Operating instructions
Transponder-Coded Safety Switch CTP-AR
10.11. Notes on operation with safe control systems
Please observe the following requirements for connection to safe control systems:
Ì Use a common power supply for the control system and the connected safety switches.
Ì A pulsed power supply must not be used for UB. Tap the supply voltage directly from the power supply unit. If the supply voltage is connected to a terminal of a safe control system, this output must provide sufficient electrical current.
Ì Always connect inputs FI1A and FI1B directly to a power supply unit or to outputs FO1A and FO1B of another EUCHNER
AR device (series connection). Pulsed signals must not be present at inputs FI1A and FI1B.
Ì The safety outputs (FO1A and FO1B) can be connected to the safe inputs of a control system. Prerequisite: The input must be suitable for pulsed safety signals (OSSD signals, e.g. from light curtains). The control system must tolerate test pulses on the input signals. This normally can be set up by parameter assignment in the control system. Observe the
13. Tech‑ nical data on page 31
Ì The following applies for single-channel control of the guard locking:
The guard locking (IMM) and the control system must have the same ground.
Ì For dual-channel control of the solenoid voltage by safe outputs of a control system, the following points must be observed (see also
):
-If possible, switch off the pulsing of the outputs in the control system.
-Pulses up to a length of max. 5 ms are tolerated.
A detailed example of connecting and setting the parameters of the control system is available for many devices at www.
euchner.de in Download » Applications » CTP. The features of the respective device are dealt with there in greater detail.
123041-03-07/15 (translation of the original operating instructions)
25
EN
Operating instructions
Transponder-Coded Safety Switch CTP-AR
Digital Output
Supply of the contro
Figure 6: Connection example for the connection to ET200
Actuator
26
(translation of the original operating instructions) 123041-03-07/15