EUCHNER CTP-AR Unicode/Multicode Safety Switch Operating instructions
Reklaam
Reklaam
Operating instructions
Transponder-Coded Safety Switch With Guard Locking
CTP-AR Unicode/Multicode
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
Contents
2
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
123041-03-07/15 (translation of the original operating instructions)
3
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
1. About this document
1.1. Scope
These operating instructions are valid for all CTP-L.-AR… from version V1.0.0. These operating instructions together with document "Safety Information and Maintenance" as well as any data sheet enclosed form the complete user information for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing special expertise in handling safety components.
1.3. Key to symbols
Symbol/depiction Significance
Printed document
Internet www
MEM
Document is available for download at www.EUCHNER.de
Document on CD
This section is applicable only if the memory card is used
DANGER
WARNING
CAUTION
Safety precautions
Danger
of death or severe injuries
Warning
about possible injuries
Caution
minor injuries possible
NOTICE
Important!
Tip
Notice
about possible device damage
Important
information
Tip/useful information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title
(document number)
Safety Information and
Maintenance CTP
(105517)
Operating instructions
(123041)
Possibly enclosed data sheet
Contents
Basic information on safe setup and service
(this document)
Item-specific information about deviations or additions
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.de. For this purpose enter the doc. no. in the search box.
4
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
2. Correct use
Safety switches series CTP-L.-… are interlocking devices with guard locking (type 4). Devices with unicode evaluation possess a high coding level; devices with multicode evaluation feature a low coding level.
In combination with a movable safety guard and the machine control, this safety component prevents the safety guard from being opened while a dangerous machine function is being performed.
This means:
Ì Starting commands that cause a dangerous machine function must become active only when the safety guard is closed and locked.
Ì The guard locking device must not be unlocked until the dangerous machine function has ended.
Ì Closing and locking a safety guard must not cause automatic starting of a dangerous machine function. A separate start command must be issued. For exceptions, refer to EN ISO 12100 or relevant C-standards.
Devices from this series are also suitable for process protection.
Before the device is used, a risk assessment must be performed on the machine, e.g. in accordance with the following standards:
Ì EN ISO 13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design
Ì EN ISO 12100, Safety of machinery – General principles for design – Risk assessment and risk reduction
Ì IEC 62061, Safety of machinery – Functional safety of safety-related electrical, electronic and programmable electronic control systems
Correct use includes observing the relevant requirements for installation and operation, particularly based on the following standards:
Ì EN ISO 13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design
Ì EN ISO 14119 (supersedes EN 1088), Safety of machinery – Interlocking devices associated with guards – Principles for design and selection
Ì EN 60204-1, Safety of machinery. Electrical equipment of machines. General requirements.
The safety switch is only allowed to be operated in conjunction with the intended EUCHNER actuators and the related connection components from EUCHNER. On the use of different actuators or other connection components, EUCHNER provides no warranty for safe function.
Connection of several devices in an AR switch chain is permitted only using devices intended for series connection in an AR switch chain. Check this in the instructions of the device in question.
A maximum of 20 safety switches are allowed to be operated in a switch chain.
Important!
Ì
Ì The user is responsible for the proper integration of the device into a safe overall system. For this purpose, the overall system must be validated, e.g. in accordance with EN ISO 13849-2.
It is only allowed to use components that are permissible in accordance with the table below.
Table 1: Possible combinations for CTP components
Actuator
EN
Safety switch
A-C-H-...
CTP-… Unicode/Multicode
Key to symbols
Combination possible
123041-03-07/15 (translation of the original operating instructions)
5
Operating instructions
Transponder-Coded Safety Switch CTP-AR
NOTICE
For information about combination with an AR evaluation unit, please refer to chapter
10.10. Connection of several CTP‑AR in a switch chain on page 23
.
3. Description of the safety function
Devices from this series feature the following safety functions:
Monitoring of guard locking and the position of the safety guard (interlocking device with guard locking according to EN ISO 14119)
Ì
6.7. Switching states on page 9
-The safety outputs are switched off when guard locking is unlocked (monitoring of the locking device).
-The safety outputs are switched off when the safety guard is open (monitoring of the door position).
-Guard locking can be activated only when the actuator is located in the switch head (failsafe locking mechanism).
Ì Safety characteristics: Category, Performance Level, PFH d
).
Control of guard locking
If the device is used as guard locking for personnel protection, control of guard locking must be regarded as a safety function.
The device does not feature a safety characteristic for control of guard locking, because the guard locking solenoid is completely disconnected from the outside (no control function within the device). It therefore does not contribute to the failure probability.
The safety level for the control of the guard locking is only defined by the external control (e. g. PFH d, ext.
monitor).
for the standstill
Guardlocking Device
PFHd ext.
(e.g. standstill monitor)
(locking mean)
6
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or if the safety instructions are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void.
5. General safety instructions
Safety switches provide personal protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Check the safe function of the safety guard particularly
Ì after any setup work
Ì after the replacement of a system component
Ì after an extended period without use
Ì after every fault
Independent of these checks, the safe function of the safety guard should be checked at suitable intervals as part of the maintenance schedule.
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components perform a personal protection function.
Ì Safety components must not be bypassed, turned away, removed or otherwise rendered ineffective. On this topic pay attention in particular to the measures for reducing the possibility of bypassing according to EN ISO 14119:2013, section 7.
Ì The switching operation must be triggered only by actuators designated for this purpose.
Ì Prevent bypassing by means of replacement actuators (only for multicode evaluation). For this purpose, restrict access to actuators and to keys for releases, for example.
Ì Mounting, electrical connection and setup only by authorized personnel possessing the following knowledge:
-specialist knowledge in handling safety components
-knowledge about the applicable EMC regulations
-knowledge about the applicable regulations on occupational safety and accident prevention.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions. You can download the operating instructions from www.EUCHNER.de.
EN
123041-03-07/15 (translation of the original operating instructions)
7
Operating instructions
Transponder-Coded Safety Switch CTP-AR
6. Function
The device permits the locking of movable safety guards.
Transponder-coded actuator
The system consists of the following components: coded actuator (transponder) and switch.
Whether the complete actuator code of the device is taught in (unicode) or not
(multicode) depends on the respective version.
Ì
Devices with unicode evaluation
: The actuator must be assigned to the safety switch by a teach-in operation so that it is detected by the system.
This unambiguous assignment ensures a particularly high level of protection against tampering. The system thereby possesses a high coding level.
Guard locking pin
Ì
Devices with multicode evaluation
: Unlike systems with unique code detection, on multicode devices a specific code is not polled but instead it is only checked whether the actuator is of a type that can be detected by the system (multicode detection). There is no exact comparison of the actuator code with the taught-in code in the safety switch (unique code detection). The system possesses a low coding level.
When the safety guard is closed, the actuator is moved into the safety switch. When the switch-on distance is reached, power is supplied to the actuator via the switch and data transfer takes place.
If a permissible code is detected, the safety outputs are switched on.
The safety outputs and the monitoring output (OL) are switched off when the safety guard is opened.
In the event of a fault in the safety switch, the safety outputs are switched off and the DIA LED illuminates red. The occurrence of failures is detected at the latest on the next demand to close the safety outputs (e.g. on starting).
6.1. Guard lock monitoring
All versions feature two safe outputs for monitoring guard locking. The safety outputs (FO1A and FO1B) are switched off when guard locking is released.
6.2. Door monitoring output (OD)
All versions have a door monitoring output. The door monitoring output is switched on as soon as the actuator is inserted in the switch head (state: safety guard closed and not locked). The door monitoring output also remains switched on when guard locking is active.
6.3. Diagnostics output (OI)
The diagnostics output is switched on in the event of a fault (switch-on condition as for DIA LED).
6.4. Guard locking monitoring output (OL)
The guard locking monitoring output is switched on when guard locking is active.
6.5. Guard locking on version CTP-L1
(guard locking actuated by spring force and released by energy ON)
Activating guard locking:
close safety guard; no voltage at the solenoid.
Releasing guard locking:
apply voltage to the solenoid.
The spring-operated guard locking functions in accordance with the closed-circuit current principle. If voltage is interrupted at the solenoid, guard locking remains active and the safety guard cannot be opened directly.
Important!
If the safety guard is open when the power supply is interrupted and the guard is then closed, guard locking is activated. This can lead to persons being locked in unintentionally.
The actuator cannot be pulled out of the switch and the safety guard is locked as long as the guard locking pin is extended.
If voltage is applied to the guard locking solenoid, the guard locking pin is retracted and the actuator is released. The safety guard can be opened.
8
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
6.6. Guard locking on version CTP-L2
(guard locking actuated by energy ON and released by spring force)
Important!
Use as guard locking for personnel protection is possible only in special cases, after strict assessment of the accident risk (see EN ISO 14119:2013, section 5.7.1)!
Activating guard locking:
apply voltage to the solenoid.
Releasing guard locking:
disconnect voltage from the solenoid.
The magnetically actuated guard locking operates in accordance with the open-circuit current principle. If voltage is interrupted at the solenoid, guard locking is released and the safety guard can be opened directly!
The safety guard can be opened as long as no voltage is applied to the guard locking solenoid.
If voltage is applied to the guard locking solenoid, the guard locking pin is held in the extended position and the safety guard is locked.
6.7. Switching states
The detailed switching states for your switch can be found in the system status table. All safety outputs, monitoring outputs and indicating LEDs are described there.
Safety guard closed and locked Safety guard closed and not locked
Safety guard open
IMP
IMM IMP
IMM
IMP
IMM
Voltage on the guard locking solenoid
CTP-L1
Voltage on the guard locking solenoid
CTP-L2
Safety outputs FO1A and FO1B
Guard locking monitoring output OL
Door monitoring output OD off on on on on on off off off on
(irrelevant)
(irrelevant) off off off
123041-03-07/15 (translation of the original operating instructions)
9
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
7. Manual release
Some situations require guard locking to be released manually (e.g. malfunctions or an emergency). A function test should be performed after release.
More information on this topic can be found in the standard EN ISO 14119:2013, section 5.7.5.1. The device can feature the following release functions:
7.1. Mechanical release and mechanical key release (can be retrofitted)
In the event of malfunctions, the guard locking can be released with the mechanical release irrespective of the state of the solenoid.
The safety outputs are switched off when the mechanical release is actuated. Use the safety outputs to generate a stop command.
The monitoring output OL is switched off; OD can assume an undefined state. Open the safety guard and close it again after resetting the mechanical release. The device will then operate normally again.
7.1.1. Actuating mechanical release
1. Unscrew locking screw
2. Using a screwdriver, turn the mechanical release to in the direction of the arrow
¨
Guard locking is released.
Important!
Ì The actuator must not be under tensile stress during manual release.
Ì After use, reset the mechanical release and screw in and seal the locking screw (for example with sealing lacquer).
Ì The mechanical key release must not be used to lock the switch during servicing to prevent activation of guard locking, for example.
Ì Loss of the unlocking function due to mounting errors or damage during mounting.
Ì
Ì Check the release function every time after mounting.
Please observe the notes on any enclosed data sheets.
Mechanical release
Locking screw
7.1.2. Actuating mechanical key release
On devices with mechanical key release (can be retrofitted), simply turn the key to release. Function as for mechanical release. For mounting, see the mechanical key release supplement.
10
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
7.2. Emergency unlocking (can be retrofitted)
Permits opening of a locked safety guard from outside the danger area without tools. For mounting, see the mounting supplement.
Important!
Ì It must be possible to operate emergency unlocking manually from outside the protected area without tools.
Ì Emergency unlocking must possess a marking indicating that it may be used only in an emergency.
Ì The actuator must not be under tensile stress during manual release.
Ì The unlocking function meets all other requirements from EN ISO 14119.
Ì Emergency unlocking meets the requirements of Category B according to EN ISO 13849-1:2008.
Ì Loss of the unlocking function due to mounting errors or damage during mounting.
Ì
Ì Check the release function every time after mounting.
Please observe the notes on any enclosed data sheets.
7.2.1. Actuating emergency unlocking
Ì Turn emergency unlocking clockwise until it clicks into place.
¨
Guard locking is released.
To reset, press the snap-in bolt inward using a small screwdriver or similar tool and turn the emergency unlocking back.
The safety outputs are switched off when emergency unlocking is actuated. Use the safety outputs to generate a stop command.
The monitoring output OL is switched off; OD can assume an undefined state. Open the safety guard and close it again after resetting emergency unlocking. The device will then operate normally again.
Snap-in bolt
7.3. Escape release (optional)
Permits opening of a locked safety guard from the danger area without tools (see chapter
13.2. Dimen‑ sion drawing safety switch CTP… on page 33
Important!
Ì It must be possible to operate the escape release manually from inside the protected area without tools.
Ì It must not be possible to reach the escape release from the outside.
Ì The actuator must not be under tensile stress during manual release.
Ì The escape release meets the requirements of Category B according to EN ISO 13849-1:2008.
7.3.1. Actuating escape release
Ì Press the red release knob to the end stop
¨
Guard locking is released.
Pull the knob out again to reset.
The safety outputs are switched off when the escape release is actuated. Use the safety outputs to generate a stop command.
The monitoring output OL is switched off; OD can assume an undefined state. Open the safety guard and close it again after resetting escape release. The device will then operate normally again.
EN
123041-03-07/15 (translation of the original operating instructions)
11
Operating instructions
Transponder-Coded Safety Switch CTP-AR
7.4. Wire front release (optional)
Release via a pull wire. Depending on the type of attachment, the wire front release can be used as emergency unlocking or escape release.
The following applies to non-latching wire front releases:
If the unlocking device is to be used for emergency unlocking, you must take one of the following measures (see EN ISO 14119:2013, section 5.7.5.3):
Ì Mount the unlocking device such that reset can only be undertaken with the aid of a tool.
Ì Alternatively, the reset can be undertaken at the control system level. E. g. by means of a plausibility check (status of the safety outputs does not match the guard locking control signal).
The emergency-unlocking specifications in chapter
apply irrespective of this.
Important!
Ì The wire front release meets the requirements of Category B according to EN ISO 13849-1:2008.
Ì The correct function depends on the laying of the pull wire and on the attachment of the pull handle, and this is the responsibility of the plant manufacturer.
Ì The actuator must not be under tensile stress during manual release.
7.4.1. Laying wire front release
Important!
Ì Loss of the release function due to mounting errors, damage or wear.
Ì Check the release function every time after mounting.
Ì
Ì When routing the wire front release, ensure that it operates smoothly.
Ì Observe the min. bending radius (100 mm) and minimize the number of bends.
The switch is not allowed to be opened.
Ì Observe the notes on the enclosed data sheets.
12
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
8. Changing the approach direction
The approach direction only needs to be changed if the switch is to be approached from the rear.
Proceed as follows:
1. Remove the screws from the safety switch
2. Set the required direction
3. Tighten the screws with a torque of 1.2 Nm
D
A
C
B
Figure 1: Changing the approach direction
123041-03-07/15 (translation of the original operating instructions)
13
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
9. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective.
Ì Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for bypassing an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì Safety switches and actuators must not be used as an end stop.
Ì Observe EN ISO 14119:2013, sections 5.2 and 5.3, for information about fastening the safety switch and the actuator.
Ì Protect the switch head against damage as well as penetrating foreign objects such as swarf, sand and blasting shot, etc.
Ì
Observe the min. door radii (see chapter
).
13.3.1. Dimension drawing for actuator CTP‑... on page
A clearance of 12 mm must be maintained around the actuator head (see
). The mounting aid provided can be used
to check this clearance.
Mounting aid
12
Mounting aid
min. 12
min. 12
Figure 2: Actuator head clearance and mounting aid
14
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10. Electrical connection
The following connection options are available:
Ì Separate operation
Ì Series connection with Y-distributors from EUCHNER (only with M12 plug connector)
Ì Series connection, e.g. with wiring in the control cabinet.
Ì Operation on an AR evaluation unit.
WARNING
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated.
Ì
Ì Monitoring outputs must not be used as safety outputs.
Lay the connection cables with protection to prevent the risk of short circuits.
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì The power supply for the evaluation electronics is electrically isolated from the power supply for the guard locking solenoid.
Ì Do not use a control system with pulsing or switch off the pulsing function in your control system.
The device generates its own test pulses on the output lines FO1A/FO1B. A downstream control system must tolerate these test pulses, which may be up to 1 ms long on AR devices.
The test pulses on AR devices are also output when the safety outputs are switched off.
Depending on the inertia of the connected device (control system, relay, etc.), this can lead to short switching processes.
Ì The inputs on an evaluation unit connected must be positive-switching, as the two outputs on the safety switch deliver a level of +24 V in the switched-on state.
Ì All the electrical connections must either be isolated from the mains supply by a safety transformer according to IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures (PELV).
Ì All electrical outputs must have an adequate protective circuit for inductive loads. The outputs must be protected with a free-wheeling diode for this purpose. RC interference suppression units must not be used.
Ì Power devices which are a powerful source of interference must be installed in a separate location away from the input and output circuits for signal processing. The cable routing for safety circuits should be as far away as possible from the cables of the power circuits.
Ì In order to avoid EMC interference, the physical environmental and operating conditions at the installation site of the device must comply with the requirements according to the standard
EN 60204-1:2006, section 4.4.2 (EMC).
CAUTION
Please pay attention to any interference fields in case of devices such as frequency converters or induction heating systems. Observe the EMC instructions in the manuals from the respective manufacturer.
Important!
If the device does not appear to function when operating voltage is applied (e.g. green STATE LED does not flash), the safety switch must be returned unopened to the manufacturer.
EN
123041-03-07/15 (translation of the original operating instructions)
15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.1. Notes about
Important!
Ì For use and operation as per the class 2 circuits” must be used.
requirements
1)
, a power supply with the feature “for use in
Alternative solutions must comply with the following requirements: a) Electrically isolated power supply unit with a max. open-circuit voltage of 30 V/DC and a limited current of max. 8 A.
b) Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be designed for max. 3.3 A and should be integrated into the 30 V DC voltage section.
Ì For use and applications as per the category code CYJV/7 must be used.
requirements 1) , a connection cable listed under the UL
1) Note on the scope of the UL approval: The devices are tested according to the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock and fire).
10.2. Safety in case of faults
Ì The operating voltage UB and the solenoid voltage IMP are reverse polarity protected.
Ì The safety outputs FO1A/FO1B are short circuit-proof
Ì A short circuit between FO1A and FO1B is detected by the switch.
Ì A short circuit in the cable can be excluded by laying the cable with protection.
10.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of switches and current required for the outputs. The following rules apply:
Max. current consumption of an individual switch I
max
I max
= I
UB
+ I
FO1A
+
FO1B
+ I
OL
+ I
OD
I
UB
= Switch operating current (40 mA)
I
OL
/I
OD
= Load current of monitoring outputs (max. 50 mA per monitoring output)
I
FO1A+FO1B
= Load current of safety outputs FO1A + FO1B (2 x max. 150 mA)
Max. current consumption of a switch chain
Σ
I
max
Σ I max
= I
FO1A+FO1B
+ n x (I
UB
+ I
OL
+ I
OD
) n = Number of connected switches
16
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.4. Requirements for connection cables
CAUTION
Ì
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì Use connection components and connection cables from EUCHNER.
On the usage of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connection cables:
For safety switches CTP-…-AR-…-SAB-… with plug connectors 2 x M12
Parameter
Conductor cross-section min.
R max.
C max.
L max.
Recommended cable type
Value
0.34
60
120
0.65
LIYY 8x or 5x0.34 mm²
For safety switches CTP-…-AR-…-SH-… with plug connector M23 (RC18)
Parameter
Conductor cross-section min.
R max.
C max.
L max.
Recommended cable type
Value
0.34
60
120
0.65
LIFY11Y min. 12-core
Unit
mm²
W /km nF/km mH/km
Unit
mm²
W /km nF/km mH/km
123041-03-07/15 (translation of the original operating instructions)
17
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.5. Maximum cable lengths
Switch chains are permitted up to a maximum overall cable length of 200 m taking into account the voltage drop as a result of the cable resistance (see table below with example data and case example).
l max
=200 m l
2 l
1 l n u n
= 24 V -20% u min
= 24 V -10% i out
SPS
PLC
5 x 0,34 mm
2
CES-AR # 1 CES-AR # n-1
n
Max. number of switches
5
6
10
CTP-AR # n
I
FO1A/FO1B
(mA)
Possible output current per channel FO1A/FO1B
10
25
50
100
150
10
25
50
100
150
10
25
50
100
150
l
1
(m)
Max. cable length from the last switch to the control system
150
100
80
50
25
120
90
70
60
50
40
25
50
25
70
18
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.5.1. Determining cable lengths using the example table
Example: 6 switches are to be used in series. Cabling with a length of 40 m is routed from a safety relay in the control cabinet to the last switch (#6). Cables with a length of 20 m each are connected between the individual CES-AR/CTP-L1-… safety switches. l
2
= 5 x 20 m l = 140 m l
1
= 40 m l n
= 20 m u n
= min. 19,2 V i
OA/OB
= 75 mA
Sicherheitsrelais
Safety Relay
CES-AR # 1 CES-AR # 2 CES-AR # 3 CES-AR # 5
CTP-AR # 4
CTP-AR # 6
Figure 3: Circuit example with six CES-AR/CTP-L1-…
A safety relay is connected downstream which consumes 75 mA on each of the two safety inputs. This operates over the whole temperature range with a voltage of 19.2 V (corresponds to 24 V -20%).
All the relevant values can now be determined using the example table:
1. Select the corresponding section in the column n (max. number of switches). Here: 6 switches.
2. In column I
FO1A/FO1B
Here: 100 mA.
(possible output current per channel FO1A/FO1B), find a current greater than or equal to 75 mA.
¨
It is then possible to determine the maximum cable length from the last switch (#6) to the control system from column l
1
. Here: a length of 50 m is permitted.
Result: The desired cable length l
1 chain l max
of 40 m is below the permitted value from the table. The overall length of the switch
of 140 m is less than the maximum value of 200 m.
¨
The planned application is therefore functional in this form.
EN
123041-03-07/15 (translation of the original operating instructions)
19
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.6. Pin assignment safety switch CTP-…-AR-…-SAB-… with plug connectors 2 x M12
Wiring diagram A
Plug connector
(view of connection side)
X1.2
X1.3
X1.4
2 x M12
X2.5
X1.1
X1.7
X1.6
X1.8
X1.5
X2.1
Pin
X 1.1
X 1.2
X 1.3
X 1.4
X 1.5
X 1.6
X 1.7
X 1.8
Designation
FI1B
UB
FO1A
FO1B
OL
FI1A
0 V UB
RST
Function
Enable input for channel 2
Operating voltage of AR electronics, 24 V DC
Safety output, channel 1
Safety output, channel 2
Guard locking monitoring output
Enable input for channel 1
Operating voltage of AR electronics 0 V
Reset input
Wire color
Connection cable 1)
WH
BN
GN
YE
GY
PK
BU
RD
X2.2
X2.4
X2.3
X 2.1
X 2.2
X 2.3
X 2.4
IMM
OD
OI
IMP
X 2.5
-
1) Only for standard EUCHNER connection cable
Operating voltage of guard locking solenoid 0 V
Door monitoring output
Diagnostics output
Operating voltage of guard locking solenoid, 24 V DC
Not used
BN
WH
BU
BK
GY
10.7. Pin assignment safety switch CTP-…-AR-…-SH-… with plug connector M23 (RC18)
Wiring diagram B
Plug connector
(view of connection side)
M23 (RC18)
With screen bonding clamp
9
8
10
11
17
16
18
12
13
19
14
15
1
7
6
5
2
4
3
Pin Designation Function
1
2
3
4
IMP
FI1A
FI1B
FO1A
Operating voltage of guard locking solenoid, 24 V DC
Enable input for channel 1
Enable input for channel 2
Safety output, channel 1
5
6
FO1B
UB
Safety output, channel 2
Operating voltage of AR electronics, 24 V DC
14
15
16
17
18
19
9
10
7
8
11
12
13
RST
OD
OI
OL
-
FE
-
-
-
-
-
IMM
0 V UB
1) Only for standard EUCHNER connection cable
Reset input
Door monitoring output
Diagnostics output
Guard locking monitoring output n.c.
Function earth (must be connected to meet the EMC requirements) n.c.
n.c.
n.c.
n.c.
n.c.
Operating voltage of guard locking solenoid 0 V
Operating voltage of AR electronics 0 V
Wire color
Connection cable 1)
VT
RD
GY
RD/BU
GN
BU
GY/PK
GN/WH
YE/WH
GY/WH
BK
GN/YE
PK
BN/GY
BN/YE
BN/GN
WH
YE
BN
20
(translation of the original operating instructions) 123041-03-07/15
10.8. Connector assignment for Y-distributor
(only for version with plug connectors 2 x M12)
Pin assignment for safety switch
CTP-L1-… (plug X1, 8-pin plug) and Y-distributor (8-pin socket)
Pin
X1.1
X1.2
Function
FI1B
UB
X1.3
X1.4
X1.5
X1.6
X1.7
X1.8
FO1A
FO1B
OL
FI1A
0 V
RST
Strapping plug 097645 4-pin, plug
(figure similar)
Y-distributor with connecting cable
111696 or 112395
Socket
2
3 4 5
6
1 8 7
M12x1
15
M12x1
15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
M12x1
Ø 14,5
33
111696
112395
200
1000
Plug
3
5
4
1
2
M12x1
15
2
1
3
5
4
Socket
Pin
X2.1
X2.2
X2.3
X2.4
X2.5
Function
UB
FO1A
0 V
FO1B
RST
Pin
X3.1
X3.2
X3.3
X3.4
X3.5
Function
UB
FI1A
0 V
FI1B
RST
EN
123041-03-07/15 (translation of the original operating instructions)
21
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.9. Connection of a single CTP-AR
If a single CTP-AR is used, connect the switch as shown in
. The monitoring outputs can be routed to a control system.
The switches can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 s. The
RST input must be connected to 0 V if it is not used.
WARNING
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated.
Important!
Ì The example shows only an excerpt that is relevant for connection of the CTP system. The example illustrated here does not show complete system planning. The user is responsible for safe integration in the overall system. Detailed application examples can be found at www.EUCHNER.de.
Simply enter the order number of your switch in the search box. All available connection examples for the device can be found under “Downloads.”
24V DC
24V
/
-B1
CTP
-F1
1
2
IMP
X2:4
1
-F2
2
UB
X1:2 X1:8
RST FI1A
X1:6
Safety inputs
FI1B
X1:1
Read head
Door monitoring
Monitoring outputs
Guardlocking active Diagnostics Safety outputs
X2:1
IMM
X2:5
NC
X1:7
0V UB
X2:2
OD
X1:5
OL
X2:3
OI
X1:3
FO1A
Connected load
X1:4
FO1B
0V
0V
/
Figure 4: Connection example for separate operation, version with plug connectors 2xM12
22
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.10. Connection of several CTP-AR in a switch chain
Important!
Ì An AR switch chain may contain a maximum of 20 safety switches.
Ì The example shows only an excerpt that is relevant for connection of the CTP system. The example illustrated here does not show complete system planning. The user is responsible for safe integration in the overall system. Detailed application examples can be found at www.EUCHNER.
de. Simply enter the order number of your switch in the search box. You will find all available connection examples for the device in Downloads.
The series connection is shown here based on the example of the version with plug connectors 2 x M12. The series connection of the version with plug connector RC18 has similar behavior, but is realized using additional terminals in a control cabinet.
The switches in the version with plug connectors 2 x M12 are connected one after the other with the aid of pre-assembled connection cables and Y-distributors. If a safety guard is opened or if a fault occurs on one of the switches, the system shuts down the machine. A higher level control system cannot, however, detect which safety guard is open or on which switch a fault has occurred with this connection technology.
The safety outputs are permanently assigned to the respective safety inputs of the downstream switch. FO1A must be routed to FI1A and FO1B to FI1B. If the connections are interchanged (e. g. FO1A to FI1B), the unit will switch to the fault state.
Always use the RST input in series connections. All switches in a chain can be reset at the same time with this reset input.
To do this, a voltage of 24 V must be applied to the RST input for at least 3 s. If input RST is not used in your application, it should be connected to 0 V.
Note the following on this aspect:
Ì A common signal must be used for all switches in the chain. This can be a changeover switch or the output of a control system. A button is not suitable because Reset must always be connected to GND during operation (see switch S11 in
Ì Reset must always be performed simultaneously for all switches of the chain.
123041-03-07/15 (translation of the original operating instructions)
23
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
Actuator
Read head
Read head
Figure 5: Connection example for operation in a CES-AR switch chain
24
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.11. Notes on operation with safe control systems
Please observe the following requirements for connection to safe control systems:
Ì Use a common power supply for the control system and the connected safety switches.
Ì A pulsed power supply must not be used for UB. Tap the supply voltage directly from the power supply unit. If the supply voltage is connected to a terminal of a safe control system, this output must provide sufficient electrical current.
Ì Always connect inputs FI1A and FI1B directly to a power supply unit or to outputs FO1A and FO1B of another EUCHNER
AR device (series connection). Pulsed signals must not be present at inputs FI1A and FI1B.
Ì The safety outputs (FO1A and FO1B) can be connected to the safe inputs of a control system. Prerequisite: The input must be suitable for pulsed safety signals (OSSD signals, e.g. from light curtains). The control system must tolerate test pulses on the input signals. This normally can be set up by parameter assignment in the control system. Observe the
13. Tech‑ nical data on page 31
Ì The following applies for single-channel control of the guard locking:
The guard locking (IMM) and the control system must have the same ground.
Ì For dual-channel control of the solenoid voltage by safe outputs of a control system, the following points must be observed (see also
):
-If possible, switch off the pulsing of the outputs in the control system.
-Pulses up to a length of max. 5 ms are tolerated.
A detailed example of connecting and setting the parameters of the control system is available for many devices at www.
euchner.de in Download » Applications » CTP. The features of the respective device are dealt with there in greater detail.
123041-03-07/15 (translation of the original operating instructions)
25
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
Digital Output
Supply of the contro
Figure 6: Connection example for the connection to ET200
Actuator
26
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
11. Setup
11.1. LED indicators
You will find a detailed description of the signal functions in chapter
12. System status table on page 30.
LED
STATE
LOCK
DIA
Color
Green
Yellow
Red
LED
STATE
LOCK
DIA
11.2. Teach-in function for actuator (only for unicode evaluation)
The actuator must be allocated to the safety switch using a teach-in function before the system forms a functional unit.
During a teach-in operation, the safety outputs are switched off, i.e. the system is in the safe state.
The teach-in operation is fully automatic.
Tip!
Prior to switching on, close the safety guard on which the actuator to be taught in is installed. The teach-in operation starts immediately after switching on. This feature simplifies above all the teaching-in with series circuits and on large systems.
Important!
Ì The teach-in operation may be performed only if the device does not have any internal errors.
Ì Devices in the condition as supplied remain in teach-in standby state until you have successfully taught in the first actuator. Once taught in, switches remain in the teach-in standby state for approx. 3 min. after each switch on.
Ì The safety switch disables the code of the previous actuator if teach-in is carried out for a new actuator. Teach-in is not possible again immediately for this actuator if a new teach-in operation is carried out. The disabled code is released again in the safety switch only after a third code has been taught-in.
Ì The safety switch can only be operated with the last actuator taught-in.
Ì If the switch detects the actuator that was most recently taught when in teach-in standby state, this state is ended immediately and the switch changes to normal state.
Ì The actuator to be taught-in is not activated if it is within the operating distance for less than 30 s.
EN
123041-03-07/15 (translation of the original operating instructions)
27
Operating instructions
Transponder-Coded Safety Switch CTP-AR
11.2.1. Teaching-in actuator
1. Establish teach-in standby:
-Devices in the condition as supplied: unlimited teach-in standby after switching on
-Switches already taught in: teach-in standby is available for approx. 3 min after switching on
¨
Teach-in standby indication, STATE LED flashes 3x repeatedly
2. Insert the actuator during teach-in standby.
¨
The automatic teach-in operation starts (duration approx. 30 s).
During the teach-in operation the STATE LED flashes (approx. 1 Hz).
Alternate flashing of the STATE and DIA LEDs acknowledges the successful teach-in operation.
Teach-in errors are indicated by the illumination of the red DIA LED and a flashing code on the green State LED (see
12. System status table on page 30
3. Switch off operating voltage UB (min. 3 s).
¨
The code of the actuator that was just taught in is activated in the safety switch.
4. Switch on operating voltage UB.
¨
The device operates normally.
11.2.2. Teach-in function with series connection, replacing and teaching in device
It is recommended not to teach in the actuators in the series connection but to teach them in one by one instead. Teach-in in a series connection works analogously to separate operation in principle. It is a prerequisite that the steps below are followed. Further steps might have to be observed for mixed switch chains (e. g. for chains with CES and CET). Observe the operating instructions for the other devices in the chain for this purpose.
Work on the wiring (e. g. during device replacement) should generally be performed in a de-energized state. On certain systems, it is nevertheless necessary to perform this work and subsequent teach-in during ongoing operation.
Input RST must be connected as shown in
Proceed as follows:
1. Open the safety guard on which the switch or actuator is to be replaced.
2. Mount the new switch or actuator and prepare it for the teach-in operation (see chapter
11.2.1. Teaching‑in actuator on page 28
).
3. Close all safety guards in the chain and activate guard locking.
4. Actuate the reset for at least 3 s (24 V on RST).
¨
On the safety switch that is positioned at a new actuator, the green LED flashes at approx. 1 Hz and the actuator is taught-in. This takes approx. 30 s. Do not switch off during this time and do not actuate reset! The teach-in operation is complete when the STATE and DIA LEDs flash alternately.
5. Actuate the reset for at least 3 s (24 V on RST).
¨
The system restarts and then continues to function in normal operation.
28
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
11.3. Functional check
WARNING
Ì
Danger of fatal injury as a result of faults in installation and functional check.
Before carrying out the functional check, make sure that there are no persons in the danger area.
Ì Observe the valid accident prevention regulations.
11.3.1. Mechanical function test
The actuator must slide easily into the actuating head. Close the safety guard several times to check the function. For devices with mechanical unlocking device (emergency unlocking or escape release), the correct function of the mechanical unlocking device must be checked as well.
11.3.2. Electrical function test
After installation and any fault, the safety function must be fully checked. Proceed as follows:
1. Switch on operating voltage.
¨
The machine must not start automatically.
¨
The safety switch carries out a self-test. The green STATE LED flashes for 10 s at 5 Hz. The green STATE LED then flashes at regular intervals.
2. Close all safety guards. Guard locking by solenoid force: activate guard locking.
¨
The machine must not start automatically. It must not be possible to open the safety guard.
¨
The green STATE LED illuminates continuously.
3. Enable operation in the control system.
¨
It must not be possible to deactivate the guard locking as long as operation is enabled.
4. Disable operation in the control system and deactivate guard locking.
¨
The safety guard must remain locked until there is no longer any risk of injury.
¨
It must not be possible to start the machine as long as the guard locking is deactivated.
Repeat steps 2 - 4 for each safety guard.
123041-03-07/15 (translation of the original operating instructions)
29
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
12. System status table
LED indicator
Output
Operating mode State
Self-test
X closed
Safety outputs FO1A and FO1B
off off on on off on closed off
Normal operation
closed off open
X off off
Teach-in operation
(only unicode) closed off
X off
X off on on off off off
X
X on off off on
X
X X
Fault display
X
X
X
X
X off off off off off off
X off off off off
X off off off
5 Hz
(10 s)
2 x
3 x
4 x
5 x
1 x inverse
1 x inverse
1 x
3 x
1 Hz
1 x
X
Self-test after power up
Normal operation, door closed and locked
Normal operation, door closed and locked, safety outputs not switched because:
- Preceding device in the switch chain signals "door open" (only with series connection)
Normal operation, door closed and
not
locked
Normal operation, door open
Device in teach-in standby
Teach-in operation
Positive acknowledgment after completion of teach-in operation
Fault in teach-in operation (only unicode)
Actuator removed from the operating distance prior to the end of the teach-in operation or faulty actuator detected.
Input fault
(e. g. missing test pulses, illogical switch state from previous switch in the switch chain)
Read error
(e. g. actuator faulty)
Output fault
(e.g. short circuit, loss of switching ability)
Disabled actuator detected
Internal fault
LED not illuminated
LED illuminated
10 Hz (8 s) LED flashes for 8 s at 10 Hz
Key to symbols
3 x LED flashes three times, and this is then repeated
X
LEDS flash alternately
Any state
After the cause has been remedied, faults can generally be reset by opening and closing the safety guard. If the fault is still displayed afterward, use the reset function or briefly interrupt the power supply. Please contact the manufacturer if the fault could not be reset after restarting.
Important!
If you do not find the displayed device status in the System status table, this indicates an internal device fault. In this case, you should contact the manufacturer.
30
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
13. Technical data
NOTICE
If a product data sheet is included with the product, the information on the data sheet applies.
13.1. Technical data for safety switch CTP-AR
Parameter min.
General
Material
- Switch head
- Switch housing
Installation position
Degree of protection with plug connector M12 with plug connector RC18
Safety class according to EN IEC 61558
Degree of contamination
Mechanical life
Ambient temperature at UB = 24 V
Actuator approach speed, max.
Actuating/extraction/retention force at 20 °C
Locking force F max
Locking force F
Zh
Weight
1)
1)
according to EN ISO 14119
Connection type (depending on version)
-20
Value typ.
Die-cast zinc
Reinforced thermoplastic
Any
IP67/IP69
IP 65
(screwed tight with the related mating connector)
III
3
1 x 10 6 operating cycles
-
20
35/30/20
F
Zh
2600
= F max
/1.3 = 2000
Approx. 0.42
2 plug connectors M12, 5 and 8-pin
1 plug connector RC18, 19-pin (as yet no UL approval)
Operating voltage UB (reverse polarity protected, regulated, residual ripple < 5%)
Current consumption I
UB
For the approval according to UL the following applies
Switching load according to UL
External fuse (operating voltage UB)
External fuse (solenoid operating voltage IMP)
Rated insulation voltage U i
Rated impulse withstand voltage U imp
Resilience to vibration
EMC protection requirements
Ready delay
Risk time for single device
Risk time delay per device
Switch-on time
Discrepancy time
Test-pulse duration
Safety outputs FO1A/FO1B
- Output voltage U
FO1A
/U
FO1B
2)
HIGH U
FO1A
/U
FO1B
LOW U
FO1A
/U
FO1B
Switching current per safety output
Utilization category acc. to EN 60947-5-2
24 ± 15% (PELV)
max.
+55
40
Operation only with UL class 2 power supply, or equivalent measures
0.25
DC 24 V, class 2
2
0.5
-
-
-
-
-
-
-
-
-
Acc. to EN 60947-5-3
Acc. to EN 60947-5-3
8
-
5
-
-
1
Semiconductor outputs, p-switching, short circuit-proof
8
50
0.5
-
260
400
10
UB - 1.5
UB
0
1 -
1
150
DC-13 24V 150 mA
Caution: outputs must be protected with a free-wheeling diode in case of inductive loads
0.5
p-switching, short circuit-proof
0.8 x UB
-
UB
50
Switching frequency
Monitoring outputs OL, OI, OD
Output voltage
Max. load
Solenoid
Solenoid operating voltage IMP (reverse polarity protected, regulated, residual ripple < 5 %)
Current consumption solenoid I
IMP
Power consumption
Duty cycle
Reliability values acc. to EN ISO 13849-1
Mission time
Monitoring of guard locking and the safety guard position
Category
Performance Level (PL)
PFH d
Control of the guard locking
Category
Performance Level (PL)
PFH d
DC 24 V +10%/-15%
400
6
100
20
4 e
4.1 x 10 -9 /h
Depends on external control
1) Only applies in combination with straight actuators.
2) Values at a switching current of 50 mA without taking into account the cable length.
Unit
°C m/min
N
N
N kg
V DC mA
V DC mA
Hz
V DC mA mA
W
% years s ms ms ms ms ms
A
A
V kV
123041-03-07/15 (translation of the original operating instructions)
31
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
13.1.1. Typical system times
Please refer to the technical data for the exact values.
Ready delay
: After switching on, the unit carries out a self-test. The system is ready for operation only after this time.
Switch-off time of safety outputs
: The max. reaction time t on to the moment when the safety outputs switch on.
is the time from the moment when the safety guard is locked
Simultaneity monitoring, safety inputs FI1A/FI1B
: If the safety inputs have different switching states for longer than a specific time, the safety outputs (FO1A and FO1B) will be switched off. The device switches to fault state.
Risk time according to EN 60947-5-3
: If an actuator moves outside the operating distance, the safety outputs (FO1A and FO1B) are switched off after the risk time at the latest.
If several devices are operated in a series connection, the risk time of the overall device chain will increase with each device added. Use the following calculation formula: t r
= t r, e
+ (n x t l
) t r
= Total risk time t r, e
= Risk time, single device (see technical data) t l
= Risk time delay per device n = Number of additional devices (total number -1)
Discrepancy time
: The safety outputs (FO1A and FO1B) switch with a slight delay in relation to each other. They assume the same signal state at the latest after the discrepancy time.
Test pulses at the safety outputs
: The device generates its own test pulses on the safety outputs (FO1A and FO1B).
A downstream control system must tolerate these test pulses.
This can usually be set up in the control systems by parameter assignment. If parameter assignment is not possible for your control system or if shorter test pulses are required, please contact our support organization.
The test pulses are also output when the safety outputs are switched off.
32
(translation of the original operating instructions) 123041-03-07/15
13.2. Dimension drawing safety switch CTP…
Version with plug connector 2 x M12
33
h
34
0,5
∅ 5.3 (4x) for screw M5x35 mm
DIN 1207/ISO 4762
Mechanical release
Locking screw
LEDs
Operating instructions
Transponder-Coded Safety Switch CTP-AR
With escape release
The actuator shaft for the escape release can be extended using support brackets (max. 94 mm)
Basic position for escape release
44 / 74 / 94
Release by pressing
M12x1
<42>
Version with plug connector M23 (RC18)
Z
30
<40>
X1
X2
M23x1
A
C
0,5
B
Plug connectors 2 x M12
Cable exit left Cable exit right
Plug connector M23
Cable exit left Cable exit right
123041-03-07/15 (translation of the original operating instructions)
33
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
With mechanical key release
max. 50
19 25
With mechanical release
21,5
With emergency unlocking
32,4
With front wire release
34
(translation of the original operating instructions) 123041-03-07/15
Operating instructions
Transponder-Coded Safety Switch CTP-AR
13.3. Technical data for actuator CTP-...
Parameter
Housing material
Weight
Ambient temperature
Degree of protection acc. to
EN IEC 60529
Mechanical life
Locking force, max.
Straight and hinged actuator
Bent actuator
Installation position
Power supply min.
-20
Value
typ.
Fiber reinforced plastic
0.03 … 0.06 (depending on version)
-
IP67/IP69K
1 x 10 6
2600
1500
Any
Inductive via read head
13.3.1. Dimension drawing for actuator CTP-...
Dimension drawing
Min. door radius
[mm]
max.
+55
Unit
Order no./item
kg
°C
N
R > 300
45 17 20 11
4,4
123041-03-07/15 (translation of the original operating instructions)
A-A 1 : 2
35
+
-
4
1
20
4,4
R>1200
R>1400
122666
A-C-H-G-SST-122666
A
A
EN
35
Operating instructions
Transponder-Coded Safety Switch CTP-AR
4,4
37,5
9
45
12,45
2,5
R>300
122667
A-C-H-W-SST-122667
4,4
5,25
A-A 1 : 2
37,2
-
+ 4
1
8
122668
A-C-H-W-SST-122668
A
A
36
(translation of the original operating instructions) 123041-03-07/15
5,5
40
50
30
18
Dimension drawing
8,5
3,25
Operating instructions
Transponder-Coded Safety Switch CTP-AR
Min. door radius
[mm]
Order no./item
122671
A-C-H-RL-LS-122671
34
+
-
4
1
4
122672
A-C-H-RR-LS-122672
R>200
R>200
26
122675
A-C-H-RO-LS-122675
40
50
8,5
13,2
30
18
16
26
R>200
122676
A-C-H-RU-LS-122676
EN
Tip!
Safety screws are included with the actuator.
123041-03-07/15 (translation of the original operating instructions)
37
Operating instructions
Transponder-Coded Safety Switch CTP-AR
14. Ordering information and accessories
Tip!
Suitable accessories, such as cables or installation material, can be found at www.EUCHNER.de.
Simply enter the order number of your item in the search box and open the item view. “Accessories” contains accessories that can be combined with the item.
15. Inspection and service
WARNING
Danger of severe injuries due to the loss of the safety function.
Ì If damage or wear is found, the complete switch and actuator assembly must be replaced. Replacement of individual parts or assemblies is not permitted
Ì Check the device for proper function at regular intervals and after every fault. For information about possible time intervals, refer to EN ISO 14119:2013, section 8.2.
Regular inspection of the following is necessary to ensure trouble-free long-term operation:
Ì
Check the switching function (see chapter
11.3. Functional check on page 29
Ì Check all additional functions (e.g. escape release, lockout mechanism, etc.)
Ì Check the secure fastening of the devices and the connections
Ì Check for soiling
No servicing is required. Repairs to the device are only allowed to be made by the manufacturer.
NOTICE
The year of manufacture is given in the laser marking at the bottom right corner. The current version number in the format (V X.X.X) can also be found on the device.
16. Service
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
Internet:
www.euchner.de
38
(translation of the original operating instructions) 123041-03-07/15
17. Declaration of conformity
Operating instructions
Transponder-Coded Safety Switch CTP-AR
123041-03-07/15 (translation of the original operating instructions)
39
EN
Euchner GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen [email protected]
www.euchner.de
Edition:
123041-03-07/15
Title:
Operating instructions Transponder-Coded Safety Switch
CTP-AR
(translation of the original operating instructions)
Copyright:
© EUCHNER GmbH + Co. KG, 07/2015
Subject to technical modifications; no responsibility is accepted for the accuracy of this information.
Laadi alla
Reklaam