Advertisement
Advertisement
Bulletin No. CUB5V-H
Drawing No. LP0645
Released 04/16
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839 www.redlion.net
MODEL CUB
®
5V - MINIATURE ELECTRONIC 5-DIGIT DC VOLTMETER
C
R
UL
US LISTED
IND. CONT. EQ.
51EB
FOUR SELECTABLE D.C. RANGES
0 to 200 mV, 2 V, 20 V, 200 V
MINIMUM AND MAXIMUM DISPLAY CAPTURE
LCD, REFLECTIVE OR RED/GREEN LED BACKLIGHTING
0.48" (12.2 mm) HIGH DIGITS
OPTIONAL SETPOINT OUTPUT CARDS
OPTIONAL SERIAL COMMUNICATIONS CARDS (RS232 or RS485)
OPTIONAL USB PROGRAMMING CARD
OPERATES FROM 9 TO 28 VDC POWER SOURCE
FRONT PANEL OR CRIMSON PROGRAMMABLE
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
NEMA 4X/IP65 SEALED FRONT BEZEL
GENERAL DESCRIPTION
The CUB5 provides the user the ultimate in flexibility, from its complete user programming to the optional setpoint control and communication capability.
The CUB5V accepts a DC Voltage input signal and provides a display in the desired unit of measure. The meter also features minimum and maximum display capture, display offset, units indicator, and programmable user input.
The display can be toggled either manually or automatically between the selected displays.
The CUB5 display has 0.48" (12.2 mm) high digits. The LCD is available in two versions, reflective and red/green backlight. The backlight version is user selectable for the desired color and also has variable display intensity.
The capability of the CUB5 can be easily expanded with the addition of option cards. Setpoint capability is field installable with the addition of the setpoint output cards. Serial communications capability for RS232 or RS485 is added with a serial option card.
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5. The
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the unit and sensors.
VOLTAGE
The CUB5V is the DC Volt meter. It features 4 voltage input ranges, that are selected by the user via a programming jumper and software input range selection. The ranges consist of following: 0 to 200 mV, 2 V, 20 V, 200 V. Users should select the appropriate voltage range that covers their maximum input.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to installationand operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
.13 (3.3)
1.54 (39.1) 1.29 (32.8)
1.30 +.024
-.000
(33 )
SEL RST
2.95 (74.9) .15 (3.8) 1.71
(43.4)
2.68
+.025
-.000
(68 )
1
o
rderinG
i
nforMation
TYPE
CUB5
Optional Plug-in Cards
Accessories
MODEL NO.
CUB5V
CUB5RLY
CUB5SNK
CUB5COM
CUB5USB
MLPS
CBLPRO
CBPRO
SFCRD
DESCRIPTION
DC Volt Meter with reflective display
DC Volt Meter with backlight display
Single Relay Option Card
Dual Sinking Open Collector Output card
RS485 Serial Communications Card
RS232 Serial Communications Card
USB Programming Card
+12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out
+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out
Programming Cable RS232 (RJ11-DB9)
Communication Cable RS485 (RJ11-DB9)
Crimson PC Configuration Software, Free Download Available 1
CBLUSB USB Programming Cable CBLUSB00
1 Crimson software is a free download from http://www.redlion.net. System requirements for the software are listed on the download page.
PART NUMBER
CUB5VR00
CUB5VB00
CUB5RLY0
CUB5SNK0
CUB5COM1
CUB5COM2
CUB5USB0
MLPS1000
MLPS2000
CBLPROG0
CBPRO007
SFCRD200
G
eneral
M
eter
S
pecificationS
1. DISPLAY: 5 digit LCD 0.48" (12.2 mm) high digits
CUB5VR00: Reflective LCD with full viewing angle
CUB5VB00: Transmissive LCD with selectable red or green LED backlight, viewing angle optimized. Display color change capability with output state when using an output module.
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input polarity protection.
MODEL
NO.
CUB5VR00
CUB5VB00
CUB5VB00
INPUT
RANGE
DISPLAY COLOR
ACCURACY
@23 °C, less than 85% RH
---
Red (max intensity)
Green (max intensity)
3. INPUT RANGES: Jumper Selectable
D.C. Voltages: 200 mV, 2 V, 20 V, 200 V
4. SIGNAL INPUTS:
INPUT
IMPEDANCE
INPUT CURRENT
@ 9 VDC
WITHOUT
CUB5RLY0
10 mA
85 mA
95 mA
MAX
INPUT
SIGNAL
INPUT CURRENT
@ 9 VDC WITH
CUB5RLY0
RESOLUTION
40 mA
115 mA
125 mA
TEMP.
COEFFICIENT
200 mVDC 0.1% of span 1.027 M Ω 75 VDC 10 µV 70 ppm / °C
2 VDC 0.1% of span 1.027 M Ω 75 VDC
20 VDC 0.1% of span 1.027 M Ω 250 VDC
.1 mV
1 mV
70 ppm / °C
70 ppm / °C
200 VDC 0.1% of span 1.027 M Ω 250 VDC 10 mV 70 ppm / °C
5. OVERRANGE RATINGS, PROTECTION & INDICATION:
9 to 28 VDC power circuit is not isolated from the signal circuit.
Input Overrange Indication: “
OLOL
Input Underrange Indication: “
”.
ULUL
”.
Display Overrange/Underrange Indication: “
6. A/D CONVERTER: 16 bit resolution
7. RESPONSE TIME:
Display: 500 msec min.
.....
”/“.....
”
Output: 800 msec max (with input filter setting of 0)
8. NORMAL MODE REJECTION: 60 dB 50/60 Hz
9. USER INPUT (USR): Programmable input. Connect terminal to common
(USR COMM) to activate function. Internal 10KΩ pull-up resistor to +9 to
28 VDC.
Threshold Levels: V
IL
= 0.7 V max; V
IH
= 2.4 V min; V
MAX
= 28 VDC
Response Time: 5 msec typ.; 50 msec debounce (activation and release)
10. CONNECTIONS: Wire clamping screw terminals
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 3.5 inch-lbs (0.395 N-m) max.
11. MEMORY: Nonvolatile E 2 PROM memory retains all programming parameters and max/min values when power is removed.
12. CONSTRUCTION: This unit is rated for Type 4X/IP65 requirements for indoor/outdoor use. Installation Category I, Pollution Degree 2. High impact plastic case with clear viewing window. Panel gasket and mounting clip included.
13. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range for CUB5VR00: -35 to 75°C
Operating Temperature Range for CUB5VB00 depends on display color
and intensity level as per below:
INTENSITY LEVEL TEMPERATURE
Red Display
Green Display
1 & 2
3
4
5
1 & 2
3
4
5
-35 to 75°C
-35 to 70°C
-35 to 60°C
-35 to 50°C
-35 to 75°C
-35 to 65°C
-35 to 50°C
-35 to 35°C
Storage Temperature: -35 to 85°C
Operating and Storage Humidity: 0 to 85% max. relative humidity (noncondensing)
Vibration to IEC 68-2-6: Operational 5-500 Hz, 5 g.
Shock to IEC 68-2-27: Operational 30 g
Altitude: Up to 2000 meters
14. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
Safety requirements for electrical equipment for measurement, control, and laboratory use:
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and Measuring
Circuits
RoHS Compliant
UL Recognized Component: File #E179259
UL Listed: File #E137808
Type 4X Indoor/Outdoor Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Refer to EMC Installation Guidelines for additional information.
15. WEIGHT: 3.2 oz (100 g)
2
o ptional
p luG
in
c ardS
ADDING OPTION CARDS
The CUB5 meters can be fitted with optional output cards and/or serial communications cards. The details for the plug-in cards can be reviewed in the specification section below. The plug-in cards, that are sold separately, can be installed initially or at a later date.
WARNING: Disconnect all power to the unit before installing
Plug-in card.
V
DS ON
: 0.7 V @ 100 mA
V
DS MAX
: 30 VDC
Offstate Leakage Current: 0.5 mA max.
RS485 SERIAL COMMUNICATIONS CARD
Type: RS485 multi-point balanced interface (non-isolated)
Baud Rate: 300 to 38.4k
Data Format: 7/8 bits; odd, even, or no parity
Bus Address: 0 to 99; max 32 meters per line
Transmit Delay: Selectable (refer to CUB5COM bulletin) Note: Measurement errors may occur if signal input common is shared with another circuit common (ie, serial common, Dual Sinking Output option card, or Power Supply common) on multiple units.
SINGLE RELAY CARD
Type: Single FORM-C relay
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive
Life Expectancy: 100,000 minimum operations
DUAL SINKING OUTPUT CARD
Type: Non-isolated switched DC, N Channel open drain MOSFET
Current Rating: 100 mA max.
RS232 SERIAL COMMUNICATIONS CARD
Type: RS232 half duplex (non-isolated)
Baud Rate: 300 to 38.4k
Data Format: 7/8 bits; odd, even, or no parity
USB PROGRAMMING CARD
Type: USB virtual comms port
Connection: Type B
Baud Rate: 300 to 38.4k
Unit Address: 0 to 99
1.0 i nStallinG the
M eter
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. Slide the panel gasket over the rear of the unit to the back of the bezel. The unit should be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case. The panel latch should be engaged in the farthest forward slot possible. To achieve a proper seal, tighten the latch screws evenly until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz [0.202 to 0.26 N-m]). Do not over-tighten the screws.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the keypad of the unit.
PANEL
NUT FASTENER
MOUNTING SCREW BEZEL
2.68
+.025
-.000
+.8
1.30
+.024
-.000
MOUNTING CLIP
PANEL
GASKET
2.0 S ettinG the
J uMperS
INPUT RANGE JUMPER
This jumper is used to select the proper input range. The input range selected in programming must match the jumper setting. Select a range that is high enough to accommodate the maximum input to avoid overloads. To access the jumper, remove the rear cover of the meter.
Warning: Exposed line voltage exists on the circuit boards. Remove all power to the meter and load circuits before accessing inside of the meter.
REMOVE/REPLACE THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd input terminals. To release the tab, insert a small, flat blade screwdriver between the tab and the plastic wall below the terminals. Inserting the screwdriver will provide enough pressure to release the tab locks. To replace the cover, align the cover with the input terminals and press down until the cover snaps into place.
MAIN CIRCUIT
BOARD
INPUT RANGE JUMPER
INPUT RANGE
JUMPER LOCATION
3
3.0 i nStallinG
p luG
-i n
c ardS
The Plug-in cards are separately purchased option cards that perform specific functions. The cards plug into the main circuit board of the meter
Comms or
Programming
Card
Range Jumpers
Setpoint Card
CAUTION: The Plug-in cards and main circuit board contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges.
Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
REMOVE/REPLACE THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd input terminals. To release the tab, insert a small, flat blade screwdriver between the tab and the plastic wall below the terminals. Inserting the screwdriver will provide enough pressure to release the tab locks. To replace the cover, align the cover with the input terminals and press down until the cover snaps into place.
Locking Tab
4.0 W irinG the
M eter
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter’s voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that the power supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed
(stranded wires should be tinned with solder.) Insert the lead under the correct screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where the unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long
4.1 POWER WIRING
DC Power
+9 to +28 VDC: +VDC
Power Common: -VDC
CAUTION: 9 to 28 VDC power circuit is not isolated from the signal circuit.
+
and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective. The following EMI suppression devices (or equivalent) are recommended:
Fair-Rite part number 0443167251 (RLC part number FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide varistor (MOV) across an AC inductive load is very effective at reducing
EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most RLC products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI.
Although the use of a snubber or varistor could be used.
RLC part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/emi for more information on
EMI guidelines, Safety and CE issues as they relate to Red Lion Controls products.
4.2 USER INPUT WIRING
Sinking Logic
USR COMM
USR
}
Connect external switching device between the
User Input terminal and User Input Common.
The user input of the meter is internally pulled up to +9 to +28 V with 10 K resistance. The input is active when it is pulled low (<0 .7 V).
PWR COMMON +9-28 VDC
PWR COMMON +9-28 VDC
4
4.3 INPUT WIRING
CAUTION: Power input common is NOT isolated from user and input commons. In order to preserve the safety of the meter application, the power input common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not, hazardous voltage may be present at the signal or user inputs and input common terminals. Appropriate considerations must then be given to the potential of the user and input commons with respect to earth ground; and the common of the plug-in cards with respect to input common.
Before connecting signal wires, the Input Range Jumper should be verified for proper position.
Voltage Signal
(self powered)
+
JUMPER
POSITION
200 mV ⁄ 2 VDC
20V ⁄ 200 VDC
MAX INPUT
VOLTAGE
75 VDC
250 VDC
4.4 SETPOINT (OUTPUT) WIRING
SINGLE SETPOINT RELAY PLUG-IN CARD
COM
N.O.
N.C.
ELECTRICAL CONNECTIONS
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD
COM
OSNK1
OSNK2
COM N.O.
N.C.
ELECTRICAL CONNECTIONS
OSNK 1(2)
(30 V MAX.)
COM
Output Common is not isolated from DC Power Common. Load must be wired between OSNK terminal and V+ of the load supply.
4.5 SERIAL COMMUNICATION WIRING
SERIAL COMMUNICATIONS PLUG-IN CARD
4.6 USB PROGRAMMING
USB PROGRAMING PLUG-IN CARD
6 5 4 3 2 1 6 5 4 3 2 1
RS485 RS232
RJ11 CONNECTOR PIN OUTS
5
5.0 r evieWinG the
f ront
B uttonS and
d iSplay
BUTTON DISPLAY MODE OPERATION
SEL Index display through enabled values
RST Resets values (MIN/MAX) or outputs
SEL RST
ENTERING PROGRAM MODE PROGRAMMING MODE OPERATION
Press and hold for 2 seconds to activate Store selected parameter and index to next parameter
Advances through the program menu
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
MAX - Maximum display capture value
MIN - Minimum display capture value
“1” - To the right of the display indicates setpoint 1 output activated.
“2” - To the right of the display indicates setpoint 2 output activated.
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between the enabled display values.
6.0 p roGraMMinG the
M eter
DISPLAY
MODE
SEL
OVERVIEW
PROGRAMMING MENU
NO
Secondary
Function
Parameters
Display and Front
Panel Key
Parameters
Pro
Signal Input
Parameters
RST
1-INP
SEL
2-SEC
SEL
3-dSP
SEL
Setpoint
Output
Parameters
4-SPt
SEL
Serial
Setup
Parameters
5-SEr
SEL
PROGRAMMING MODE ENTRY (SEL BUTTON)
It is recommended all programming changes be made off line, or before installation. The meter normally operates in the Display Mode. No parameters can be programmed in this mode. The Programming Mode is entered by pressing and holding the SEL button. If it is not accessible then it is locked by either a security code, or a hardware lock.
MODULE ENTRY (SEL & RST BUTTONS)
The Programming Menu is organized into separate modules. These modules group together parameters that are related in function. The display will alternate between
Pro
and the present module. The RST button is used to select the desired module. The displayed module is entered by pressing the SEL button.
MODULE MENU (SEL BUTTON)
Each module has a separate module menu (which is shown at the start of each module discussion). The SEL button is pressed to advance to a particular parameter to be changed, without changing the programming of preceding parameters. After completing a module, the display will return to
Programming may continue by accessing additional modules.
Pro NO .
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and the selections/value for that parameter. The RST button is used to move through the selections/values for that parameter. Pressing the SEL button, stores and activates the displayed selection/value. This also advances the meter to the next parameter.
For numeric values, press the RST button to access the value. The right hand most digit will begin to flash. Pressing the RST button again increments the digit by one or the user can hold the RST button and the digit will automatically scroll. The SEL button will advance to the next digit. Pressing and holding the
SEL button will enter the value and move to the next parameter.
PROGRAMMING MODE EXIT (SEL BUTTON)
The Programming Mode is exited by pressing the SEL button with
Pro NO return the meter to the Display Mode. (If power loss occurs before returning to the Display Mode, verify recent parameter changes.) displayed. This will commit any stored parameter changes to memory and
PROGRAMMING TIPS
It is recommended to start with Module 1 and proceed through each module in sequence. When programming is complete, it is recommended to record the parameter programming and lock out parameter programming with the user input or programming security code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 2. This is useful when encountering programming problems.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will appear. This is used to illustrate the display alternating between the parameter on top and the parameter’s Factory Setting on the bottom. In most cases, selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
USrIN
N0
Selection/Value
Factory Settings are shown.
6
6.1 Module 1 - S
iGnal
i
nput
p
araMeterS
(
1-INP
)
PARAMETER MENU
1-INP
SEL
rANGE
Input
Range
dECPt
Display
Decimal
Point
OFSEt
Display
Offset
Value
FILtr
Filter
Setting
bANd
Filter
Band
StYLE
Scaling
Style
INP 1 dSP 1 INP 2
Input Value for Scaling
Point 1
Display Value
For Scaling
Point 1
Input Value for Scaling
Point 2
dSP 2
Display Value
For Scaling
Point 2
USrIN
User Input
Function
U-ASN
User Input
Assignment
Pro
CUB5V INPUT RANGE
rAN6E
200u
SELECTION
0.2u
2u
RANGE
RESOLUTION
200.00 mV
2.0000 V
SELECTION
20u
200u
RANGE
RESOLUTION
20.000 V
200.00 V
Select the input range that corresponds to the external signal. This selection should be high enough to avoid input signal overload but low enough for the desired input resolution. This selection and the position of the Input Range
Jumper must match.
SCALING STYLE
StYLE
KEy
KEy APLY
(
KEY
If Input Values and corresponding Display Values are known, the Key-in
) scaling style can be used. This allows scaling without the presence or changing of the input signal. If Input Values have to be derived from the actual input signal source or simulator, the Apply ( APLY ) scaling style must be used.
DISPLAY DECIMAL POINT
dECPt
0 0.0
0.00
0.000
0.0000
0
Select the decimal point location for the Input, MIN and MAX displays. This selection also affects the dSP1
and dSP2
parameters and setpoint values.
DISPLAY OFFSET VALUE
OFSEt
0.00
-19999
to
19999
The display can be corrected with an offset value. This can be used to compensate for signal variations or sensor errors. This value is automatically updated after a Zero Display to show how far the display is offset. A value of zero will remove the effects of offset.
INP 1
INPUT VALUE FOR SCALING POINT 1
0
to
29999
0.00
For Key-in (
For Apply (
KEY
(The Input Range selection sets the decimal location for the Input Value).
APLY
) style, enter the first Input Value using the front panel buttons.
) style, the meter shows the previously stored Input Value. To retain this value, press the SEL button to advance to the next parameter. To change the Input Value, press the RST button and apply the input signal to the meter. Adjust the signal source externally until the desired Input Value appears.
Press the SEL button to enter the value being displayed.
dSP 1
DISPLAY VALUE FOR SCALING POINT 1
-19999
to
99999
0.00
for
Enter the first Display Value by using the front panel buttons. This is the same
KEY and APLY scaling styles. The decimal point follows the dECPt selection.
FILTER SETTING
FILtr
0,1 2 3
1
If the displayed value is difficult to read due to small process variations or noise, increased levels of filtering will help to stabilize the display. Software filtering effectively combines a fraction of the current input reading with a fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1 for the filter uses 1/4 of the new input and 3/4 of the previous display to generate the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A filter value of 3 uses 1/16 new and 15/16 previous.
FILTER BAND
bANd
10
0
to
199
display units
The filter will adapt to variations in the input signal. When the variation exceeds the input filter band value, the filter disengages. When the variation becomes less than the band value, the filter engages again. This allows for a stable readout, but permits the display to settle rapidly after a large process change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of ‘0’ keeps the filter permanently engaged at the filter level selected above.
INP 2
INPUT VALUE FOR SCALING POINT 2
0
to
29999
100.00
For Key-in ( panel buttons.
For Apply (
KEY
APLY
) style, enter the known second Input Value using the front
) style, the meter shows the previously stored Input Value for
Scaling Point 2. To retain this value, press the SEL button to advance to the next parameter. To change the Input Value, press the RST button and apply the input signal to the meter. Adjust the signal source externally until the desired Input
Value appears. Press the SEL button to enter the value being displayed.
dSP 2
DISPLAY VALUE FOR SCALING POINT 2
-19999
to
99999
100.00
Enter the second Display Value by using the front panel buttons. This is the same for KEY and APLY scaling styles.
General Notes on Scaling
1. When using the Apply (
APLY
) scaling style, input values for scaling points must be confined to the signal input imits of the selected range.
2. The same Input Value should not correspond to more than one Display Value.
(Example: 10 V can not equal 0 and 10.)
3. For input levels beyond the programmed Input Values, the meter extends the
Display Value by calculating the slope from the two coordinate pairs ( INP1 / dSP1
&
INP2
/ dSP2
).
7
USrIN
NO
DISPLAY
NO
MODE
No Function
P-Loc
ZErO rESEt
Program Mode Lock-out
Zero Input
(Edge triggered)
Reset (Edge triggered)
d-HLd
Display Hold
USER INPUT FUNCTION d-SEL d-LEV
COLOr
Display Select
(Edge Triggered)
Display Intensity Level
(Edge Triggered)
Backlight Color
(Edge Triggered)
DESCRIPTION
User Input disabled.
See Programming Mode Access chart
(Module 3).
Zero the Input Display value causing
Display Reading to be Offset.
Resets the assigned value(s) to the current input value.
Holds the assigned display, but all other meter functions continue as long as activated (maintained action).
Advance once for each activation.
Increase intensity one level for each activation (backlight version only).
Change backlight color with each activation (backlight version only).
DISPLAY MODE
Print Request
P-r5t
Print and Reset
rSt-1 rSt-2 rSt12
Setpoint 1 Reset
Setpoint 2 Reset
Setpoint 1 and 2 Reset
DESCRIPTION
Serial transmit of the active parameters selected in the Print Options menu
(Module 5).
Same as Print Request followed by a momentary reset of the assigned value(s).
Resets setpoint 1 output.
Resets setpoint 2 output.
Reset both setpoint 1 and 2 outputs.
USER INPUT ASSIGNMENT
U-ASN
dSP
HI
LO
HI-LO dSP
Select the value(s) to which the User Input Function is assigned. The User
Input Assignment only applies if a selection of reset, display hold, or print and reset is selected in the User Input Function menu.
6.2 Module 2 - S
econdary
f
unction
p
araMeterS
(
2-SEC
)
2-SEC
SEL
HI-En
Max Display
Enable
HI-t
Max Capture
Delay Time
HI-En
NO
MAX DISPLAY ENABLE
NO YES
Enables the Maximum Display Capture capability.
PARAMETER MENU
LO-En
Min Display
Enable
LO-t
Min Capture
Delay TIme
CodE
FCS
Factory
Service
Operations
Pro
RESTORE FACTORY DEFAULT SETTINGS
66
CodE
Access Code
For Service
Operations
Entering Code 66 will overwrite all user settings with the factory settings. The meter will display return to CodE 00 . Press the rESEt
and then
SEL button to exit the module.
HI-t
2.0
MAX CAPTURE DELAY TIME
0.0
to
999.9
seconds
When the Input Display is above the present MAX value for the entered delay time, the meter will capture that display value as the new MAX reading.
A delay time helps to avoid false captures of sudden short spikes.
LO-En
Enables the Minimum Display Capture capability.
LO-t
NO
NO YES
When the Input Display is below the present MIN value for the entered delay time, the meter will capture that display value as the new MIN reading. A delay time helps to avoid false captures of sudden short spikes.
FCS
2.0
MIN DISPLAY ENABLE
MIN CAPTURE DELAY TIME
0.0
to
999.9
seconds
FACTORY SERVICE OPERATIONS
NO yES
NO
Select yES to perform either of the Factory Service Operations shown below.
8
CodE
50
VIEW VERSION DISPLAY
Entering Code 50 will display the version (x.x) of the meter. The display then returns to button to exit the module.
CodE 00 . Press the SEL
CALIBRATION
CodE
48
The CUB5V uses stored voltage calibration values to provide accurate voltage measurements. Over time, the electrical characteristics of the components inside the meter will slowly change, with the result that the stored calibration values no longer accurately define the input circuit. For most applications, recalibration every 1 to 2 years should be sufficient.
Calibration of the CUB5V involves an input voltage calibration, which should only be performed by individuals experienced in calibrating electronic equipment. Allow a 30 minute warm up before performing any calibration related procedures. The following procedures should be performed at an ambient temperature of 15 to 35°C (59 to 95°F).
CAUTION: The accuracy of the calibration equipment will directly affect the accuracy of the CUB5V.
Voltage Calibration
1. Connect a precision DC voltage source with an accuracy of 0.01% or better to the INP+ (positive) and COMM (negative) terminals of the CUB5V. Set the output of the voltage source to zero.
2. With the display at will display
3. Press the RST button to select the range to be calibrated.
4. Press the SEL button. Display reads
5. With the voltage source set to zero (or a dead short applied to the input), press
SEL . Display reads
6. When the display reads the selected range, apply full-scale input signal for the range. (Note: For 200V range, apply 100V as indicated on the display.)
Press SEL . Display reads
7. Repeat steps 3 through 6 for each input range to be calibrated. When display reads
CAL NO
CAL NO
.
CodE 48
CALC
, press the
0.0v
.
for about 8 seconds.
SEL
, press and hold the
CALC
SEL
for about 8 seconds.
button for 2 seconds. Unit
button to exit calibration.
6.3 Module 3 - d
iSplay and
f
ront
p
anel
B
utton
p
araMeterS
(
3-dSP
)
PARAMETER MENU
3-dSP
Backlight Unit Only
SEL
dSP-t SEL rSt ZErO ScroL UNItS COLOr d-LEV
Display
Update Time
Front Panel
Display
Select Enable
Front Panel
Reset Enable
Zero Display
W/Display
Reset
Display
Scroll
Enable
Units
Indicator
Selection
Display
Color
Display
Intensity
Level
CodE
Programming
Security Code
Pro
DISPLAY UPDATE TIME
dSP-t
1
0.5
1 2
seconds
This parameter sets the display update time in seconds.
DISPLAY COLOR (BACKLIGHT UNIT ONLY)
COLOr
rEd
rEd 6rn
Enter the desired display color, red or green. This parameter is active for backlight units only.
SEL
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
yES NO
yES
The displays.
yES selection allows the SEL button to toggle through the enabled
d-LEV
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)
1
to
5
5
Enter the desired Display Intensity Level (1-5). The display will actively dim or brighten as levels are changed. This parameter is active for backlight units only.
rSt
FRONT PANEL RESET ENABLE (RST)
NO dSP
HI
LO
HI-LO
dSP
This selection allows the RST button to reset the selected value(s).
ZERO DISPLAY WITH DISPLAY RESET
ZErO
NO
yES NO
This parameter enables the RST button or user input to zero the input display value, causing the display reading to be offset.
Note: For this parameter to operate, the RST button or User Input being used must be set to dSP and the Input value must be displayed. If these conditions are not met, the display will not zero.
CodE
PROGRAMMING SECURITY CODE
000
to
999
000
The Security Code determines the programming mode and the accessibility of programming parameters. This code can be used along with the Program
Mode Lock-out (
Two programming modes are available. Full Programming mode allows all parameters to be viewed and modified. Quick Programming mode permits only the Setpoint values to be modified, but allows direct access to these values without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered at the CodE
P-Loc code value, Quick Programming may be accessible before the appears (see chart).
) in the User Input Function parameter (Module 1).
prompt in order to access Full Programming mode. Depending on the
CodE
prompt
DISPLAY SCROLL ENABLE
ScroL
NO
yES NO
The yES selection allows the display to automatically scroll through the enabled displays. The scroll rate is every 4 seconds. This parameter only appears when the MAX or MIN displays are enabled.
UNITS INDICATOR SELECTION
UNItS
OFF
OFF LISt SEGS
This parameter activates the Units Indicator on the display. There are two methods of selecting the Indicator. List will present a group of Units preprogrammed into the meter. Segments allows the user to choose which of the segments should light.
USER INPUT
FUNCTION
USER INPUT
STATE
SECURITY
CODE
MODE WHEN “SEL”
BUTTON IS PRESSED
0 Full Programming not P-Loc ______
FULL PROGRAMMING
MODE ACCESS
Immediate Access
1-99 Quick Programming
After Quick Programming with correct code entry
at CodE prompt *
100-999 CodE prompt
With correct code entry at CodE prompt *
0 Programming Lock No Access
Active
1-99 Quick Programming
CodE prompt
No Access
P-Loc
100-999
Not Active 0-999 Full Programming
With correct code entry at CodE prompt *
Immediate Access
* Entering Code 222 allows access regardless of security code.
9
6.4 Module 4 - S
etpoint
o
utput
p
araMeterS
(
4-SPt
)
PARAMETER MENU
4-SPt
SEL
SPSEL
Setpoint
Select
Act-n
Setpoint
Action
SPt-n
Setpoint
Value
HYS-n
Hysteresis
Value
tON-n
On Time
Delay
tOF-n
Off Time
Delay
rSt-n
Output Reset
Action
rEn-n
Output Reset
W/Display
Reset
Stb-n
Standby
Operation
Backlight
Unit Only
ChC-n
Change Display
Color with
Output State
Pro
The Setpoint Output Parameters are only active when an optional output module is installed in the meter.
SPSEL
NO
SETPOINT SELECT
NO SP-1 SP-2
Enter the setpoint (output) to be programmed. The parameters will reflect the chosen setpoint number. After the chosen setpoint is completely programmed, the display will return to each setpoint to be programmed. Select
NO
n
in the following
SPSEL
. Repeat steps for
to exit the module. The number of setpoints available is setpoint output card dependent.
SETPOINT 2 ENABLE
Enb-2
NO
YES NO
Select
YES
to enable Setpoint 2 and access the setup parameters. If selected, the unit returns to
SPSEL
and setpoint 2 is disabled.
NO
is
SPt-n
10000
SETPOINT VALUE
-19999
to
99999
Enter the desired setpoint value. The decimal point position for the setpoint and hysteresis values follow the selection set in Module 1.
HYS-n
2
HYSTERESIS VALUE
1
to
59999
Enter desired hysteresis value. See Setpoint Output Figures for visual explanation of how setpoint output actions (balanced and unbalanced) are affected by the hysteresis. When the setpoint is a control output, usually balanced hysteresis is used. For alarm applications, usually unbalanced hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay can be used to prevent false triggering during process transient events.
SETPOINT ACTION
Act-n
HI-bL LO-bL HI-Ub LO-Ub
HI-Ub
Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action.
HI-bL
=
LO-bL =
HI-Ub
=
LO-Ub =
High Acting, with balanced hysteresis
Low Acting, with balanced hysteresis
High Acting, with unbalanced hysteresis
Low Acting, with unbalanced hysteresis
tON-n
0.0
ON TIME DELAY
0.0
to
599.9
seconds
Enter the time value in seconds that the output is delayed from turning on after the trigger point is reached. A value of 0.0 allows the meter to update the output status per the response time listed in the Specifications.
OFF TIME DELAY
tOF-n
0.0
0.0
to
599.9
seconds
Enter the time value in seconds that the output is delayed from turning off after the trigger point is reached. A value of 0.0 allows the meter to update the output status per the response time listed in the Specifications.
SP + ½Hys
SP
SP - ½Hys
OUTPUT
STATE
OFF
ON
OFF
TRIGGER POINTS
High Acting (Balanced Hys) = HI-bL
SP + ½Hys
Hys SP
SP - ½Hys
OUTPUT
STATE
OFF
ON
OFF
TRIGGER POINTS
Low Acting (Balanced Hys) = LO-bL
Hys
SP - Hys
SP
OUTPUT
STATE
OFF
ON
OFF
TRIGGER POINTS
High Acting (Unbalanced Hys) = HI-Ub
Hys
SP + Hys
SP
OUTPUT
STATE
OFF
ON
OFF
TRIGGER POINTS
Low Acting (Unbalanced Hys) = LO-Ub
Hys
10
OUTPUT RESET ACTION
rSt-n
Auto LAtCH L-dLY
Auto
Enter the reset action of the output. See figure for details.
Auto
= Automatic action; This action allows the output to automatically reset off at the trigger points per the Setpoint Action shown in
Setpoint Output Figures. The “on” output may be manually reset (off) immediately by the front panel RST button or user input.The output remains off until the trigger point is crossed again.
LAtCH
= Latch with immediate reset action; This action latches the output on at the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel RST
button or user input manual reset, serial reset command or meter power cycle. When the user input or RST button is activated (momentary action), the corresponding “on” output is reset immediately and remains off until the trigger point is crossed again. (Previously latched alarms will be off if power up Display Value is lower than setpoint value.)
L-dLY = Latch with delay reset action; This action latches the output on at the trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch means that the output can only be turned off by the front panel RST button or user input manual reset, serial reset command or meter power cycle. When the user input or RST button is activated (momentary action), the meter delays the event until the corresponding “on” output crosses the trigger off point. (Previously latched outputs are off if power up Display Value is lower than setpoint value. During a power cycle, the meter erases a previous reset if it is not activated at power up.)
L-dLY
MANUAL
RESET
SP - Hys
SP
OUTPUT
STATE
{
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
Setpoint Output Reset Actions
OFF
OFF
OFF
Hys
rEn-n
OUTPUT RESET WITH DISPLAY RESET
NO YES
YES
This parameter enables the RST button or user input to reset the output when the display is reset.
Note: For this parameter to operate, the RST button or User Input being used must be set to dSP and the Input value must be displayed. If these conditions are not met, the output will not reset.
STANDBY OPERATION
Stb-n
NO
NO YES
When YES , the output is disabled (after a power up) until the trigger point is crossed. Once the output is on, the output operates normally per the Setpoint
Action and Output Reset Action.
ChC-n
CHANGE DISPLAY COLOR w/OUTPUT STATE
NO
NO YES
This parameter enables the backlight CUB5 to switch the backlight color when the output state changes. This parameter is only active for the backlight version.
6.5 Module 5 - S
erial
S
etup
p
araMeterS
(
5-SEr
)
5-SEr
SEL
bAUd
Baud Rate
dAtA
Data Bit
PAr
PARAMETER MENU
Parity Bit
Addr
Meter
Address
Abbr
Abbreviated
Printing
OPt
Options
The Serial Setup Parameters are only active when one of the optional serial communication/programming cards is installed in the meter.
Refer to the CUB5COM bulletin for details on CUB5 RS232 or RS485 serial communications.
Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements.
Pro
LIMITED WARRANTY
(a) Red Lion Controls Inc., Sixnet Inc., N-Tron Corporation, or Blue Tree Wireless Data, Inc. (the “Company”) warrants that all Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY
WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF
FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A
THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE OF PERFORMANCE, USAGE OF TRADE OR
OTHERWISE. Customer shall be responsible for determining that a Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii) Customer alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion, either (i) repair or replace the
Product; or (ii) credit or refund the price of Product provided that, if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE REMEDY AND COMPANY’S
ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH IN PARAGRAPH (a).
11
cuB5v proGraMMinG QuicK overvieW
Input Range
Access Code For Service Operations
Factory Service
Min Capture Delay
Display Intensity
Display Color
Indicator Selection
Scroll Enable
Max Capture Delay
Setpoint Select
Meter Addres

Public link updated
The public link to your chat has been updated.
Advertisement