Puls PIC240.241D DIN rail power supply Owner's Manual

Add to My manuals
20 Pages

advertisement

Puls PIC240.241D DIN rail power supply Owner's Manual | Manualzz
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
POWER SUPPLY








AC 100-240V Wide-range Input
Active PFC
Width only 49mm
Efficiency up to 95.2%
Safe HiccupPLUS Overload Mode
Full Power Between -25°C and +55°C
DC-OK Relay Contact
3 Year Warranty
PRODUCT DESCRIPTION
SHORT-FORM DATA
These PIANO series units are extraordinarily compact,
industrial grade power supplies that focus on the
essential features needed in today’s industrial
applications. The excellent cost/performance ratio
presents many new and exciting opportunities without
compromising quality or reliability.
Output voltage
Adjustment
range
Output current
The addition of a DC-OK signal makes the unit suitable
for many industry applications such as process control,
factory automation or many other critical applications,
where preventive function monitoring can help to avoid
long downtimes.
Nominal
Factory setting
24 – 28V
24.1V
10.0 – 8.6A
Below +55°C amb.
6.25 – 5.4A
At +70°C ambient
Derate linearly between +55°C and +70°C
Input voltage AC AC 100-240V
±10%
Mains frequency 50-60Hz
±6%
AC Input current 2.15 / 1.15A
At 120 / 230Vac
Power factor
0.99 / 0.95
At 120 / 230Vac
AC Inrush current 14 / 26A pk
At 120 / 230Vac,
40°C, cold start
Efficiency
94.0 / 95.2%
At 120 / 230Vac
Losses
15.3 / 12.1W
At 120 / 230Vac
Hold-up time
37 / 37ms
At 120 / 230Vac
Temperature
-25 to +70°C
range
Size (WxHxD)
49x124x124mm
Weight
540g / 1.2lb
ORDER NUMBERS
MAIN APPROVALS
The mechanically robust housing is made of a highgrade, reinforced molded material, which permits the
units to be used in surrounding temperatures up to
70°C.
The unit is equipped with a wide-range input voltage
stage, many safety approvals and a wide operational
temperature range, which makes the unit applicable for
global use.
Power Supply
PIC240.241D
Accessory
YR2.DIODE
UF20.241
Redundancy module
Buffer Module
IEC 61010-2-201
DC 24V
UL 61010-2-201
IEC 62368
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
1/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
INDEX
Page
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Intended Use .......................................................3
Installation Instructions ......................................4
AC-Input...............................................................5
DC-Input...............................................................6
Input Inrush Current ...........................................6
Output .................................................................7
Hold-up Time .......................................................8
DC-OK Relay Contact ..........................................8
Efficiency and Power Losses................................9
Functional Diagram...........................................10
Front Side and User Elements ...........................10
Connection Terminals .......................................11
Lifetime Expectancy ..........................................11
MTBF ..................................................................11
EMC ....................................................................12
Environment ......................................................13
Page
17. Safety and Protection Features........................ 14
18. Dielectric Strength............................................ 15
19. Approvals and Fulfilled Standards................... 16
20. Regulatory Compliance .................................... 16
21. Physical Dimensions and Weight ..................... 17
22. Accessory ........................................................... 18
22.1. PIRD20.241 Redundancy Module ............. 18
22.2. UF20.241 Buffer module .......................... 18
23. Application Notes ............................................. 19
23.1. Charging of Batteries ............................... 19
23.2. Series Operation ....................................... 19
23.3. Parallel Use to Increase Output Power .... 19
23.4. Parallel Use for 1+1 Redundancy ............. 19
23.5. Operation on Two Phases ........................ 20
23.6. Use in a Tightly Sealed Enclosure ............ 20
The information given in this document is correct to the best of our knowledge and experience at the time of
publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the
word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is
subject to revision. We therefore kindly ask you to always use the latest issue of this document (available under
www.pulspower.com).
No part of this document may be reproduced or utilized in any form without our prior permission in writing.
Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as
domestic refuse.
TERMINOLOGY AND ABREVIATIONS
PE and
symbol
PE is the abbreviation for Protective Earth and has the same meaning as the symbol
.
Earth, Ground
This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d.
To be defined, value or description will follow later.
AC 230V
A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
230Vac
A figure with the unit (Vac) at the end is a momentary figure without any additional
tolerances included.
50Hz vs. 60Hz
As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz mains
frequency. AC 120V parameters are valid for 60Hz mains frequency.
may
A key word indicating flexibility of choice with no implied preference.
shall
A key word indicating a mandatory requirement.
should
A key word indicating flexibility of choice with a strongly preferred implementation.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
2/20
PIC240.241D
PIANO-Series
24V, 10A, 240W, SINGLE PHASE INPUT
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring, measurement, Audio/Video, information or communication equipment or the like. Do not
use this device in equipment where malfunction may cause severe personal injury or threaten human life.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the device is not
suited to supply a local DC power network in residential, commercial and light-industrial environments. No restrictions
apply for local DC power networks in industrial environments.
If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the device is not
suited to supply a local DC power network in residential, commercial and light-industrial environments. No restrictions
apply for local DC power networks in industrial environments.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
3/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
2. INSTALLATION INSTRUCTIONS
WARNING
-
Risk of electrical shock, fire, personal injury or death.
Turn power off before working on the device and protect against inadvertent re-powering.
Do not open, modify or repair the device.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation instructions:
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection.
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the device.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are
designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient
temperatures up to +55°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire
enter the terminal connection. Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide protection against
spilled liquids.
The isolation of the device is designed to withstand impulse voltages of overvoltage category III according to IEC
60664-1.
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use without a proper PE
(Protective Earth) connection.
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage between the input
terminal and the PE potential must not exceed 300Vac.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not
cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) the overvoltage category is reduced
to level II and a reduction in output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with
less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 20A without additional protection device. For
higher branch circuits use an additional protection device. If an external input protection device is utilized, do not use
one smaller than a 10A B- or 6A C-characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient
or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
4/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
3. AC-INPUT
The device is suitable to be supplied from TN, TT or IT mains networks with AC voltage.
Nom.
Allowed voltage L or N to earth
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
AC 100-240V
90-264Vac
Continuous operation
264-300Vac
Occasionally for maximal 500ms
Max.
300Vac
Continuous, according to IEC 60664-1
Nom. 50–60Hz
±6%
Typ.
81Vac
Steady-state value, see Fig. 3-1
Typ.
63Vac / 71Vac
At no load / nominal load, steady-state value, see Fig. 3-1
See recommendations in chapter 2.
Input current
Power factor
Crest factor
Typ.
Typ.
Typ.
AC 100V
2.6A
0.99
1.6
AC 120V
2.15A
0.99
1.7
AC 230V
1.15A
0.95
2.0
Start-up delay
Rise time
Typ.
Typ.
460ms
60ms
320ms
60ms
250ms
60ms
Typ.
230ms
230ms
230ms
Max.
200mV
200mV
200mV
Turn-on overshoot
Fig. 3-1 Input voltage range, typ.
Rated
input range
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
max.
500ms
Turn-on
Shut-down
POUT
VIN
90V
Fig. 3-3 Input current vs. output load at 24V
3A
a
b
1.5
c
1.0
Rise
Time
Fig. 3-4 Power factor vs. output load
1.00
a
0.95
b
0.90
0.85
a) 100/120Vac
b) 230Vac
0.80
0.5
0
Start-up
delay
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
2.0
- 5%
Output
Voltage
264V 300Vac
Input Current, typ.
2.5
At 24V, 10A, see Fig. 3-3
At 24V, 10A, see Fig. 3-4
At 24V, 10A, The crest factor is the
mathematical ratio of the peak
value to RMS value of the input
current waveform.
See Fig. 3-2
At 24V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
At 24V, 10A const. current load,
10mF load capacitance, see Fig. 3-2
See Fig. 3-2
0.75
0
1
2
3
Overshoot
AC input
AC input range
4
5
6
7
8
9 10A
Output Current
Output Current
0.70
1
2
3
4
5
6
7
8
9 10A
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
5/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
4. DC-INPUT
Do not operate this power supply with DC-input voltage.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after
turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
Max.
Typ.
Typ.
Max.
AC 100V
14.5Apeak
7Apeak
11.5Apeak
1A²s
AC 120V
17Apeak
8.5Apeak
14Apeak
1A²s
AC 230V
32Apeak
16Apeak
26Apeak
1A²s
At 40°C, cold start
At 25°C, cold start
At 40°C, cold start
At 40°C, cold start
Fig. 5-1 Input inrush current, typical behavior
230Vac input, 24V 10A output, 25°C ambient
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
6/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
6. OUTPUT
The output provides a SELV/PELV/ES1 rated voltage, which is galvanically isolated from the input voltage.
The output is designed to supply any kind of loads, including capacitive and inductive loads. The output can supply any
kind of loads, including unlimited inductive and capacitive loads. If capacitors with a capacitance >2F are connected,
the unit might charge the capacitor in an intermittent mode.
The output is electronically protected against overload, no-load and short-circuits. In case of a protection event,
audible noise may occur.
Output voltage
Adjustment range
Nom.
DC 24V
24-28V
30V
Typ.
Guaranteed value
This is the maximum output voltage which can occur at
the clockwise end position of the potentiometer due
to tolerances. It is not a guaranteed value which can be
achieved.
24.1V
±0.2%, at full load and cold unit
10mV
Between 90 and 300Vac
100mV
Between 0A and 10A, static value, see Fig. 6-1
100mVpp
Bandwidth 20Hz to 20MHz, 50Ohm
10.0A
At 24V and an ambient temperatures below 55°C
6.25A
At 24V and 70°C ambient temperature
8.6A
At 28V and an ambient temperatures below 55°C
5.4A
At 28V and 70°C ambient temperature
Derate linearly between +55°C and +70°
Continuous current
For output voltage above 13Vdc, see Fig. 6-1
Intermittent current1) For output voltage below 13Vdc, see Fig. 6-1
13.0A
Continuous current, see Fig. 6-1
14.5A
Intermittent current peak value for typ. 1s
Load impedance 50mOhm, see Fig. 6-2
Discharge current of output capacitors is not included.
Intermittent current average value (R.M.S.)
5.5A
Load impedance 50mOhm, see Fig. 6-2
2 850µF
Included inside the power supply
Max.
35V
Max.
Factory settings
Line regulation
Load regulation
Ripple and noise voltage
Output current
Typ.
Max.
Max.
Max.
Nom.
Nom.
Nom.
Nom.
Overload behaviour
Overload/ short-circuit current Max.
Typ.
Max.
Output capacitance
Back-feeding loads
The unit is resistant and does not show malfunctioning
when a load feeds back voltage to the power supply. It
does not matter whether the power supply is on or off.
The absorbing energy can be calculated according to
the built-in large sized output capacitor.
1) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2-5s. After this, the
output is switched off for approx. 7s before a new start attempt with duration of 1s is automatically performed. This cycle is repeated as
long as the overload exists. If the overload has been cleared, the device will operate normally.
Fig. 6-1 Output voltage vs. output current, typ.
Output voltage
Adjustment range
28V
24V
Normal
operation
A
A: continuous current
B: intermittent current
0A
2.5A
5.0A 7.5A
Normal
operation
Short -circuit
14.5A
13V
0V
Fig. 6-2 Short-circuit on output, intermittent current, typ.
Output
Current
First
pulse
B
10A 12.5A 15A
Output current
t
0
2-5s
7s
1s
7s
1s
7s
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
7/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
7. HOLD-UP TIME
The hold-up time is the time during which a power supply’s output voltage remains within specification following the
loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several
seconds. The green DC-ok lamp is also on during this time.
Hold-up Time
AC 100V
74ms
58ms
37ms
29ms
Typ.
Min.
Typ.
Min.
Fig. 7-1 Hold-up time vs. input voltage
AC 120V
74ms
58ms
37ms
29ms
80ms
70
60
50
40
30
20
10
0
At 24V, 5A, see Fig. 7-1
At 24V, 5A, see Fig. 7-1
At 24V, 10A, see Fig. 7-1
At 24V, 10A, see Fig. 7-1
Fig. 7-2 Shut-down behavior, definitions
a) 24V 5A typ. c) 24V 10A typ.
b) 24V 5A min. d) 24V 10A min.
Hold-up Time
a
b
c
d
Zero Transition
Input
Voltage
- 5%
Output
Voltage
Hold-up Time
Input Voltage
90
AC 230V
74ms
58ms
37ms
29ms
230Vac
120
8. DC-OK RELAY CONTACT
This feature monitors the output voltage on the output terminals of a running power supply.
Contact closes
Contact opens
Switching hysteresis
Contact ratings
Isolation voltage
As soon as the output voltage reaches 22V.
As soon as the output voltage falls below 22V.
Typically 0.3V
Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
Output Voltage
22V
open
closed
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
8/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
9. EFFICIENCY AND POWER LOSSES
Efficiency
Average efficiency*)
Typ.
Typ.
AC 100V
93.2%
92.7%
Power losses
Typ.
Typ.
Typ.
2.8W
9.6W
17.5W
*)
AC 120V
94.0%
93.1%
AC 230V
95.2%
93.9%
2.8W
8.5W
15.3W
2.6W
7.3W
12.1W
At 24V, 10A
25% at 2.5A, 25% at 5A,
25% at 7.5A. 25% at 10A
At 24V, 0A
At 24V, 5A
At 24V, 10A
The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 9-1 Efficiency vs. output current at 24V,
typ.
Fig. 9-2 Losses vs. output current at 24V, typ.
Efficiency
Power Losses
96%
95
(c)
94
(b)
(a)
93
(a) 100Vac
(b) 120Vac
(c) 230Vac
92
91
Output Current
90
2
3
4
5
6
7
8
9
24W
21
18
15
12
9
6
3
0
10A
(a) 100Vac
(b) 120Vac
(c) 230Vac
(a)
(b)
(c)
Output Current
0
1
2
3
4
5
6
7
8
9 10A
Fig. 9-3 Efficiency vs. input voltage at 24V,
10A, typ.
Fig. 9-4 Losses vs. input voltage at 24V, 10A,
typ.
Efficiency
Power Losses
96%
20W
95
18
94
16
93
14
92
12
91
Input Voltage
90
100 120
180
230
264Vac
10
Input Voltage
8
100 120
180
230
264Vac
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
9/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
10. FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram
L
N
Input Fuse
Input Filter
Input Rectifier
Inrush Current Limiter
PFC
Converter
Temperature
Shutdown
Power
Converter
Output
OverVoltage
Protection
Output
Filter
+
+
-
DC-ok
Relay
DC-ok
Contact
DC-ok
LED
Output
Voltage
Regulator
VOUT
11. FRONT SIDE AND USER ELEMENTS
Fig. 11-1 Front side
A
Input Terminals
N, L
Line input
PE (Protective Earth) input
B
Output Terminals
Two identical + poles and two identical - poles
+
Positive output
–
Negative (return) output
C
DC-OK LED (green)
On, when the output voltage is above 18V.
D Output Voltage Adjustment Potentiometer
E
DC-OK Relay Contact
The DC-OK relay contact is not synchronized with the DC-OK LED.
See chapter 8 for details.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
10/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
12. CONNECTION TERMINALS
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Type
Solid wire
Stranded wire
American Wire Gauge
Max. wire diameter (including ferrules)
Recommended tightening torque
Wire stripping length
Screwdriver
Input
Screw termination
Max. 6mm2
Max. 4mm2
AWG 20-10
2.8mm
Max. 1Nm, 9lb-in
7mm / 0.28inch
3.5mm slotted or crosshead No 2
Output
Screw termination
Max. 6mm2
Max. 4mm2
AWG 20-10
2.8mm
Max. 1Nm, 9lb-in
7mm / 0.28inch
3.5mm slotted or crosshead No 2
DC-OK-Signal
Push-in termination
Max. 1.5mm2
Max. 1.5mm2
AWG 24-16
1.6mm
7mm / 0.28inch
3mm slotted to open
the spring
13. LIFETIME EXPECTANCY
The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by
the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and
is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors
only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated
theoretical lifetime which can be used to compare devices.
Lifetime expectancy
AC 100V
47 000h
89 000h
133 000h
252 000h
AC 120V
55 000h
93 000h
156 000h
262 000h
AC 230V
74 000h
103 000h
209 000h
291 000h
At 24V, 10A and 40°C
At 24V, 5A and 40°C
At 24V, 10A and 25°C
At 24V, 5A and 25°C
14. MTBF
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h
means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be
determined if the failed unit has been running for 50 000h or only for 100h.
For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value.
MTBF SN 29500, IEC 61709
MTBF MIL HDBK 217F
AC 100V
655 000h
1 149 000h
323 000h
441 000h
72 000h
94 000h
AC 120V
736 000h
1 267 000h
345 000h
471 000h
78 000h
101 000h
AC 230V
822 000h
1 391 000h
374 000h
508 000h
85 000h
111 000h
At 24V, 10A and 40°C
At 24V, 10A and 25°C
At 24V, 10A and 40°C, Ground Benign GB40
At 24V, 10A and 25°C, Ground Benign GB25
At 24V, 10A and 40°C, Ground Fixed GF40
At 24V, 10A and 25°C, Ground Fixed GF25
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
11/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
15. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments.
The device complies with EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 and EN 61000-3-3.
The device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may
cause undesired operation.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the device is not
suited to supply a local DC power network in residential, commercial and light-industrial environments. No restrictions
apply for local DC power networks in industrial environments.
EMC Immunity
Electrostatic discharge
EN 61000-4-2
Electromagnetic RF field
Fast transients (Burst)
EN 61000-4-3
EN 61000-4-4
Surge voltage on input
EN 61000-4-5
Surge voltage on output
EN 61000-4-5
Surge voltage on DC-OK
Conducted disturbance
Mains voltage dips
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
Voltage interruptions
Powerful transients
EN 61000-4-11
VDE 0160
Contact discharge
Air discharge
80MHz-2.7GHz
Input lines
Output lines
DC-OK signal (coupling clamp)
LN
L  PE, N  PE
++ / -  PE
DC-OK signal  PE
0.15-80MHz
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0V
Over entire load range
8kV
8kV
10V/m
4kV
2kV
2kV
2kV
4kV
500V
1kV
1kV
10V
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
5000ms
750V, 0.3ms
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Performance criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission
input lines
Conducted emission
output lines
Radiated emission
Harmonic input current
Voltage fluctuations, flicker
EN 55011, EN 55032, FCC Part 15,
CISPR 11, CISPR 32
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Class B
Limits for DC power port acc.
EN 61000-6-3 not fulfilled
Class B
Fulfilled, Class A limits
Fulfilled, tested with constant
current loads, non pulsing
EN 55011, EN 55032
EN 61000-3-2
EN 61000-3-3
Switching frequencies:
PFC converter
Main converter
60kHz to 140kHz
65kHz to 150kHz
Input voltage and load dependent
Output voltage and load dependent
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
12/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
16. ENVIRONMENT
Operational temperature
Storage temperature
Output de-rating
Humidity
Atmospheric pressure
Altitude
Over-voltage category
Impulse withstand voltage
Degree of pollution
Vibration sinusoidal
Shock
Audible noise
Operational temperature is the same as the ambient
or surrounding temperature and is defined as the air
temperature 2cm below the unit.
-40°C to +85°C (-40°F to 185°F)
For storage and transportation
6W/°C
Between +55°C and +70°C (131°F to 140°F)
15W/1000m or 5°C/1000m
For altitudes >2000m (6560ft), see Fig. 16-2
The de-rating is not hardware controlled. The user has to take this into consideration to
stay below the de-rated current limits in order not to overload the unit.
5 to 95% r.h.
According to IEC 60068-2-30
110-54kPa
See Fig. 16-2 for details
Up to 5000m (16 400ft)
See Fig. 16-2 for details
II
According to IEC 60664-1, for altitudes up to 5000m
4kV (according to over-voltage
Input to PE
category III)
According to IEC 60664-1, for altitudes up to 2000m
2
According to IEC 60664-1, not conductive
2-17.8Hz: ±1.6mm;
According to IEC 60068-2-6
17.8-500Hz: 2g
2 hours / axis
30g 6ms, 20g 11ms
According to IEC 60068-2-27
3 bumps per direction, 18
bumps in total
Shock and vibration is tested in combination with DIN-Rails according to EN 60715 with a
height of 15mm and a thickness of 1.3mm and standard orientation.
Some audible noise may be emitted from the power supply during no load, overload or
short circuit.
-25°C to +70°C (-13°F to 158°F)
Fig. 16-1 Output current vs. ambient temp.
Allowed Output Current at 24V
Fig. 16-2 Output current vs. altitude
Allowed Output Current at 24V
10A
10.0A
9.4A
8.1A
A
B
6.25A
A... Tamb < 45°C
B... Tamb < 55°C
0
-25
0
+55 +70°C
Ambient Temperature
Altitude 0m
AP*) 110kPa
*) Atmospheric pressure
2000m
80kPa
4000m 5000m
62kPa 54kPa
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
13/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
17. SAFETY AND PROTECTION FEATURES
Isolation resistance
Output over-voltage protection
500mOhm
Min.
500mOhm
Min.
500mOhm
Min.
500mOhm
Typ.
Max.
30.5Vdc
32.0Vdc
In case of an internal defect, a redundant circuit limits the maximum output
voltage. The output shuts down and automatically attempts to restart.
I
According to IEC 61140
A PE (Protective Earth) connection is required
IP20
According to EN/IEC 60529
Output shut-down with automatic restart.
Included
Temperature sensors are installed on critical
components inside the unit and turn the unit off in
safety critical situations, which can happen e.g. when
ambient temperature is too high, ventilation is
obstructed or the de-rating requirements are not
followed. There is no correlation between the
operating temperature and turn-off temperature
since this is dependent on input voltage, load and
installation methods.
MOV (Metal Oxide
For protection values see chapter 15 (EMC).
Varistor)
Not user replaceable slow-blow high-braking
Included
capacity fuse
0.30mA / 0.79mA
At 100Vac, 50Hz, TN-,TT-mains / IT-mains
0.42mA / 1.1mA
At 120Vac, 60Hz, TN-,TT-mains / IT-mains
0.67mA / 1.7mA
At 230Vac, 50Hz, TN-,TT-mains / IT-mains
0.37mA / 0.94mA
At 110Vac, 50Hz, TN-,TT-mains / IT-mains
0.54mA / 1.33mA
At 132Vac, 60Hz, TN-,TT-mains / IT-mains
0.88mA / 2.18mA
At 264Vac, 50Hz, TN-,TT-mains / IT-mains
Class of protection
Ingress protection
Over-temperature protection
Input transient protection
Internal input fuse
Touch current (leakage current)
At delivered condition between input and output,
measured with 500Vdc
At delivered condition between input and PE,
measured with 500Vdc
At delivered condition between output and PE,
measured with 500Vdc
At delivered condition between output and DC-OK
contacts, measured with 500Vdc
Min.
Typ.
Typ.
Typ.
Max.
Max.
Max.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
14/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
18. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground.
The output is insulated to the input by a double or reinforced insulation.
Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all inputterminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings
to the value in the table below.
We recommend that either the + pole or the – pole shall be connected to the protective earth system. This helps to
avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur.
Type test
60s
A
2500Vac
Routine test
5s
2500Vac
2500Vac
500Vac
500Vac
Field test
5s
Field test cut-off
current settings
2000Vac
> 15mA
2000Vac
> 15mA
500Vac
> 20mA
500Vac
> 1mA
Fig. 18-1 Dielectric strength
Input
DC-ok
*)
B
L
N
B
A
D
Output
Earth, PE
C
+
-
B
3000Vac
C
500Vac
D
500Vac
B*)
When testing input to DC-OK ensure that the maximal voltage between DC-OK and
the output is not exceeded (column D). We recommend connecting DC-OK pins and
the output pins together when performing the test.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
15/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
19. APPROVALS AND FULFILLED STANDARDS
UL Certificate
Listed equipment for category NMTR - UL 61010-2-201 Electrical
Equipment for Measurement, Control and Laboratory Use Particular requirements for control equipment
Applicable for US and Canada
E-File: E198865
CB Scheme Certificate
IEC 61010-2-201 Electrical Equipment for Measurement, Control
and Laboratory Use - Particular requirements for control
equipment
CB Scheme Certificate
IEC 62368-1 Audio/video, information and communication
technology equipment - Safety requirements
Output safety level: ES1
Manufacturer's Declaration (Online Document)
Airborne Contaminants Corrosion Test
Severity Level: G3 Harsh
H2S: 100ppb
NOx: 1250ppb
Cl2: 20ppb
SO2: 300ppb
Test Duration: 3 weeks, which simulates a service life of at least 10
years
Paint Wetting Impairment Substances Test (or LABS-Test)
Tested for Zone 2 and test class C1 according to VDMA 24364-C1L/W for solvents and water-based paints
UL 61010
IEC 61010
IEC 62368
ISA-71.04-1985
VDMA 24364
20. REGULATORY COMPLIANCE
EU Declaration of
Conformity
REACH Directive
WEEE Directive
RoHS (China RoHS 2)
EAC TR Registration
The CE mark indicates conformance with the
- EMC directive
- Low-voltage directive
- RoHS directive
Manufacturer's Statement
EU-Directive regarding the Registration, Evaluation,
Authorization and Restriction of Chemicals
Manufacturer's Statement
EU-Regulation on Waste Electrical and Electronic Equipment
Registered in Germany as business to business (B2B) products.
Manufacturer's Statement
Administrative Measures for the Restriction of the Use of
Hazardous Substances in Electrical and Electronic Products
25 years
EAC Certificate
EAC EurAsian Conformity - Registration Russia, Kazakhstan
and Belarus
8504408200, 8504409000
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
16/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
21. PHYSICAL DIMENSIONS AND WEIGHT
Width
Height
Depth
Weight
DIN-Rail
Plastic Material of Housing
Installation Clearances
Penetration protection
49mm
1.93’’
124mm 4.88’’
124mm 4.88’’
The DIN-rail height must be added to the unit depth to calculate the total required
installation depth.
540g / 1.2lb
Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
Flame retardant Polycarbonate (PC) - UL94-V0
Vicat softening temperature specified with 149°C according to ASTM D1525
See chapter 2
Small parts like screws, nuts, etc. with a diameter larger than 4mm
Fig. 21-1 Front view
Fig. 21-2 Side view
All dimensions in mm
All dimensions in mm
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
17/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
22. ACCESSORY
22.1. PIRD20.241 REDUNDANCY MODULE
The PIRD20.241 is a dual redundancy module, which can be used to build 1+1 or N+1 redundant
systems.
The device is equipped with two 10A nominal input channels, which are individually decoupled by
utilizing diode technology. The output can be loaded with a nominal 20A continuous current.
The device does not require an additional auxiliary voltage and is self-powered even in case of a
short circuit across the output.
The unit is very narrow and only requires 39mm width on the DIN-rail.
See chapter 23.4 for wiring information.
22.2. UF20.241 BUFFER MODULE
The UF20.241 buffer module is a supplementary device for DC 24V power supplies. It delivers
power to bridge typical mains failures or extends the hold-up time after the AC power is turned
off.
When the power supply provides a sufficient voltage, the buffer module stores energy in the
integrated electrolytic capacitors. When the mains voltage is lost, the stored energy is released to
the DC-bus in a regulated process.
The buffer module can be added in parallel to the load circuit at any given point and does not
require any control wiring.
One buffer module can deliver 20A additional current and can be added in parallel to increase
the output ampacity or the hold-up time.
For longer hold-up times the UF40.241 might also be an option.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
18/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
23. APPLICATION NOTES
23.1. CHARGING OF BATTERIES
Do not use the power supply to charge batteries.
23.2. SERIES OPERATION
Unit A
AC
Devices of the same type can be connected in series for higher output
voltages. It is possible to connect as many units in series as needed, providing
the sum of the output voltage does not exceed 150Vdc. Voltages with a
potential above 60Vdc must be installed with a protection against touching.
Avoid return voltage (e.g. from a decelerating motor or battery) which is
applied to the output terminals.
DC
+
Unit B
AC
Keep an installation clearance of 15mm (left / right) between two power
supplies and avoid installing the power supplies on top of each other. Do
not use power supplies in series in mounting orientations other than the
standard mounting orientation.
+
-
DC
Load
+
-
Earth
(see notes)
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices.
23.3. PARALLEL USE TO INCREASE OUTPUT POWER
Do not use the power supply in parallel to increase the output power.
23.4. PARALLEL USE FOR 1+1 REDUNDANCY
The device can be used to built 1+1 redundant systems.
1+1 Redundancy:
Devices can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain
amount of extra power to support the load in case one device fails. The simplest way is to put two devices in parallel.
This is called a 1+1 redundancy. In case one device fails, the other one is automatically able to support the load current
without any interruption. It is essential to use a redundancy module to decouple devices from each other. This
prevents that the defective unit becomes a load for the other device and the output voltage cannot be maintained any
more.
1+1 redundancy allows ambient temperatures up to +70°C.
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices.
Recommendations for building redundant power systems:
-
Use separate input fuses for each device.
Use separate mains systems for each device whenever it is possible.
Monitor the individual devices. Therefore, use the DC-OK signal of the device.
It is desirable to set the output voltages of all devices to the same value (± 100mV) or leave it at the factory setting.
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
19/20
PIC240.241D
24V, 10A, 240W, SINGLE PHASE INPUT
PIANO-Series
Wiring examples:
Fig. 23-1 1+1 Redundant wiring with a PIRD20.241 redundancy module
Failure
Monitor
+ +
- -
+ +
Output
24V 10A
DCOK
o
o
PIC240.241D
Power Supply
I
- -
- -
Output
24V 10A
Input Input
2
1
o
o
DCOK
+ +
PIC240.241D
Power Supply
PIRD20.241
Redundancy
Module
Output
Input
Input
L N PE
L N PE
-
+ +
10A
Load
I
L
N
PE
23.5. OPERATION ON TWO PHASES
The power supply can also be used on two-phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying
voltage is below 240V+10%.
240V +10% max.
Ensure that the wire, which is connected to the N-terminal, is
appropriately fused.
Power Supply
L1
L3
The maximum allowed voltage between a Phase and the PE must be
below 300Vac.
L2
AC
L
N
PE
DC
23.6. USE IN A TIGHTLY SEALED ENCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of
1cm.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
Enclosure size
Input voltage
Load
Temperature inside the box
Temperature outside the box
Temperature rise
Case A
180x180x165mm
Rittal Typ IP66 Box
PK 9519 100, plastic
230Vac
24V, 8A; (=80%)
39.8°C
21.0°C
18.8K
Case B
180x180x165mm
Rittal Typ IP66 Box
PK 9519 100, plastic
230Vac
24V, 10A; (=100%)
44.7°C
21.0°C
23.7K
Mar. 2021 / Rev. 2.0 DS-PIC240.241D-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
20/20