Cat. No. W241-E1-2
SYSMAC
C200H–PID0 _
PID Control Unit
C200H-PID0
j
PID Control Unit
Operation Manual
Revised March 2000
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1993
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
ii
About this Manual:
This manual describes the installation and operation of the C200H-PID0 j PID Control Unit and includes the sections described below. Also briefly described is the basic operation and installation of the
C200H-DSC01 Data Setting Console.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the C200H-PID0 j PID Control Unit and Data Setting Console.
Section 1 provides PID Control Unit features and describes its basic system configuration.
Section 2 provides information on the connections and settings of the PID Control Unit.
Section 3 provides the basic operating procedures of the Data Setting Console including parameter settings and displays.
Section 4 provides the C200H PC’s memory allocation for the PID Control Unit. Basic programming procedures and examples are also provided.
Section 5 describes possible errors and provides measures for dealing with them.
The three Appendices provide references dealing with specifications, dimensions, and key operations.
!
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
iii
TABLE OF CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1 – System Configuration and Features
. . . . . . . . . . . . . . . . . . .
SECTION 2 – Connections and Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Setting Console Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3 – Data Setting Console Operation . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Parameter Displays and Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-2 How to Display and Set Parameter Data . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4 – PC Memory Allocation and Programming . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Allocation Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example with SW2-1 in the Fixed Position . . . . . . . . . . . . . . . . . . . .
4-3-2 Example 1: Write with SW2-1 in the Normal Position . . . . . . . . . . . .
Example 2: Read with SW2-1 in the Normal Position
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5 – Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
v
PRECAUTIONS
This section provides general precautions for using the C200H-PID0 j PID Control Unit and related devices.
The information contained in this section is important for the safe and reliable application of the C200H-PID0 j PID
Control Unit. You must read this section and understand the information contained before attempting to set up or operate the C200H-PID0 j PID Control Unit.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
vii
Safety Precautions
1
2
3
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
•
Personnel in charge of installing FA systems.
•
Personnel in charge of designing FA systems.
•
Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the relevant manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!
WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC system to the above-mentioned applications.
3 Safety Precautions
!
WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
!
WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, in order to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents.
•
Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
•
The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
viii
Application Precautions
4
5
•
The PC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
•
When the 24-VDC output (service power supply to the PC) is overloaded or short-circuited, the voltage may drop and result in the outputs being turned
OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
Operating Environment Precautions
!
Caution Do not operate the control system in the following locations:
•
Locations subject to direct sunlight.
•
Locations subject to temperatures or humidity outside the range specified in the specifications.
•
Locations subject to condensation as the result of severe changes in temperature.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to exposure to water, oil, or chemicals.
•
Locations subject to shock or vibration.
!
Caution Take appropriate and sufficient countermeasures when installing systems in the following locations:
•
Locations subject to static electricity or other forms of noise.
•
Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radioactivity.
•
Locations close to power supplies.
!
Caution The operating environment of the PC system can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC system. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
5 Application Precautions
Observe the following precautions when using the PC system.
!
WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.
•
Always ground the system to 100
Ω
or less when installing the Units. Not connecting to a ground of 100
Ω
or less may result in electric shock.
•
Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
•
Mounting or dismounting I/O Units, CPU Units, Memory Units, or any other
Units.
•
Assembling the Units.
•
Setting DIP switches or rotary switches.
•
Connecting cables or wiring the system.
•
Connecting or disconnecting the connectors.
ix
Application Precautions 5
!
Caution Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC or PC Units. Always heed these precautions.
•
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
•
Always use the power supply voltages specified in this manual. An incorrect voltage may result in malfunction or burning.
•
Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
•
Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
•
Do not apply voltages to the Input Units in excess of the rated input voltage.
Excess voltages may result in burning.
•
Do not apply voltages or connect loads to the Output Units in excess of the maximum switching capacity. Excess voltage or loads may result in burning.
•
Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning.
•
Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in this manual. Incorrect tightening torque may result in malfunction.
•
Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit.
•
Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
•
Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning.
•
Wire correctly. Incorrect wiring may result in burning.
•
Mount Units only after checking terminal blocks and connectors completely.
•
Be sure that the terminal blocks, Memory Units, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
•
Check the user program for proper execution before actually running it on the
Unit. Not checking the program may result in an unexpected operation.
•
Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
•
Changing the operating mode of the PC.
•
Force-setting/force-resetting any bit in memory.
•
Changing the present value of any word or any set value in memory.
•
Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation.
•
Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables.
•
Do not place objects on top of the cables or other wiring lines. Doing so may break the cables.
•
Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
•
When replacing parts, be sure to confirm that the rating of a new part is correct.
Not doing so may result in malfunction or burning.
x
Application Precautions 5
•
Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any static built-up. Not doing so may result in malfunction or damage.
xi
SECTION 1
System Configuration and Features
This section provides PID Control Unit features and the basic system configuration.
1
Features
1-1 Features
The PID Control Unit scales inputs from connected sensors and then carries out
PID control according to preset parameters.
Advanced PID Control
Stable PID control is achieved using advanced PID control and an auto-tuning feature. ON/OFF control can also be selected.
Two PID Control Loops with a Single Unit
Two PID control loops are possible with one Unit.
High-speed Sampling Period of 100 ms
A sampling period of 100 ms is achieved with two loops, enabling high-speed
PID control.
Input Noise Reduction with Digital Filter
Mitigation of sudden input fluctuations makes the PID Control Unit effective in quick-response systems.
Comprehensive Output Specifications
Three types of output specification versions are available: C200H-PID01 for transistor output, C200H-PID02 for voltage output, and C200H-PID03 for current output.
Eight Banks of Data Settings
Eight data values such as set point (SP) and alarm set values can be preset in eight data banks for easy selection.
Data Input and Display
The C200H-DSC01 Data Setting Console (sold separately) is used to input data and display present values (PV) and set values (SV). The easy-to-read display can be panel-mounted.
User Programs Allows Reading and Writing of Data
Data can be set and retrieved by means of C200H user programs.
2
Basic System Configuration
1-2 Basic System Configuration
SYSMAC C200H/C200HS PC
C200H-PID0 j
PID Control Unit
Connecting cables:
C200H-CN225 (2 m)
C200H-CN425 (4 m)
Recommended cable:
ES1000-CA021-051 (0.5 m)
ES1000-CA021-102 (1 m)
ES1000-CA021-202 (2 m)
Data Setting Console
C200H-DSC01
24 VDC
Mixture
Loop 1
Flow sensor
Loop 2
Air
Valve
Flow sensor
Gas
Valve
Remote I/O Terminal or
Connector Terminal
Block Converter Unit
Relay box
PID Control Unit Models
Output type
Model
Transistor output
C200H-PID01
Voltage output Current output
C200H-PID02 C200H-PID03
Number of Units The PID Control Unit belongs to the C200H Special I/O Unit group. A maximum of ten Special I/O Units (including PC Link Units) can be mounted on the CPU
Rack, Expansion I/O Rack, and Slave Rack.
Note Configure the Units such that the maximum current supplied for each Rack is greater than or equal to the total current consumption for the Units.
Refer to the C200H PC Operation Manuals for details on configuring systems.
Number of Units Mountable on Slave Rack
The number of Special I/O Units used with a Slave Rack is limited by data transmission considerations, as shown in the table below. The numbers in the table
3
Basic System Configuration
A
High-speed Counter Units
Position Control Units
(NC111/112)
ASCII Unit
Analog I/O Units
ID Sensor Units
Fuzzy Logic Unit
4 units max.
Precautions indicate the maximum number of Units of groups A, B, C, or D which can be used with a single Slave Rack.
B
High-density and Mixed I/O
Units
Temperature Control Units
Heat/Cool Temperature
Control Units
PID Control Units
Cam Positioner Unit
8 units max.
C
Temperature Sensor Units
Voice Unit
6 units max.
D
Position Control Unit
(NC211)
2 units max.
Note 1. When a combination of Units from groups A, B, C, and D is used, the number from each group must satisfy both the following equations:
3A + B + 2C + 6D
≤
12
A + B + C + D
≤
8
2. Other Units can be added until the total number of units reaches ten. If PC
Link Units are used, the number of Units including the PC Link Units must not exceed ten.
The IR area of the C200H Special I/O Unit is allocated according to the setting of the unit number switch on the front panel, not the address of the slot where the
unit is mounted. Refer to 4-1 Memory Allocation for the allocation of the memory
area.
With the C200 H, leave the two slots next to the CPU free. It is not possible to use devices connected to the CPU (such as the Programming Console) if these slots are occupied.
If the C200H Slave Rack is connected to another SYSMAC model Remote I/O
Master Unit, such as the C120, C500, C1000H, or C2000H, it is not possible to use a Special I/O Unit with the C200H Slave Rack.
WARNING Always turn the C200H power off before connecting or disconnecting a Unit, terminal block, or output connector.
Additional Function
Caution Connect thermocouples with the appropriate compensating conductor.
Wire I/O leads in separate ducts from power leads to prevent noise problems.
The function described below has been added to products with the following lot number and later ones.
07 Z 4 O
1994 (last digit of the year)
December (X: October, Y: November, Z: December)
07 (7th day of the month)
Description of Function
RAM Write Commands
•
Previous commands allowed reading and writing to the EEPROM only. These new commands allow writing to the RAM.
•
When various settings require frequent rewriting, write to the RAM and, after confirming the setting values, save the data by writing it to the EEPROM. The data written to the RAM is deleted when the power is turned off.
4
Basic System Configuration
•
List of RAM Write Commands
Parameter
Set point
Execution bank number
Alarm SV 1
Alarm SV 2
Input shift value
Proportional band
Integral (reset) time
Derivative (rate) time
Decimal point position
Scaling lower limit
Scaling upper limit
Control period
Hysteresis
Alarm hysteresis
Digital filter
Alarm 1 mode
Alarm 2 mode
5
5
5
5
6
6
5
5
4
4
5
4
4
4
4
4
4
Command
0
2
3
4
5
6
9
E
7
8
4
5
2
3
7
8
4
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Write Read
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
5
SECTION 2
Connections and Settings
This section provides information on the connections and settings of the PID Control Unit.
Data Setting Console Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Switch Settings
2-1 Nomenclature
C200H-PID0 j
Front Panel
Model label
Cover
RUN indicator
SW2
(Switching memory contents and setting direction under the cover)
SW1
(Unit number setting)
Data Setting Console connector
Rear Panel
SW202
(Input type setting)
SW203
(Operation and function settings)
Rack connector
Output connector
Input terminal block
Indicators
RUN Lit when the PID Control Unit is operating normally.
2-2 Switch Settings
The function and setting of switches are identical for all models, except for
SW202.
Unit Number
SW1 Unit number setting
8
6
4
2
(1)
0
(9)
(3)
(7)
(5)
The cut-out indicates the selected position. Negative numbers are not indicated. Turn the switch with a flat-blade screwdriver.
Turn the switch until it clicks in position. Do not leave the switch between two settings.
The addresses are allocated as shown in the following table according to the
Unit number setting.
8
Switch Settings
Unit no.
setting
Allocated address
5
6
3
4
0
1
2
7
8
9
Wd 100 to 109
Wd 110 to 119
Wd 120 to 129
Wd 130 to 139
Wd 140 to 149
Wd 150 to 159
Wd 160 to 169
Wd 170 to 179
Wd 180 to 189
Wd 190 to 199
The switch is factory-set to 0.
Note If the Unit number is set to an existing Unit number, an alarm occurs and the
C200H does not operate.
Turn the C200H power off before setting the Unit number. If the setting is changed with the power on, the new setting is not valid until the power is turned off and back on again.
Switching Memory Contents and Setting Direction
SW2 Switching memory contents and setting direction
Remove the cover and set the switch with the tip of a ballpoint pen or similar object.
ON
OFF
Switch no.
Function
ON
OFF
Pin 1
Switching memory contents
Normal
Fixed
Pin 2
Setting direction
C200H PC
Data Setting Console
The new setting is valid immediately after the switch setting is changed.
Removing and Attaching the Cover
Removing the Cover Attaching the Cover
Insert a small flat-blade screwdriver between the case and the cover at the top of the Unit and lever off the cover.
Place the right edge of the cover against the case and press into position.
Switching Memory Contents The contents of the allocated memory differ according to the Unit number setting.
9
Switch Settings
Setting Direction
Input Type
Normal
Fixed
Parameters can be designated as required using
commands (Refer to 4-1 Memory Allocation).
Parameters are allocated in advance.
Refer to 4-1 Memory Allocation for details of the memory contents.
Selects whether the data settings are made from the Data Setting Console or from the C200H PC, using a user program or Programming Console.
Executed Bank Number
The setting of the executed bank number is made from the C200H PC, regardless of the ON/OFF setting of this switch.
SW202 Input type setting
Switch number
0
1
4
5
2
3
8
9
6
7
Loop 1
4 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
4 to 20 mA
4 to 20 mA
4 to 20 mA
1 to 5 V
1 to 5 V
0 to 5 V
Loop 2
4 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
1 to 5 V
0 to 5 V
0 to 10 V
0 to 5 V
0 to 10 V
0 to 10 V
The switch is factory-set to 0.
The selected position is shown by the arrow. Turn the switch with a small flatblade screwdriver.
The permissible setting range for measurement is –999 to 9999 (EU).
Operation and Function Setting
SW203 Operation and Function Setting
OFF
NO
ON
10
Switch Settings
Input Approximation
Loop 2
SP Write Mode
Display Units
Control Action
Control Method
6
Pin no.
5
4
3
2
1
Function
Loop 2
Input approximation
Loop 1
Input approximation
Loop 2
SP write mode
Control action
Control method
OFF
Straight line
ON
Square root approximation
Straight line Square root approximation
Disabled or not used Enabled
EEPROM and RAM RAM
Reverse Normal
PID control ON/OFF control
The switch is factory-set to OFF.
Set each loop to either straight line (no approximation) or square root approximation.
Set to “enabled” to use input loop 2, or to “disabled” to use only input loop 1. It is not possible to use only input loop 2.
Note Always set this switch to the ON (disabled) position when input loop 2 is not used. A sensor error occurs if this switch is set to the OFF (enabled) position when no temperature sensor is connected to loop 2.
This setting selects the SP storage memory. Set it to ON or use RAM Write commands if the writing is to be frequently changed.
Selects whether setting and SVs displayed on the Data Setting Console are in
Celsius or Fahrenheit.
Reverse:
The output is increased when the measured temperature is below the SP (i.e., a negative temperature difference).
Normal:
The output is increased when the measured temperature is above the SP (i.e., a positive temperature difference).
Selects the method of control.
11
Wiring
2-3 Wiring
2-3-1 Input Wiring
C200H-PID0 j
Voltage input
Loop 1
Current input
Voltage input
Loop 2
Current input
24 VDC
0.2 A
The 24-VDC output from the C200H
CPU or the Power Supply Units is convenient.
A5
A6
A7
A8
A9
A0
A1
A2
A3
A4
Refer to the table below.
A3
A4
A5
A6
A7
A8
A9
Terminal no.
A0
A1
A2
Vin (–)
Vin (+) lin (–) lin (+)
Vin (–)
Vin (+) lin (–) lin (+)
24 VDC
GND
Terminal name
Loop 1
Loop 2
Input Wiring Precautions
1, 2, 3...
1. The PID Control Unit will not operate correctly if the SW202 setting does not match the type of inputs that are connected. In addition, each loop can be connected to either voltage inputs or current inputs, but not to both. For example, if Loop 1 is set for voltage input, then current input will not work.
2. If no input lead is connected to Loop 2, turn SW203-4 on the rear of the Unit
ON to disable Loop 2. A sensor error occurs if this switch is set to the OFF
(enabled) position when no sensor is connected to Loop 2.
3. Be sure to wire the polarity correctly for each input.
4. Wire I/O leads in separate ducts from power leads to prevent noise problems.
5. A voltage of 24 VDC is used for the voltage output, current output and Data
Setting Console power supply.
6. The terminal block is removable. Make sure that it is attached correctly after the input wiring connections are completed.
12
Wiring
Terminal Block
Connections
2-3-2 Output Wiring
Connection Diagrams
C200H-PID01 Transistor Output
Use crimp terminals for wiring. Take care not to overtighten the terminal screws.
Tighten the screws to a torque of 0.8 N S m.
Crimp Terminals
The screws on the terminal block are M3.5 self-rising terminal screws. Use the following types of M3.5 crimp terminals.
7 mm max.
7 mm max.
Soldered Lead
Strip insulation from 7 to 10 mm at the end of the wire and carefully solder the lead.
ÉÉÉ
7 to 10 mm
10
+
24 VDC 24 VDC
NC: Not connected
The pairs of terminals B2 to A2 and B1 to A1 are shorted internally. Always supply power to the 24-VDC terminal (B1) as this drives the internal circuits.
13
Wiring
C200H-PID02/PID03 Voltage/Current Output
Circuit Diagrams
C200H-PID01 Transistor Output
C200H-PID02 Voltage Output
C200H-PID03 Current Output
14
OUT (+)
OUT (–)
24 VDC
OUT
COM
OUT (+)
OUT (–)
Wiring
Applicable Connectors
Connector Wiring
Precautions
Connection Precautions
Output Cable
The following connector set manufactured by Fujitsu is included with the Unit:
FCN-361J032-AU (soldering connector)
FCN-360C032-B (cover)
After soldering the lead to each pin, insulate with heat-shrink tube to prevent shorting with the adjacent terminal.
Tighten the screws after inserting the connector into the Unit. Push the connector firmly into the Remote I/O Terminal or Connector Terminal Block Converter
Unit until it fully locks.
The output cables in the table below are recommended.
Model
ES1000-CA021-051
ES1000-CA021-102
ES1000-CA021-202
Cable length (L)
50 cm
1 m
2 m
32-pin connector
(manufactured by Fujitsu)
FCN-361J032-AU
20-pin connector
(manufactured by OMRON)
XG4M-2030
L
30
63
16.1
28
46
Wiring Diagrams
32-pin connector
Pin no.
Wire no.
Pin no.
Wire no.
B4
B3
B2
B1
B16
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
#1
#2
#3
#4
#5
#6
#7
#8
#9
#10
A16
A15
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
#11
#12
#13
#14
#15
#16
#17
#18
#19
#20
Note Pins A11 through A16 and B11 through B16 are not connected.
20-pin connector
Pin no.
Wire no.
Pin no.
Wire no.
6
7
8
9
10
3
4
5
1
2
#1
#2
#3
#4
#5
#6
#7
#8
#9
#10
11
12
13
14
15
16
17
18
19
20
#11
#12
#13
#14
#15
#16
#17
#18
#19
#20
Note The pin numbers of the 20-pin connector are marked for convenience.
Refer to them from the
∆
mark.
15
Wiring
Remote I/O Terminal
The Remote I/O Terminal in the table below is recommended for transistor output.
Model Specification
G7TC-OC08 Common (+)
Relays used
8 x G7T-1112S (max. resistive load: 220 VAC, 2A)
Note One P7TF-OS08 I/O Terminal and two G7T-1112S Relays may be purchased separately and used.
Wiring Diagram External View
24 VDC
Connector Terminal Block
Converter Unit
The Connector Terminal Block Converter Units in the table below are recommended for voltage output and current output type.
Model
XW2B-20G4
XW2B-20G5
Terminal screw size
M 2.4
M 3.5
External View
2-3-3 Data Setting Console Cables
Connecting Cable Use the connecting cables in the table below (sold separately) to connect the
Unit to the Data Setting Console.
Model
C200H-CN225
C200H-CN425
2 m
4 m
Cable length (L)
L
39
17.3
17.5
16.1
10
16
Wiring
Connection Precautions
1, 2, 3...
1. Tighten the lock screws after inserting the connector into the Unit.
2. Push the connector firmly into the Data Setting Console until the clips fully lock.
3. The Data Setting Console uses power from input terminals A8 and A9 of the
PID Control Unit, supplied through the connecting cable.
4. Install the supplied connector cover when the Data Setting Console is not used.
17
SECTION 3
Data Setting Console Operation
This section provides the basic operating procedures of the Data Setting Console including parameter settings and displays.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Parameter Displays and Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-2 How to Display and Set Parameter Data . . . . . . . . . . . . . . . . . . . . . . . .
19
Operating Procedure
3-1 Operating Procedure
After preparing the C200H PC, follow the procedure below to use the PID Control Unit.
1, 2, 3...
1. Set the switches on the front and rear panels according to the operating con-
ditions. (Refer to 2-2 Switch Settings.)
Set SW2-2 under the display cover to the OFF position to enable data setting from the Data Setting Console.
2. Mount to Rack.
Turn off the C200H power supply before mounting or dismounting the
C200H on the Rack.
3. Connect the input wiring. (Refer to 2-3 Wiring.)
The 24-VDC power supply must be connected. The Data Setting Console will not operate unless the 24-VDC power supply is connected. The sensors can be connected immediately before the system is tested.
4. Connect the Data Setting Console. (Refer to 2-3-3 Data Setting Console
Cables.)
5. Turn on the 24-VDC and the C200H power supplies.
Set the C200H to PROGRAM mode.
6. Use the Data Setting Console to make the settings for the parameters that need to be changed. (Refer to the rest of this section.)
7. Test operation and adjust data. (Refer to the rest of this section.)
Connect the output wiring and turn on the heater power. To start the test operation, turn ON the RUN bit of the loop that is to be controlled with a device such as the Programming Console. Monitor the control conditions and adjust the data until the required control is achieved. During operation, the
“bank no.” is switched to “executed bank no.” and cannot be changed from the Data Setting Console. To change it, use a device such as the Programming Console, or else use the user program.
8. Create the user programs. (Refer to
Section 4 PC Memory Allocation and
Programming.)
Arrange the data for the test operation, and create the user programs for data setting, monitoring, switching the bank number, and so on. Set SW2-2 under the display cover to the ON position to enable data setting from the
C200H PC.
9. Start operation.
20
Data Flow
3-2 Data Flow
The data flow in the PID Control Unit is shown in the diagram below.
Read
PID Control Unit Write executed bank no.
C200H PC
Write
ON
SW2-2
OFF
Data Setting Console
Read
Data Settings from Data
Setting Console
The read operation and setting the executed bank number are possible from a user program or from a device, such as the Programming Console, regardless of the ON/OFF setting of SW2-2.
Data written from the Data Setting Console and data written with the EEPROM write commands when SW2-1 (switching memory contents) is set to Normal are written to the PID Control Unit EEPROM and are consequently retained when the power supply is turned OFF.
Data written with RAM write commands when SW2-1 (switching memory contents) is set to Normal, the SP value set when SW2-1 is set to Fixed, and executed bank number settings made from the C200H PC are written directly to
RAM and are not saved to EEPROM. This data is lost when the power supply is turned OFF.
Set SW2-2 under the display cover to the OFF position to enable data setting from the Data Setting Console.
The “bank no.” can be set when operation is stopped (i.e., when the RUN bit is
OFF). During operation it is switched to “executed bank no.” and cannot be changed from the Data Setting Console. To change the executed bank number, use a user program or a device such as the Programming Console.
Operation begins when the RUN bit of the output relay turns ON. (For information on output relays, refer to Section 4 PC Memory Allocation and Programming.
21
Nomenclature and Features
3-3 Nomenclature and Features
3-3-1 Nomenclature
Front View
Side View
Data display
Operation indicators
Display for Cam
Positioner
Cover
Display Key
(With cover open)
Level Key
Down Key
Up Key
Operation keys
Select parameters
Set data
Switch Loops
Loop Key
PID Control Unit connector
Connecting cable (sold separately)
C200H-CN225 (2 m)
C200H-CN425 (4 m)
Panel mounting bracket
(Refer to Appendix B Dimensions for details about panel mounting.)
Rear View
22
The bottom row of the operation keys have upper and lower labels. The upper labels apply to PID Control Unit operation. The lower labels are for the Cam Positioner Unit.
Two display sheets are supplied: one for the PID Control Unit and one for the
Cam Positioner Unit. If the Data Setting Console is to be used with the PID Control Unit only, attach the display sheet for the PID Control Unit.
Note The Data Setting Console will not operate unless a 24-VDC power supply is connected to the PID Control Unit input terminals.
Nomenclature and Features
3-3-2 Features
Data Display
Name Function
PV (Process
Value)
Displays the PV or the parameter symbol selected with the Level or Display Key (Refer to next page).
SV (Set Value) The display is as follows, according to the PV display contents.
BK (Bank
Number)
PV (process value):
Parameter symbol:
SV (set value) is displayed.
Setting/monitor data is displayed.
Displays the bank number of the data presently being displayed.
During operation, the executed bank number is displayed. (See note)
Note Operation begins when the RUN bit of the output relay turns ON.
Operation Indicators
Name
LOOP2
OUT (Output)
AT
(Auto-tuning)
HB (Heater
Burnout)
ALM1 (Alarm)
Function
Indicates whether the displayed settings relate to Loop 1 or Loop
2. Press the Loop Key and hold down for approximately 2 seconds to switch between Loop 1 and Loop 2.
Indicator OFF: Loop 1
Indicator ON: Loop 2
Turns ON when the output is ON for transistor output or voltage output types.
Blinks at approximately 1 second intervals during auto-tuning.
These indicators relate to the tl di l d loop.
Turns ON to indicate a heater burnout alarm.
Turns ON to indicate the temperature is in the alarm range set with Alarm SV 1
(upper- and lower-limit alarm). Refer to the following page.
Display Patterns
Display Pattern 1 Display Pattern 2
Process value
Executed bank number or displayed bank number
Indicator OFF: Loop 1
Indicator ON: Loop 2
Set point
Executed bank number or displayed bank number
Indicator OFF: Loop 1
Indicator ON: Loop 2
Parameter symbol
SV (Set value)
Monitored value
Execution status
23
Parameter Displays and Settings
Operation Keys
Name
Level Key
Display Key
Loop Key
Up Key
Down Key
Function
The parameter items are divided into three display groups (Refer to display levels 0 to 2 in the table below). Press this key to switch from one group to another. The display levels automatically cycle in the sequence 0 –> 1 –> 2 –> 0 when the key is held down for approximately 2 seconds.
Press this key to select the required parameter from the selected display level 0 to 2 (Refer to table below).
The parameters cycle automatically when the key is held down.
Press this key for approximately two seconds to switch between
Loop 1 and Loop 2.
Press this key to increment SV.
The SV increment continuously while the key is held down. The
SV display blinks when the value reaches its upper limit.
Press this key to decrement an SV.
The SV decreases continuously while the key is held down. The
SV display blinks when the value reaches its lower limit.
3-4 Parameter Displays and Settings
3-4-1 Table of Parameters
Display level
0
Parameter
PV monitor
(see note 3)
Manual output volume
(see note 6)
Set point (see note 3)
Bank number
Alarm SV 1 (see notes 3, 4)
Alarm SV 2 (see notes 3, 4)
Input shift value
(see note 3)
Proportional band
(see note 1)
Integral (reset) time (see note 1)
Derivative (rate) time (see note 1)
Display symbol
--o
Write Read Loop no.
No
Yes
Yes
Yes
Yes
Yes
Bank no.
No
No
Data range
Scaling lower limit –10% to scaling upper limit +10%
-5 to 105%
---
Yes Yes Yes Yes Scaling lower limit to scaling
bk
See note 5
al–1
Yes Yes Yes Yes Alarm mode
1, 4, 5:
al–2
Yes
Yes
Yes
Yes
Yes
No
Yes upper limit
1 to 8
Other:
–999 to 9999
in–5
Yes Yes Yes Yes –999 to 9999
Default value Page
(Unit: EU)
0%
0 EU
1
0 EU
0 EU
p
Yes Yes Yes Yes 0.0 to 999.9% FS 10.0% FS
i
Yes Yes Yes Yes 0 to 9999 s 240 s
d
Yes Yes Yes Yes 0 to 9999 s 40 s
24
Parameter Displays and Settings
Display level
1
Parameter
Decimal point position
Scaling lower limit
Display symbol
Write Read Loop no.
Bank no.
dp
Yes Yes Yes No
inl
Yes Yes Yes No
Data range
0 to 3
2
Scaling upper limit
Digital filter
Control period
(see note 1)
Hysteresis (see note 2)
Alarm hysteresis
(see note 4)
Control output variable monitor
Auto-tuning start/ stop (see note 1)
Copy bank
Input-type monitor
Alarm 1 mode
Alarm 2 mode
inh df cp hys hysa o at bcpy in-t alt1 alt2
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
No
Yes
No
No
No
No
No
No
Yes: Possible.
No: Not possible or not required.
0.0 to 100.0% FS
0.0 to 100.0%
---
---
0 to 9
0 to 9
Default value Page
1
-999 to (scaling upper limit – 1 digit)
(Scaling lower limit + 1) to 9999
0 to 100 s
1 to 99 s
0
1000
0 s
20 s
0.2% FS
0.0 to 100.0% FS 0.1% FS
0.0%
---
---
Setting for
SW202
2
Note 1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (Switch 203-1 = ON)
3. The decimal point position is set by the “decimal point position” parameter.
4. Does not apply when Alarm Mode = 0.
5. Writing is not possible during operation (i.e., when RUN is ON).
6. Only when the output relay “MAN” bit = 1.
3-4-2 How to Display and Set Parameter Data
Basic Operation
When not specifically explained, use the keys as described below.
Changing the Display Level
When the Level Key is pressed, the leading parameter for each level is displayed.
Changing Parameters
When the Display Key is pressed, the parameters are displayed in order. There may be skips depending on the model and DIP switch settings.
Changing the SV
Pressing the Up Key or the Down Key changes the SV. The SV is retrieved automatically.
Changing the Loop
The loop is changed each time the Loop Key is pressed. It can be confirmed by means of the LOOP 2 indicator.
25
Parameter Displays and Settings
Manual Output Volume (Display Level 0)
PV
SV
Process value (monitored every 100 ms)
Manual output volume of currently selected loop (Unit: %)
Parameter signal of manual output volume
PV and SV (Display Level 0)
Settings
•
This is used to manually manipulate the output volume. It is valid when the output relay “MAN” bit is ON.
•
The “MAN” bit can be turned ON and OFF by means of a device such as the
Programming Console, or by means of the user program. For details, refer to
Section 4 PC Memory Allocation and Programming.
PV
SV
Process value (monitored every 100 ms)
Set point of currently selected bank and loop (unit:EU)
Bank Number (Display Level 0)
Valid SV Range
Set the set point in the range between the scaling lower limit and the scaling upper limit.
Error Display
When a sensor error occurs, one of the codes below and the detected temperature blink alternately in the PV display.
ser1 ser2
The analog input is out of the range: (input measurement range +
10%FS). That is, 10%FS below the lower limit or 10%FS above ser1 : Loop1 or Loop1 and Loop2 simultaneously.
ser2 : Loop2
PV
SV
Bank number parameter symbol
Currently set bank number.
During control operation: Executed bank number
Control operation interrupted: Currently displayed bank number
Settings
•
The bank number can be changed.
•
The changed SV is reflected in the bank number display (BK).
Bank Number and Executed Bank Number
The executed bank number cannot be changed from the Data Setting Console.
When changing these parameters from the Data Setting Console, stop operation. While operation is stopped, the bank number setting can be changed.
26
Parameter Displays and Settings
Alarm SV 1 (Display Level 0)
PV Alarm 1 parameter symbol
SV
Alarm SV of currently selected bank and loop (unit: EU)
Invalid if ALARM mode = 0.
Alarm SV 2 (Display Level 0)
PV Alarm 2 parameter symbol
SV
Alarm SV of currently selected bank and loop (unit: EU)
Invalid if ALARM mode = 0.
Input Shift Value (Display Level 0)
PV
SV
Input shift value parameter symbol
Input shift value of currently selected bank and loop (unit:
EU)
If the displayed value differs from the actual value due to the sensor position or some other conditions, set the input shift value such that the correct value is displayed.
Proportional Band (Display Level 0)
PV
Proportional Band parameter symbol
SV
Proportional band of currently selected bank and loop
(unit: %FS)
•
This sets the proportional band. It is valid only when SW203-1 is set to OFF
(i.e., PID control).
•
This value is reflected even when auto-tuning (AT) is executed.
•
If this value is set to “0.0,” ON/OFF control is executed with PID control selected.
Integral (Reset) Time (Display Level 0)
PV Integral time parameter symbol
SV
Integral time of currently selected bank and loop
(unit: second)
•
This sets the integral time. It is valid only when SW203-1 is set to OFF (i.e., PID control).
•
This value is reflected even when auto-tuning (AT) is executed.
Derivative (Rate) Time (Display Level 0)
PV
SV
Derivative time parameter symbol
Derivative time of currently selected bank and loop
(unit: second)
27
Parameter Displays and Settings
•
This sets the integral time. It is valid only when SW203-1 is set to OFF (i.e., PID control).
•
This value is reflected even when auto-tuning (AT) is executed.
Decimal Point Position (Display Level 1)
PV
SV
Decimal point position parameter symbol
Decimal point position of currently selected loop
The decimal point position setting applies to the following parameters:
PV monitor, SV, alarm SV, and input shift value.
Scaling Lower Limit (Display Level 1)
PV
SV
Scaling lower limit parameter symbol
Scaling lower limit of currently selected loop
This sets the scaling lower limit. The default value is 0%.
Scaling Upper Limit (Display Level 1)
PV
SV
Scaling upper limit parameter symbol
Scaling upper limit of currently selected loop
Digital Filter (Display Level 1)
This sets the scaling upper limit. The default value is 1000%.
PV
SV
Digital filter parameter symbol
Time constant of currently selected loop (unit: seconds)
This delays the response to sudden input changes. The SV is designated by “T” in the illustration below.
Input
After Passing Through the Filter of Set Value “T”
100%
63%
0
0 T
(s)
→
28
Parameter Displays and Settings
Control Period (Display Level 1)
PV Control period parameter symbol
SV
•
This sets the control period. It is valid when SW203-1 is OFF (PID control).
•
The control period is the time required to complete one transistor output or voltage output ON/OFF cycle.
ON
OFF
Control period of currently selected loop
(Unit: seconds)
ON time
Control period
Hysteresis (Display Level 1)
PV Hysteresis parameter symbol
SV Hysteresis of currently selected bank and loop
(Unit: %FS)
•
Hysteresis prevents control output chattering and eliminates noise influences.
•
When switching from ON to OFF, operation proceeds at the set point. When switching from OFF to ON, operation proceeds at a lower point determined by the hysteresis SV, as shown in the illustration below.
Hysteresis
ON
OFF
Set point
Hysteresis is applied in the following situations.
•
When ON/OFF control is selected (i.e., when SW203-1 is ON).
•
When advanced PID control is selected (i.e., when SW203-1 is OFF) and P
(proportional band) is 0.
Alarm Hysteresis (Display Level 1)
PV
SV
Alarm hysteresis parameter symbol
Alarm hysteresis of currently selected loop
(Unit: %FS)
•
Alarm hysteresis prevents alarm output chattering and eliminates noise influences. It is invalid when both ALARM mode 1 and ALARM mode 2 are set to
“0.”
•
When switching from OFF to ON, operation proceeds at the set point. When switching from ON to OFF, a hysteresis SV operating band is provided which
29
Parameter Displays and Settings
may be either higher or lower than the set point, depending on the ALARM mode.
Lower Limit Mode Upper Limit Mode
Hysteresis Hysteresis
ON ON
OFF
OFF
Alarm SV Alarm SV
The alarm output is OFF if the present value lies within the hysteresis band when the Unit is turned on.
Control Output Variable Monitor (Display Level 2)
PV
SV
Control output variable monitor parameter symbol
Control output variable of currently selected loop
(Unit: %) Monitored every 100 ms.
The relationship between the control output variable and control period is defined by the formula below:
ON time
Control output variable (%) = x 100
Control period
The control output variable during ON/OFF control (when SW203-1 on the rear panel is ON) is ON = 100% and OFF = 0%.
Auto-tuning Start/Stop (Display Level 2)
PV
Process value
SV
Set point
AT start/stop parameter symbol AT indicator blinks
•
The auto-tuning operation begins when the Up Key is pressed. The PV and SV return to the respective present value and set point displays. While auto-tuning is in progress the AT indicator blinks.
•
To interrupt, press the Level and Display Keys again to display at . When at appears, press the Up Key. When the interrupt is executed, the AT display disappears and the process value is displayed.
•
When auto-tuning is completed, the AT indicator stops blinking and the P, I, and
D data is written to EEPROM.
Copy Bank (Display Level 2)
PV
SV
Copy bank parameter symbol Execute bank copy Bank being copied Bank copy completed
•
When the Up Key is pressed, the data other than the set point is copied from bank number 1 to banks 2 through 8.
•
Use this method to create data in banks 2 through 8 by slightly modifying the data in bank number 1.
30
Parameter Displays and Settings
Input-type Monitor (Display Level 2)
PV
SV
Note Cannot be set.
Alarm 1 and Alarm 2 Modes (Display Level 2)
PV
SV
Input-type monitor parameter symbol
SW202 set value
Alarm 1 Mode parameter symbol
Alarm 1 Mode of currently selected loop
PV
SV
Alarm 2 Mode parameter symbol
Alarm 2 Mode of currently selected loop
Select the desired alarm type from the following chart and set the number (X: set value)
ALARM mode
0 No alarm
Alarm Type
0
Alarm Range
SP
1 Upper- and lower-limit alarm x x
2
3
4
Upper-limit alarm
Lower-limit alarm
Upper- and lower-limit range alarm x x x x
5
6
7
Upper- and lower-limit alarm with standby sequence
Upper-limit alarm with standby sequence
Lower-limit alarm with standby sequence
Absolute-value upper-limit alarm x x x x
8 x
9 Absolute-value lower-limit alarm x
Standby Sequence
When the power is turned on, the value is below the set point, so alarm output status occurs with regard to the lower limit alarm. In this situation, if “lower limit
31
Parameter Displays and Settings
alarm with standby sequence” is selected, the standby sequence recognizes that the value is out of the alarm range and then outputs an alarm when the value enters the alarm range once more.
Lower Limit Alarm with Standby Sequence
Standby sequence cancel point
Hysteresis
OFF point
Alarm SV
0
°
C
Alarm output
The standby sequence is restarted in the following situations.
•
When the power is turned on.
•
When the set point is changed.
•
When the executed bank number is changed.
•
When the ALARM mode is changed.
•
When changing from stop to run.
32
SECTION 4
PC Memory Allocation and Programming
This section provides the C200H PC’s memory allocation for the PID Control Unit. Basic programming procedures and examples are also provided.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Allocation Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example with SW2-1 in the Fixed Position . . . . . . . . . . . . . . . . . . . . .
Example 1: Write with SW2-1 in the Normal Position
Example 2: Read with SW2-1 in the Normal Position
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
Memory Allocation
4-1 Memory Allocation
Memory Allocation
C200H PC
According to the Unit number switch setting on the front of the C200H PID Control Unit, 10 words are allocated for each Unit number in the Special I/O Unit IR area between IR100 to IR199, which is used as the I/O refresh data area. The IR area used by the C200H PID Control Unit is refreshed on each C200H PC I/O refresh scan.
PID Control Unit
IR area
Unit#0 IR100 to IR109
Unit#1 IR110 to IR119
Unit#2 IR120 to IR129
Unit#3 IR130 to IR139
Unit#4 IR140 to IR149
Unit#5 IR150 to IR159
Unit#6 IR160 to IR169
Unit#7 IR170 to IR179
Unit#8 IR180 to IR189
Unit#9 IR190 to IR199
I/O refresh data area
OUT
IN
Wd (n)
to
Wd (n+2)
Wd (n+3)
to
Wd (n+9)
Output refresh
Input refresh
(n=100 + 10 x Unit number) During PC I/O refresh, each scan is executed for the outputs (PC to PID Control Unit) followed by the inputs (PID
Control Unit to PC).
The terms “output” and “input” are defined from the C200H PC side.
Note A Duplicate I/O Unit error occurs if the set Unit number corresponds to the number of an existing Special I/O Unit.
Selecting Allocated Data The data allocated to each IR word due to the Unit number setting is determined by the setting of SW2-1 on the front of the Unit.
ON
OFF
Normal All data can be set using commands.
Fixed Parameters are fixed for the set point (SV).
This setting becomes valid immediately when the switch is set.
34
Memory Allocation
4-1-1 Memory Allocation Table
SW2-1 in Fixed Position
(n=100 + 10 x Unit number)
I/O
Output n
Input
Word n+1 n+2 n+3 n+4 n+5 n+6 n+7 n+8 n+9
0 to 9, F
Loop 1 SP (see note)
Bit
15 14 13
Loop 1 SP (see note)
12 11 10 09 08 07 06 05 04 03 02 01 00
0 to 9, F
Loop 2 SP (see note)
0 to 9 0 to 9 0 to 9
0 to 9, F
Loop 1 executed bank
0 to 9
Loop 2 executed bank
0 to 9
Loop 1
MAN RUN
Loop 2
MAN RUN
0 to 9
0
Loop 1 PV (see note)
0 to 9, F
Loop 2 PV (see note)
0 to 9 0 to 9 0 to 9
0 to 9 0 to 9 0 to 9
0 to 9 0 to 9 0 to 9 0 to 9, F
Loop 2 SP (see note)
0 to 9, F
Loop 1 executed bank
0 to 9
Loop 2 executed bank
0 to 9
0
0 to 9
0 0 SW 2
2 1
Loop 1 status data
0 Sensor error
0 0 0
MAN
RUN 0 0 0 Control output
AT 0 AL1 AL2
Loop 2 status data
0 Sensor error
0 0 0
MAN
RUN 0 0 0 Control output
AT 0 AL1 AL2
Note Four digits BCD and the decimal point position are designated by the “decimal point position” parameter. The most significant digit (F) = minus (–).
SW2-1 in Normal Position
(n=100 + 10 x Unit number)
I/O
Output
Word n n+1 n+2
15 14 13 12
Read/write instruction
Read/write Loop no.
Write data (see note)
0 to 9, F
Loop 1 executed bank
11 10
Bank no.
09
0 to 9
Loop 2 executed bank
Bit
08 07 06 05
Instruction
0 to 9
Loop 1 Loop 2
04 03 02 01
0 to 9
0 0
MAN RUN MAN RUN
Input n+3 Loop 1 PV (see note)
0 to 9, F 0 to 9 0 to 9 0 to 9
00
Write quest
35
Memory Allocation
Input n+4 n+5 n+6 n+7 n+8 n+9
15 14 13
Loop 2 PV (see note)
12
0 to 9, F
Read data (see note)
0 to 9, F
0
Loop 1 executed bank
11
0 to 9
0 to 9
Write error
0
10
0
09 08
Loop 2 executed bank
Bit
Write complete
07
0 to 9
0 to 9
0
0
06 05 04 03 02 01
0 to 9
0 to 9
0
0
0
0
00
0
SW2
2 1
Read complete
Loop 1 status data
0 Sensor error
0 0
Loop 2 status data
0 Sensor error
0 0
0
0
MAN
RUN
MAN
RUN
0
0
0
0
0
0
Control output
Control output
AT
AT
0
0
AL1
AL1
AL2
AL2
Note Four digits BCD and the decimal point position are designated by the “decimal point position” parameter. The most significant digit (F) = minus (–).
4-1-2 Memory Contents
SW2-1 in Fixed Position
I/O
Output n
Word
Address
Bit
15 to 00 n+1 15 to 00 n+2 15 to 12
11 to 08
07
06
05
04
03 to 00
(n=100 + 10 x Unit number)
Data contents Data item
Loop 1 SP Sets the Loop 1 and Loop 2 SP (set point) as 4-digit BCD data.
Set the most significant digit to F for minus (–).
Loop 2 SP
Loop 1 executed bank number
Loop 2 executed bank number
Loop 1
MAN
Loop 1
RUN
Loop 2
MAN
Loop 2
RUN
---
(n+2) and can are written directly to RAM. (Refer to 4-3 Programming.)
Sets the bank number executed for Loop 1 and Loop 2 as 1-digit
BCD data. Set executed bank numbers from 1 to 8. If the value is set out of this range, the bank number reverts to the previous
This is the Loop 1 Manual Output Mode bit. When it is set to 1, the Unit goes into Manual Output Mode.
This is the Loop 1 Run/Stop bit. When it is set to 1, operation starts; when it is set to 0, operation stops.
This is the Loop 2 Manual Output Mode bit. When it is set to 1, the Unit goes into Manual Output Mode.
This is the Loop 2 Run/Stop bit. When it is set to 1, operation starts; when it is set to 0, operation stops.
Not used. Set to 0.
36
Memory Allocation
Input
I/O n+3
Word
Address
Bit
15 to 00 n+4 n+5 n+6 n+7
15 to 00
15 to 00
15 to 00
15 to 12
11 to 08
07 to 02
01
00 n+8 Loop 1 n+9 Loop 2
15
14
03
02
01
00
13 to 10
09
08
07 to 05
04
Data item Data contents
Loop 1 PV Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit
---
MAN
RUN
---
Control output
AT
---
AL1
AL2
Loop 2 PV
Loop 1 SP )
Loop 2 SP
Th i ifi di i i F f i ( ) g
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
Loop 1 executed bank number
Loop 2 executed bank number
--Not used. Each bit is set to 0.
SW2-2
SW2-1
---
Sensor error
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
Outputs the ON/OFF status of SW2-1 (switching memory contents).
0: Fixed
1: Normal
Not used. Set to 0.
Loop 1/2 status data
Bit set to 1 if the sensor is not connected, a sensor wire is broken, or the input data exceeds the operational temperature range.
Not used. Each bit is set to 0.
ON (set to 1) for Manual Output Mode.
ON (set to 1) during operation.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or voltage output) is ON.
Bit set to 1 during auto-tuning (AT).
Not used. Set to 0.
Bit set to 1 when the value enters the set alarm
SW2-1 in Normal Position
I/O
Output
(n=100 + 10 x Unit number) n
Word
Address
Bit
Data item Data contents
15 and 14 Read/Write The data bit sets operation to read or write.
Write = 01 Read = 00
13 and 12 Loop no.
The data bit sets the Loop Number to which the read or write operation applies.
Loop 1 = 01, Loop 2 = 10
11 to 08
07 to 00
Bank no.
Sets the bank number to which the read or write operation applies as 1-digit BCD data. Set executed bank numbers from 1 to 8.
Command
Sets the command code (Refer to page 40) for the
read or write operation as 2-digit BCD data.
Read/Write command
37
Memory Allocation
I/O
Output
Input
n+1
Word
Address
Bit
15 to 00 n+2 n+3 n+4 n+5 n+6
Data item Data contents
15 to 12
11 to 08
07
06
05
04
03 to 01
00
Write data Set the SP for a write operation as 4-digit BCD data. The least significant digit of the actual data matches the least significant digit of the set value. Set the most significant digit to F for minus
(–) values. The write operation commences when the write request flag (Wd (n+2), bit 00 ) turns ON.
Loop 1 executed bank number
Loop 2 executed bank number
Loop 1
MAN
Loop 1
RUN
Set the bank number currently executed for Loop 1 and Loop 2 as
1-digit BCD data. Executed bank numbers are from 1 to 8. If the value is set out of this range, the bank number reverts to the
This is the Loop 1 Manual Output Mode bit. When it is set to 1, the Unit goes into Manual Output Mode.
This the Loop 1 Run/Stop bit. When it is set to 1, operation starts; when it is set to 0, operation stops.
Loop 2
MAN
Loop 2
RUN
---
This is the Loop 2 Manual Output Mode bit. When it is set to 1, the Unit goes into Manual Output Mode.
This the Loop 2 Run/Stop bit. When it is set to 1, operation starts; when it is set to 0, operation stops.
Not used. Set to 0.
Write request
Turn this bit ON to write the data in Wd (n+1), by means of this command.
Turn this bit OFF after the Write Complete Flag (Wd (n+6), bit 08) turns ON.
Loop 1 PV Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit 15 to 00
15 to 00 Loop 2 PV
“decimal point position” parameter. Set the most significant digit to F for minus (–) values.
15 to 00 Read data Outputs the data read with the commands set with Wd (n). The decimal point position is designated by the “decimal point position
” parameter. Set the most significant digit to F for minus (–) values.
--Not used. Each bit is set to 0.
15 to 12
11 Write error Bit set to 1 when the write data exceeds the set permissible range. The bit is automatically set to 0 when the Write Request
Flag (Wd (n+2), bit 00) turns OFF.
10 and 09 ---
08 Write complete
Not used. Each bit is set to 0.
Bit set to 1 when the write operation executed by means of the command set with Wd (n) ends normally. The bit is automatically set to 0 when the Write Request Flag (Wd (n+2), bit 00) turns
OFF.
07 to 01
00
---
Read complete
Not used. Each bit is set to 0.
Bit set to 1 when the read operation executed by means of the command set with Wd (n) ends normally. The bit is automatically set to 0 when the next command is set.
38
Memory Allocation
Input
I/O n+7
Word
Address
Bit
15 to 12
11 to 08
07 to 02
01
00 n+8 Loop 1
2
15
14
03
02
01
00
13 to 10
09
08
07 to 05
04
Data item Data contents
---
Sensor error
---
MAN
RUN
---
Control output
AT
---
AL1
AL2
Loop 1 executed bank number
Loop 2 executed bank number
---
SW2-2
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
SW2-1
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
Outputs the ON/OFF status of SW2-1 (switching memory contents).
0: Fixed
1: Normal
Not used. Set to 0.
Loop 1/2
Bit set to 1 if an input is not connected, an input wire is broken, or the input data exceeds the operational range.
Not used. Each bit is set to 0.
ON (set to 1) for Manual Output Mode.
ON (set to 1) during operation.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or voltage output) is ON.
Bit set to 1 during auto-tuning (AT).
Not used. Set to 0.
Bit set to 1 when the value enters the set alarm
39
Memory Allocation
4-1-3 Table of Commands
The command codes shown below are set in bits (Wd n) 07 to 00 when the
SW2-1 (switching memory contents) on the front panel is set in the Normal position.
EEPROM Write/Read Commands
Parameter Command
Write Read Loop no.
Bank no.
Actual data range
SV data range
Default value
Set point (see note 3) 0 0 Yes Yes Yes Yes 0 EU
Manual output volume
(see note 6)
0 1
Execution bank number 0 2
Alarm SV 1 (see notes
3, 4)
0 3
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Scaling lower limit to scaling upper limit
-5 to 105% F005 to
0105
1 to 8 0001 to
0008
Alarm mode
1, 4, 5:
0000 to
0%
1
0 EU
Alarm SV 2 (see notes
3, 4)
0 4 Yes Yes Yes Yes 0 EU
Input shift value (see note 3)
Proportional band (see note 1)
Integral (reset) time
(see note 1)
Derivative (rate) time
(see note 1)
Decimal point position
0 5
0 6
0 7
0 8
1 2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Other:
–999 to 9999
0.0 to 999.9
F999 to
9999
–999 to 9999 F999 to
9999
0000 to
9999
0 to 9999 s
0 to 9999 s
0 EU
10.0 %FS
240 s
40 s
1
Scaling lower limit
Scaling upper limit
Control period (see note
1)
1 7
Hysteresis (see note 2) 1 8
Alarm hysteresis (see note 4)
Digital filter
Control output variable monitor
Auto-tuning start/stop
(see note 1)
Copy bank
Input-type monitor
Alarm 1 mode
1 3
1 4
1 9
2 0
2 1
2 2
2 3
2 4
Yes
Yes
Yes
Yes
Yes
1 E Yes
No
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
No
Yes
No
No
No
No
No
No
No
0 to 3 0000 to
0003
-999 to (scaling upper limit value – 1 digit)
(Scaling lower limit + 1 digit) to 9999
1 to 99 s 0001 to
0099
0.0 to 100.0
0.0 to 100.0
0 to 100
0000 to
1000
0000 to
1000
0000 to
0100
–5.0 to
105.0%
---
F050 to
1050
AT start =
0001
AT stop =
0000
---
0 to 9
0 to 9
0000 to
0009
0000 to
0
100.0
20 s
0.2 %FS
0.1 %FS
0 s
0.0%
---
---
Setting for
SW202
2
Alarm 2 mode 2 5
Yes: Possible.
No: Not possible or not required.
Note 1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (Switch 203-1 = ON)
40
Memory Allocation
3. The decimal point position is designated by the “decimal point position” parameter.
4. Does not apply when Alarm Mode = 0.
5. Writing is not possible during operation (i.e., when RUN is ON).
6. Only when the output relay “MAN” bit is 1.
7. When writing to the EEPROM with the set point command “00”, set the
SW203-3 to OFF.
RAM Write Commands
Parameter
Set point (see note 3)
Execution bank number 4 2
Alarm SV 1 (see notes
3, 4)
Command
4 0
4 3
Write Read Loop no.
Yes No Yes
Yes
Yes
No
No
Yes
Yes
Bank no.
Yes
No
Yes
Actual data range
Scaling lower limit to scaling upper limit
1 to 8
SV data range
0001 to
0008
Alarm mode
1, 4, 5:
0000 to
0 EU
1
Default value
0 EU
Alarm SV 2 (see notes
3, 4)
Input shift value (see note 3)
Proportional band (see note 1)
Integral (reset) time
(see note 1)
Derivative (rate) time
(see note 1)
Decimal point position
Scaling lower limit
Scaling upper limit
4 4
4 5
4 6
4 7
4 8
5 2
5 3
5 4
Control period (see note
1)
5 7
Hysteresis (see note 2) 5 8
Alarm hysteresis (see note 4)
Digital filter
Alarm 1 mode
Alarm 2 mode
5 9
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
5 E Yes
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
No
No
Other:
–999 to 9999
0.0 to 999.9
F999 to
9999
–999 to 9999 F999 to
9999
0000 to
9999
0 to 9999 s
0 to 9999 s
0 to 3
-999 to (scaling upper limit value – 1 digit)
(Scaling lower limit + 1 digit) to 9999
1 to 99 s 0001 to
0099
0.0 to 100.0
0.0 to 100.0
0000 to
1000
0000 to
1000
0 to 100
0 to 9
0000 to
0003
0000 to
0100
0000 to
0 EU
0 EU
10.0 %FS
240 s
40 s
1
0
100.0
20 s
0.2 %FS
0.1 %FS
0 s
6 4
6 5
Yes No Yes No 2
Yes: Possible.
No: Not possible or not required.
Note 1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (Switch 203-1 = ON)
3. The decimal point position is designated by the “decimal point position” parameter.
4. Does not apply when Alarm Mode = 0.
5. RAM write commands write data only to the RAM regardless of the setting of the Switch 203-3 (SP write mode).
6. Any data written using RAM write commands is deleted when the power is turned OFF.
41
Programming
7. RAM write commands cannot be used to read data.
4-2 Data Flow
Data Settings
Refer to 3-2 Data Flow for the data flow in the PID Control Unit.
Before setting data with a user program or the Programming Console, turn ON
SW2-2 of the Unit to enable data setting from the C200H PC. However, the executed bank number can be set with a user program or from the Programming
Console regardless of the ON/OFF setting of SW2-2.
SW2-1 (switching memory contents) may be set in either the OFF (Fixed) or ON
(Normal) position, but care is required as the setting of this switch changes the stored data contents.
4-3 Programming
4-3-1 Example with SW2-1 in the Fixed Position
Description and Conditions
Example: The user program makes the following settings:
Loop 1 SP = 80.0
Loop 2 SP = 90.0
Loop 1 executed bank number = 1
Loop 2 executed bank number = 3
Conditions: C200H-PID01
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set OFF (Fixed) and SW2-2 set ON (C200H PC).
Sample Program
25315 10701
1 cycle ON (C200H)
10700
Fixed
Reading Monitored Data
42
MOV (21)
Set #0800 for word 100 (Loop 1 SP).
#0800
100
MOV (21)
Set #0900 for word 101 (Loop 2 SP).
#0900
101
MOV (21)
END (01)
#1350
102
Set #1350 for word 102 (executed bank number).
#1350
Run bit ON
Loop 2 executed bank number
Loop 1 executed bank number
Be sure to set the correct values for the Loop 1 and Loop 2 SP.
The SV value is #0000 (0%) if no data is set. If the executed bank number is set to a value out of the range from 1 to 8 the bank number reverts to the previous value
(default value = 1).
Read monitored data into the program using Wd (n+3) to (n+9).
Programming
4-3-2 Example 1: Write with SW2-1 in the Normal Position
Description and Conditions
Example Before running the program, make the following parameter settings:
Loop 1 SP = 20.0 (Bank no. = 1)
Loop 2 SP = 8.05 (Bank no. = 2)
Loop 1 executed bank number = 1; decimal point position = 1
Loop 2 executed bank number = 2; decimal point position = 2
This is an example of a program that writes data to the EEPROM.
When writing to the RAM, add 4 to the leftmost digit of the command.
Conditions C200H-PID01
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
43
Programming
Sample Program
10701 10700
(C200H) Normal
25315 10701
1 cycle ON (C200H) Normal
23200
23201
10700
23202
23201
10608 Write complete
23203
23204
23203
10608
Write complete
23205
44
Next page
DIFU (13)
23200
SW2-2 (10701) switch ON detection
(C200H PC)
23201
Program runs when operation is started or
SW2-2 turned ON
MOV (21)
#1250
102
MOV (21)
#5100
100
MOV (21)
#0200
101
DIFD (14)
23203
S
KEEP(11)
23202
#1250
Run bit ON
Loop 2 executed bank number
Loop 1 executed bank number
#5100
SP setting instruction
Bank number
Bit data : 0101
Loop 1
Write
Write data (20.0)
Wait for completion of write, and then proceed to next step
R
MOV (21)
MOV (21)
#6200
100
#0805
101
#6200
SP setting command
Bank number
Bit data:
0110
Loop 2
Write
Write data (8.05)
DIFD (14)
23205
S
KEEP(11)
23204
Wait for completion of write, and then proceed to next step
R
MOV (21)
MOV (21)
#5012
100
#0001
101
#5012
Decimal point position command
Bank number not required
Bit data:
0101
Loop 1
Write
Write data (1st digit)
Programming
23206
23205
10608 Write complete
23207
23208
10608
Write complete
23201
23203
23205
23207
DIFD (14)
23207
S
KEEP(11)
23206
Wait for completion of write, and then proceed to next step
R
MOV (21)
MOV (21)
#6012
100
#0002
101
#6012 Decimal point position command
Bank number not required
Bit data: 0110
Loop 2
Write
Write data (2nd digit)
S
KEEP(11)
10200
R
Write request
DIFD (14)
23208
END (01)
45
Programming
Timing Chart
1 cycle
25315
(1 cycle ON)
23201
23202
23203
23204
23205
23206
23207
10200
(Write request)
10608
(Write complete)
↑
: Point of Write command execution
In addition to the timing above, 23201 turns ON for one cycle on the ON rising edge of SW2-2 (10701) and a write request (10200) turns ON at a timing one cycle behind 23208.
4-3-3 Example 2: Read with SW2-1 in the Normal Position
Description and Conditions
Example: After writing is completed, the following data is read to the DM area:
Loop 1 PV:
→
DM0000
Loop 1 control output variable:
→
DM0001
Conditions: C200H-PID01
Unit number set to 0 (allocated memory: IR100 to IR109.
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
46
Programming
Sample Program
Insert the program below before the END instruction in the program on page 45.
25313
Normally ON
23208
(A)
23207
10608
Write complete
23300 10701 10700
(C200H) Normal
23307
23301
23302
10600 Read complete
23303
23304
MOV (21)
103
DM0000
DIFD (14)
23300
S
KEEP(11)
23208
R
23301
Read Loop 1 PV from IR103 to DM
0000.
Read operation is not affected by
SW2-1 and SW2-2 settings.
Runs next Read command when final write complete is detected.
23307 repeatedly executes the Read command when each Read Complete is detected.
MOV (21)
#1020
100
DIFD (14)
23302
S
KEEP(11)
23303
#1020
Control output variable monitor command
Bank number not required
Bit data: to read data
0001
Wait for Read Complete
Loop 1
Read
R
DIFD (14)
23304
MOV (21)
105
DM0001
MOV (21)
#0000
2000
DIFD (14)
23307
Read data from IR105 to DM 0001.
(B)
47
Programming
10701 10700
(C200H)
Normal
25315 10701 10700
1 cycle
ON
(C200H)
Normal
23200
Change the above program as shown below if only reading is to be carried out.
Replace part (A) of the program with the following program.
DIFU (13)
23200
SW2-2 (10701) switch ON detection (C200H PC)
23300
Program runs when operation is started or SW2-2 turned ON
Timing Chart
Add an END instruction (01) at position (B) of the program.
1 cycle
23301
23302
23303
23304
23307
Wd 105
(Read data)
10600
(Read complete)
140 ms min. (see note)
↑
: Point of Read command execution
Note It takes more than 140 ms for the Read Complete Flag (10600) to turn ON again after it is turned OFF.
48
Programming
4-3-4 Operation Timing
Write Operation Timing
Command (Wd n)
Write data (Wd n+1)
Data (1) Data (2) Data (3) Data (4)
Write request
(Wd n+2), bit 00
ON
OFF
Write complete
(Wd n+6), bit 08
ON
OFF
Approx.
140 ms
1, 2, 3...
1. The data is written to the PID Control Unit EEPROM when the Write Request
Flag turns ON.
2. The Write Complete Flag turns ON when the data writing operation is completed. It takes approximately 140 ms to write the data.
3. The Write Complete Flag automatically turns OFF when the Write Request
Flag turns OFF.
Check to be sure that the Write Complete Flag has turned ON before turning
OFF the Write Request Flag. If the Write Request Flag is set to OFF before the Write Complete Flag turns ON, the write operation will not be successful.
Temporarily turn the Write Request Flag OFF before executing the second and subsequent write operations. Writing is enabled on the ON rising edge of the Write Request Flag.
The Loop 1 and 2 executed bank number (Wd n+2) sets data directly. The data is written to the PID Control Unit RAM. If the value is set out of this range, the bank number reverts to the previous value (default value = 1).
Timing for a Read Operation
Command (n) Command (A) Command (B)
Read complete
(Wd n+6), bit 00
ON
OFF
Read data
(Wd n+5)
Approx.
140 ms
Read data (A) Read data (B)
I/O Refresh
1, 2, 3...
1. The read data is output to Wd (n+5) approximately 140 ms after the Read command is executed.
2. The read data is updated every 100 ms.
3. When the Read command is modified, turn OFF the Read Complete Flag to execute the next read operation.
PID control will not be executed properly unless there are at least 20 ms between I/O refresh operations. When creating the program, be sure that all of the conditions descried below are satisfied.
•
The cycle time must be a minimum of 20 ms. If the program processing time is short, it is recommended that the fixed cycle time instruction (SCAN18) be used.
•
When IORF(97) is executed for the PID Control Unit, there must be an interval of at least 20 ms between prior and subsequent end refreshes.
49
Programming
•
The time interval for executing IORF(97) must be a minimum of 20 ms.
Normal I/O refresh (End refresh)
20 ms min. (cycle time)
Normal I/O refresh (End refresh)
20 ms min.
IORF(97) (I/O refresh instruction)
20 ms min.
IORF(97) (I/O refresh instruction)
20 ms min.
Normal I/O refresh (End refresh)
50
SECTION 5
Troubleshooting
This section describes possible errors and provides measures for dealing with them.
51
Error Detection
Error Detection
When an error occurs in an input or in the Unit, details of the error are output to the Data Setting Console and input relays (words n+8 and n+9).
Sensor Input Errors
Display
ser1
Error name
Loop 1 sensor error
The following table shows the Data Setting Console display and error contents.
Output status after error
Control output:
The transistor output or voltage output turns OFF or the current output falls below 2 mA.
Alarm output:
Cause
Reading is
±
10%FS out of sensor measurement range (i.e., 10%FS below the lower limit or
10%FS above the upper limit).
Remedy
Check the sensor wiring.
Replace the sensor.
Replace the Unit.
Correctly set switch
SW203-4.
ser2
Loop 2 sensor error
Data Setting Console assuming the input is
±
10%FS.
wiring
Defective input sensor
Defective Unit
SW203-4 is OFF (Loop
2 enabled) but no sensor connected to Loop 2.
When a sensor error occurs, one of the codes above and the detected value are displayed alternately.
If a Loop 1 sensor error ser1 and a Loop 2 sensor error ser2 occur simultaneously, ser1 is displayed preferentially. Even if a sensor error is detected in one Loop, the other Loop continues to operate normally. Control operation restarts automatically five seconds after the cause of the error is corrected.
The following bits are set when a sensor input error occurs.
Loop 1 sensor error
Loop 2 sensor error
Wd. n+8, bit 14 = 1
Wd. n+9, bit 14 = 1
Alarm
Display
ALM1 indicator lit
ALM2 indicator lit
Error name
Alarm 1
Alarm 2
Cause
The value is in the alarm range set with
Alarm SV 1.
The value is in the alarm range set with
Alarm SV 2.
Remedy
Check the object being controlled.
Error displayed when an abnormality occurs in the loop currently being displayed. No indicator is provided to show an ALM2 alarm.
The bits shown in the table below are set to 1 when an alarm occurs.
Wd (n+8)
Wd (n+9)
Bit 01 = 1
Bit 00 = 1
Bit 01 = 1
Bit 00 = 1
Alarm 1
Alarm 2
Alarm 1
Alarm 2
Loop 1
Loop 2
EEPROM Error
Display e111
Error name
EEPROM error
Output status after error Cause
Defective
EEPROM
Remedy
Replace the Unit
Control output:
The transistor output or voltage output is OFF or the current output is less than
2 mA.
Alarm output is OFF.
52
Error Detection
Duplicate I/O Unit
Special I/O Unit Error
RUN Indicator Unlit
No Data Setting Console
Display
The RUN indicator turns off when an EEPROM error occurs.
The Unit number duplicates the number of another Special I/O Unit. The SR bit
25415 turns ON when an Duplicate I/O Unit error occurs. Refer to AR0000 to
AR0011 for the duplicated Unit number. The C200H PC will not operate during a duplicate I/O error.
Set the Unit number to a separate number.
I/O refresh not operating correctly between the CPU Unit and PID Unit. The PID
Control Unit is operating based on the contents of the previous refresh. Refer to
AR0000 to AR0015 for the Unit number where the error occurred. After correcting the cause of the error, set the Special I/O Unit Restart Flag (AR0100 to
AR0109) to restart operation.
The C200H power supply is turned on but the RUN indicator is not lit. None of the errors described previously are detected. Replace the Unit.
•
No 24-VDC power supply is connected to the PID Control Unit input terminals
A8 and A9.
•
The connecting cable is disconnected.
•
The connecting cable is broken.
•
A circuit in the Data Setting Console is defective.
•
A circuit in the PID Control Unit is defective.
After determining the cause of the error, correct the problem or replace the Unit.
53
Appendix A
Specifications
General Specifications
Conforms to the C200H PC specifications.
Item
Input signal refresh
No. of input points (loops)
C200H-PID0
4 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V j Specifications
Two points (two loops, each of which consists of a voltage and a current)
Control mode PID, ON/OFF (selectable with a switch on the rear panel)
(advanced PID control with auto-tuning)
Setting/designation accuracy
±
0.5% FS
±
1 digit max. The SV and displayed value match. There is no relative error.
Hysteresis 0.0 to 100.0% FS (in units of 0.1 %FS)
Alarm hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
0.0 to 100.0% FS (in units of 0.1 %FS)
0.0 to 999.9 (in units of 0.1)
0 to 9999 s (in units of 1 s)
0 to 9999 s (in units of 1 s)
Control period
Sampling period
Output refresh period
Display refresh period
Input shift range
Scaling setting range
Digital filter setting range
Alarm output setting range
Manual output setting range
1 to 99 s (in units of 1 s)
100 ms
100 ms
100 ms
–999 to 9999 (see note 1)
–999 to 9999 (see note1)
0 to 100 s (in units of 1 s)
–999 to 9,999
–5 to 105%
No. of banks 8 banks
Internal current consumption 5 VDC, 0.33 A max.
External supply voltage
Dimensions (see note 2)
24 VDC
+10%
/
–15%
, 0.2 A min.
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
Weight 360 g
Note 1. The decimal point position is designated by a parameter setting.
2. Refer to Appendix B Dimensions.
55
Specifications
Output Characteristics
Transistor Output (Pulse) C200H-PID01
External supply voltage
Max. load voltage
Max. load current
Residual voltage when ON
Leakage current when OFF
Voltage Output (Pulse) C200H-PID02
Output voltage
Max. load current
Current Output (Linear) C200H-PID03
Output current
Permissible load impedance
Current value accuracy
Appendix A
24 VDC +10% /
–15%
24 VDC ( collector supplied voltage) max.
100 mA max.
3 V max.
0.3 mA max.
12 VDC
40 mA (with short-protective circuit)
4 to 20 mA
600
Ω
max.
4
±
0.3 to 20
±
1 mA
56
Appendix B
Dimensions
PID Control Unit
Weight: 360 g
Unit Dimensions
Mounting Dimensions
130
34.5
20
100.5
120.5
131.5
11
Data Setting Console
Weight: 120 g
Unit Dimensions
Approx. 200
17
96
48
3
12 45
57
44
91
57
Dimensions
Mounting Dimensions
Panel Cutout
Appendix B
Clearance
92
+0.8
0
45
+0.6
0
Panel thickness 1 to 4 mm
Clearance of at least 150 mm
Allow a clearance of at least 150 mm behind the Data Setting Console when it is installed in the panel to allow cable connectors to be inserted. A clearance of 50 mm is sufficient if the rear panel can be opened.
58
Appendix C
Parameters and Key Operations
The Data Setting Console key operations and their relation to parameters are shown in the following table.
Display Level 0
Power on
0
1
(MAN)
LVL
Display Level 1 dp
Decimal point position
LVL
Display Level 2 o
Output variable monitor
LVL o
PV inl
Scaling lower limit at
Auto-tuning start/stop
PV
SP inh
Scaling upper limit bcpy
Copy bank bk
Bank number df
Digital filter in–t
Input-type monitor al–1
Alarm 1 SV cp
Control period alt1
Alarm 1 mode al–2
Alarm 2 SV hys
Hysteresis alt2
Alarm 2 mode in–s
Input shift value hysa
Alarm hysteresis p
Proportional band i
Integral time d
Derivative time
59
A
autotuning start/stop setting, 30
B
C
Connector Terminal Block Converter Unit, 16
control output variable monitor setting, 30
cover, removal and replacement, 9
D
data flow, 21 data setting, 21
Data Setting Console
connecting cable and precautions, 16
parameter and setting tables, 24
E
F
I
Index
M
O
operating environment, precautions, ix
Operation and Function Setting, 10
connectors and cable, 15 diagrams, 15 precautions, 15
P
programming, examples, 42 , 46
R
S safety precautions. See precautions
selecting allocated memory, 34
setting and displaying parameters, method, 25
Slave Rack, number of mountable Units, 3
specifications, general, table, 55
switching memory contents, 9 switching memory contents and setting direction, 9
T troubleshooting
alarm, 52 data setting errors, 52
61
62
U
Unit components, dimensions, 57
Index