Note !. Schneider Electric FX 3NET

Add to My manuals
58 Pages

advertisement

Note !. Schneider Electric FX 3NET | Manualzz

Installation Instruction 66571764GB3 Fire Detection

26

MAINTENANCE 67: (r)

MAINTENANCE 68: (r)

MAINTENANCE 69: (r)

FAULT 70: (r)

FAULT 71: (r)

FAULT 72: (r)

FAULT 73: (r)

FAULT 74: (r)

FAULT 75: (r)

FAULT 76: (r)

FAULT 77: (r)

FAULT 78: (r)

FAULT 79: (r)

FAULT 80: (r)

FAULT 81: (r)

FAULT 82: (r)

FAULT 83: (r)

FAULT 84: (r)

FAULT 85: (r,s)

FAULT 86: (r)

FAULT 87: (?) show it as fault warning.

− Saturation of infrared detector at CoPTIR/PTIR sensor

− 80% of drift limit (when “report dirty detector” requested)

− 99% of drift limit (when “report dirty detector” requested)

− Undefined fault code from ALC/SySeAp device.

− Memory write operation of the device failed

− Memory read operation of the device failed

− Communication troubles with device.

− Self test of the detector failed.

− Beam sensor CPU fault

− Beam sensor align targeting

− Beam sensor general fault

− Beam sensor signal too high

− cell life expiration of CoPTIR sensor

− The SW of ALC board is not compatible for desired sounder mode

− Input module has been configured as "fire router fault". When module alarms FX show it as fault warning.

− Input module has been configured as "VACIE fault". When module alarms FX show it as fault warning.

− Unsupported address device has been configured to the loop of LC board

(The SW of LC is older than configuration made with WinFXNet).

− Power failure of supervised output circuit of a module

− The OEM code of the device is not Esmi/Pelco code.

− The control of output of SySeAp device did not work

MAINT 88: (?)

MAINT 89: (?)

FAULT 90: (r,s)

− Unacceptable device

ALC: detector is not Intellia, device is XP95 but not configured

MAINTENANCE 91: (r)

FAULT 92: (r)

FAULT 93: (r)

FAULT 94: (r)

FAULT 95: (r)

FAULT 96: (?)

MAINTENANCE 98: (r)

FAULT 99: (r)

− break in input line of the CLC unit

− short circuit in input line of the CLC unit

− voltage problem in input line of the CLC unit

− Voice evacuation mute input active time expired

− simulated maintenance (service command)

− simulated fault (service command)

s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)

r = running time when device is normally monitored

c = loop is configured with PC

n = loop is not configured

Note !

Fault delays / timeouts

Reason for Fault 52 ( no PW1 received) must be active for 99sec. before the fault is shown.

Delay for fault 63 (PW4 out of limits) is 30 sec. if any good pulses are received, counter will stop, and if no bad pulses with in 10sec, the counter is reset

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

Installation Instruction 66571764GB3

12. Conventional detector lines

12.1 Measuring the Cables

1. Disconnect all power from the control panel.

2. Measure the resistance between the wires of the conventional line cable. Set the meter to low voltage resistance measurement

(not diode measurement).

Depending on connected devices the result should be:

- If all devices are normally open (NO) types and no EOL resistor is connected the meter should indicate a break in the line

- If all devices are normally open (NO) types and an EOL resistor is connected the meter should indicate the value of the EOL resistor.

- If some devices are normally closed (NC) types the meter should indicate the parallel connection of the series resistances of those devices

If the resistance meter indicates other values, the cause of the fault must be located. (It may be a detector connected the wrong way or a short circuit in the conductors).

3. Short-circuit the wires of the conventional detection line cable at the control panel during measuring.

4. Disconnect the end-of-line resistors from those conventional detection line terminals to which the cables are to be connected.

5. Take the end-of-line resistor with you and walk to the end of the line and measure the resistance between the wires of the cable.

The maximum allowed resistance is 100

Ω (50 Ω if the line goes through an Exi barrier). If the resistance is higher, there is a break in the line (did you remember short-circuit the cable wires at the control panel). Locate the breaks and eliminate them.

6. Connect the end-of-line resistors to their respective places (the last detector or manual call point of the line or the end-of-line unit box connected after the last device).

Fire Detection

27

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

advertisement

Related manuals

advertisement

Table of contents