- Home
- Home security & automation
- Security access control systems
- Schneider Electric
- FX 3NET
- Datasheet
advertisement
Installation Instruction 66571764GB3
16/2012
FX 3NET FIRE ALARM SYSTEM
Installation and commissioning manual
Fire Detection
Read this manual carefully before installation and commissioning!
Installation and commissioning must be performed according to this manual.
This Installation and Commissioning Manual is to be kept together with the control panel.
Installation Instruction 66571764GB3 Fire Detection
2
Contents
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
3
Connectors on FMPX, DAPX, REPX and REPX-OB- board and MCOX and MCOX-OB- board .... 56
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
4
10
11
12
13
14
15
16
6
7
8
9
2
3
4
5
1. About this document
For non-experienced installers this document provides sufficient information to install the FX_ panel (FX, FXL;
FXM, FXS) and to commission the whole system successfully.
Experienced installers may select to connect all loops and IO connections at once without testing the connections in between.
However, it is strongly recommended always to do the preliminary checks and an initial test run before any cables
(except the necessary main supply) are connected to the panel.
This document uses the following acronyms for the various units (component boards) in the panel:
1 MC2 – Master Controller
PS – Power Supply
UI2 – User Interface
SLC – Loop Controller
CLC – Conventional Line Controller
ALC - Loop Controller
IOC - IO Controller
OCA – Output Controller
LB2-32 – Panel LED Board 2: 32 LED indications
LB80 – Zone LED Board: 80 LED indications
REPX and REPX-OB protocol repeater
MCOX and MCOX-OB logical controller
ZLPX and ZLOX-IC Zone Led control unit
CODI – Communication adapter
FMPX – Fireman panel
DAPX – Delay alarm panel
NOTE: If SLC loop controller is configured to LC protocol, please read document.O1771GB0
2. Typical placement of the units in a panel
FX cabinet
The FX cabinet has space for the following
- 1 x UI2
- 1 x MC2
- 1 x PSB (4.0 A)
- 2 x Battery (B) 12 V / 17 Ah
- Option board (OP) total 5 pcs:
SLC/ALC/CLC, max. 4 pcs
IOC, max. 4 pcs
OCA, max. 4 pcs
MCOX-OB, max. 1 pcs
REPX-OB, max. 1 pcs
ZLPX-IC, max. 1 pcs
MC2
PSB
OP
OP
B B
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
FXL cabinet
The FXL cabinet has space for the following
- 1 x UI2
- 1 x MC2
- 1 x PSB (4.0 A)
- Option board (OP) total 9 pcs:
SLC/ALC/CLC, max. 4 pcs
IOC, max. 4 pcs
OCA, max. 4 pcs
MCOX-OB, max. 1 pcs
REPX-OB, max. 1 pcs
ZLPX-IC, max. 1 pcs
MC2
OP
Fire Detection
OP
OP
5
PSB
OP
FXM cabinet
The FX battery cabinet has space for the following
- 1 x UI2
- 1 x MC2
- 1 x PSA (2.2 A)
- 2 x Battery (B) 12 V / 12 Ah
- Option board (OP) total 2 pcs:
SLC/ALC/CLC, max. 2 pcs
IOC, max. 2 pcs
OCA, max. 2 pcs
MCOX-OB, max. 1 pcs
REPX-OB, max. 1 pcs
ZLPX-IC, max. 1 pcs
MC2
PSA
B
OP
B
FXS cabinet
The FXS cabinet has space for the following
- 1 x UI2
- 1 x MC2
- Option board (OP) total 1 pcs:
SLC/ALC/CLC, max. 1 pcs
IOC, max. 1 pcs
OCA, max. 1 pcs
MCOX-OB, max. 1 pcs
REPX-OB, max. 1 pcs
ZLPX-IC, max. 1 pcs
Note! Power supply feed has to be brought from an
FX, FXL or FXM panel.
MC2
OP
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
AX/FX/IX-BAT battery cabinet
The FX battery cabinet has space for the following
- 4 x battery 12 V / 17 Ah
- Fire alarm and Fault warning router
Fire Detection
6
B B
B B
FXM-BAT battery cabinet
The FXM battery cabinet has space for the following
- 4 x battery 12 V / 12 Ah
B
B B
B
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
FX-CAB mounting cabinet
Fire Detection
7
FXM-CAB mounting cabinet
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
FXM-RMFW mounting frame
Fire Detection
8
FXM-RMFW
FXM/
FXM-RMFW
FXM + FX-MAP/
FXM-RMFW + FX-RMFW
FXM + FXM-BAT +FX-MAP/
2 x FXM-RMFW + FX-RMFW
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
FX-RMFW mounting frame
Fire Detection
9
FX-RMFW
FX/
FX-RMFW
FX + FX-MAP/
2 x FX-RMFW
FX + FX-MAP +FX-BAT/
3 x FX-RMFW
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
3. Installation, FX and FXL - control panels
The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet.
The weight of the control panel excl. batteries is 11 kg and incl. batteries (2 x 17 Ah) 23 kg. The weight of the chart file cabinet is 9 kg.
The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.
The weight of the battery cabinet excl. batteries is 7 kg and incl. batteries (4 x 17 Ah) 31 kg.
FX control panel
Chart cabinet
Battery cabinet
Fire Detection
10
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
4. Installation, FXM - control panel
The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet.
The weight of the control panel is exl. batteries is 8 kg and incl. batteries 20 kg.
The weight of the battery cabinet is exl. batteries is 4 kg and incl. batteries 28 kg. The weight of the chart file cabinet is 9 kg.
The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.
FXM control panel
Battery cabinet
Chart cabinet
7
6
Fire Detection
370
370
11
424
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
5. Installation, FXS - control panel
The mounting surface must be flat and it must bear the weight of the control panel and the chart file cabinet.
The weight of the control panel is 4.4 kg.
The weight of the chart file cabinet is 9 kg.
The mounting is to be made straight to the wall surface, without any distance bushings or similar, to ensure ingress protection class of IP30.
FXS control panel
Chart cabinet
Fire Detection
12
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
6. Connecting main power supply
Connect the mains supply (230 VAC)
There must be a separate fuse (10 A) for the control panel power supply.
Cable 3 x 1.5 mm².
Fire Detection
13
Note!
FXS has not any built-in power supply. The power is fed to the FXS panel from FX or FXM power supply unit using 2 power lines. The power supply PI1 and PI2 inputs in FXS are on the MC2 board. Both must be connected and the “PI in use”- jumper on MC2 must be set.
FXS panel: MC2 board
PO 2
+24V-
PO 1
+24V-
FX or FXM panel:
PSA or PSB board
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
14
7. Commissioning
7.1 Necessary devices and documents
Devices
• A universal measuring instrument (voltage, current, resistance, diode).
• A PC and the configuration tool, if the configuration is done when commissioning.
Documents
• This Installation and Commissioning manual.
• Operation manual.
• Planning and installation documents for the project.
• Client/project configuration data if the configuration is done when commissioning.
7.2 Order of commissioning
1. Check that the installation has been done correctly according to the plans.
2. Make preliminary checks on the control panel.
3. Test run the control panel.
4. Connect detector loops.
5. Connect monitored output lines.
6. Make site specific settings.
7. Connect the outputs.
8. Connect the inputs.
9. Connect the serial communication ports.
10. Configure the system if required according to the plan or site specific features.
11. Connect the router to the defined control panel.
WARNING!
Do not use an isolation resistance meter for measuring resistance!
Note!
The system does not require configuration in order to function.
On the other hand, client specific features may require configuration.
Note!
For SLC only (System Sensor devices).
If the system is not configured and a loop has the same addresses for both detectors and I/O-modules, the detectors will be assigned addresses from the low range
(01…159) and the I/O-modules from the high range (201 and 359).
Usually it is easier to start up loops, if the control panel is not configured.
Note!
On ALCA / ALCB - loop (Intellia devices) all detectors and modules must have individual addresses from 1 to 126.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
15
8.
8.1
Preliminary checks
General
The aim of the preliminary checks is to assure that the settings are correct and that the control panel has not suffered any defects during transportation or installation. This is obviously most easy to do when no external cables are connected, except for the necessary power supply connection.
8.2 Preliminary checks
1. Check that all power is disconnected from the control panel.
The cable from the transformer to the power supply component board is disconnected from the terminal 30VAC on the component board.
The battery cable is disconnected from the battery terminal BATT on the component board.
FXS: PI1 and PI2 are disconnected.
2. Check that the mains cable is connected to the mains terminal.
3. Check that the separate fuse reserved for the control panel is in its place.
MC2 jumper settings
‘Side CPU not in use’ jumper should not be in place in FX
NET systems in seeing panels provided with a fire routing equipment. In case of a system fault the assistant processor takes care of the system communication. If there is a fire alarm in one of the system panels the assistant processor controls: o the fire routing output CO1 of the MC2 unit
(independent of the configuration of the CO1) o the fire alarm device output of the MC2 unit
(independent of the configuration of the output) o the general fire alarm LED o the panel specific fire alarm LED (LB2-32) o the buzzer of the panel
1. Check the following settings:
The “CONF” jumper is not in place.
The “PULSED” jumper is not in place (for continuous alarm device signal) or in place (for pulsing alarm device signal).
The “PROG” jumper is not in place.
The “PI IN USE” jumper is not in place.
FXS: PI IN USE in place!
The “IOC’S” jumper is correctly set for the number of
IOC’s and OCA’s in the panel.
The “LC’S” jumper is correctly set for the number of
SLC’s, ALC’s and CLC’s in the panel.
2. Check also that there is a 4.7 k
Ω end-of-line resistor in the terminals for the monitored output line.
3. Check also that there is a 4.7 k
Ω end-of-line resistor in the terminals for the monitored input lines.
CONFIG
PULSED
PROG UPD
PI IN USE
IOC’S LC’S
RS485
Gnd - +
SYS 1
Gnd - +
RS232
Tx Rx Gnd
SYS 2
Gnd - +
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
SLC jumper settings
1. Check the following settings:
“Prog Update” jumper is not in place.
“Dev LED” jumper is in place if you want the detector leds to flash when communicating with the panel or not in place otherwise.
Set the right ID. The range is 1…4/panel and is common to SLC, ALC and CLC units.
2. Check also that there is a wire between A+ and B+ as well as between A- and B- in the terminals for both loops.
Fire Detection
16
CLC jumper settings
1. Check the following settings:
Set the right ID. The range is 1…4/panel and is common to
SLC ALC and CLC units.
Check also that all conventional line terminals have their
EOL resistors connected to the terminals.
ALC jumper settings
1. Check the following settings:
“Prog Update” jumper is not in place.
“Dev LED” jumper is in place if you want the detector leds to flash when communicating with the panel or not in place otherwise.
Set the right ID. The range is 1…4/panel and is common to
SLC, ALC and CLC units.
2. Check also that there is a wire between A+ and B+ as well as between A- and B- in the terminals for both loops.
IOC jumper settings
1. Check the following settings:
Set the right ID. The range is 1…4/FX and FXL panel. The
ID must be different for each IOC and OCA.
The monitored output line configuration jumpers are set for desired operation (pulsed or continuous signal).
Check also that there are 4.7k
Ω end-of-line resistors in the terminals for each monitored output line.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
OCA jumper settings
1. Check the following settings:
Set the right ID. The range is 1…4/FX and FXL panel. The
ID must be different for each IOC and OCA.
Fire Detection
17
2. Press the “BUZZER SILENCE”- button.
9. Control panel test run: Note differences with the FXS!
9.1 Mains connection
Note! The panel is in access level 2 when the cover is removed.
1. Switch the panel on by connecting the cable between the transformer and the terminal 30VAC on the power supply component board.
FXS: Connect power supply cables “P1” and “P2” to the
MC2 PI1 and PI2 terminals.
The backlight of the display flashes for about 20 s.
The display will show the text:
The text “Panel starting up” will disappear from the display when all addresses are scanned for presence.
After approximately one minute from start the panel will indicate a fault alarm due to the missing battery:
Note: FXS does not give any fault alarm, because there in
FXS is not built-in power supply and battery.
LCD display shows:
13:36 14.09.2007
FX
Fire Panel
Activate menu by pressing wheel
Panel starting up
Buzzer beeps continuously.
FAULT-led blinks.
FAULT 1/1
PS battery fault
Panel starting up
The audible signal is silenced.
The “FAULT”- led becomes fixed.
The LCD remains the same.
The panel will also indicate a fault alarm for missing. configuration data if the panel is not configured.
This fault alarm can be reset and will not appear again.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
9.2 Battery connection
1. Install the batteries in the cabinet. Check that the battery cable is disconnected from the battery terminal BATT.
Fire Detection
18
2. Check battery polarity from the markings on the battery.
3. Connect the battery cables to the poles as follows:
The batteries are 12 V batteries. If two batteries are used, they are connected in series.
If four batteries are used, two series connected pairs are connected in parallel (Voltage is 24 VDC).
4. Connect the battery cable to the battery terminal BATT on the PS component board.
5. Reset the battery fault indication in the control panel by pressing the “RESET”- button until the pulsed audible signal stops.
WARNING!
Connecting the batteries in the wrong way may cause a short circuit in the batteries, which may lead to an explosion, a strong electric arc or fire in the battery cables.
The “FAULT”- led goes out.
The display shows the text:
13:36 14.09.2007
FX
Fire Panel
Activate menu by pressing wheel
Panel starting up
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
10. Cable handling and preliminary measurements
WARNING!
Check by measuring that there is no power in the cables.
10.1 Cable handling and measurements
At every stage of commissioning, power must be disconnected from the control panel before the cables are installed.
First disconnect the battery then the mains.
1. Peel off the cable plastic and protective shields. Be careful not to let peeling remains drop onto the component board or between the back wall of the cabinet and the component board.
2. Make sure that the cables have been marked and that the markings can be seen after the peeling.
3. If the cables used are shielded, measure, before connecting the shield that the resistance between the shield and the cabinet ground exceeds 1 M
Ω. If the resistance is smaller, the cable shield is in contact with the construction of the building:
- The outer sleeve of the cable has been damaged.
- The protective shield is in connection to the construction of the building in a detector socket.
Repair the fault. Then connect the cable shield to the cabinet ground.
4. Measure for each cable: the resistance between the cable shield and the wires. The resistance must exceed 1 M
Ω. If the value is smaller, the earth leak must be located and repaired.
>1M Ω
5. If the cables used are not shielded, measure the resistance between the wires and cabinet ground. It must also exceed 1 M
Ω.
>1M Ω >1M Ω
19
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
10.2 Cable table
Cable connection
Addressable detection circuit cables, SLC- loop
Addressable detection circuit cables, ALC- loop
Conventional detection circuit cables, CLC- line
Sub-detection circuits of conventional zone modules, SLC- loop
Sub-detection circuits of conventional zone modules, ALC- loop
Power supply to conventional zone modules
Conductors x area
2 x 0.5 mm
2
+ shield
2 x 1.0 mm
2
+ shield
2 x 0.5 mm
2
+ shield
2 x 1.0 mm
2
+ shield
2 x 0.5 mm
2
+ shield
2 x 1.0 mm
2
+ shield
Sub-detection circuits of conventional zone modules
Sub-detection circuits of conventional zone modules
2 x 0.5 mm
2
+ shield
2 x 1.0 mm
2
+ shield
Conventional Exi-area sub-loop unit
Printer connection
- Serial data
Serial connections
- INFO
- FX NET
2 x 0.5 mm
2
+ shield
2 x 1.0 mm
2
+ shield
2 x 0.5 mm
2
+ shield
5 x 0.5 mm
2
+ shield
3 x 0.5 mm
2
+ shield
Serial connections between FX NET panels, 2 serial line
System1 line
System2 line
FX clean contact input lines
Cable 1:
4 x 0.5 mm
2
+ shield
Cable 2:
4 x 0.5 mm
2
+ shield
2 x 0.5 mm
2
Max. length
810 m
(60
Ω)
1600 m
(60
Ω)
810 m
(60
Ω)
1500 m
(60
Ω)
1200 m
(100
Ω)
2400 m
(100
Ω)
1200 m
(100
Ω)
600m
(50 Ω)
625 m
(50
Ω)
1200 m
(50
Ω)
625 m
(50
Ω)
1200 m
(50
Ω)
150 m
15 m
1000 m
1000 m
1000 m
Comments
Cable resistance max. 50
Ω.
From panel through the address module to the Eex barrier resistance max. 50
Ω total. If power supply is brought to several units through the same cable, the real length of this part must be multiplied with the number of units when comparing with the maximum length.
Loop resistance from the Exi-barrier to most distant detector max.12
Ω. Loop capacitance max. 390 nF.
RS232
RS485
Fire Detection
20
The cable resistance of the loop is max. 60
Ω and the capacitance max. 180 nF between conductor and shield, 360 nF between conductors. Max. voltage drop is 6 V.
The cable resistance of the loop is max. 60
Ω and the capacitance max. 180 nF between conductor and shield, 360nF between conductors. Max. voltage drop is 9 V.
The cable resistance of the loop is max. 50
Ω, if an Exi barrier is connected to the loop, otherwise max 100
Ω.
The max. allowed capacitance of the cable is 0.5µF.
Conventional zone module EM210E-CZ, EM210E-CZR,
M512ME and conventional detectors or conventional manual call points.
Conventional zone module EMI-310-CZ / EMI410-CZ and conventional detectors or conventional manual call points.
2 X RS 485
Note!
Isolated Gnd terminals in RS485 Serial connection must be connected between the panels using signal wire not shield.
FX clean contact output lines
2 x 0.5 mm
2
2 x 1.0 mm
2
or
FX monitored output lines – fire bell, sounder line
- fault buzzer line
Addressable monitor modules, SLC- loop
- monitor lines
Addressable control modules, SLC- loop
- power supply
2 x 0.5 mm
2
2 x 1.0 mm
2
or
2 x 2.5 mm
2
or
2 x 0.5 mm
2 shield
2 x 0.5 mm
2 x 1.5 mm
2 x 2.5 mm
2
2
2
+
or
or
2000 m
To be calculated separately
The equipment receiving the contact signal may have restrictions on cable properties.
Load controlled by the relay output may restrict allowed resistance and length per cross section.
Relay contact rating is 30 VDC 1 A
To be calculated separately
Max. allowed voltage drop defines cable to be used.
625 m
(50
Ω)
Monitor modules M500ME, M503ME, M501ME,
EM210E, EM220E, EM221E.
To be calculated separately
Control modules M500CHE, EM201E, EM221E, M201 and
M240.
Number and distances of the relay control modules define the
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
21
- alarm line
Addressable monitor modules, ALC- loop
- monitor lines
Addressable control modules, ALC- loop
- power supply
- alarm line
Mains supply cable
2 x 0.5 mm
2
+ shield
2 x 0.5 mm
2 x 1.5 mm
2
2
or
2 x 2.5 mm
2
or
3 x 1.5 mm
2
625 m
(50
Ω) conductor area and length of the power supply cable.
Monitor modules EMI- 310, EMI-310+, EMI-311, EMI-311/240,
EMI-333, -EMI-410, EMI-410+, EMI-411.
Mini monitor modules 55000-833 APO, 55000-832 APO.
To be calculated separately
Control modules EMI-301, EMI-311, EMI-311/240, EMI-301S,
EMI-401, EMI-401S,EMI-411.
Mains connection:
- 230 ±10% V AC, 50-60 Hz, - maximum power 160 W
- separate fuse 10 A
Note!
The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.0 A in alarm condition.
The standby time required for the system may limit the max. load of the outputs.
Note!
The max. current consumption of the FXM - control panel (with PSA- power supply board), all loops and addresses and all control panel outputs is 0.5 A in standby condition and 2.2 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
22
11. Addressable detector loops
11.1 Measuring the Cables
Disconnect all power from the control panel.
1. Measure the resistance between the loop wires + and - so that the resistance meter positive (feeding) probe is in the
+ -conductor. The resistance must exceed 1 k
Ω. If the resistance is smaller, locate the cause of the fault and repair it. (It may be a detector or address unit connected the wrong way or a short circuit isolator).
First disconnect the battery, then the mains
>1k
Ω
2. Measure the loop cable + wire resistance from the output and return ends. Also measure the – wire. The loop resistance of the + and – wires added together can be max. 60
Ω on SLC - loop and 60 Ω on ALC - loop.
The difference between the + and – wire resistances should not exceed 5
Ω. The possible causes of a fault must be located and repaired.
Note!
If there are short circuit isolators in the loop, resistance measuring of the loop cable will give false results. The short circuit isolators must be by-passed by connecting links over the isolators.
<30
Ω
<30
Ω
3. Remove short circuit isolators’ by-passes.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
11.2 Connecting the loop to the control panel
Each FX-SLC and FX–ALCB board has connectors for two loops, FX-ALCA board has only one loop.
1. Check that all power has been disconnected from the control panel.
2. If shielded cable is used, connect the shield to the nearest earth screw in the back plate.
3. Connect the loop wires to the LOOP terminals of the
SLC/ALC board.
Outgoing end to terminals A+ and A-.
Return end to terminals B+ and B- .
23
11.3 Functional check of the loop
1. Start the control panel by switching the power on.
2. Wait until the text “PANEL STARTING UP” disappears from the display (about 3 minutes).
3. Verify in the panel display that all addresses are indeed found by selecting “Loops/Address points” from the menu, and stepping through all addresses in all loops. (This is not necessary if the panel is configured).
First connect the transformer cable, then the battery cable.
The text ‘Panel starting up’ disappears from the bottom of the display.
The detector loop is in order if the control panel does not give fire, fault or service indications at the start up.
Otherwise the fault must be located by following the instructions below.
4. If the panel indicates fire alarm, press the “BUZZER
SILENCE” button, scroll the alarm indications with the
“MORE ALARMS”- button and note them.
Possible causes for fire alarm:
- A manual call point is pressed down; the glass has been broken or taken off.
5. Eliminate the causes of fire alarm and reset the indications by pressing the “RESET”- button until the pulsed signal stops.
6. Repeat the above mentioned procedures until there are no more fire alarms.
-
-
A manual call point or another device connected to the input of an addressable monitoring unit is in active state.
Smoke, water vapour or thick dust in a smoke detector.
- Heat close to a heat detector.
Possible causes for fault or maintenance warnings:
7. If the panel indicates fault or maintenance warning press the “BUZZER SILENCE” button, scroll the indications with the “MORE ALARMS”- button and note them.
8. Eliminate the causes of fault and maintenance warnings and reset the indications by pressing the “RESET”- button until the pulsed signal stops.
9. Repeat the above mentioned procedures until there are no more fault and maintenance warnings.
-
-
-
A break or a short circuit in the loop. See below for how to find the fault.
An earth leak in the loop. See below for how to find the fault.
An address fault in the loop. See table below for possible address fault indications.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
24
A short circuit indication is caused by a loop component connected the wrong way or a short circuit in the wires. If short circuit isolators are used, the shorted part of the loop between the closest isolators will be non-operative. By scrolling trough the addresses list for the shorted loop and comparing with the installation plan, the shorted area can be located. (If the panel is configured, it will indicate fault alarm for all addresses between the operated short circuit isolators).
A break in the loop is easily found by disconnecting the return end of the loop and comparing the addresses that the panel can communicate with, with the installation plan.
An earth fault can most easy be found by splitting the loop in two parts, disconnecting the return end of the loop from the panel and restart. If the panel still indicates earth fault, the location is in the still connected part of the loop, otherwise in the non-connected part. By splitting the faulty part of the loop in two and restarting again, you will soon find the reason for the earth fault.
Fault and maintenance warnings of the loop devices are identified by codes in the display. The codes and a short explanation of each are listed below.
Fault and maintenance warnings of address point
s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)
The loop has to be re-scanned again after the reason of warning has been fixed.
r = running time when device is normally monitored
c = loop is configured with PC
n = loop is not configured
MAINTENANCE 00: (s,c)
MAINTENANCE 01: (s,c)
MAINTENANCE 02: (s,c)
− The anytype of device has been configured for this address but no device is installed.
Indicated only once and will disappear after resetting the warning
− No device has been configured to this address but some device is installed.
Indicated only once and will disappear after resetting the warning
− Definite type of device has been configured but no device is installed.
This warning can be removed only by installing device to this address or changing the configuration and scanning the loop again.
− The configured type/family and installed type/family is not the same or
MAINTENANCE 03: (s,c) protocols of devices are not same (types are.
This warning can be removed only by changing device to this address or changing the configuration.
MAINTENANCE 04: (s,n) − NA
MAINTENANCE 05: (s,n) − Illegal address. For example address 0 found in the loop scanning phase.
− Factory setting of address switches are 0,0. The LED’s of the unit blinks
FAULT 06: (s,c/n)
FAULT 07: (s,n)
FAULT 08: (s,n)
FAULT 09: (s,c/n) automatically for easier identification (when LED blink jumper is not installed).
Note! It is not possible to detect any other fault or fire conditions for a unit that has the 00 address.
− Unknown type of device installed to the loop. The address is not polled any more.
− Device removed from this address during the loop disablement. The fault is detected when the loop is re-enabled again.
Note! The panel has to be boot to clean up MC loop database
− The type of device is changed during the loop disablement.
Note! The panel has to be boot to clean up MC loop database
− New addresses (devices) are found in the loop.
Indicated only once and will disappear after resetting the warning
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
25
MAINTENANCE 11: (s,c) − Siren control (separate remote LED control) have been configured for
SySe sensor (500 series) but the feature not exist in the sensor (old one)
− Technical alarm input configured for LC address but SW version of LC is
FAULT 12: (s,c)
FAULT 13: (s,c/n) not compatible (> 1.3),
− Two or more Apollo devices are at the same address ("double address”).
MAINTENANCE 14:(s,c/n)
− Bad scan responses of a device.
MAINTENANCE 15:(s,c/n) − The type ID bits is not compatible with memory ID of Apollo unit
MAINTENANCE 16: (s,c) − Apollo protocol family of device and configuration mismatch
FAULT 17: (s,c/n)
(S90/XP95/Discovery),
− Two or more SySeAp devices are at the same address ("double address”) Yellow LED of units is ON.
− Two or more SySeClip and SySeAp devices are at the same address
FAULT 18: (s,c/n)
("double address”).
MAINTENANCE 19:(s,c/n) − “Sub” address of SySeAp multi module overlaps with a some other unit.
−
FAULT 20: (r)
MAINTENANCE 21: (r)
FAULT 22: (r)
FAULT 51: (r)
− There is an internal fault in a SySeAp device
− A SySeAp device is detached and attached at the loop (powered up)
− A sub address of multi module is out of the address range (a sub address would be > 159)
− Too low analog value received from analog sensor or fault in the internal
FAULT 52: (r)
FAULT 53: (r)
FAULT 54: (r)
FAULT 55: (r)
FAULT 56: (r)
FAULT 57: (r)
FAULT 58: (r)
MAITENANCE 59: (r)
MAINTENANCE 60: (r)
MAINTENANCE 61: (r)
FAULT 62: (r)
FAULT 63: (r)
FAULT 64: (r)
FAULT 65: (r)
FAULT 66: (r) operation of an sensor
− The address does not respond (or bad response)
− Two or more devices have the same address ("double address”).
− Break in the input circuit of a monitor module.
− Break in the output circuit of a control module.
− Short circuit in output circuit of a control module.
− The input unit has been configured as "fault input". When the input alarm activated the FX shows it as fault warning.
− The input unit has been configured as "zone disablement device" and the disablement time exceeds (default time 12 hours).
− The input unit is configured as "maintenance input". When the input alarms the FX shows it as maintenance warning.
− A dirty detector. If the analog value of the detector has exceeded the maintenance limit for more than 24 hours, this warning is indicated.
− If detector exceeds value (during 24h) after user reset this fault warning, fault warning is re-generated immediately.
− Also at case that value of some other detector(s) stay over the maintenance limit (but 24h timeout has not expired) at the moment when user select from the menu “report dirty detector” and press “enable” at access level 3, this fault warning is created.
− drift compensation alert of 2251TEM / 7251LASER / OMNI and other new intelligent sensors. (OMNI / 2251TEM >200 <560; 7251LASER
>200 < 650)
− 6 months to cell life expiration of CoPTIR sensor
− Break or short circuit at the conventional sub loop of conventional zone module.
− Invalid response from detector (> 4000 µs for normal sensors, >860 and
< 1600 for the OMNI sensor .
− Unstable value read from SySeAp device
− System Sensor beam detector 6500 in alignment mode.
− Device type (or functional type ) changed when loop is running.
− Sensor with separate remote LED control feature is changed to same type device without this feature. More often this event is indicated with fault 64
− Input alarm function is "fault in extinguisher". When module alarms FX
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
26
MAINTENANCE 67: (r)
MAINTENANCE 68: (r)
MAINTENANCE 69: (r)
FAULT 70: (r)
FAULT 71: (r)
FAULT 72: (r)
FAULT 73: (r)
FAULT 74: (r)
FAULT 75: (r)
FAULT 76: (r)
FAULT 77: (r)
FAULT 78: (r)
FAULT 79: (r)
FAULT 80: (r)
FAULT 81: (r)
FAULT 82: (r)
FAULT 83: (r)
FAULT 84: (r)
FAULT 85: (r,s)
FAULT 86: (r)
FAULT 87: (?) show it as fault warning.
− Saturation of infrared detector at CoPTIR/PTIR sensor
− 80% of drift limit (when “report dirty detector” requested)
− 99% of drift limit (when “report dirty detector” requested)
− Undefined fault code from ALC/SySeAp device.
− Memory write operation of the device failed
− Memory read operation of the device failed
− Communication troubles with device.
− Self test of the detector failed.
− Beam sensor CPU fault
− Beam sensor align targeting
− Beam sensor general fault
− Beam sensor signal too high
− cell life expiration of CoPTIR sensor
− The SW of ALC board is not compatible for desired sounder mode
− Input module has been configured as "fire router fault". When module alarms FX show it as fault warning.
− Input module has been configured as "VACIE fault". When module alarms FX show it as fault warning.
− Unsupported address device has been configured to the loop of LC board
(The SW of LC is older than configuration made with WinFXNet).
− Power failure of supervised output circuit of a module
− The OEM code of the device is not Esmi/Pelco code.
− The control of output of SySeAp device did not work
MAINT 88: (?)
MAINT 89: (?)
FAULT 90: (r,s)
− Unacceptable device
ALC: detector is not Intellia, device is XP95 but not configured
MAINTENANCE 91: (r)
FAULT 92: (r)
FAULT 93: (r)
FAULT 94: (r)
FAULT 95: (r)
FAULT 96: (?)
MAINTENANCE 98: (r)
FAULT 99: (r)
− break in input line of the CLC unit
− short circuit in input line of the CLC unit
− voltage problem in input line of the CLC unit
− Voice evacuation mute input active time expired
−
− simulated maintenance (service command)
− simulated fault (service command)
s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)
r = running time when device is normally monitored
c = loop is configured with PC
n = loop is not configured
Note !
Fault delays / timeouts
Reason for Fault 52 ( no PW1 received) must be active for 99sec. before the fault is shown.
Delay for fault 63 (PW4 out of limits) is 30 sec. if any good pulses are received, counter will stop, and if no bad pulses with in 10sec, the counter is reset
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
12. Conventional detector lines
12.1 Measuring the Cables
1. Disconnect all power from the control panel.
2. Measure the resistance between the wires of the conventional line cable. Set the meter to low voltage resistance measurement
(not diode measurement).
Depending on connected devices the result should be:
- If all devices are normally open (NO) types and no EOL resistor is connected the meter should indicate a break in the line
- If all devices are normally open (NO) types and an EOL resistor is connected the meter should indicate the value of the EOL resistor.
- If some devices are normally closed (NC) types the meter should indicate the parallel connection of the series resistances of those devices
If the resistance meter indicates other values, the cause of the fault must be located. (It may be a detector connected the wrong way or a short circuit in the conductors).
3. Short-circuit the wires of the conventional detection line cable at the control panel during measuring.
4. Disconnect the end-of-line resistors from those conventional detection line terminals to which the cables are to be connected.
5. Take the end-of-line resistor with you and walk to the end of the line and measure the resistance between the wires of the cable.
The maximum allowed resistance is 100
Ω (50 Ω if the line goes through an Exi barrier). If the resistance is higher, there is a break in the line (did you remember short-circuit the cable wires at the control panel). Locate the breaks and eliminate them.
6. Connect the end-of-line resistors to their respective places (the last detector or manual call point of the line or the end-of-line unit box connected after the last device).
Fire Detection
27
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
28
12.2 Connection principles
12.2.1 Conventional line
Min/max. value of conventional devices internal resistance is depending of detectors threshold voltage and the
EOL.
Conventional line 4k7
End of line resistance: 4k7, 5%
Max. Line resistance: 100 Ω
Max load from all detectors in loop: 1.8 mA
Line resistance max. 100
Ω
Compatible detectors
(threshold voltage / alarm resistance):
8V / 50 -
1000 Ω, 5 %
5V / 110 -
1300 Ω, 5 %
3V / 140 –
1500 Ω, 5 %
1V / 180 –
1700 Ω, 5 %
0V / 200 –
1800 Ω, 5 %
Conventional line 2k94
End of line resistance: 2k94, 1%
Max Line resistance: 100 Ω
Max load from all detectors in loop: 4 mA
Compatible detectors (threshold voltage / alarm resistance):
8V / 50 -
550 Ω, 5 %
5V / 110 -
750 Ω, 5 %
3V / 150 –
880 Ω, 5 %
1V / 190 –
1010 Ω, 5 %
0V / 210 –
1070 Ω, 5 %
Line resistance max. 100
Ω
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
12.2.2 Input line
End of line resistance: 4k7, 5%
Max. Line resistance: 100 Ω
Alarm resistance: 1k33 – 2k15, 5% (e.g. 4k87 and 2k94 in parallel = 1k833)
Line resistance max. 100
Ω
Fire Detection
29
Line resistance max. 100
Ω
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
12.3 Connecting the line to the control panel
Each CLC board has 16 conventional lines (detection circuits).
1. Disconnect all power from the control panel.
2. If shielded cable is used, connect the shield to the cabinet ground screw in the back plate.
Note!
The free shielded wire must be as short as possible!
3. Connect the pair of wires of the conventional line to the terminals of the CLC board retaining polarity.
Fire Detection
30
12.4 Functional check of the loop
1. Start the control panel by switching the power on. First connect the transformer cable, then the battery cable.
2. Wait until the text “PANEL STARTING UP” disappears from the display (about 3 minutes).
The detector loop is in order if the control panel does not give fire, fault or service indications at the start up.
Otherwise the fault must be located by following the instructions below.
3. If the panel indicates fire alarm, press the “BUZZER
SILENCE” button, scroll the alarm indications with the
“MORE ALARMS”- button and note them.
4. Eliminate the causes of fire alarm and reset the indications by pressing the “RESET”- button until the pulsed signal stops.
Possible causes for fire alarm:
- A manual call point is pressed down; the glass has been broken or taken off.
- Smoke, water vapour or thick dust in a smoke detector.
- Heat close to a heat detector.
5. Repeat the above mentioned procedures until there are no more fire alarms.
6. If the panel indicates fault or maintenance warning press the “BUZZER SILENCE” button, scroll the indications with the “MORE ALARMS”- button and note them.
Possible causes for fault warnings:
- A break or a short circuit in the loop.
7. Eliminate the causes of fault and maintenance warnings and reset the indications by pressing the “RESET”- button until the pulsed signal stops.
8. Repeat the above mentioned procedures until there are no more fault and maintenance warnings.
9. Test that each detector and manual call point gives an alarm. Test procedures for the various devices are given in the documentation for those devices.
- An earth leak in the loop.
Note!
CLC default value for the short circuit is a fault!
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
31
12.5 Compatible detectors and manual call points
Compatibility of detectors with the CLC conventional line is determined by the following factors:
- Supply voltage range
- Current consumption in standby condition
- Voltage across the detector in alarm condition
- Series resistance (either in the detector or in the base)
- End-Of-Line resistor
The voltage supplied by the CLC to the conventional line is 21 Vdc to 24 Vdc. The maximum allowable voltage drop in the cable is 21 V minus the lowest operating voltage of the connected devices.
If the line goes through an Exi barrier, the maximum allowed cable resistance and current consumption is less than for a normal line.
The following table shows the required series resistor for a number of detector voltages (in alarm condition), the two allowed EOL types and whether or not a Exi barrier is connected to the loop.
Conventional Line
EOL resistor / Exi
Max. cable resistance
Max. detector load
Threshold voltage over detector / allowed serial resistance in alarm condition
4k7, 5% / not Exi 2k94, 1% / not Exi
100 Ω 100 Ω
4k7, 5% / Exi
50 Ω
2k94, 1% / Exi
50 Ω
1.8 mA
8 V / 50 -
1000 Ω
4.0 mA
8V / 50 -
550 Ω
1.5 mA
8 V / 10 -
700 Ω
3.0 mA
8V / 10 -
320 Ω
5 V / 110 -
1300 Ω 5 V / 110 - 750Ω 5 V / 150 - 1050 Ω 5V / 170 - 550 Ω
3 V / 140 -
1500 Ω 3 V / 150 - 880Ω 3 V / 250 - 1250 Ω 3V / 280 - 710 Ω
1 V / 180 -
1700 Ω 1 V / 190 - 1010Ω 1 V / 340 - 1500 Ω 1V / 380 - 880 Ω
0 V / 200 -
1800 Ω 0 V / 210 - 1070Ω 0 V / 390 - 1600 Ω 0V / 440 - 960 Ω
Input Line
When CLC input is configured as input line, only EOL 4k7 can be used. If it is configured as Exi-area input, line alarm resistance values are different. See table below and chapter 12.2.2.
EOL resistor / Exi
Max. cable resistance
Alarm resistance
4k7, 5%
100 Ω
1k33 – 2k15, 5%
(e.g. 4k87 and 2k94 in parallel =
1k833)
4k7, 5% Exi
100 Ω
715 –
1870 Ω, 5%
(e.g. 4k87 and 2k94 in parallel =
1k833)
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
13. Monitored output lines
13.1 Measuring the cables and connecting the end-of-line resistors
1. Disconnect all power from the control panel.
2. Measure the resistance between the monitored output line cable wires so that the resistance meter positive (feeding) measuring end is in the “–“ wire of the line. The resistance meter must indicate a break. If the resistance meter indicates a resistance value, the cause of the fault must be located. (It may be an alarm device connected the wrong way, a serial diode missing from the alarm device or a short circuit in the conductors).
Fire Detection
32
OL
3. Short-circuit the monitored output line cable wires at the control panel during measuring.
4. Disconnect the end-of-line resistors from those monitored output line outputs to which the cables are to be connected.
5. Measure the resistance between the wires of the cable at the last alarm device or end-of-line unit box in each monitored output line with the resistance meter. The allowed resistance should not be more than 300
Ω depending on the current consumption of the alarm devices connected to the same line (See picture on the
right). If the resistance is considerably higher, there is a break in the line (did you remember short-circuit the cable wires at the control panel). Locate the breaks and eliminate them.
6. Take the end-of-line resistors to their respective places
(the last alarm device of the line or the end-of-line unit box connected after the last alarm device) and connect them.
Note!
There must not be other resistors or end-of-line units in the monitored output line.
<300 Ω 4k7
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
33
13.2 Connecting the monitored output lines to the control panel
The FX-MC board has one monitored output line connector.
Note! If the ‘Side CPU not in use’- jumper is NOT in place in the MC2 (system assistant processor is in use), then in the case of the MC2 system fault the system assistant processor controls the CO1 output as a fire router output regardless of the configuration.
The FX-IOC board has four monitored output line connectors.
1. Check that all power has been disconnected from the control panel.
2. Connect the monitored output line cable wires to the terminals as follows:
- The fire alarm line is connected to the output marked with bell symbol on the MC and the outputs 1 to 3 marked with the bell symbol on the IOC.
- The fault alarm line is connected to the output 4 marked with the bell symbol on the IOC.
- 4.7 k
Ω resistors are left in the terminals of outputs that are not in use.
Note!
The above usages of the outputs are valid for non-configured panels. If configured, the purpose may have been changed.
Verify with the configuration.
4k7
4k7
4k7
4k7
13.3 Functional check of monitored output lines
1. Start the control panel. The monitored output lines are in order if the control panel does not give fault indications.
2. If the alarm devices give fault indications, press the
“BUZZER SILENCE”- button on the user panel.
3. You may also want to silence fault warning devices by pressing the “SILENCE/RESOUND” button.
Possible causes of fault indications:
- A short circuit in the line, the end-ofline resistor is too small (should be
4.7k
Ω), a serial diode is missing from an alarm device or the device has been connected with the wrong polarity.
- A break in the line, the end-of-line resistor is missing or its resistance is too big.
- An earth leak in the line.
4. Eliminate the causes for fault indication and reset the panel by pressing the “RESET”- button until the audible signal stops.
5. Test the monitored output line operation as follows:
6. Press the wheel to activate the menu and select:
7. Then press the wheel again and select:
8. Press the “TEST”- button, at which the display will show the text:
Pressing the wheel activates all fire alarm devices.
9. The test is stopped by pressing the “TEST”- button. Check the operation of the alarm devices. Eliminate any faults and repeat the test until all alarm devices operate.
Note! Ensure that all persons in the building have been informed of the alarm device test.
CONTROLS
FIRE ALARM DEVICES CONTROL
PRESS WHEEL TO ACTIVATE THE
CONTROL
ACTIVE
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
34
14. Control outputs
14.1 Clean relay outputs
The FX-MC2 board has three clean contact outputs.
Each FX-IOC board has two clean contact outputs.
Each FX-OCA board has 16 clean contact outputs.
The function of the outputs is defined with the configuration tool.
The default functions of the outputs of a control panel that has not been configured are:
MC2-CO1 Note! If the ‘Side CPU not in use’- jumper is in place in the Fire alarm router activation
MC2 (system assistant processor is NOT in use), then in the case of the MC2 system fault the system assistant processor does NOT control the CO1 output as a fire router output regardless of the configuration.
MC2-CO2 Fault warning router activation The relay is energized in normal condition and releases in fault warning condition or if power is removed regardless of
the configuration.
MC2-CO3
IOC-CO1
Fire alarm output
IOC-CO2
OCA-CO1-2
OCA-CO3-4
OCA-CO5-6
OCA-CO7-8
OCA-CO9-10
OCA-CO11-12
Fire alarm output
Fire alarm output
Fire alarm output
Fire door output
Pre-alarm output
Technical alarm output
Fault warning output
Maintenance warning output
OCA-CO13-14
OCA-CO15-16
Disablement output
Access level 2 output
1. Disconnect all power from the control panel.
2. Select suitable outputs and connect the device to be controlled to the output.
The relay contacts are rated for max. 30 VDC, 1 A.
WARNING!
Voltage 230 VAC must not be brought to the relay contacts.
If a device with 230 VAC is to be controlled, a suitable intermediate relay must be used. It is to be placed in a casing outside the control panel cabinet and equipped with a protective diode (e.g.
1N4005).
Test the fire outputs control operation as follows:
SYS 1
Gnd - +
SYS 2
Gnd - +
CO3
NO C NC
CO2
NC C NO
RS232
Tx Rx Gnd
1. Start the control panel.
2. Press the wheel to activate the menu and select:
3. Then press again the wheel and select:
CONTROLS
FIRE OUTPUTS CONTROL
4. Press the “TEST”- button, at which the display will show the text:
5. Pressing the wheel activates all control outputs.
6. The test is stopped by pressing the “TEST”- button.
PRESS WHEEL TO ACTIVATE THE
CONTROL
ACTIVE
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
14.2 Free power outputs
The power supply is normally 27 VDC, max. 500 mA. During a power failure the supply follows the battery voltage. The power supply may momentarily be 30 VDC at the most.
IOC, SLC and ALCB, PO1 and PO2
ALCA only PO1
MC2, only PO
Fire Detection
24VDC / 500mA
35
24VDC / 500mA
24VDC / 2A / 4 A
PSA , PO1 and PO2; 2 A
PSB , PO1 and PO2; 4 A
24VDC / 2 A / 4 A
Note!
The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.5 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.
Note!
The max. current consumption of the FXM - control panel (with PSA- power supply board), all loops and addresses and all control panel outputs is 0.5 A in standby condition and 2.2 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.
1. Start the control panel.
2. If the control panel gives a fault indication press the “BUZZER SILENCE” button. You may also want to press the “SILENCE/RESOUND” button to silence fault warning devices.
3. If the control panel gives an earth fault indication, the cause may be an earth leak in the cable or an earth leak caused by the device to be supplied with power.
4. Power output fault indication means overload or short circuit in the output.
5. Disconnect all power from the control panel, repair any fault and restart the control panel.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
36
15. Signal inputs
15.1 Connecting the inputs to the control panel
The FX-MC2 board has two clean contact input connectors.
Each FX-IOC board has four clean contact input connectors.
Input Default Function
MC2-IN1 Fault in fire alarm router equipment
Default state also configurable as
Normally open / monitored Normally open / closed
Monitored / not monitored
MC2-IN2 Fault in fault warning router equipment Normally open / monitored Normally open / closed
Monitored / not monitored
Normally open / monitored Normally closed / monitored
1k54
4k7
1k54
4k7
Normally closed / not monitored
Input Default Function
IOC-IN1 Fault warning
Normally open / not monitored
Default state also configurable as
Normally closed Normally open
IOC-IN2 Fault in extinguisher Normally closed Normally open
IOC-IN3 Extinguisher activated Normally open Normally closed
IOC-IN4 Smoke vents activated Normally open Normally closed
IN 1
IN 2
IN 3
IN 4
1. Disconnect all power from the control panel.
2. Select suitable inputs and connect the device to be monitored (e.g. extinguisher call point, router fault output) to the control panel.
3. Start the control panel.
4. If the control panel gives an earth leak indication, press the “BUZZER SILENCE”- button and disconnect all power. Repair any fault and restart the control panel.
5. Test the operation of the inputs with the connected device (remember that a fire alarm or fault warning also activates fire and fault alarm devices and alarm routing equipment).
15.2 Testing the inputs
The inputs for Fault in fire alarm router, Fault in fault warning router and Fault in extinguisher can be tested without activation of fault warning outputs, as follows:
Press the wheel to activate the menu and select: INPUT INTERFACES
Then press again the wheel and select:
Press the “TEST”- button, at which the display will show the text:
MC MONITORED INPUT 1 or 2
IN TEST STATE
The display indicates now the status of the input.
The test is stopped by pressing the “TEST”- button.
FAULT or OK
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
37
16. Info-line devices / connections
16.1 INFO-fault messages
Text at display Description fault in info port X comm. info X external device fault 0 info X external device fault 1 info X external device fault 2 info X device fault 3 info X device fault 4
When acknowledge bit not received after 10 retries of some message or external system will send "EXTERNAL FAULT" message
MCO/Repeater reports that outport of the unit has communication fault
MCO/Repeater reports that external port of the unit has communication fault.
MCO reports that control logic part of unit has recognized problems
When transmitting does not success for some reason. Monitored internal by
SW.
Note! configuration bit "not monitored" does not prevent this fault *
When receiver gets whole time a lot of rubbish, not real Info frames. Monitored internal by SW.
Note! configuration bit "not monitored" does not prevent this fault
IC unit reports about power input 1 fault
IC unit reports about fault in the configuration files of IC
IC unit reports about fault which is unknown for FX info X external device fault 5 info X external device fault 7 info X external device fault 255
X = 0; Info configured to RS232 service port
X = 1; Info configured to RS485 at SA board
16.2 FMPX
Picture 1. Connection between FX-panel and FMPX
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
16.3 DAPX
Fire Detection
38
Picture 2. Connection between FX-panel and DAPX
16.4 REPX and REPX-OB
Picture 3. Connection between FX-panel and REPX
Note! If REPX-OB is installed in FX: rack, only INFO line needs to be connected.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
16.5 MCOX and MCOX-OB
Fire Detection
39
Picture 4. Connection between FX-panel and MCOX
Note! If MCOX-OB is installed in FX: rack, only INFO line needs to be connected
16.6 CODI / Codinet
There are two versions of CODIs: CODI and CODINET.
Only CODINET may be used in panel communications (19200bd).
CODI is only up to 9600bd.
The Codinet 24Vdc power input is isolated
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
40
17.
Note! The panel is set to the configuration mode with configuration tool. This can be done also with the following procedure.
Set control panel to access level 3.
1.
2.
3. enter.
4. Repeat with the other digits.
5. Press “ENABLE” when the right code is entered.
6. The panel is now in access level 3.
7.
6.
Configuration
Select with “MENU”-button from main menu.
Press the wheel.
Select the first digit with the wheel and press the wheel to
Set panel to configuration state.
Set control panel to the configuration state by putting a jumper in position “CONF” on the MC board. The display shows the text:
7. Transfer the configuration.
8. Connect configuration cable to the terminal RS232.
9. Configure the control panel with the configuration tool
10. Remove the configuration cable from the terminal RS232
CURRENT ACCESS LEVEL:2
CHANGE TO ACCESS LEVEL 3:0000
CURRENT ACCESS LEVEL: 3
CONFIGUARTION STARTED
READY FOR CONFIGURATION and the jumper from the position “CONF” on the MC.
Restart the panel.
11. Restart the control panel by pressing “RESET” button on the
MC.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
18. Serial communication ports
RS232 and RS485 serial communication ports using INFO protocol are on the top of the FX-MC2 board. These ports are isolated.
FX panel can communicate with INFO devices such as FMPX, MCOX etc. via these ports. Also a printer using serial communication can be connected to either of these ports.
NOTE! Only one of these ports can be connected at a time.
Connectors SYS 1 and SYS 2 are used for interpanel communication in networked systems.
The RS 232 connector in the middle of the connector row is used for configuration and maintenance .
Fire Detection
41
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
18.1 FX 3NET communication network
FX_
FRE
“Seeing”
= Communication cable
- one twisted pair
- shielded
Building 1
FX_
“Seeing”
Fire Routing
Building 2
FX_
“Seeing”
S1
S1
S2
S1
S2
S1
S2
S1
S2
S1
S2
Fire Detection
42
“Visible”
FX_
“Visible”
FX_
“Visible”
FX_
“Visible”
FX_
1a
1b
2a
2b, Spare wire, not in use
System 1(S1) and System 2 (S2) = serial communication line
Picture 5. Example: FX 3NET communication network
18.2 Communication grounding
FX x serial adapter
2b, Spare wire, not in use
FX y serial adapter
1a
1b
2a
1a
1b
2a
2b, Spare wire, not in use
FX x chassis
FX y chassis
2b, Spare wire, not in use
1a
1b
2a
All serial communication cable shields are connected to the grounding filter.
Max length 10mm
All serial communication cable shields are connected to the grounding filter.
Max length 10mm
2a
2b, Spare wire, not in use
Cable shield is connected ONLY in FXNET panel
2b, Spare wire, not in use 2a
FMPX
1b
1a
1b
1a
Picture 6. Communication grounding in the FX NET system
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
18.3 Modem connections in the communication network
1 2 .... N 5 6 .... X
FxNet FxNet
…
FxNet FxNet FxNet
…
FxNet
SAB
SYSTEM SYSTEM
1 2
SAB
SYSTEM SYSTEM
1 2
SAB
SYSTEM SYSTEM
1 2
SAB
SYSTEM SYSTEM
1 2
SAB
SYSTEM SYSTEM
1 2
SAB
SYSTEM SYSTEM
1 2
2x 2W Rs 485 (system1 and system2)
Max cable length 1000m
CodiNet rs232<=>485 converter rs-485
CodiNet rs232<=>485 converte r
Fiber
Modem
Tx Rx rs-232
Fiber
Modem
Tx Rx
Rs 485 / fibre modems ( Moxa)
Multi- or single mode fibres max.fibre legth is depending of the fibre type
Group of
Fx-panels
Fiber
Modem
Fiber
Modem
Fire Detection
43
22 23 .... 32
FxNet
SAB
SYSTEM SYSTEM
1 2
FxNet
SAB
SYSTEM SYSTEM
1 2 rs-485
CodiNet rs232<=>485 converter rs-232
CodiNet rs232<=>485 converter
Fiber
Modem
Tx Rx
Fiber
Modem
Tx Rx
CodiNet rs232<=>485 converter rs-485
CodiNet rs232<=>485 converter
Fiber
Modem
Tx Rx rs-232
Fiber
Modem
Tx Rx
Panels can be connected to this point with modems rs-485
CodiNet rs232<=>485 converter
CodiNet rs232<=>485 converter rs-232
Fiber
Modem
Tx Rx
Fiber
Modem
Tx Rx
…
FxNet
SAB
SYSTEM SYSTEM
1 2
Fiber
Modem
Fiber
Modem
NOTE!
Do NOT connect panels so that the signal path between any panels goes thru more than two modem pairs / line
NOTE 2!
Even if the fiber modem have rs-485 connections it’s allways recommended to use it on rs-232 mode and use CodiNet- coverter between the fiber modem and the panel if the lentgh of the copper cable on the rs-485 connection is more than ~100m
Picture 7. Max. two modem pairs between two panels
1. Disconnect all power from the control panel.
Group of
Fx-panels
No modem connections on this point !
2. Connect the RS485 serial communication wires to the
RS485 terminals (INFO) and
System1 terminals (RS485 type) and
System2 terminals (RS485 type) as follows
Signal wires to terminals T/R + and T/R – and GND.
(Note that shield wire of the cable can not be connected to the GND terminal).
The shields of the cables may not be connected to the metal part (earth) of the cabinet directly. The shields must be connecter through the parallel connected capacitor and varistor as follows
(because long distances may cause big differences in earth potential). Loosen three screws of the backplate. Install the small circuit board from the SA package under the screws and tighten the screws and connect the shield to the terminals.
3. Connect the RS232 serial communication conductors to the RS232 terminals as follows:
The control panel transmitter wire to terminal TxD
The control panel receiver wire to terminal RxD.
GND wire (not shield) to terminal GND.
Connect the shield directly to the metal part (earth) of the cabinet.
4. Start the control panels: first visible panels and
then seeing panels
5. If the control panel gives an earth leak indication, line fault (one of S1 and S2 is not functioning) or communication fault (either of S1 and S2 is not functioning), press the “BUZZER SILENCE”- button and disconnect all power from the control panel. Repair any fault and restart the control panel.
6. If the control panel has been configured, the operation of serial communication should be tested
(remember that a fire or fault also activates fire or fault alarm devices and alarm routing equipment).
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
44
19. Alarm routing equipment
19.1 Connecting the alarm routing equipment to the control panel
The alarm routing equipment must not be connected until all other necessary commissioning procedures have been performed.
Note! Inform the alarm receiver about the alarm routing equipment test.
1. Disconnect all power from the control panel.
2. Connect the alarm routing equipment to the terminals CO1,
CO2 and PO on the MC2 board.
The default function of CO1 and CO2 are:
CO1 = Fire Alarm Router
NOTE! If the ‘Side CPU Not in use’- jumper is in place in the
MC2 (system assistant processor is NOT in use), then in the case of the MC2 system fault the system assistant
-
+
Fire processor does NOT control the CO1 output as a fire router output regardless of the configuration.
CO2 = Fault Warning Router
The PO terminal provides 24 VDC supply for the routing equipment.
Note! CO2 is energized (as drawn) when the panel is in normal condition
3. Start the control panel.
Fault
Fire routing equipment
If the control panel gives a fault indication, press the “BUZZER SILENCE”- button.
If the control panel gives an earth leak indication, the cause may be an earth leak in the cable or an earth leak caused by the alarm routing equipment.
If the control panel gives a power output fault indication, the alarm routing equipment connected draws too much current and is probably faulty or the connection is wrong.
Disconnect all power from the control panel, repair any fault and restart the control panel.
Test the alarm transmission (combined test of fault warning router and fire alarm router) operation as follows:
4. Press the wheel to activate the menu and select: ALARM TRANSMISSION TEST
5. Press the “TEST”- button, at which the display will show the text: PRESS WHEEL TO ACTIVATE THE
TEST
6. Pressing the wheel activates the fault warning router.
7. After 30 seconds also the fire alarm router is activated.
ALARM TRANSMISSION TEST
STAGE 1
Fault routing activated
ALARM TRANSMISSION TEST
8. After a further 30 seconds the test stops automatically. The test
STAGE 2
Fire routing activated
ALARM TRANSMISSION TEST can also be stopped at any time by pressing the “TEST” – button.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20. FX, FXL and FXM connections
20.1 FX and FXL panel external connections, SLC
Fire Detection
Serial (RS485) communication with other FX panels (2 pcs)
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
45
Master controller
FX-MC2
Serial (RS232) communication with printer or maintenance tool (PC)
Ethernet connection, INFO communication: Future option
USB connection, maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC, short circuit protected, 500 mA
Monitored output (Bells, sounders, beacon), 500 mA
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
REPX-OB or
MCOX-OB or
ZLPX-IC
INFO communication
INFO communication
External communication (not in ZLPX-IC)
Loop controller
FX-SLC
0…4 pcs
For each FX-SLC: Two addressable detection circuits, each with 159 detector addresses + 159 IO-module addresses
For each FX-SLC: Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Loop controller
FX-CLC
0…4 pcs
For each FX-CLC: 16 Conventional detection circuits, function configurable
Input/output controller
FX-IOC
0…4 pcs
Clean contact signal inputs (4 pcs), function configurable
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Output controller
FX-OCA
0…4 pcs
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Power supply
FX-PSB
Power supply outputs 24 VDC (2 pcs), short circuit protected, 4 A each
230 VAC / 50 Hz / 160 VA
Battery 24 VDC (max 68 Ah)
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.2 FX and FXL panel external connections, ALC
Fire Detection
Serial (RS485) communication with other FX panels (2 pcs)
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
46
Master controller
FX-MC2
Serial (RS232) communication with printer or maintenance tool (PC)
Ethernet connection, INFO communication: Future option
USB connection, maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC, short circuit protected, 500 mA
Monitored output (Bells, sounders, beacon), 500 mA
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
REPX-OB or
MCOX-OB or
ZLPX-IC
INFO communication
INFO communication
External communication (not in ZLPX-IC)
Loop controller
FX-ALCA, FX-ALCB
0…4 pcs
FX-ALCA: One addressable detection circuits, with 126 addresses
FX-ALCB: Two addressable detection circuits, each 126 addresses
FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA
FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each
Loop controller
FX-CLC
0…4 pcs
For each FX-CLC: 16 Conventional detection circuits, function configurable
Input/output controller
FX-IOC
0…4 pcs
Clean contact signal inputs (4 pcs), function configurable
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Output controller
FX-OCA
0…4 pcs
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Power supply
FX-PSB
Power supply outputs 24 VDC (2 pcs), short circuit protected, 4 A each
230 VAC / 50 Hz / 160 VA
Battery 24 VDC (max 68 Ah)
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.3 FXM panel external connections, SLC
Fire Detection
Serial (RS485) communication with other FX panels (2 pcs)
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
47
Master controller
FX-MC2
Serial (RS232) communication with printer or maintenance tool (PC)
Ethernet connection, INFO communication: Future option
USB connection, maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC, short circuit protected, 500 mA
Monitored output (Bells, sounders, beacon), 500 mA
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
REPX-OB or
MCOX-OB or
ZLPX-IC
INFO communication
INFO communication
External communication (not in ZLPX-IC)
Loop controller
FX-SLC
0…2 pcs
For each FX-SLC: Two addressable detection circuits, each with 159 detector addresses + 159 IO-module addresses
For each FX-SLC: Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Loop controller
FX-CLC
0…2 pcs
For each FX-CLC: 16 Conventional detection circuits, function configurable
Input/output controller
FX-IOC
0…2 pcs
Clean contact signal inputs (4 pcs), function configurable
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Output controller
FX-OCA
0…2 pcs
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Power supply
FX-PSA
Power supply outputs 24 VDC (2 pcs), short circuit protected, 2 A each
230 VAC / 50 Hz / 80 VA
Battery 24 VDC (max 34 Ah)
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.4 FXM panel external connections, ALC
Fire Detection
Serial (RS485) communication with other FX panels (2 pcs)
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
48
Master controller
FX-MC2
Serial (RS232) communication with printer or maintenance tool (PC)
Ethernet connection, INFO communication: Future option
USB connection, maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC, short circuit protected, 500 mA
Monitored output (Bells, sounders, beacon), 500 mA
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
REPX-OB or
MCOX-OB or
ZLPX-IC
INFO communication
INFO communication
External communication (not in ZLPX-IC)
Loop controller
FX-ALCA, FX-ALCB
0…2 pcs
FX-ALCA: One addressable detection circuits, with 126 addresses
FX-ALCB: Two addressable detection circuits, each 126 addresses
FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA
FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each
Loop controller
FX-CLC
0…2 pcs
For each FX-CLC: 16 Conventional detection circuits, function configurable
Input/output controller
FX-IOC
0…2 pcs
Clean contact signal inputs (4 pcs), function configurable
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Output controller
FX-OCA
0…2 pcs
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Power supply
FX-PSA
Power supply outputs 24 VDC (2 pcs), short circuit protected, 2 A each
230 VAC / 50 Hz / 80 VA
Battery 24 VDC (max 34 Ah)
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.5 FXS panel external connections, SLC
Master controller
FX-MC2
Fire Detection
Serial (RS485) communication with other FX panels (2 pcs)
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
Serial (RS232) communication with printer or maintenance tool (PC)
Ethernet connection, INFO communication: Future option
USB connection, maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC, short circuit protected, 500 mA
Monitored output (Bells, sounders, beacon), 500 mA
Power supply input 24 VDC (2 pcs) from an FX, FXL or FXM panel, separately monitored for low voltage
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
49
REPX-OB or
MCOX-OB or
ZLPX-IC
INFO communication
INFO communication
External communication (not in ZLPX-IC)
Loop controller
FX-SLC
0…1 pcs
For each FX-SLC: Two addressable detection circuits, each with 159 detector addresses + 159 IO-module addresses
For each FX-SLC: Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Loop controller
FX-CLC
0…1 pcs
For each FX-CLC: 16 Conventional detection circuits, function configurable
Input/output controller
FX-IOC
0…1 pcs
Clean contact signal inputs (4 pcs), function configurable
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Output controller
FX-OCA
0…1 pcs
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.6 FXS panel external connections, ALC
Master controller
FX-MC2
Fire Detection
Serial (RS485) communication with other FX panels (2 pcs)
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
Serial (RS232) communication with printer or maintenance tool (PC)
Ethernet connection, INFO communication: Future option
USB connection, maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC, short circuit protected, 500 mA
Monitored output (Bells, sounders, beacon), 500 mA
Power supply input 24 VDC (2 pcs) from an FX, FXL or FXM panel, separately monitored for low voltage
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
50
REPX-OB or
MCOX-OB or
ZLPX-IC
INFO communication
INFO communication
External communication (not in ZLPX-IC)
Loop controller
FX-ALCA, FX-ALCB
0…1 pcs
FX-ALCA: One addressable detection circuits, with 126 addresses
FX-ALCB: Two addressable detection circuits, each 126 addresses
FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA
FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each
Loop controller
FX-CLC
0…1 pcs
For each FX-CLC: 16 Conventional detection circuits, function configurable
Input/output controller
FX-IOC
0…1 pcs
Clean contact signal inputs (4 pcs), function configurable
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Output controller
FX-OCA
0…1 pcs
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Note!
The max. current consumption of the FX - control panel (with PSB- power supply board), all loops and addresses and all control panel outputs is 1 A in standby condition and 4.0 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.
Note!
The max. current consumption of the FXM - control panel
(with PSA- power supply board), all loops and addresses and all control panel outputs is 0.5 A in standby condition and 2.2 A in alarm condition. The standby time required for the system may limit the max. load of the outputs.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.7 Connectors on the MC2 board
Terminal name
PI 1
Connector symbol
24 V -
24 V +
Purpose
Power supply 1 in (-)
Power supply 1 in (+)
PI 2
PO
MO
CO 1
CO 2
CO 3
24 V -
24 V +
24 V -
24 V +
-
+
Power supply 2 in (-)
Power supply 2 in (+)
Power supply out (-)
Power supply out (+)
Monitored output line (-)
Monitored output line (+)
Relay output 1 NC
Relay output 1 C
Relay output 1 NO
Relay output 2 NO
Relay output 2 C
Relay output 2 NC
Relay output 3 NC
Relay output 3 C
Relay output 3 NO
+
IN 1 Input 1
-
+
IN 2 Input 2
-
RS232
SYSTEM 1
SYSTEM 2
RS485/RS232
Ethernet
USB
CTS
RTS
GND
RxD
TxD
T/R +
T/R -
Gnd
T/R +
T/R -
Gnd
T/R +
T/R -
Gnd
RJ45
Micro
USB
Clear To Send
Request To Send
Ground
Received data
Transmit data
Transmit/Received Data +
Transmit/Received Data -
Ground
Transmit/Received Data +
Transmit/Received Data -
Ground
Transmit/Received Data +
Transmit/Received Data -
Ground
INFO communication
Fire Detection
51
Description
For external power supply only. Not to be used if the panel is equipped with an internal power supply unit.
For external power supply only. Not to be used if the panel is equipped with an internal power supply unit.
Power supply out for auxiliary equipment
General fire monitored output line as default. Other functions can be selected with the configuration tool.
Fire alarm router output as default
Fault warning router output as default. The relay is energized in normal condition (as drawn) and releases in fault condition.
Fire alarm output as default
Fault in fire alarm router. Monitored and normally open as default function. Other functions can be selected with the configuration tool.
Fault in fault warning router. Monitored and normally open as default function. Other functions can be selected with the configuration tool.
Serial communication with printer or configuration / maintenance tool
Serial communication with other FX panels
Serial communication with other FX panels
Serial communication with INFO/FMP/MCO/ABC or other alarm management systems
Future option
Configuration / Maintenance tool
RS485
Gnd - +
SYS 1
Gnd - +
RS232
Tx Rx Gnd
SYS 2
Gnd - +
CO3
NO C NC
RS232
Tx Rx Gnd Cs Rs
+ PO -
CO2
NC C NO
CO1
NO C NC
- + - + + PI1
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.8 Connectors on the PSA and PSB - board
Connector symbol
Purpose
Terminal name
30 VAC
BATT
PO 1
PO 2
-
+
24 V -
24 V +
24 V -
24 V +
Battery -
Battery +
Power supply 1 out -
Power supply 1 out +
Power supply 2 out -
Power supply 2 out +
Fire Detection
Description
30 VAC input from transformer.
Connection for the standby battery.
Power supply output 1 for external load.
Power supply output 2 for external load.
52
PO 2
+24V-
PO 1
+24V-
20.9 Connectors on each SLC board
Terminal name
PO 1
PO 2
LOOP 1
LOOP 2
Connector symbol
24 V -
24 V +
24 V -
24 V +
B -
B +
A -
A +
B -
B +
Purpose
Power supply out (-)
Power supply out (+)
Power supply out (-)
Power supply out (+)
Return end -
Return end +
Outgoing end -
Outgoing end +
A -
A +
Return end -
Return end +
Outgoing end -
Outgoing end +
BATT
+ -
Description
Power output for loop devices in loop 1 that require external power supply.
Power output for loop devices in loop 2 that require external power supply.
System Sensor- loop devices.
System Sensor- loop devices.
Loop 2
A+ A-
Loop 2
B+ B-
Loop 1
A+ A-
Loop 1
B+ B-
PO 2
+24V-
PO 1
+24V-
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.10 Connectors on each CLC board
Terminal name
Connector symbol
Purpose
1
…
16
-
+
-
+
Conventional line 1 -
Conventional line 1 +
Conventional line 16 -
Conventional line 16 +
Description
Fire Detection
53
+ 16 + 15 + 12 + 11 + 8 + 7 + 4 + 3 -
+ 14 + 13 + 10 + 9 -
20.11 Connectors on each IOC board
Terminal name
Connector symbol
Purpose
1
2
Monitored output line 1 -
Monitored output line 1 +
Monitored output line 2 -
Monitored output line 2 +
3
4
PO 1
PO 2
24 V -
24 V +
24 V -
24 V +
Monitored output line 3 -
Monitored output line 3 +
Monitored output line 4 -
Monitored output line 4 +
Power supply 1 out -
Power supply 1 out +
Power supply 2 out -
Power supply 2 out +
CO 1
CO 2
Relay output 1 NC
Relay output 1 C
Relay output 1 NO
Relay output 2 NC
Relay output 2 C
Relay output 2 NO
IN 1
IN 2
IN 3
IN 4
-
+
-
+
-
+
-
+
Clean contact input 1
Clean contact input 2
Clean contact input 3
Clean contact input 4
+ 6 + 5 + 2 + 1 -
Description
Fire monitored output line as default.
Fire monitored output line as default.
Fire monitored output line as default.
Fault warning device line as default.
Power supply output 1.
Power supply output 1.
Clean contact relay output. General fire alarm output as default.
Clean contact relay output.
IN 4
+ -
IN 3
+ -
IN 2
+ -
IN 1
+ -
CO 2 CO 1 PO 2
+24V-
PO 1
+24V+ 4 + 3 + 2 + 1 -
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.12 Connectors on each OCA-board
Terminal name
Connector symbol
Purpose
CO 1-2
Relay output 1-2 NC
Relay output 1-2 C
Relay output 1-2 NO
Relay output 3-4 NC
CO 3-4
CO 5-6
CO 7-8
Relay output 3-4 C
Relay output 3-4 NO
Relay output 5-6 NC
Relay output 5-6 C
Relay output 5-6 NO
Relay output 7-8 NC
Relay output 7-8 C
Relay output 7-8 NO
CO 9-10
CO 11-12
CO 13-14
CO 15-16
Relay output 9-10 NC
Relay output 9-10 C
Relay output 9-10 NO
Relay output 11-12 NC
Relay output 11-12 C
Relay output 11-12 NO
Relay output 13-14 NC
Relay output 13-14 C
Relay output 13-14 NO
Relay output 15-16 NC
Relay output 15-16 C
Relay output 15-16 NO
Description
Fire alarm output.
Fire door output.
Pre-alarm output.
Technical alarm output.
Fault warning output.
Disablement output.
Access level 2 output.
Fire Detection
Maintenance warning output.
54
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.13 Connectors on each ALCA- board
Terminal name
Connector symbol
Purpose
PO 1
LOOP 1
24 V -
24 V +
B -
B +
A -
A +
Power supply out (-)
Power supply out (+)
Return end -
Return end +
Outgoing end -
Outgoing end +
Description
Fire Detection
55
Power output for loop devices in loop 1 that require external power supply.
Intellia loop devices.
20.14 Connectors on each ALCB- board
Terminal name
PO 1
PO 2
LOOP 1
LOOP 2
Connector symbol
24 V -
24 V +
24 V -
24 V +
B -
B +
A -
A +
B -
B +
Purpose
Power supply out (-)
Power supply out (+)
Power supply out (-)
Power supply out (+)
Return end -
Return end +
Outgoing end -
Outgoing end +
A -
A +
Return end -
Return end +
Outgoing end -
Outgoing end +
Description
Power output for loop devices in loop 1 that require external power supply.
Power output for loop devices in loop 2 that require external power supply.
Intellia loop devices.
Intellia loop devices.
Loop 2
A+ A-
Loop 2
B+ B-
Loop 1
A+ A-
Loop 1
B+ B-
PO 2
+24V-
PO 1
+24V-
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3 Fire Detection
20.15 Connectors on FMPX, DAPX, REPX and REPX-OB- board and MCOX and MCOX-OB- board
Isolated serial port for
3 rd
part external devices
Terminal name
RS232
RS485
Connector symbol
TXD
RXD
GND
RTS
CTS
T/R-
Description
For 3 rd
part devices. Ie. integration to BMS.
Line IN
RS485
RS232
T/R+
GND
T/R-
T/R+
TXD
RXD
GND
GND
Configuration / input port. Panel connection must be disconnected during configuration.
Line OUT RS485
Power input 1 PI 1
Power input 2 PI 2
T/R-
T/R+
24 V -
24 V +
24 V -
24 V +
For PELCO devices using INFO- protocol.
Note! Both inputs must be connected.
56
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
20.16 Connectors on CODINET modem adapter
Terminal name
Connector symbol
Purpose
CO1
(D9-connector)
2:RxD (in)
3:TxD (out)
4:DTR (out)
5:ISO GND
TE4
TE3
6:DSR (in)
7:RTS (out)
NC
DSR
RxD
TxD
ISO GND
DTS DTR
RS232-line.
TE2
TE1
+24 V
GND
T/R+
T/R-
R+
R-
ISO GND
Power input. (Isolated)
RS485-line.
J1 Mounted
Terminating resistor of 120 ohm between ±T/R. Normally not used.
J2
Mounted
(default)
Not mounted
RS485 2-wires, ±T/R.
RS485 4-wires, ±T/R and ±R.
Description
Fire Detection
57
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
Installation Instruction 66571764GB3
0832
Pelco Finland Oy P.O. Box 415, 02601 Espoo Finland
For FX 0832-CPD-1082 Issue 4
For FXL 0832-CPD-1083 Issue 3
For FXM 0832-CPD-1084 Issue 3
EN 54-2:1997/AC:1999/A1:2006
EN 54-4:1997/AC:1999/A1:2002/A2:2006
Options:
7.8; 7.9.1; 7.10.3; 7.11; 7.12.2; 7.13; 8.3; 8.4; 8.9; 9.5;
10
Control and indicating equipment for fire detection and fire alarm systems for buildings
FX, FXL, FXM
Other technical data:
66571764: installation and commissioning
66571744: operation manual
66571758 (SLC), 66571761 (ALC): system planning (held by the manufacturer )
Pelco Finland Oy
P.O.Box 415, 02601 Espoo
Kalkkipellontie 6, 02650 Espoo
Tel. 010 446 511
Fax 010 446 5103 www.pelco.com/nordic
Fire Detection
58
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 FX 3NET FIRE ALARM SYSTEM
- 1 Installation and commissioning manual
- 1 Read this manual carefully before installation and commissioning!
- 2 Contents
- 4 NOTE: If SLC loop controller is configured to LC protocol, please read document.O1771GB0
- 4 FX cabinet
- 5 FXL cabinet
- 5 FXM cabinet
- 5 FXS cabinet
- 6 AX/FX/IX-BAT battery cabinet
- 6 FXM-BAT battery cabinet
- 7 FX-CAB mounting cabinet
- 7 FXM-CAB mounting cabinet
- 8 FXM-RMFW mounting frame
- 9 FX-RMFW mounting frame
- 15 8. Preliminary checks
- 15 MC2 jumper settings
- 16 SLC jumper settings
- 16 CLC jumper settings
- 16 ALC jumper settings
- 16 IOC jumper settings
- 17 OCA jumper settings
- 17 Note! The panel is in access level 2 when the cover is removed.
- 23 Each FX-SLC and FX–ALCB board has connectors for two loops, FX-ALCA board has only one loop.
- 26 Note !
- 26 Fault delays / timeouts
- 28 12.2.1 Conventional line
- 28 Conventional line 4k7
- 28 Conventional line 2k94
- 29 12.2.2 Input line
- 29 End of line resistance: 4k7, 5%
- 30 Each CLC board has 16 conventional lines (detection circuits).
- 31 Conventional Line
- 31 Input Line
- 33 The FX-MC board has one monitored output line connector.
- 33 The FX-IOC board has four monitored output line connectors.
- 37 X = 0; Info configured to RS232 service port
- 37 Picture 1. Connection between FX-panel and FMPX
- 38 Picture 2. Connection between FX-panel and DAPX
- 38 Picture 3. Connection between FX-panel and REPX
- 38 Note! If REPX-OB is installed in FX: rack, only INFO line needs to be connected.
- 39 Picture 4. Connection between FX-panel and MCOX
- 39 Note! If MCOX-OB is installed in FX: rack, only INFO line needs to be connected
- 42 System 1(S1) and System 2 (S2) = serial communication line
- 42 Picture 5. Example: FX 3NET communication network
- 42 Picture 6. Communication grounding in the FX NET system
- 43 Picture 7. Max. two modem pairs between two panels