Each CLC board has 16 conventional lines (detection circuits).. Schneider Electric FX 3NET

Add to My manuals
58 Pages

advertisement

Each CLC board has 16 conventional lines (detection circuits).. Schneider Electric FX 3NET | Manualzz

Installation Instruction 66571764GB3

12.3 Connecting the line to the control panel

Each CLC board has 16 conventional lines (detection circuits).

1. Disconnect all power from the control panel.

2. If shielded cable is used, connect the shield to the cabinet ground screw in the back plate.

Note!

The free shielded wire must be as short as possible!

3. Connect the pair of wires of the conventional line to the terminals of the CLC board retaining polarity.

Fire Detection

30

12.4 Functional check of the loop

1. Start the control panel by switching the power on. First connect the transformer cable, then the battery cable.

2. Wait until the text “PANEL STARTING UP” disappears from the display (about 3 minutes).

The detector loop is in order if the control panel does not give fire, fault or service indications at the start up.

Otherwise the fault must be located by following the instructions below.

3. If the panel indicates fire alarm, press the “BUZZER

SILENCE” button, scroll the alarm indications with the

MORE ALARMS”- button and note them.

4. Eliminate the causes of fire alarm and reset the indications by pressing the “RESET”- button until the pulsed signal stops.

Possible causes for fire alarm:

- A manual call point is pressed down; the glass has been broken or taken off.

- Smoke, water vapour or thick dust in a smoke detector.

- Heat close to a heat detector.

5. Repeat the above mentioned procedures until there are no more fire alarms.

6. If the panel indicates fault or maintenance warning press the “BUZZER SILENCE” button, scroll the indications with the “MORE ALARMS”- button and note them.

Possible causes for fault warnings:

- A break or a short circuit in the loop.

7. Eliminate the causes of fault and maintenance warnings and reset the indications by pressing the “RESET”- button until the pulsed signal stops.

8. Repeat the above mentioned procedures until there are no more fault and maintenance warnings.

9. Test that each detector and manual call point gives an alarm. Test procedures for the various devices are given in the documentation for those devices.

- An earth leak in the loop.

Note!

CLC default value for the short circuit is a fault!

Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic

Document Number 66571764GB3 16 2012

advertisement

Related manuals

advertisement

Table of contents