarity from the markings on the battery.

3. Connect the battery cables to the poles as follows:

The batteries are 12 V batteries. If two batteries are used, they are connected in series.

If four batteries are used, two series connected pairs are connected in parallel (Voltage is 24 VDC).

4. Connect the battery cable to the battery terminal BATT on the PS component board.

5. Reset the battery fault indication in the control panel by pressing the “RESET”- button until the pulsed audible signal stops.

WARNING!

Connecting the batteries in the wrong way may cause a short circuit in the batteries, which may lead to an explosion, a strong electric arc or fire in the battery cables.

The “FAULT”- led goes out.

The display shows the text:

13:36 14.09.2007

FX

Fire Panel

Activate menu by pressing wheel

Panel starting up

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

10. Cable handling and preliminary measurements

WARNING!

Check by measuring that there is no power in the cables.

10.1 Cable handling and measurements

At every stage of commissioning, power must be disconnected from the control panel before the cables are installed.

First disconnect the battery then the mains.

1. Peel off the cable plastic and protective shields. Be careful not to let peeling remains drop onto the component board or between the back wall of the cabinet and the component board.

2. Make sure that the cables have been marked and that the markings can be seen after the peeling.

3. If the cables used are shielded, measure, before connecting the shield that the resistance between the shield and the cabinet ground exceeds 1 M

Ω. If the resistance is smaller, the cable shield is in contact with the construction of the building:

- The outer sleeve of the cable has been damaged.

- The protective shield is in connection to the construction of the building in a detector socket.

Repair the fault. Then connect the cable shield to the cabinet ground.

4. Measure for each cable: the resistance between the cable shield and the wires. The resistance must exceed 1 M

Ω. If the value is smaller, the earth leak must be located and repaired.

>1M Ω

5. If the cables used are not shielded, measure the resistance between the wires and cabinet ground. It must also exceed 1 M

Ω.

>1M Ω >1M Ω

19

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

10.2 Cable table

Cable connection

Addressable detection circuit cables, SLC- loop

Addressable detection circuit cables, ALC- loop

Conventional detection circuit cables, CLC- line

Sub-detection circuits of conventional zone modules, SLC- loop

Sub-detection circuits of conventional zone modules, ALC- loop

Power supply to conventional zone modules

Conductors x area

2 x 0.5 mm

2

+ shield

2 x 1.0 mm

2

+ shield

2 x 0.5 mm

2

+ shield

2 x 1.0 mm

2

+ shield

2 x 0.5 mm

2

+ shield

2 x 1.0 mm

2

+ shield

Sub-detection circuits of conventional zone modules

Sub-detection circuits of conventional zone modules

2 x 0.5 mm

2

+ shield

2 x 1.0 mm

2

+ shield

Conventional Exi-area sub-loop unit

Printer connection

- Serial data

Serial connections

- INFO

- FX NET

2 x 0.5 mm

2

+ shield

2 x 1.0 mm

2

+ shield

2 x 0.5 mm

2

+ shield

5 x 0.5 mm

2

+ shield

3 x 0.5 mm

2

+ shield

Serial connections between FX NET panels, 2 serial line

System1 line

System2 line

FX clean contact input lines

Cable 1:

4 x 0.5 mm

2

+ shield

Cable 2:

4 x 0.5 mm

2

+ shield

2 x 0.5 mm

2

Max. length

810 m

(60

Ω)

1600 m

(60

Ω)

810 m

(60

Ω)

1500 m

(60

Ω)

1200 m

(100

Ω)

2400 m

(100

Ω)

1200 m

(100

Ω)

600m

(50 Ω)

625 m

(50

Ω)

1200 m

(50

Ω)

625 m

(50

Ω)

1200 m

(50

Ω)

150 m

15 m

1000 m

1000 m

1000 m

Comments

Cable resistance max. 50

Ω.

From panel through the address module to the Eex barrier resistance max. 50

Ω total. If power supply is brought to several units through the same cable, the real length of this part must be multiplied with the number of units when comparing with the maximum length.

Loop resistance from the Exi-barrier to most distant detector max.12

Ω. Loop capacitance max. 390 nF.

RS232

RS485

Fire Detection

20

The cable resistance of the loop is max. 60

Ω and the capacitance max. 180 nF between conductor and shield, 360 nF between conductors. Max. voltage drop is 6 V.

The cable resistance of the loop is max. 60

Ω and the capacitance max. 180 nF between conductor and shield, 360nF between conductors. Max. voltage drop is 9 V.

The cable resistance of the loop is max. 50

Ω, if an Exi barrier is connected to the loop, otherwise max 100

Ω.

The max. allowed capacitance of the cable is 0.5µF.

Conventional zone module EM210E-CZ, EM210E-CZR,

M512ME and conventional detectors or conventional manual call points.

Conventional zone module EMI-310-CZ / EMI410-CZ and conventional detectors or conventional manual call points.

2 X RS 485

Note!

Isolated Gnd terminals in RS485 Serial connection must be connected between the panels using signal wire not shield.

FX clean contact output lines

2 x 0.5 mm

2

2 x 1.0 mm

2

or

FX monitored output lines – fire bell, sounder line

- fault buzzer line

Addressable monitor modules, SLC- loop

- monitor lines

Addressable control modules, SLC- loop

- power supply

2 x 0.5 mm

2

2 x 1.0 mm

2

or

2 x 2.5 mm

2

or

2 x 0.5 mm

2 shield

2 x 0.5 mm

2 x 1.5 mm

2 x 2.5 mm

2

2

2

+

or

or

2000 m

To be calculated separately

The equipment receiving the contact signal may have restrictions on cable properties.

Load controlled by the relay output may restrict allowed resistance and length per cross section.

Relay contact rating is 30 VDC 1 A

To be calculated separately

Max. allowed voltage drop defines cable to be used.

625 m

(50

Ω)

Monitor modules M500ME, M503ME, M501ME,

EM210E, EM220E, EM221E.

To be calculated separately

Control modules M500CHE, EM201E, EM221E, M201 and

M240.

Number and distances of the relay control modules define the

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

21

- alarm line

Addressable monitor modules, ALC- loop

- monitor lines

Addressable control modules, ALC- loop

- power supply

- alarm line

Mains supply cable

2 x 0.5 mm

2

+ shield

2 x 0.5 mm

2 x 1.5 mm

2

2

or

2 x 2.5 mm

2

or

3 x 1.5 mm

2

625 m

(50

Ω) conductor area and length of the power supply cable.

Monitor modules EMI- 310, EMI-310+, EMI-311, EMI-311/240,

EMI-333, -EMI-410, EMI-410+, EMI-411.

Mini monitor modules 55000-833 APO, 55000-832 APO.

To be calculated separately

Control modules EMI-301, EMI-311, EMI-311/240, EMI-301S,

EMI-401, EMI-401S,EMI-411.

Mains connection:

- 230 ±10% V AC, 50-60 Hz, - maximum power 160 W

- separate fuse 10 A

Note!

The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.0 A in alarm condition.

The standby time required for the system may limit the max. load of the outputs.

Note!

The max. current consumption of the FXM - control panel (with PSA- power supply board), all loops and addresses and all control panel outputs is 0.5 A in standby condition and 2.2 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

22

11. Addressable detector loops

11.1 Measuring the Cables

Disconnect all power from the control panel.

1. Measure the resistance between the loop wires + and - so that the resistance meter positive (feeding) probe is in the

+ -conductor. The resistance must exceed 1 k

Ω. If the resistance is smaller, locate the cause of the fault and repair it. (It may be a detector or address unit connected the wrong way or a short circuit isolator).

First disconnect the battery, then the mains

>1k

Ω

2. Measure the loop cable + wire resistance from the output and return ends. Also measure the – wire. The loop resistance of the + and – wires added together can be max. 60

Ω on SLC - loop and 60 Ω on ALC - loop.

The difference between the + and – wire resistances should not exceed 5

Ω. The possible causes of a fault must be located and repaired.

Note!

If there are short circuit isolators in the loop, resistance measuring of the loop cable will give false results. The short circuit isolators must be by-passed by connecting links over the isolators.

<30

Ω

<30

Ω

3. Remove short circuit isolators’ by-passes.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

11.2 Connecting the loop to the control panel

Each FX-SLC and FX–ALCB board has connectors for two loops, FX-ALCA board has only one loop.

1. Check that all power has been disconnected from the control panel.

2. If shielded cable is used, connect the shield to the nearest earth screw in the back plate.

3. Connect the loop wires to the LOOP terminals of the

SLC/ALC board.

Outgoing end to terminals A+ and A-.

Return end to terminals B+ and B- .

23

11.3 Functional check of the loop

1. Start the control panel by switching the power on.

2. Wait until the text “PANEL STARTING UP” disappears from the display (about 3 minutes).

3. Verify in the panel display that all addresses are indeed found by selecting “Loops/Address points” from the menu, and stepping through all addresses in all loops. (This is not necessary if the panel is configured).

First connect the transformer cable, then the battery cable.

The text ‘Panel starting up’ disappears from the bottom of the display.

The detector loop is in order if the control panel does not give fire, fault or service indications at the start up.

Otherwise the fault must be located by following the instructions below.

4. If the panel indicates fire alarm, press the “BUZZER

SILENCE” button, scroll the alarm indications with the

MORE ALARMS”- button and note them.

Possible causes for fire alarm:

- A manual call point is pressed down; the glass has been broken or taken off.

5. Eliminate the causes of fire alarm and reset the indications by pressing the “RESET”- button until the pulsed signal stops.

6. Repeat the above mentioned procedures until there are no more fire alarms.

-

-

A manual call point or another device connected to the input of an addressable monitoring unit is in active state.

Smoke, water vapour or thick dust in a smoke detector.

- Heat close to a heat detector.

Possible causes for fault or maintenance warnings:

7. If the panel indicates fault or maintenance warning press the “BUZZER SILENCE” button, scroll the indications with the “MORE ALARMS”- button and note them.

8. Eliminate the causes of fault and maintenance warnings and reset the indications by pressing the “RESET”- button until the pulsed signal stops.

9. Repeat the above mentioned procedures until there are no more fault and maintenance warnings.

-

-

-

A break or a short circuit in the loop. See below for how to find the fault.

An earth leak in the loop. See below for how to find the fault.

An address fault in the loop. See table below for possible address fault indications.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

24

A short circuit indication is caused by a loop component connected the wrong way or a short circuit in the wires. If short circuit isolators are used, the shorted part of the loop between the closest isolators will be non-operative. By scrolling trough the addresses list for the shorted loop and comparing with the installation plan, the shorted area can be located. (If the panel is configured, it will indicate fault alarm for all addresses between the operated short circuit isolators).

A break in the loop is easily found by disconnecting the return end of the loop and comparing the addresses that the panel can communicate with, with the installation plan.

An earth fault can most easy be found by splitting the loop in two parts, disconnecting the return end of the loop from the panel and restart. If the panel still indicates earth fault, the location is in the still connected part of the loop, otherwise in the non-connected part. By splitting the faulty part of the loop in two and restarting again, you will soon find the reason for the earth fault.

Fault and maintenance warnings of the loop devices are identified by codes in the display. The codes and a short explanation of each are listed below.

Fault and maintenance warnings of address point

s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)

The loop has to be re-scanned again after the reason of warning has been fixed.

r = running time when device is normally monitored

c = loop is configured with PC

n = loop is not configured

MAINTENANCE 00: (s,c)

MAINTENANCE 01: (s,c)

MAINTENANCE 02: (s,c)

− The anytype of device has been configured for this address but no device is installed.

Indicated only once and will disappear after resetting the warning

− No device has been configured to this address but some device is installed.

Indicated only once and will disappear after resetting the warning

− Definite type of device has been configured but no device is installed.

This warning can be removed only by installing device to this address or changing the configuration and scanning the loop again.

− The configured type/family and installed type/family is not the same or

MAINTENANCE 03: (s,c) protocols of devices are not same (types are.

This warning can be removed only by changing device to this address or changing the configuration.

MAINTENANCE 04: (s,n) − NA

MAINTENANCE 05: (s,n) − Illegal address. For example address 0 found in the loop scanning phase.

− Factory setting of address switches are 0,0. The LED’s of the unit blinks

FAULT 06: (s,c/n)

FAULT 07: (s,n)

FAULT 08: (s,n)

FAULT 09: (s,c/n) automatically for easier identification (when LED blink jumper is not installed).

Note! It is not possible to detect any other fault or fire conditions for a unit that has the 00 address.

− Unknown type of device installed to the loop. The address is not polled any more.

− Device removed from this address during the loop disablement. The fault is detected when the loop is re-enabled again.

Note! The panel has to be boot to clean up MC loop database

− The type of device is changed during the loop disablement.

Note! The panel has to be boot to clean up MC loop database

− New addresses (devices) are found in the loop.

Indicated only once and will disappear after resetting the warning

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

25

MAINTENANCE 11: (s,c) − Siren control (separate remote LED control) have been configured for

SySe sensor (500 series) but the feature not exist in the sensor (old one)

− Technical alarm input configured for LC address but SW version of LC is

FAULT 12: (s,c)

FAULT 13: (s,c/n) not compatible (> 1.3),

− Two or more Apollo devices are at the same address ("double address”).

MAINTENANCE 14:(s,c/n)

− Bad scan responses of a device.

MAINTENANCE 15:(s,c/n) − The type ID bits is not compatible with memory ID of Apollo unit

MAINTENANCE 16: (s,c) − Apollo protocol family of device and configuration mismatch

FAULT 17: (s,c/n)

(S90/XP95/Discovery),

− Two or more SySeAp devices are at the same address ("double address”) Yellow LED of units is ON.

− Two or more SySeClip and SySeAp devices are at the same address

FAULT 18: (s,c/n)

("double address”).

MAINTENANCE 19:(s,c/n) − “Sub” address of SySeAp multi module overlaps with a some other unit.

FAULT 20: (r)

MAINTENANCE 21: (r)

FAULT 22: (r)

FAULT 51: (r)

− There is an internal fault in a SySeAp device

− A SySeAp device is detached and attached at the loop (powered up)

− A sub address of multi module is out of the address range (a sub address would be > 159)

− Too low analog value received from analog sensor or fault in the internal

FAULT 52: (r)

FAULT 53: (r)

FAULT 54: (r)

FAULT 55: (r)

FAULT 56: (r)

FAULT 57: (r)

FAULT 58: (r)

MAITENANCE 59: (r)

MAINTENANCE 60: (r)

MAINTENANCE 61: (r)

FAULT 62: (r)

FAULT 63: (r)

FAULT 64: (r)

FAULT 65: (r)

FAULT 66: (r) operation of an sensor

− The address does not respond (or bad response)

− Two or more devices have the same address ("double address”).

− Break in the input circuit of a monitor module.

− Break in the output circuit of a control module.

− Short circuit in output circuit of a control module.

− The input unit has been configured as "fault input". When the input alarm activated the FX shows it as fault warning.

− The input unit has been configured as "zone disablement device" and the disablement time exceeds (default time 12 hours).

− The input unit is configured as "maintenance input". When the input alarms the FX shows it as maintenance warning.

− A dirty detector. If the analog value of the detector has exceeded the maintenance limit for more than 24 hours, this warning is indicated.

− If detector exceeds value (during 24h) after user reset this fault warning, fault warning is re-generated immediately.

− Also at case that value of some other detector(s) stay over the maintenance limit (but 24h timeout has not expired) at the moment when user select from the menu “report dirty detector” and press “enable” at access level 3, this fault warning is created.

− drift compensation alert of 2251TEM / 7251LASER / OMNI and other new intelligent sensors. (OMNI / 2251TEM >200 <560; 7251LASER

>200 < 650)

− 6 months to cell life expiration of CoPTIR sensor

− Break or short circuit at the conventional sub loop of conventional zone module.

− Invalid response from detector (> 4000 µs for normal sensors, >860 and

< 1600 for the OMNI sensor .

− Unstable value read from SySeAp device

− System Sensor beam detector 6500 in alignment mode.

− Device type (or functional type ) changed when loop is running.

− Sensor with separate remote LED control feature is changed to same type device without this feature. More often this event is indicated with fault 64

− Input alarm function is "fault in extinguisher". When module alarms FX

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

26

MAINTENANCE 67: (r)

MAINTENANCE 68: (r)

MAINTENANCE 69: (r)

FAULT 70: (r)

FAULT 71: (r)

FAULT 72: (r)

FAULT 73: (r)

FAULT 74: (r)

FAULT 75: (r)

FAULT 76: (r)

FAULT 77: (r)

FAULT 78: (r)

FAULT 79: (r)

FAULT 80: (r)

FAULT 81: (r)

FAULT 82: (r)

FAULT 83: (r)

FAULT 84: (r)

FAULT 85: (r,s)

FAULT 86: (r)

FAULT 87: (?) show it as fault warning.

− Saturation of infrared detector at CoPTIR/PTIR sensor

− 80% of drift limit (when “report dirty detector” requested)

− 99% of drift limit (when “report dirty detector” requested)

− Undefined fault code from ALC/SySeAp device.

− Memory write operation of the device failed

− Memory read operation of the device failed

− Communication troubles with device.

− Self test of the detector failed.

− Beam sensor CPU fault

− Beam sensor align targeting

− Beam sensor general fault

− Beam sensor signal too high

− cell life expiration of CoPTIR sensor

− The SW of ALC board is not compatible for desired sounder mode

− Input module has been configured as "fire router fault". When module alarms FX show it as fault warning.

− Input module has been configured as "VACIE fault". When module alarms FX show it as fault warning.

− Unsupported address device has been configured to the loop of LC board

(The SW of LC is older than configuration made with WinFXNet).

− Power failure of supervised output circuit of a module

− The OEM code of the device is not Esmi/Pelco code.

− The control of output of SySeAp device did not work

MAINT 88: (?)

MAINT 89: (?)

FAULT 90: (r,s)

− Unacceptable device

ALC: detector is not Intellia, device is XP95 but not configured

MAINTENANCE 91: (r)

FAULT 92: (r)

FAULT 93: (r)

FAULT 94: (r)

FAULT 95: (r)

FAULT 96: (?)

MAINTENANCE 98: (r)

FAULT 99: (r)

− break in input line of the CLC unit

− short circuit in input line of the CLC unit

− voltage problem in input line of the CLC unit

− Voice evacuation mute input active time expired

− simulated maintenance (service command)

− simulated fault (service command)

s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)

r = running time when device is normally monitored

c = loop is configured with PC

n = loop is not configured

Note !

Fault delays / timeouts

Reason for Fault 52 ( no PW1 received) must be active for 99sec. before the fault is shown.

Delay for fault 63 (PW4 out of limits) is 30 sec. if any good pulses are received, counter will stop, and if no bad pulses with in 10sec, the counter is reset

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

12. Conventional detector lines

12.1 Measuring the Cables

1. Disconnect all power from the control panel.

2. Measure the resistance between the wires of the conventional line cable. Set the meter to low voltage resistance measurement

(not diode measurement).

Depending on connected devices the result should be:

- If all devices are normally open (NO) types and no EOL resistor is connected the meter should indicate a break in the line

- If all devices are normally open (NO) types and an EOL resistor is connected the meter should indicate the value of the EOL resistor.

- If some devices are normally closed (NC) types the meter should indicate the parallel connection of the series resistances of those devices

If the resistance meter indicates other values, the cause of the fault must be located. (It may be a detector connected the wrong way or a short circuit in the conductors).

3. Short-circuit the wires of the conventional detection line cable at the control panel during measuring.

4. Disconnect the end-of-line resistors from those conventional detection line terminals to which the cables are to be connected.

5. Take the end-of-line resistor with you and walk to the end of the line and measure the resistance between the wires of the cable.

The maximum allowed resistance is 100

Ω (50 Ω if the line goes through an Exi barrier). If the resistance is higher, there is a break in the line (did you remember short-circuit the cable wires at the control panel). Locate the breaks and eliminate them.

6. Connect the end-of-line resistors to their respective places (the last detector or manual call point of the line or the end-of-line unit box connected after the last device).

Fire Detection

27

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

28

12.2 Connection principles

12.2.1 Conventional line

Min/max. value of conventional devices internal resistance is depending of detectors threshold voltage and the

EOL.

Conventional line 4k7

End of line resistance: 4k7, 5%

Max. Line resistance: 100 Ω

Max load from all detectors in loop: 1.8 mA

Line resistance max. 100

Compatible detectors

(threshold voltage / alarm resistance):

8V / 50 -

1000 Ω, 5 %

5V / 110 -

1300 Ω, 5 %

3V / 140 –

1500 Ω, 5 %

1V / 180 –

1700 Ω, 5 %

0V / 200 –

1800 Ω, 5 %

Conventional line 2k94

End of line resistance: 2k94, 1%

Max Line resistance: 100 Ω

Max load from all detectors in loop: 4 mA

Compatible detectors (threshold voltage / alarm resistance):

8V / 50 -

550 Ω, 5 %

5V / 110 -

750 Ω, 5 %

3V / 150 –

880 Ω, 5 %

1V / 190 –

1010 Ω, 5 %

0V / 210 –

1070 Ω, 5 %

Line resistance max. 100

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

12.2.2 Input line

End of line resistance: 4k7, 5%

Max. Line resistance: 100 Ω

Alarm resistance: 1k33 – 2k15, 5% (e.g. 4k87 and 2k94 in parallel = 1k833)

Line resistance max. 100

Fire Detection

29

Line resistance max. 100

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

12.3 Connecting the line to the control panel

Each CLC board has 16 conventional lines (detection circuits).

1. Disconnect all power from the control panel.

2. If shielded cable is used, connect the shield to the cabinet ground screw in the back plate.

Note!

The free shielded wire must be as short as possible!

3. Connect the pair of wires of the conventional line to the terminals of the CLC board retaining polarity.

Fire Detection

30

12.4 Functional check of the loop

1. Start the control panel by switching the power on. First connect the transformer cable, then the battery cable.

2. Wait until the text “PANEL STARTING UP” disappears from the display (about 3 minutes).

The detector loop is in order if the control panel does not give fire, fault or service indications at the start up.

Otherwise the fault must be located by following the instructions below.

3. If the panel indicates fire alarm, press the “BUZZER

SILENCE” button, scroll the alarm indications with the

MORE ALARMS”- button and note them.

4. Eliminate the causes of fire alarm and reset the indications by pressing the “RESET”- button until the pulsed signal stops.

Possible causes for fire alarm:

- A manual call point is pressed down; the glass has been broken or taken off.

- Smoke, water vapour or thick dust in a smoke detector.

- Heat close to a heat detector.

5. Repeat the above mentioned procedures until there are no more fire alarms.

6. If the panel indicates fault or maintenance warning press the “BUZZER SILENCE” button, scroll the indications with the “MORE ALARMS”- button and note them.

Possible causes for fault warnings:

- A break or a short circuit in the loop.

7. Eliminate the causes of fault and maintenance warnings and reset the indications by pressing the “RESET”- button until the pulsed signal stops.

8. Repeat the above mentioned procedures until there are no more fault and maintenance warnings.

9. Test that each detector and manual call point gives an alarm. Test procedures for the various devices are given in the documentation for those devices.

- An earth leak in the loop.

Note!

CLC default value for the short circuit is a fault!

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

31

12.5 Compatible detectors and manual call points

Compatibility of detectors with the CLC conventional line is determined by the following factors:

- Supply voltage range

- Current consumption in standby condition

- Voltage across the detector in alarm condition

- Series resistance (either in the detector or in the base)

- End-Of-Line resistor

The voltage supplied by the CLC to the conventional line is 21 Vdc to 24 Vdc. The maximum allowable voltage drop in the cable is 21 V minus the lowest operating voltage of the connected devices.

If the line goes through an Exi barrier, the maximum allowed cable resistance and current consumption is less than for a normal line.

The following table shows the required series resistor for a number of detector voltages (in alarm condition), the two allowed EOL types and whether or not a Exi barrier is connected to the loop.

Conventional Line

EOL resistor / Exi

Max. cable resistance

Max. detector load

Threshold voltage over detector / allowed serial resistance in alarm condition

4k7, 5% / not Exi 2k94, 1% / not Exi

100 Ω 100 Ω

4k7, 5% / Exi

50 Ω

2k94, 1% / Exi

50 Ω

1.8 mA

8 V / 50 -

1000 Ω

4.0 mA

8V / 50 -

550 Ω

1.5 mA

8 V / 10 -

700 Ω

3.0 mA

8V / 10 -

320 Ω

5 V / 110 -

1300 Ω 5 V / 110 - 750Ω 5 V / 150 - 1050 Ω 5V / 170 - 550 Ω

3 V / 140 -

1500 Ω 3 V / 150 - 880Ω 3 V / 250 - 1250 Ω 3V / 280 - 710 Ω

1 V / 180 -

1700 Ω 1 V / 190 - 1010Ω 1 V / 340 - 1500 Ω 1V / 380 - 880 Ω

0 V / 200 -

1800 Ω 0 V / 210 - 1070Ω 0 V / 390 - 1600 Ω 0V / 440 - 960 Ω

Input Line

When CLC input is configured as input line, only EOL 4k7 can be used. If it is configured as Exi-area input, line alarm resistance values are different. See table below and chapter 12.2.2.

EOL resistor / Exi

Max. cable resistance

Alarm resistance

4k7, 5%

100 Ω

1k33 – 2k15, 5%

(e.g. 4k87 and 2k94 in parallel =

1k833)

4k7, 5% Exi

100 Ω

715 –

1870 Ω, 5%

(e.g. 4k87 and 2k94 in parallel =

1k833)

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

13. Monitored output lines

13.1 Measuring the cables and connecting the end-of-line resistors

1. Disconnect all power from the control panel.

2. Measure the resistance between the monitored output line cable wires so that the resistance meter positive (feeding) measuring end is in the “–“ wire of the line. The resistance meter must indicate a break. If the resistance meter indicates a resistance value, the cause of the fault must be located. (It may be an alarm device connected the wrong way, a serial diode missing from the alarm device or a short circuit in the conductors).

Fire Detection

32

OL

3. Short-circuit the monitored output line cable wires at the control panel during measuring.

4. Disconnect the end-of-line resistors from those monitored output line outputs to which the cables are to be connected.

5. Measure the resistance between the wires of the cable at the last alarm device or end-of-line unit box in each monitored output line with the resistance meter. The allowed resistance should not be more than 300

Ω depending on the current consumption of the alarm devices connected to the same line (See picture on the

right). If the resistance is considerably higher, there is a break in the line (did you remember short-circuit the cable wires at the control panel). Locate the breaks and eliminate them.

6. Take the end-of-line resistors to their respective places

(the last alarm device of the line or the end-of-line unit box connected after the last alarm device) and connect them.

Note!

There must not be other resistors or end-of-line units in the monitored output line.

<300 Ω 4k7

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

33

13.2 Connecting the monitored output lines to the control panel

The FX-MC board has one monitored output line connector.

Note! If the ‘Side CPU not in use’- jumper is NOT in place in the MC2 (system assistant processor is in use), then in the case of the MC2 system fault the system assistant processor controls the CO1 output as a fire router output regardless of the configuration.

The FX-IOC board has four monitored output line connectors.

1. Check that all power has been disconnected from the control panel.

2. Connect the monitored output line cable wires to the terminals as follows:

- The fire alarm line is connected to the output marked with bell symbol on the MC and the outputs 1 to 3 marked with the bell symbol on the IOC.

- The fault alarm line is connected to the output 4 marked with the bell symbol on the IOC.

- 4.7 k

Ω resistors are left in the terminals of outputs that are not in use.

Note!

The above usages of the outputs are valid for non-configured panels. If configured, the purpose may have been changed.

Verify with the configuration.

4k7

4k7

4k7

4k7

13.3 Functional check of monitored output lines

1. Start the control panel. The monitored output lines are in order if the control panel does not give fault indications.

2. If the alarm devices give fault indications, press the

BUZZER SILENCE”- button on the user panel.

3. You may also want to silence fault warning devices by pressing the “SILENCE/RESOUND” button.

Possible causes of fault indications:

- A short circuit in the line, the end-ofline resistor is too small (should be

4.7k

Ω), a serial diode is missing from an alarm device or the device has been connected with the wrong polarity.

- A break in the line, the end-of-line resistor is missing or its resistance is too big.

- An earth leak in the line.

4. Eliminate the causes for fault indication and reset the panel by pressing the “RESET”- button until the audible signal stops.

5. Test the monitored output line operation as follows:

6. Press the wheel to activate the menu and select:

7. Then press the wheel again and select:

8. Press the “TEST”- button, at which the display will show the text:

Pressing the wheel activates all fire alarm devices.

9. The test is stopped by pressing the “TEST”- button. Check the operation of the alarm devices. Eliminate any faults and repeat the test until all alarm devices operate.

Note! Ensure that all persons in the building have been informed of the alarm device test.

CONTROLS

FIRE ALARM DEVICES CONTROL

PRESS WHEEL TO ACTIVATE THE

CONTROL

ACTIVE

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

34

14. Control outputs

14.1 Clean relay outputs

The FX-MC2 board has three clean contact outputs.

Each FX-IOC board has two clean contact outputs.

Each FX-OCA board has 16 clean contact outputs.

The function of the outputs is defined with the configuration tool.

The default functions of the outputs of a control panel that has not been configured are:

MC2-CO1 Note! If the ‘Side CPU not in use’- jumper is in place in the Fire alarm router activation

MC2 (system assistant processor is NOT in use), then in the case of the MC2 system fault the system assistant processor does NOT control the CO1 output as a fire router output regardless of the configuration.

MC2-CO2 Fault warning router activation The relay is energized in normal condition and releases in fault warning condition or if power is removed regardless of

the configuration.

MC2-CO3

IOC-CO1

Fire alarm output

IOC-CO2

OCA-CO1-2

OCA-CO3-4

OCA-CO5-6

OCA-CO7-8

OCA-CO9-10

OCA-CO11-12

Fire alarm output

Fire alarm output

Fire alarm output

Fire door output

Pre-alarm output

Technical alarm output

Fault warning output

Maintenance warning output

OCA-CO13-14

OCA-CO15-16

Disablement output

Access level 2 output

1. Disconnect all power from the control panel.

2. Select suitable outputs and connect the device to be controlled to the output.

The relay contacts are rated for max. 30 VDC, 1 A.

WARNING!

Voltage 230 VAC must not be brought to the relay contacts.

If a device with 230 VAC is to be controlled, a suitable intermediate relay must be used. It is to be placed in a casing outside the control panel cabinet and equipped with a protective diode (e.g.

1N4005).

Test the fire outputs control operation as follows:

SYS 1

Gnd - +

SYS 2

Gnd - +

CO3

NO C NC

CO2

NC C NO

RS232

Tx Rx Gnd

1. Start the control panel.

2. Press the wheel to activate the menu and select:

3. Then press again the wheel and select:

CONTROLS

FIRE OUTPUTS CONTROL

4. Press the “TEST”- button, at which the display will show the text:

5. Pressing the wheel activates all control outputs.

6. The test is stopped by pressing the “TEST”- button.

PRESS WHEEL TO ACTIVATE THE

CONTROL

ACTIVE

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

14.2 Free power outputs

The power supply is normally 27 VDC, max. 500 mA. During a power failure the supply follows the battery voltage. The power supply may momentarily be 30 VDC at the most.

IOC, SLC and ALCB, PO1 and PO2

ALCA only PO1

MC2, only PO

Fire Detection

24VDC / 500mA

35

24VDC / 500mA

24VDC / 2A / 4 A

PSA , PO1 and PO2; 2 A

PSB , PO1 and PO2; 4 A

24VDC / 2 A / 4 A

Note!

The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.5 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.

Note!

The max. current consumption of the FXM - control panel (with PSA- power supply board), all loops and addresses and all control panel outputs is 0.5 A in standby condition and 2.2 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.

1. Start the control panel.

2. If the control panel gives a fault indication press the “BUZZER SILENCE” button. You may also want to press the “SILENCE/RESOUND” button to silence fault warning devices.

3. If the control panel gives an earth fault indication, the cause may be an earth leak in the cable or an earth leak caused by the device to be supplied with power.

4. Power output fault indication means overload or short circuit in the output.

5. Disconnect all power from the control panel, repair any fault and restart the control panel.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

36

15. Signal inputs

15.1 Connecting the inputs to the control panel

The FX-MC2 board has two clean contact input connectors.

Each FX-IOC board has four clean contact input connectors.

Input Default Function

MC2-IN1 Fault in fire alarm router equipment

Default state also configurable as

Normally open / monitored Normally open / closed

Monitored / not monitored

MC2-IN2 Fault in fault warning router equipment Normally open / monitored Normally open / closed

Monitored / not monitored

Normally open / monitored Normally closed / monitored

1k54

4k7

1k54

4k7

Normally closed / not monitored

Input Default Function

IOC-IN1 Fault warning

Normally open / not monitored

Default state also configurable as

Normally closed Normally open

IOC-IN2 Fault in extinguisher Normally closed Normally open

IOC-IN3 Extinguisher activated Normally open Normally closed

IOC-IN4 Smoke vents activated Normally open Normally closed

IN 1

IN 2

IN 3

IN 4

1. Disconnect all power from the control panel.

2. Select suitable inputs and connect the device to be monitored (e.g. extinguisher call point, router fault output) to the control panel.

3. Start the control panel.

4. If the control panel gives an earth leak indication, press the “BUZZER SILENCE”- button and disconnect all power. Repair any fault and restart the control panel.

5. Test the operation of the inputs with the connected device (remember that a fire alarm or fault warning also activates fire and fault alarm devices and alarm routing equipment).

15.2 Testing the inputs

The inputs for Fault in fire alarm router, Fault in fault warning router and Fault in extinguisher can be tested without activation of fault warning outputs, as follows:

Press the wheel to activate the menu and select: INPUT INTERFACES

Then press again the wheel and select:

Press the “TEST”- button, at which the display will show the text:

MC MONITORED INPUT 1 or 2

IN TEST STATE

The display indicates now the status of the input.

The test is stopped by pressing the “TEST”- button.

FAULT or OK

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

37

16. Info-line devices / connections

16.1 INFO-fault messages

Text at display Description fault in info port X comm. info X external device fault 0 info X external device fault 1 info X external device fault 2 info X device fault 3 info X device fault 4

When acknowledge bit not received after 10 retries of some message or external system will send "EXTERNAL FAULT" message

MCO/Repeater reports that outport of the unit has communication fault

MCO/Repeater reports that external port of the unit has communication fault.

MCO reports that control logic part of unit has recognized problems

When transmitting does not success for some reason. Monitored internal by

SW.

Note! configuration bit "not monitored" does not prevent this fault *

When receiver gets whole time a lot of rubbish, not real Info frames. Monitored internal by SW.

Note! configuration bit "not monitored" does not prevent this fault

IC unit reports about power input 1 fault

IC unit reports about fault in the configuration files of IC

IC unit reports about fault which is unknown for FX info X external device fault 5 info X external device fault 7 info X external device fault 255

X = 0; Info configured to RS232 service port

X = 1; Info configured to RS485 at SA board

16.2 FMPX

Picture 1. Connection between FX-panel and FMPX

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

16.3 DAPX

Fire Detection

38

Picture 2. Connection between FX-panel and DAPX

16.4 REPX and REPX-OB

Picture 3. Connection between FX-panel and REPX

Note! If REPX-OB is installed in FX: rack, only INFO line needs to be connected.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

16.5 MCOX and MCOX-OB

Fire Detection

39

Picture 4. Connection between FX-panel and MCOX

Note! If MCOX-OB is installed in FX: rack, only INFO line needs to be connected

16.6 CODI / Codinet

There are two versions of CODIs: CODI and CODINET.

Only CODINET may be used in panel communications (19200bd).

CODI is only up to 9600bd.

The Codinet 24Vdc power input is isolated

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

40

17.

Note! The panel is set to the configuration mode with configuration tool. This can be done also with the following procedure.

Set control panel to access level 3.

1.

2.

3. enter.

4. Repeat with the other digits.

5. Press “ENABLE” when the right code is entered.

6. The panel is now in access level 3.

7.

6.

Configuration

Select with “MENU”-button from main menu.

Press the wheel.

Select the first digit with the wheel and press the wheel to

Set panel to configuration state.

Set control panel to the configuration state by putting a jumper in position “CONF” on the MC board. The display shows the text:

7. Transfer the configuration.

8. Connect configuration cable to the terminal RS232.

9. Configure the control panel with the configuration tool

10. Remove the configuration cable from the terminal RS232

CURRENT ACCESS LEVEL:2

CHANGE TO ACCESS LEVEL 3:0000

CURRENT ACCESS LEVEL: 3

CONFIGUARTION STARTED

READY FOR CONFIGURATION and the jumper from the position “CONF” on the MC.

Restart the panel.

11. Restart the control panel by pressing “RESET” button on the

MC.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

18. Serial communication ports

RS232 and RS485 serial communication ports using INFO protocol are on the top of the FX-MC2 board. These ports are isolated.

FX panel can communicate with INFO devices such as FMPX, MCOX etc. via these ports. Also a printer using serial communication can be connected to either of these ports.

NOTE! Only one of these ports can be connected at a time.

Connectors SYS 1 and SYS 2 are used for interpanel communication in networked systems.

The RS 232 connector in the middle of the connector row is used for configuration and maintenance .

Fire Detection

41

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

18.1 FX 3NET communication network

FX_

FRE

“Seeing”

= Communication cable

- one twisted pair

- shielded

Building 1

FX_

“Seeing”

Fire Routing

Building 2

FX_

“Seeing”

S1

S1

S2

S1

S2

S1

S2

S1

S2

S1

S2

Fire Detection

42

“Visible”

FX_

“Visible”

FX_

“Visible”

FX_

“Visible”

FX_

1a

1b

2a

2b, Spare wire, not in use

System 1(S1) and System 2 (S2) = serial communication line

Picture 5. Example: FX 3NET communication network

18.2 Communication grounding

FX x serial adapter

2b, Spare wire, not in use

FX y serial adapter

1a

1b

2a

1a

1b

2a

2b, Spare wire, not in use

FX x chassis

FX y chassis

2b, Spare wire, not in use

1a

1b

2a

All serial communication cable shields are connected to the grounding filter.

Max length 10mm

All serial communication cable shields are connected to the grounding filter.

Max length 10mm

2a

2b, Spare wire, not in use

Cable shield is connected ONLY in FXNET panel

2b, Spare wire, not in use 2a

FMPX

1b

1a

1b

1a

Picture 6. Communication grounding in the FX NET system

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

18.3 Modem connections in the communication network

1 2 .... N 5 6 .... X

FxNet FxNet

FxNet FxNet FxNet

FxNet

SAB

SYSTEM SYSTEM

1 2

SAB

SYSTEM SYSTEM

1 2

SAB

SYSTEM SYSTEM

1 2

SAB

SYSTEM SYSTEM

1 2

SAB

SYSTEM SYSTEM

1 2

SAB

SYSTEM SYSTEM

1 2

2x 2W Rs 485 (system1 and system2)

Max cable length 1000m

CodiNet rs232<=>485 converter rs-485

CodiNet rs232<=>485 converte r

Fiber

Modem

Tx Rx rs-232

Fiber

Modem

Tx Rx

Rs 485 / fibre modems ( Moxa)

Multi- or single mode fibres max.fibre legth is depending of the fibre type

Group of

Fx-panels

Fiber

Modem

Fiber

Modem

Fire Detection

43

22 23 .... 32

FxNet

SAB

SYSTEM SYSTEM

1 2

FxNet

SAB

SYSTEM SYSTEM

1 2 rs-485

CodiNet rs232<=>485 converter rs-232

CodiNet rs232<=>485 converter

Fiber

Modem

Tx Rx

Fiber

Modem

Tx Rx

CodiNet rs232<=>485 converter rs-485

CodiNet rs232<=>485 converter

Fiber

Modem

Tx Rx rs-232

Fiber

Modem

Tx Rx

Panels can be connected to this point with modems rs-485

CodiNet rs232<=>485 converter

CodiNet rs232<=>485 converter rs-232

Fiber

Modem

Tx Rx

Fiber

Modem

Tx Rx

FxNet

SAB

SYSTEM SYSTEM

1 2

Fiber

Modem

Fiber

Modem

NOTE!

Do NOT connect panels so that the signal path between any panels goes thru more than two modem pairs / line

NOTE 2!

Even if the fiber modem have rs-485 connections it’s allways recommended to use it on rs-232 mode and use CodiNet- coverter between the fiber modem and the panel if the lentgh of the copper cable on the rs-485 connection is more than ~100m

Picture 7. Max. two modem pairs between two panels

1. Disconnect all power from the control panel.

Group of

Fx-panels

No modem connections on this point !

2. Connect the RS485 serial communication wires to the

RS485 terminals (INFO) and

System1 terminals (RS485 type) and

System2 terminals (RS485 type) as follows

Signal wires to terminals T/R + and T/R – and GND.

(Note that shield wire of the cable can not be connected to the GND terminal).

The shields of the cables may not be connected to the metal part (earth) of the cabinet directly. The shields must be connecter through the parallel connected capacitor and varistor as follows

(because long distances may cause big differences in earth potential). Loosen three screws of the backplate. Install the small circuit board from the SA package under the screws and tighten the screws and connect the shield to the terminals.

3. Connect the RS232 serial communication conductors to the RS232 terminals as follows:

The control panel transmitter wire to terminal TxD

The control panel receiver wire to terminal RxD.

GND wire (not shield) to terminal GND.

Connect the shield directly to the metal part (earth) of the cabinet.

4. Start the control panels: first visible panels and

then seeing panels

5. If the control panel gives an earth leak indication, line fault (one of S1 and S2 is not functioning) or communication fault (either of S1 and S2 is not functioning), press the “BUZZER SILENCE”- button and disconnect all power from the control panel. Repair any fault and restart the control panel.

6. If the control panel has been configured, the operation of serial communication should be tested

(remember that a fire or fault also activates fire or fault alarm devices and alarm routing equipment).

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

44

19. Alarm routing equipment

19.1 Connecting the alarm routing equipment to the control panel

The alarm routing equipment must not be connected until all other necessary commissioning procedures have been performed.

Note! Inform the alarm receiver about the alarm routing equipment test.

1. Disconnect all power from the control panel.

2. Connect the alarm routing equipment to the terminals CO1,

CO2 and PO on the MC2 board.

The default function of CO1 and CO2 are:

CO1 = Fire Alarm Router

NOTE! If the ‘Side CPU Not in use’- jumper is in place in the

MC2 (system assistant processor is NOT in use), then in the case of the MC2 system fault the system assistant

-

+

Fire processor does NOT control the CO1 output as a fire router output regardless of the configuration.

CO2 = Fault Warning Router

The PO terminal provides 24 VDC supply for the routing equipment.

Note! CO2 is energized (as drawn) when the panel is in normal condition

3. Start the control panel.

Fault

Fire routing equipment

If the control panel gives a fault indication, press the “BUZZER SILENCE”- button.

If the control panel gives an earth leak indication, the cause may be an earth leak in the cable or an earth leak caused by the alarm routing equipment.

If the control panel gives a power output fault indication, the alarm routing equipment connected draws too much current and is probably faulty or the connection is wrong.

Disconnect all power from the control panel, repair any fault and restart the control panel.

Test the alarm transmission (combined test of fault warning router and fire alarm router) operation as follows:

4. Press the wheel to activate the menu and select: ALARM TRANSMISSION TEST

5. Press the “TEST”- button, at which the display will show the text: PRESS WHEEL TO ACTIVATE THE

TEST

6. Pressing the wheel activates the fault warning router.

7. After 30 seconds also the fire alarm router is activated.

ALARM TRANSMISSION TEST

STAGE 1

Fault routing activated

ALARM TRANSMISSION TEST

8. After a further 30 seconds the test stops automatically. The test

STAGE 2

Fire routing activated

ALARM TRANSMISSION TEST can also be stopped at any time by pressing the “TEST” – button.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20. FX, FXL and FXM connections

20.1 FX and FXL panel external connections, SLC

Fire Detection

Serial (RS485) communication with other FX panels (2 pcs)

Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX

45

Master controller

FX-MC2

Serial (RS232) communication with printer or maintenance tool (PC)

Ethernet connection, INFO communication: Future option

USB connection, maintenance tool (PC)

Fire Alarm Router Equipment (Alarm transmitter)

Fault Warning Router Equipment (Alarm transmitter)

Fire Alarm Output

Power supply output 24 VDC, short circuit protected, 500 mA

Monitored output (Bells, sounders, beacon), 500 mA

Fault in Fire Alarm Router Equipment (Alarm transmitter)

Fault in Fault Warning Router Equipment (Alarm transmitter)

REPX-OB or

MCOX-OB or

ZLPX-IC

INFO communication

INFO communication

External communication (not in ZLPX-IC)

Loop controller

FX-SLC

0…4 pcs

For each FX-SLC: Two addressable detection circuits, each with 159 detector addresses + 159 IO-module addresses

For each FX-SLC: Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Loop controller

FX-CLC

0…4 pcs

For each FX-CLC: 16 Conventional detection circuits, function configurable

Input/output controller

FX-IOC

0…4 pcs

Clean contact signal inputs (4 pcs), function configurable

Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable

Monitored relay outputs (4 pcs), max 500 mA each, function configurable

Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Output controller

FX-OCA

0…4 pcs

Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable

Power supply

FX-PSB

Power supply outputs 24 VDC (2 pcs), short circuit protected, 4 A each

230 VAC / 50 Hz / 160 VA

Battery 24 VDC (max 68 Ah)

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.2 FX and FXL panel external connections, ALC

Fire Detection

Serial (RS485) communication with other FX panels (2 pcs)

Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX

46

Master controller

FX-MC2

Serial (RS232) communication with printer or maintenance tool (PC)

Ethernet connection, INFO communication: Future option

USB connection, maintenance tool (PC)

Fire Alarm Router Equipment (Alarm transmitter)

Fault Warning Router Equipment (Alarm transmitter)

Fire Alarm Output

Power supply output 24 VDC, short circuit protected, 500 mA

Monitored output (Bells, sounders, beacon), 500 mA

Fault in Fire Alarm Router Equipment (Alarm transmitter)

Fault in Fault Warning Router Equipment (Alarm transmitter)

REPX-OB or

MCOX-OB or

ZLPX-IC

INFO communication

INFO communication

External communication (not in ZLPX-IC)

Loop controller

FX-ALCA, FX-ALCB

0…4 pcs

FX-ALCA: One addressable detection circuits, with 126 addresses

FX-ALCB: Two addressable detection circuits, each 126 addresses

FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA

FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each

Loop controller

FX-CLC

0…4 pcs

For each FX-CLC: 16 Conventional detection circuits, function configurable

Input/output controller

FX-IOC

0…4 pcs

Clean contact signal inputs (4 pcs), function configurable

Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable

Monitored relay outputs (4 pcs), max 500 mA each, function configurable

Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Output controller

FX-OCA

0…4 pcs

Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable

Power supply

FX-PSB

Power supply outputs 24 VDC (2 pcs), short circuit protected, 4 A each

230 VAC / 50 Hz / 160 VA

Battery 24 VDC (max 68 Ah)

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.3 FXM panel external connections, SLC

Fire Detection

Serial (RS485) communication with other FX panels (2 pcs)

Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX

47

Master controller

FX-MC2

Serial (RS232) communication with printer or maintenance tool (PC)

Ethernet connection, INFO communication: Future option

USB connection, maintenance tool (PC)

Fire Alarm Router Equipment (Alarm transmitter)

Fault Warning Router Equipment (Alarm transmitter)

Fire Alarm Output

Power supply output 24 VDC, short circuit protected, 500 mA

Monitored output (Bells, sounders, beacon), 500 mA

Fault in Fire Alarm Router Equipment (Alarm transmitter)

Fault in Fault Warning Router Equipment (Alarm transmitter)

REPX-OB or

MCOX-OB or

ZLPX-IC

INFO communication

INFO communication

External communication (not in ZLPX-IC)

Loop controller

FX-SLC

0…2 pcs

For each FX-SLC: Two addressable detection circuits, each with 159 detector addresses + 159 IO-module addresses

For each FX-SLC: Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Loop controller

FX-CLC

0…2 pcs

For each FX-CLC: 16 Conventional detection circuits, function configurable

Input/output controller

FX-IOC

0…2 pcs

Clean contact signal inputs (4 pcs), function configurable

Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable

Monitored relay outputs (4 pcs), max 500 mA each, function configurable

Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Output controller

FX-OCA

0…2 pcs

Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable

Power supply

FX-PSA

Power supply outputs 24 VDC (2 pcs), short circuit protected, 2 A each

230 VAC / 50 Hz / 80 VA

Battery 24 VDC (max 34 Ah)

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.4 FXM panel external connections, ALC

Fire Detection

Serial (RS485) communication with other FX panels (2 pcs)

Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX

48

Master controller

FX-MC2

Serial (RS232) communication with printer or maintenance tool (PC)

Ethernet connection, INFO communication: Future option

USB connection, maintenance tool (PC)

Fire Alarm Router Equipment (Alarm transmitter)

Fault Warning Router Equipment (Alarm transmitter)

Fire Alarm Output

Power supply output 24 VDC, short circuit protected, 500 mA

Monitored output (Bells, sounders, beacon), 500 mA

Fault in Fire Alarm Router Equipment (Alarm transmitter)

Fault in Fault Warning Router Equipment (Alarm transmitter)

REPX-OB or

MCOX-OB or

ZLPX-IC

INFO communication

INFO communication

External communication (not in ZLPX-IC)

Loop controller

FX-ALCA, FX-ALCB

0…2 pcs

FX-ALCA: One addressable detection circuits, with 126 addresses

FX-ALCB: Two addressable detection circuits, each 126 addresses

FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA

FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each

Loop controller

FX-CLC

0…2 pcs

For each FX-CLC: 16 Conventional detection circuits, function configurable

Input/output controller

FX-IOC

0…2 pcs

Clean contact signal inputs (4 pcs), function configurable

Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable

Monitored relay outputs (4 pcs), max 500 mA each, function configurable

Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Output controller

FX-OCA

0…2 pcs

Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable

Power supply

FX-PSA

Power supply outputs 24 VDC (2 pcs), short circuit protected, 2 A each

230 VAC / 50 Hz / 80 VA

Battery 24 VDC (max 34 Ah)

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.5 FXS panel external connections, SLC

Master controller

FX-MC2

Fire Detection

Serial (RS485) communication with other FX panels (2 pcs)

Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX

Serial (RS232) communication with printer or maintenance tool (PC)

Ethernet connection, INFO communication: Future option

USB connection, maintenance tool (PC)

Fire Alarm Router Equipment (Alarm transmitter)

Fault Warning Router Equipment (Alarm transmitter)

Fire Alarm Output

Power supply output 24 VDC, short circuit protected, 500 mA

Monitored output (Bells, sounders, beacon), 500 mA

Power supply input 24 VDC (2 pcs) from an FX, FXL or FXM panel, separately monitored for low voltage

Fault in Fire Alarm Router Equipment (Alarm transmitter)

Fault in Fault Warning Router Equipment (Alarm transmitter)

49

REPX-OB or

MCOX-OB or

ZLPX-IC

INFO communication

INFO communication

External communication (not in ZLPX-IC)

Loop controller

FX-SLC

0…1 pcs

For each FX-SLC: Two addressable detection circuits, each with 159 detector addresses + 159 IO-module addresses

For each FX-SLC: Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Loop controller

FX-CLC

0…1 pcs

For each FX-CLC: 16 Conventional detection circuits, function configurable

Input/output controller

FX-IOC

0…1 pcs

Clean contact signal inputs (4 pcs), function configurable

Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable

Monitored relay outputs (4 pcs), max 500 mA each, function configurable

Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Output controller

FX-OCA

0…1 pcs

Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.6 FXS panel external connections, ALC

Master controller

FX-MC2

Fire Detection

Serial (RS485) communication with other FX panels (2 pcs)

Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX

Serial (RS232) communication with printer or maintenance tool (PC)

Ethernet connection, INFO communication: Future option

USB connection, maintenance tool (PC)

Fire Alarm Router Equipment (Alarm transmitter)

Fault Warning Router Equipment (Alarm transmitter)

Fire Alarm Output

Power supply output 24 VDC, short circuit protected, 500 mA

Monitored output (Bells, sounders, beacon), 500 mA

Power supply input 24 VDC (2 pcs) from an FX, FXL or FXM panel, separately monitored for low voltage

Fault in Fire Alarm Router Equipment (Alarm transmitter)

Fault in Fault Warning Router Equipment (Alarm transmitter)

50

REPX-OB or

MCOX-OB or

ZLPX-IC

INFO communication

INFO communication

External communication (not in ZLPX-IC)

Loop controller

FX-ALCA, FX-ALCB

0…1 pcs

FX-ALCA: One addressable detection circuits, with 126 addresses

FX-ALCB: Two addressable detection circuits, each 126 addresses

FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA

FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each

Loop controller

FX-CLC

0…1 pcs

For each FX-CLC: 16 Conventional detection circuits, function configurable

Input/output controller

FX-IOC

0…1 pcs

Clean contact signal inputs (4 pcs), function configurable

Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable

Monitored relay outputs (4 pcs), max 500 mA each, function configurable

Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each

Output controller

FX-OCA

0…1 pcs

Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable

Note!

The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.0 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.

Note!

The max. current consumption of the FXM - control panel

(with PSA- power supply board), all loops and addresses and all control panel outputs is 0.5 A in standby condition and 2.2 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.7 Connectors on the MC2 board

Terminal name

PI 1

Connector symbol

24 V -

24 V +

Purpose

Power supply 1 in (-)

Power supply 1 in (+)

PI 2

PO

MO

CO 1

CO 2

CO 3

24 V -

24 V +

24 V -

24 V +

-

+

Power supply 2 in (-)

Power supply 2 in (+)

Power supply out (-)

Power supply out (+)

Monitored output line (-)

Monitored output line (+)

Relay output 1 NC

Relay output 1 C

Relay output 1 NO

Relay output 2 NO

Relay output 2 C

Relay output 2 NC

Relay output 3 NC

Relay output 3 C

Relay output 3 NO

+

IN 1 Input 1

-

+

IN 2 Input 2

-

RS232

SYSTEM 1

SYSTEM 2

RS485/RS232

Ethernet

USB

CTS

RTS

GND

RxD

TxD

T/R +

T/R -

Gnd

T/R +

T/R -

Gnd

T/R +

T/R -

Gnd

RJ45

Micro

USB

Clear To Send

Request To Send

Ground

Received data

Transmit data

Transmit/Received Data +

Transmit/Received Data -

Ground

Transmit/Received Data +

Transmit/Received Data -

Ground

Transmit/Received Data +

Transmit/Received Data -

Ground

INFO communication

Fire Detection

51

Description

For external power supply only. Not to be used if the panel is equipped with an internal power supply unit.

For external power supply only. Not to be used if the panel is equipped with an internal power supply unit.

Power supply out for auxiliary equipment

General fire monitored output line as default. Other functions can be selected with the configuration tool.

Fire alarm router output as default

Fault warning router output as default. The relay is energized in normal condition (as drawn) and releases in fault condition.

Fire alarm output as default

Fault in fire alarm router. Monitored and normally open as default function. Other functions can be selected with the configuration tool.

Fault in fault warning router. Monitored and normally open as default function. Other functions can be selected with the configuration tool.

Serial communication with printer or configuration / maintenance tool

Serial communication with other FX panels

Serial communication with other FX panels

Serial communication with INFO/FMP/MCO/ABC or other alarm management systems

Future option

Configuration / Maintenance tool

RS485

Gnd - +

SYS 1

Gnd - +

RS232

Tx Rx Gnd

SYS 2

Gnd - +

CO3

NO C NC

RS232

Tx Rx Gnd Cs Rs

+ PO -

CO2

NC C NO

CO1

NO C NC

- + - + + PI1

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.8 Connectors on the PSA and PSB - board

Connector symbol

Purpose

Terminal name

30 VAC

BATT

PO 1

PO 2

-

+

24 V -

24 V +

24 V -

24 V +

Battery -

Battery +

Power supply 1 out -

Power supply 1 out +

Power supply 2 out -

Power supply 2 out +

Fire Detection

Description

30 VAC input from transformer.

Connection for the standby battery.

Power supply output 1 for external load.

Power supply output 2 for external load.

52

PO 2

+24V-

PO 1

+24V-

20.9 Connectors on each SLC board

Terminal name

PO 1

PO 2

LOOP 1

LOOP 2

Connector symbol

24 V -

24 V +

24 V -

24 V +

B -

B +

A -

A +

B -

B +

Purpose

Power supply out (-)

Power supply out (+)

Power supply out (-)

Power supply out (+)

Return end -

Return end +

Outgoing end -

Outgoing end +

A -

A +

Return end -

Return end +

Outgoing end -

Outgoing end +

BATT

+ -

Description

Power output for loop devices in loop 1 that require external power supply.

Power output for loop devices in loop 2 that require external power supply.

System Sensor- loop devices.

System Sensor- loop devices.

Loop 2

A+ A-

Loop 2

B+ B-

Loop 1

A+ A-

Loop 1

B+ B-

PO 2

+24V-

PO 1

+24V-

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.10 Connectors on each CLC board

Terminal name

Connector symbol

Purpose

1

16

-

+

-

+

Conventional line 1 -

Conventional line 1 +

Conventional line 16 -

Conventional line 16 +

Description

Fire Detection

53

+ 16 + 15 + 12 + 11 + 8 + 7 + 4 + 3 -

+ 14 + 13 + 10 + 9 -

20.11 Connectors on each IOC board

Terminal name

Connector symbol

Purpose

1

2

Monitored output line 1 -

Monitored output line 1 +

Monitored output line 2 -

Monitored output line 2 +

3

4

PO 1

PO 2

24 V -

24 V +

24 V -

24 V +

Monitored output line 3 -

Monitored output line 3 +

Monitored output line 4 -

Monitored output line 4 +

Power supply 1 out -

Power supply 1 out +

Power supply 2 out -

Power supply 2 out +

CO 1

CO 2

Relay output 1 NC

Relay output 1 C

Relay output 1 NO

Relay output 2 NC

Relay output 2 C

Relay output 2 NO

IN 1

IN 2

IN 3

IN 4

-

+

-

+

-

+

-

+

Clean contact input 1

Clean contact input 2

Clean contact input 3

Clean contact input 4

+ 6 + 5 + 2 + 1 -

Description

Fire monitored output line as default.

Fire monitored output line as default.

Fire monitored output line as default.

Fault warning device line as default.

Power supply output 1.

Power supply output 1.

Clean contact relay output. General fire alarm output as default.

Clean contact relay output.

IN 4

+ -

IN 3

+ -

IN 2

+ -

IN 1

+ -

CO 2 CO 1 PO 2

+24V-

PO 1

+24V+ 4 + 3 + 2 + 1 -

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.12 Connectors on each OCA-board

Terminal name

Connector symbol

Purpose

CO 1-2

Relay output 1-2 NC

Relay output 1-2 C

Relay output 1-2 NO

Relay output 3-4 NC

CO 3-4

CO 5-6

CO 7-8

Relay output 3-4 C

Relay output 3-4 NO

Relay output 5-6 NC

Relay output 5-6 C

Relay output 5-6 NO

Relay output 7-8 NC

Relay output 7-8 C

Relay output 7-8 NO

CO 9-10

CO 11-12

CO 13-14

CO 15-16

Relay output 9-10 NC

Relay output 9-10 C

Relay output 9-10 NO

Relay output 11-12 NC

Relay output 11-12 C

Relay output 11-12 NO

Relay output 13-14 NC

Relay output 13-14 C

Relay output 13-14 NO

Relay output 15-16 NC

Relay output 15-16 C

Relay output 15-16 NO

Description

Fire alarm output.

Fire door output.

Pre-alarm output.

Technical alarm output.

Fault warning output.

Disablement output.

Access level 2 output.

Fire Detection

Maintenance warning output.

54

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.13 Connectors on each ALCA- board

Terminal name

Connector symbol

Purpose

PO 1

LOOP 1

24 V -

24 V +

B -

B +

A -

A +

Power supply out (-)

Power supply out (+)

Return end -

Return end +

Outgoing end -

Outgoing end +

Description

Fire Detection

55

Power output for loop devices in loop 1 that require external power supply.

Intellia loop devices.

20.14 Connectors on each ALCB- board

Terminal name

PO 1

PO 2

LOOP 1

LOOP 2

Connector symbol

24 V -

24 V +

24 V -

24 V +

B -

B +

A -

A +

B -

B +

Purpose

Power supply out (-)

Power supply out (+)

Power supply out (-)

Power supply out (+)

Return end -

Return end +

Outgoing end -

Outgoing end +

A -

A +

Return end -

Return end +

Outgoing end -

Outgoing end +

Description

Power output for loop devices in loop 1 that require external power supply.

Power output for loop devices in loop 2 that require external power supply.

Intellia loop devices.

Intellia loop devices.

Loop 2

A+ A-

Loop 2

B+ B-

Loop 1

A+ A-

Loop 1

B+ B-

PO 2

+24V-

PO 1

+24V-

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3 Fire Detection

20.15 Connectors on FMPX, DAPX, REPX and REPX-OB- board and MCOX and MCOX-OB- board

Isolated serial port for

3 rd

part external devices

Terminal name

RS232

RS485

Connector symbol

TXD

RXD

GND

RTS

CTS

T/R-

Description

For 3 rd

part devices. Ie. integration to BMS.

Line IN

RS485

RS232

T/R+

GND

T/R-

T/R+

TXD

RXD

GND

GND

Configuration / input port. Panel connection must be disconnected during configuration.

Line OUT RS485

Power input 1 PI 1

Power input 2 PI 2

T/R-

T/R+

24 V -

24 V +

24 V -

24 V +

For PELCO devices using INFO- protocol.

Note! Both inputs must be connected.

56

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

20.16 Connectors on CODINET modem adapter

Terminal name

Connector symbol

Purpose

CO1

(D9-connector)

2:RxD (in)

3:TxD (out)

4:DTR (out)

5:ISO GND

TE4

TE3

6:DSR (in)

7:RTS (out)

NC

DSR

RxD

TxD

ISO GND

DTS DTR

RS232-line.

TE2

TE1

+24 V

GND

T/R+

T/R-

R+

R-

ISO GND

Power input. (Isolated)

RS485-line.

J1 Mounted

Terminating resistor of 120 ohm between ±T/R. Normally not used.

J2

Mounted

(default)

Not mounted

RS485 2-wires, ±T/R.

RS485 4-wires, ±T/R and ±R.

Description

Fire Detection

57

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

0832

Pelco Finland Oy P.O. Box 415, 02601 Espoo Finland

For FX 0832-CPD-1082 Issue 4

For FXL 0832-CPD-1083 Issue 3

For FXM 0832-CPD-1084 Issue 3

EN 54-2:1997/AC:1999/A1:2006

EN 54-4:1997/AC:1999/A1:2002/A2:2006

Options:

7.8; 7.9.1; 7.10.3; 7.11; 7.12.2; 7.13; 8.3; 8.4; 8.9; 9.5;

10

Control and indicating equipment for fire detection and fire alarm systems for buildings

FX, FXL, FXM

Other technical data:

66571764: installation and commissioning

66571744: operation manual

66571758 (SLC), 66571761 (ALC): system planning (held by the manufacturer )

Pelco Finland Oy

P.O.Box 415, 02601 Espoo

Kalkkipellontie 6, 02650 Espoo

Tel. 010 446 511

Fax 010 446 5103 www.pelco.com/nordic

Fire Detection

58

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents