Installation Instruction 66571764GB3 Fire Detection
37
16. Info-line devices / connections
16.1 INFO-fault messages
Text at display Description fault in info port X comm. info X external device fault 0 info X external device fault 1 info X external device fault 2 info X device fault 3 info X device fault 4
When acknowledge bit not received after 10 retries of some message or external system will send "EXTERNAL FAULT" message
MCO/Repeater reports that outport of the unit has communication fault
MCO/Repeater reports that external port of the unit has communication fault.
MCO reports that control logic part of unit has recognized problems
When transmitting does not success for some reason. Monitored internal by
SW.
Note! configuration bit "not monitored" does not prevent this fault *
When receiver gets whole time a lot of rubbish, not real Info frames. Monitored internal by SW.
Note! configuration bit "not monitored" does not prevent this fault
IC unit reports about power input 1 fault
IC unit reports about fault in the configuration files of IC
IC unit reports about fault which is unknown for FX info X external device fault 5 info X external device fault 7 info X external device fault 255
X = 0; Info configured to RS232 service port
X = 1; Info configured to RS485 at SA board
16.2 FMPX
Picture 1. Connection between FX-panel and FMPX
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
advertisement
Related manuals
advertisement
Table of contents
- 1 FX 3NET FIRE ALARM SYSTEM
- 1 Installation and commissioning manual
- 1 Read this manual carefully before installation and commissioning!
- 2 Contents
- 4 NOTE: If SLC loop controller is configured to LC protocol, please read document.O1771GB0
- 4 FX cabinet
- 5 FXL cabinet
- 5 FXM cabinet
- 5 FXS cabinet
- 6 AX/FX/IX-BAT battery cabinet
- 6 FXM-BAT battery cabinet
- 7 FX-CAB mounting cabinet
- 7 FXM-CAB mounting cabinet
- 8 FXM-RMFW mounting frame
- 9 FX-RMFW mounting frame
- 15 8. Preliminary checks
- 15 MC2 jumper settings
- 16 SLC jumper settings
- 16 CLC jumper settings
- 16 ALC jumper settings
- 16 IOC jumper settings
- 17 OCA jumper settings
- 17 Note! The panel is in access level 2 when the cover is removed.
- 23 Each FX-SLC and FX–ALCB board has connectors for two loops, FX-ALCA board has only one loop.
- 26 Note !
- 26 Fault delays / timeouts
- 28 12.2.1 Conventional line
- 28 Conventional line 4k7
- 28 Conventional line 2k94
- 29 12.2.2 Input line
- 29 End of line resistance: 4k7, 5%
- 30 Each CLC board has 16 conventional lines (detection circuits).
- 31 Conventional Line
- 31 Input Line
- 33 The FX-MC board has one monitored output line connector.
- 33 The FX-IOC board has four monitored output line connectors.
- 37 X = 0; Info configured to RS232 service port
- 37 Picture 1. Connection between FX-panel and FMPX
- 38 Picture 2. Connection between FX-panel and DAPX
- 38 Picture 3. Connection between FX-panel and REPX
- 38 Note! If REPX-OB is installed in FX: rack, only INFO line needs to be connected.
- 39 Picture 4. Connection between FX-panel and MCOX
- 39 Note! If MCOX-OB is installed in FX: rack, only INFO line needs to be connected
- 42 System 1(S1) and System 2 (S2) = serial communication line
- 42 Picture 5. Example: FX 3NET communication network
- 42 Picture 6. Communication grounding in the FX NET system
- 43 Picture 7. Max. two modem pairs between two panels