WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter and apply this product.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
For a minimum size dialog
application, refer to
Chapters A and B.
User manual
December
2003
Software
XBT-L1000 ver 4.30
Magelis range
Alphanumeric and matrix
XBT-H/P/E/HM/PM
General Contents
If you are not familiar with man/machine dialog using a Magelis terminal
If you are an XBT expert and you want to learn about the Magelis functions
If you are a PLC programmer and you want to become acquainted with PLC/
Magelis dialog
If you want information about your
Magelis terminal
If you want to set up a Magelis application as an example
XBT technical sheets
Glossary
Error messages
If you want to find a specific piece of information
Introduction
Magelis functions
PLC and Terminal communications Dialog
Operating the terminal
C
D
Application development example
E
Appendices
F
Index
A
B
I
Starting up
M
Magelis
Magelis
Magelis
Chapter A
Introduction
A
A - 1
A - 2 Magelis
Contents
Contents
This chapter includes the following topics :
1. Man/machine dialog with Magelis _____________________________________ 5
Production monitoring _____________________________________________ 6
Preventive maintenance ___________________________________________ 6
Corrective maintenance ____________________________________________ 6
Process control __________________________________________________ 6
2. Structure of Magelis applications ______________________________________ 7
Terminals with 2 or 4 lines (H, P, E) __________________________________ 8
Matrix screen terminals (HM, PM) ___________________________________ 11
3. Application pages ________________________________________________ 14
4. Alarm pages ____________________________________________________ 16
5. Form pages _____________________________________________________ 17
6. Terminal operating modes __________________________________________ 18
7. Controlling the control system _______________________________________ 19
Momentary contact command ______________________________________ 19
Push-on/push-off toggle command __________________________________ 20
8. Dialog between the PLC and the terminal ______________________________ 20
Data associated with the fields _____________________________________ 21
Principle of terminal "command and status" exchanges __________________ 21
9. Control system production file _______________________________________ 22
10. General specifications ____________________________________________ 23
A
Magelis A - 3
Contents
A - 4 Magelis
1. Man/machine dialog with Magelis
A
1. Man/machine dialog with Magelis
The main functions of Magelis terminals are to :
Display data from the control system,
Modify the control system parameters,
Control the process using discrete commands.
Display data from the control system
Signal control system faults
Programming the terminal with
XBT-L1OOO
Indicator lamps
- communication status
- Key strokes enabled
- Control the control system
- Change the page
R1
R3
F1
F3
F5
F2
F4
F6
Modify the control system parameters
Record and time-stamp the occurrence of control system alarm
R2
R4
F7 F8
F9 F10
F11 F12
- Control the control system
- Change the page
(Only XBT-
PM)
- Print fault log
- Print production data
Communicate with the control system :
Telemecanique, April,
Modicon, Siemens, etc,
PLCs.
A
Magelis A - 5
1. Man/machine dialog with Magelis
PRINT The applications associated with Magelis can be :
Production monitoring
Display process status messages :
Automatic operation
Start hydraulic unit
End of lift of manipulator
Rotation of grip to right
Preventive maintenance
Counting parts for production monitoring :
Type 1 housing : 7555
Base unit : 1200
Counting with indication if threshold exceeded :
Number of drillings 3137
Change tool at 4000
Corrective maintenance
Indication of process faults :
Oil level too low
Door open
Process control
Process control via configurable function keys :
Pressurizing P
Start Cycle SC
P
SC
Modification of the process parameters :
Level 1: 556
Limit n12 : 725
Part of the page displayed on the terminal by scrolling; 2 lines or 4 lines depending on the terminal.
A - 6 Magelis
2. Structure of Magelis applications
2. Structure of Magelis applications
A Magelis application is the entire dialog between the user and the automated process. This consists of :
- criteria linked to the control system :
- production monitoring,
- preventive maintenance,
- corrective maintenance,
- process control.
- criteria concerning the user :
- user interface,
- level of involvement.
- criteria concerning setting up the dialog application itself
- programming,
- debugging,
- updating.
These characteristics mean that your application must be structured.
An application will consist of a series of pages, which can form a tree structure, as in the diagram below :
A
Ex.
PRODUCTION
DISPLAY ->
<ASSEMBLY
<PAINTING
MAINTENANCE ->
ASSEMBLY
<- PRODUCTS 1 :130
PRODUCTS 2 :100
PREPARATION
PAINTING
BLUE 10
GREEN 50
YELLOW 40
PRODUCT 1
VERSION 1
VERSION 2
VERSION 3
Pages
DISPLAY
PARTS X 150
PARTS Y 120
REJECTS 12
MAINTENANCE
TOOLS 12 : 130
CHANGE TOOL at 200
Magelis
Part of the page displayed on the terminal by scrolling; 2 lines or 4 lines depending on the terminal.
A - 7
2. Structure of Magelis applications
Terminals with 2 or 4 lines (H, P, E)
Page
- A page can contain a maximum of 25 lines .
- The length of the lines on each page depends on the capacity of the
MAGELIS terminal. The number of lines on each page, displayed during operation, depends on the capacity of the Magelis terminal :
- 2*20 characters
- 2*40 characters
- 4*40 characters
- A page is displayed as follows :
CHANGE TOOLS
PIN1-25
PIN2-736
PIN3-947
PIN4-125
PIN7-222
PIN8-456
Lines on the page displayed on the display unit, 2 or 4 lines depending on the terminal.
Lines on the page displayed on the display unit, 2 or 4 lines depending on the terminal.
- A page is identified by a number and a name (optional).
The page can then be displayed on the terminal by commands from the terminal or the PLC.
- Access to pages can be protected by a password.
-
See chapter F, § 1. XBT technical sheets, Page 5
, for informations of the technical characteristics of the various Magelis terminals.
- The PC software, XBT- L1000, is used to create dialog pages.
- Two types of page can be used :
application pages
alarm pages
+1
-
1
A - 8 Magelis
2. Structure of Magelis applications
Line
Each line consists of alphanumeric text and can include :
variable fields, that is zones for :
- either the display of values reflecting the status of the control system : status of a bit, of a single or double word, of a floating point word, or an ASCII string.
- or the entry of parameters for operating the control system :
- modification of bits, single or double words, floating point words, or an ASCII string.
A line can contain several fields.
The display format can be binary, decimal, hexadecimal, floating point or alphanumeric.
A
links enabling access to other dialog pages via the keys (depending on the type of terminal)
Ex.
Dialog lines to indicate a repair procedure :
REPAIR
LOCK THE AXIS AT ZERO POSITION
CHANGE TO MANUAL
CHANGE THE PART
Dialog lines with variable fields :
LEVEL 1 556
LIMIT 12 725
Magelis A - 9
2. Structure of Magelis applications
Ex.
Links
PRODUCTION
<ASSEMBLY ->
<PAINTING
MAINTENANCE ->
Fields
ASSEMBLY
<- PRODUCTS 1 :130
PRODUCTS 2 :100
PREPARATION
PAINTING
BLUE 10
GREEN 50
YELLOW 40
INDIGO 40
PRODUCT 1
VERSION 1
VERSION 2
VERSION 3
Links
Fields
DISPLAY
PARTS X 150
PARTS Y 120
REJECTS 12
MAINTENANCE
STATUS
TOOLS 12 : 130
CHANGE TOOL at 200
Ex.
A - 10
You can manage your own man/machine dialog application with the page numbers alone and with no links.
Page n
Page n
° 1
° 2
PRODUCTION
ASSEMBLY
PAINTING
MAINTENANCE
ASSEMBLY
PRODUCTS 1 :130
PRODUCTS 2 :100
Page n ° 3
PREPARATION
PAINTING
BLUE 10
GREEN 50
YELLOW 40
INDIGO 55
Magelis
2. Structure of Magelis applications
Matrix screen terminals (HM, PM)
Page
The display equipping the XBT-HM or XBT-PM terminals is an LCD mono-chrome screen with a display capacity of 8 x 40 characters.
With double height, double width and double size character facility, the respective capacities are :
- 8 x 40 characters
- 4 x 40 characters
- 8 x 20 characters
- 4 x 20 characters
A
Magelis
Each page can include the following features :
a background image with the same size as the screen and associated to each application page.
For the XBT-PM, this background picture can also integrate the dynamic function keys "labels".
alphanumeric text with the following properties and sizes :
- Single size
- Double width
- Double height
- Double size
It is possible to have different size characters on the same line of text.
A - 11
2. Structure of Magelis applications
A - 12
variable fields used :
- either to display values reflecting the status of the control system: status of a bit, of a single or double word, of a floating point word, or an ASCII string.
- or to enter parameters for operating the control system : modification of bits, single or double words, floating point words, or an ASCII string.
The display format can be binary, decimal, hexadecimal, floating point or alphanumeric.
links giving the operator the possibility of directly displaying other pages using the arrow keys (direct link ; only for XBT-HM).
For more informations about
(
arrows utilization, arrow only on XBT-HM)
dynamic graphic objects of the "indicator" type enabling graphic representation of the control system data.
Bar graph object
Used to provide a graphic representation of the control system data (e.g.
level in a tank).
Parameters to be defined
Reference of the variable associated with the object.
Format: 16 bit signed or unsigned word.
Type of bar graph:
- Vertical (single size or double size)
- Horizontal (single size or double size)
Min/max limit exceeded, indicated by flashing display.
The min/max values are those seen by the operator, in other words after conversion.
Conversion factor
For further information, refer to the XBT L1000 software on-line help.
Magelis
2. Structure of Magelis applications
Meter object
Used to provide a graphic representation of the control system data (e.g.
supply voltage monitoring)
Parameters to be defined
Reference of the variable associated with the object.
Format: 16 bit signed or unsigned word.
Minimum, maximum limits.
Min/max limit exceeded, indicated by flashing display.
For further information, refer to the XBT L1000 software on-line help.
A
Magelis
- A page is identified by a number, a name (optional),
- The pages are called up by pressing the function keys (static and dynamic function keys for the XBT-PM), by the PLC,
- The keys or the arrow keys are used to navigate within a page,
- The pages are defined using the XBT-L1000 programming software, and saved in the terminal.
A - 13
3. Application pages
3. Application pages
Application pages are for :
- Monitoring the control system.
- Performing operations on the control system.
- Maintaining the control system.
Application pages can be displayed (depending on the type of terminal) either :
- initiated by the control system (1),
- by configurable static (2) or dynamic (5) function keys,
- from a menu (3),
- from their name or number (4).
Maintenance ->
(3) (2) (5)
(XBT-PM)
Number of drillings : 3137
Change tool at 4000
Page 12
(4) (1)
Application pages form the basic architecture of the dialog.
Structuring the series of pages
It is advisable to organize the application pages into a menu format to reflect the stages in the machine cycle .
On every line of an application page, it is possible to create a link towards the right (->) and a link towards the left(<-). Each link gives access to another application page via the arrow keys.
A - 14 Magelis
3. Application pages
Ex.
MENU
ASSEMBLY LINE
PRODUCTION
MONITORING ->
REPAIR ASSISTANCE
<- MECH ELEC ->
PART OK 1524
SCRAP 27
TIME MONITORING ->
GRIP Nos 1
GRIP Nos 2
DOWNSTREAM TRANSFER
UPSTREAM TRANSFER
MOTOR SUPPLIES ->
MEAS. SUPPLIES ->
Ex.
The indicator lamps for the and keys, managed by the terminal, show the operator whether a page can be displayed by pressing the corresponding key.
An active line (line on which the cursor is located) signals the access to another page by displaying the -> and/or <- characters in reverse video.
Active lines
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
->
->
->
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
->
->
->
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
->
->
->
A
Magelis A - 15
4. Alarm pages
4. Alarm pages
An alarm page has the same characteristics as an application page with regard to :
- the text,
- the fields.
The additional feature of an alarm page is its event-triggered display. The control system's word bit is assigned to each alarm page. If the word bit is at state 1, the page is displayed.
Ex.
A sensor fault occurs. The bit associated with the sensor fault changes to 1 in the control system.
Sensor fault
ATTENTION PRESSURE SENSOR FAULT
CHANGE TO MANUAL
Entry in a variable field is not possible on an alarm page.
On the XBT-HM and XBT-PM, the background picture and the first line are flashing during alarm.
On the XBT-PM, the dynamic function keys can’t be used in an alarm page.
A - 16 Magelis
5. Form pages
Advantages of alarm pages
- Display of an alarm page takes priority over an application page.
- It is possible to assign priority to an alarm page (0 to 16).
- It is possible to record (log) alarm pages to help with trouble shooting in the control system.
- The alarms are time-stamped.
- It is possible to force the operator to acknowledge alarms before continuing process operation ; this is useful when an alarm is transient.
- Magelis XBT-E terminals have a relay output whose contact is closed when an alarm page appears. This function can be configured by the user for each alarm page.
- It is possible to continious print alarms for products with output printer.
A
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The XBT does not support any type of processor nor machine control in association with alarms. It is designer's responsibility to consider programming PLC logic to account for programmed alarms.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
5. Form pages
Magelis
The form pages are used for printing only.
They are used for creating measurement and production follow-up reports, labels, etc.
A form page can include:
- texts,
- alphanumeric variables,
A - 17
6. Terminal operating modes
- frames for designing tables,
- control codes specific to the printer used
For more informations,
see chapter B, § 13. Forms, Page 49 .
6. Terminal operating modes
Magelis terminals have 3 operating modes :
Recording mode enabling Magelis terminal and XBT-L1000 exchanges.
Running mode enabling the terminal connected to the control system in order to control it.
Confidential mode (except XBT-H and XBT-HM) enabling, in addition to the functions of running mode, access by password to privileged functions (log, recipe, etc).
A - 18 Magelis
7. Controlling the control system
Recording Mode
Magelis/XBT-L1000 Exchanges
R1
R3
F1
F3
F5
F2
F4
F6
R2
R4
F7 F8
F9 F10
F11 F12
Running Mode
Dialog with the control system
Password
7. Controlling the control system
Confidential Mode
Dialog with the control system, log, recipe, etc.
Magelis terminals allow the control system to be commanded by function keys. Two types of command are possible :
Momentary contact command
By pressing a function key (static or dynamic function keys for XBT-PM), the control system's bit is activated ; the action stops when the key is released.
A
Magelis A - 19
8. Dialog between the PLC and the terminal
Ex.
Controlling a motor xxxxxxx
Push-on/push-off toggle command
Ex.
The control system is activated by pressing the function key (static or dynamic function keys for XBT-PM). The action is halted by pressing the function key again.
Command to advance a conveyor belt.
TROLLEY
FORWARD
XBT-L1000 software can be used to assign the desired command to each function key.
8. Dialog between the PLC and the terminal
The man/machine dialog between the Magelis terminal and the PLC consists of an exchange of data between the two devices. Different types
A - 20 Magelis
8. Dialog between the PLC and the terminal of data can be exchanged.
Data associated with fields
PLC
Command data from the PLC
to the terminal
MAGELIS
TERMINAL
A
Status data fron the terminal to the PLC
Data associated with the fields
The principle of the data exchanges associated with the fields depends on the protocol chosen which in turn depends on the type of PLC.
Whether the terminal is master or client of the dialog, it takes charge of the exchanges :
- updating the fields (reading the values in the PLC)
- entry and modification of fields (writing the values to the PLC)
No PLC communication program needs to be written.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
If communications between XBT and PLC are lost, operator's control over machine may be lost completely or partially. It is designer's responsibility to consider programming PLC logic to account for this situation. One of the good ways to do that is to monitor "Communication control word" of the dialog table from the PLC program.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Principle of terminal "command and status" exchanges
To simplify the dialog the data are grouped together in a table : the dialog table located in the PLC.
Magelis A - 21
9. Control system production file
- Commands from the PLC and to the terminal
- Status data from the terminal and to the PLC
Consisting of n consecutive words (words of 16 bits), this table has two parts.
Status table
Status data from the terminal to the PLC.
Command table
Commands from the PLC
to the terminal
The number of words in the table depends on the choice of status data and the commands the user wishes to process via the dialog. The XBT-
L1000 software is used to make this choice.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
PLC memory zone allocated for the XBT dialog table must NOT be used for anything else. It is designer's responsibility to program PLC logic properly.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
9. Control system production file
Some Magelis terminals enable a "production file" to be printed based on the data from :
- application pages,
- alarm pages (log).
A - 22 Magelis
10. General specifications
Ex.
The application and alarm pages are printed and time-stamped, and the contents of the fields indicated.
The alarm log pages are printed and the occurrence of faults is timestamped, but there is no indication of the content of the fields
The print command can be initiated by :
- pressing the PRINT button on the terminal,
- the PLC.
A
Production data printed each evening.
Print command
R1
R3
F1
F3
F2
F5
F4
F6
R2
R4
F7 F8
F9 F10
F11 F12
10. General specifications
This section gives the general characteristics of Magelis terminals. For
informations of characteristics of each terminal, see chapter F, § 1. XBT technical sheets, Page 5 .
Magelis A - 23
10. General specifications
Power supply
Memories
Communication protocols
Number of application pages
(*1)
Number of alarm pages (*1)
Display
Keypad
Signalling
Real-time clock, relay, buzzer
Temperature
24V DC
Voltage limits : 18 to 30 V DC
Ripple : 5 % maximum
XBT-H811050 is supplied by TSX07
( use XBT-Z968 - 03 cable).
Application : FLASH EEPROM
Fault log : battery backed RAM
Multi-protocol, protocol can be downloaded by diskette using XBT-L1000 software
For 2 lines per page and 2 variables per page:
XBT-H8: 100
XBT-H : 200 XBT-HM:300
XBT-P : 400 XBT-PM:400
XBT-E : 800
256 (for 2 lines per page)
XBT-H8: 128 pages
XBT-HM XBT-PM
- LCD or fluorescent
- 2 to 4 lines, 20 to 40 characters per line
- Matrix LCD monochrome
Customizable membrane keypad
1 communication status indicator lamp
1 indicator lamp per function key, the display of which is controlled by the PLC program
1 indicator lamp per service key : this indicator lamp is lit up if the key is accessible
1 keypad use indicator lamp
XBT-H8: no indicator lamp.
XBT-E
Operation : 0 to 50 ° C (32,0 to 122,0 ° F)
Storage :
- 40 ° +70 ° C (-40 ° +158 ° F) for a fluorescent display
- 20 ° + 60 ° C (-4 ° +140 ° F) for an LCD display
A - 24 Magelis
10. General specifications
Magelis - PC link with XBT-L1000
XBT
RS232
Magelis - PLC/control system link
XBT
RS232/RS485
XBT
RS232/RS485
RS422
Control system
A
RS485
XBT XBT
Magelis - printer link
XBT Other equipment
XBT
RS232
Magelis
(*1) The XBT-L1000 software shows, as a percentage, when the application is created, the level of occupation of the application depending on the type of terminal. For more information on the number of pages,
see chapter F, § 1. XBT technical sheets, Page 5
.
A - 25
10. General specifications
A - 26 Magelis
Magelis
Chapter B
Magelis functions
B
B - 1
B - 2 Magelis
Contents
Contents
This chapter includes the following topics :
1. Organization of Magelis functions _____________________________________ 5
2. Starting up the Magelis terminal ______________________________________ 6
3. Operating principle ________________________________________________ 7
Basic principle ___________________________________________________ 7
Recording mode _________________________________________________ 9
Running mode __________________________________________________ 10
Configuration for operation ________________________________________ 12
4. Page display ____________________________________________________ 14
Display when powered up _________________________________________ 14
Displaying a page via a function key _________________________________ 14
Page display initiated by the PLC ___________________________________ 15
5. Entry and modification of variables ___________________________________ 16
Entry request ___________________________________________________ 16
Entry principle __________________________________________________ 16
6. Alarms _________________________________________________________ 18
Structure of alarm pages __________________________________________ 18
Alarm page parameters ___________________________________________ 20
Display priority __________________________________________________ 22
Acknowledgement of alarms _______________________________________ 24
Control of alarm relay : XBT-E ______________________________________ 25
Alarm display ___________________________________________________ 26
7. Alarm log _______________________________________________________ 28
Principles ______________________________________________________ 28
Log display _____________________________________________________ 30
Clear log ______________________________________________________ 32
Print log _______________________________________________________ 33
8. Process control via function keys ____________________________________ 35
9. Locking function keys via the PLC ___________________________________ 37
10. Printing _______________________________________________________ 39
General _______________________________________________________ 39
Stop printing ____________________________________________________ 41
Continous printing of an alarm page _________________________________ 41
Display Hard Copy _______________________________________________ 42
B
Magelis B - 3
Contents
Log printing ____________________________________________________ 42
Form printing ___________________________________________________ 42
Free format printing ______________________________________________ 42
11. Configuration ___________________________________________________ 43
12. Product selftest _________________________________________________ 47
13. Forms ________________________________________________________ 49
Purposes ______________________________________________________ 49
Definition ______________________________________________________ 49
Utilization ______________________________________________________ 51
B - 4 Magelis
1. Organization of Magelis functions
B
1. Organization of Magelis functions
Magelis terminals (or XBTs) offer a number of functions.
The flow charts below show the links between these functions. The table at the bottom of each page shows whether your terminal has access to the function.
Switch the terminal on
Transfer the XBT-L1000 application to the terminal : Recording mode
Move to Running mode
(change cable)
B
Display of application pages
Display pages
Entry modification of process parameters
Entry / modification
Error process
Processing alarm pages
Alarms command
Password
Printing the application page
Change to confidential mode
Confidential mode
Access to protected pages, configuration, configuration of languages, adjust time of XBTs real-time clock, Selftest
Magelis B - 5
2. Starting up the Magelis terminal
2. Starting up the Magelis terminal
Please refer to the service instructions.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Connect the serial link and printer link to the XBT with the power OFF.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
B - 6 Magelis
3. Operating principle
3. Operating principle
Basic principle
1 - MAGELIS terminals have 3 operating modes :
Recording mode enables XBT-L1000 <-> MAGELIS exchanges.
XBT
B
- Running mode enables, when connected with the process, the control system to be controlled.
XBT
Confidential mode enables, in addition to the functions of the running mode, access by password to privileged functions (log, etc).
Operating mode
PASSWORD
Magelis
Confidential mode
XBT-H, XBT-HM
No confidential mode
XBT-P
Magelis
XBT-PM XBT-E
B - 7
3. Operating principle
2 - When the terminal is powered up the operating mode is selected automatically, according to the connection of the XBT :
- if the XBT is connected to the PC with XBT-L1000 software : save mode.
- if the XBT is connected to the control system : running mode (with the possibility of changing to confidential mode).
Magelis XBT-H, XBT-HM
No confidential mode
XBT-P XBT-PM XBT-E
B - 8 Magelis
3. Operating principle
Recording mode
Exchanges between the MAGELIS terminal and XBT-L1000
2 types of exchange are possible :
Loading the man/machine dialog application and the control system link protocol into the terminal.
XBT
RS232C / RS485 serial link
B
PC with XBT-L1000
Transfer into XBT-L1000 of an application in the MAGELIS terminal.
The SYST indicator lamp blinks during the transfer * .
Communication indicator lamp *
- indicator lamp on : no cable or incorrect wiring,
- indicator lamp off : correct cable, no exchange with the PC:XBT-L1000
- indicator lamp blinking : exchanges with the PC:XBT-L1000.
Procedure with XBT-L1000
Select the Transfer/Export menu.
PC<-> Magelis terminal cables. Connection port to the PC
9-pin male serial port : XBT-Z915.
25-pin female serial port : XBT-Z905.
9-pin female serial port : XBT-Z9152.
Magelis XBT-H, XBT-HM
* No indicator lamp on
XBT-H811050
XBT-P XBT-PM XBT-E
Magelis B - 9
3. Operating principle
WIRING :
XBT-Z915
PC
Running mode
The running mode is used to control the control system :
- Page display.
- Entry/modification of process parameter values.
- Process control (discrete).
- Printing.
- Viewing and acknowledgement of an alarm.
If the terminal has a MENU key, you can access the following additional functions :
- display of application pages (indirectly),
- consult the alarm log,
- access to the terminal configuration (printer link, real-time clock, link with the control system, languages)
- access to the product references,
- access to the terminal selftest functions (keyboard, display…)
Magelis XBT-H, XBT-HM
No function menu
XBT-P XBT-PM XBT-E
B - 10 Magelis
3. Operating principle
Ex.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Pressing the MENU key allows the inexperienced or untrained operator to accidentally display the wrong page, modify the terminal configuration or lose the messages and alarms on the screen. This can lead to confusion, panicking, and, as a consequence, to loss of control over the machine. It is strongly recommended that the PLC be programmed to lock the MENU key as well as the other currently unused keys in order to prevent this from happening.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
B
Example : Display of an application page
Solution 1 : once the Menu screen is displayed, press the and the 4 arrow key indicator lamps blink.
PAGE NUMBER _ _ ->
LIST OF PAGES ->
ALARM LOG ->
CONFIGURATIONS ->
Enter the page number and press ENTER (see
§ 5)
key
Solution 2
Magelis
LIST OF PAGES
00001 :
00002 :
00003 :
...
In this mode the SYS indicator lamp is off.
XBT-H, XBT-HM XBT-P
Select the required page access the page.
XBT-PM XBT-E
Magelis B - 11
3. Operating principle
Configuration for operation
Operation via the terminal port RS485 type of a PLC
- Terminals concerned: XBT-H / XBT-HM / XBT-P / XBT-PM / XBT-E with UNITELWAY protocol.
- PLC : TELEMECANIQUE PLC with an RS485 type terminal port interface (type TSX07, TSX17 etc.).
- Type of link : RS485 point-to-point.
- Protocol :UNITELWAY
RS485
XBT Control system
Operation with point-to-point direct link to the control system
- In this case the control system designates a system other than a PLC.
- Terminals concerned: all, except terminals using UNITELWAY protocol * .
- Type of link :
- RS422 or RS485.
- RS232.
- Protocol: control system function.
XBT
RS422/RS485
RS232
Control system
Magelis XBT-H, XBT-HM
* XBT-H811050
UNITELWAY protocol only
XBT-P XBT-PM XBT-E
B - 12 Magelis
3. Operating principle
Operation on a PLC communication network
- Terminals concerned: XBTH / XBTP / XBTE with UNITELWAY protocol.
- PLC : TELEMECANIQUE PLC with an RS485 type terminal port interface (type TSX07, TSX17 etc.).
- Type of link : RS485 point-to-point.
- Protocol :UNITELWAY
B
RS485
XBT XBT XBT Other equipment
Communication indicator lamp *
- indicator lamp on : no cable or incorrect wiring,
- indicator lamp off : correct cable, no exchange with the PLC
- indicator lamp blinking : exchanges with the PLC.
Magelis XBT-H, XBT-HM
* No indicator lamp on
XBT-H811050
Magelis
XBT-P XBT-PM XBT-E
B - 13
4. Page display
4. Page display
Display when powered up
Design using XBT L1000:
The procedure for displaying a default page is as follows:
- Select the Configuration/Terminal Parameters menu.
- Select the default page to be displayed.
Displaying a page via a function key
It is possible to display a page directly by pressing a function key. (Static or dynamic for XBT-PM).
Example :
Ex.
TEMP Temperature
Magelis
Procedure for assigning a function key to a page with XBT-
L1000
- Select the Configuration / Function keys menu.
- Select the group of keys, then the required function key. Confirm with
OK.
- Select the type of action : direct access.
- If necessary, associate a label in the case of dynamic function keys
(XBT-PM).
- Select the page
- Confirm with OK.
For XBT-PM, it is possible to choose between static and dynamic function keys by the Configuration menu.
XBT-P XBT-PM XBT-E XBT-H, XBT-HM
Except for XBT-
H011010
XBT-H012010, XBT-
H811050
B - 14 Magelis
4. Page display
Page display initiated by the PLC
The dialog table (
See chapter C, § 4. Principle of the dialog table,
Page 9 ) is used for dialog between the PLC and the terminal. In this table
a word is reserved into which the program writes the number of the page to be processed.
Ex.
PLC
(1) Program
Display page 25
TERMINAL
C
B
Dialog table
25
(4) H'FFFF'
(2) XBT reads the table
25
(3) Display page 25
The terminal reads the dialog table in the PLC (2) and displays the required page (3). It is not necessary to write a program in the PLC to control the communication.
(4) Once the command is processed, the terminal writes H'FFFF' in the page word to be processed.
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
Magelis B - 15
5. Entry and modification of variables
5. Entry and modification of variables
Reminder
A page consists of text and fields. A field may correspond to values which have to be filled in (write) or modified (read/write) by the user or to values written by the PLC.
Ex.
Text Temperature = Field
Entry request
By the operator
Entry mode is accessed with the MOD key.
By the PLC
The PLC writes the number of the field in the word "Field to enter" in the dialog table.
Entry principle
- If the field contains more than 1 digit, the digit to be entered is displayed in steady mode, whilst the other digits blink.
- If the field contains 1 digit, the digit to enter blinks.
- The LEDs of the arrow keys blink. Note : when the LEDs are off, the corresponding keys are inactive.
Entry via numeric keypad
Keys 0 to 9 and +/- (toggle function, + is the default sign) are used to enter data.
- Select the digit to be entered using the arrow keys.
- Enter this digit, the following digit (to the right) stops blinking.
Magelis XBT-H, XBT-HM
Except XBT-H001010,
002010, 021010,
022010 and XBT-
HM007010, 027010
XBT-P XBT-PM XBT-E
B - 16 Magelis
5. Entry and modification of variables
Type of data : bits, single words, double words, floating point words, character strings.
Display format : binary, decimal (maximum of 5 decimal places), hexadecimal, numbered list.
Limits : If the entry limits of a value have been defined with XBT-L1000 software, any entry outside these limits produces a warning message and a return to entry mode.
Access type : Read, Write, Read/Write, Immediate Write, Immediate
Read/Write.
B
Numbered list : XBT-L1000 software enables a text to be assigned to each value of the variable associated with the field.
- Programming with XBT-L1000 : Access the window defining the characteristics of the field, select Format/Type, click on List and assign a text to each value.
- Operation with the terminal : use the arrow keys.
For more information,
See chapter D, "Numbered list", Page 19.
Magelis XBT-H, XBT-HM
Except XBT-H001010, 002010,
021010, 022010 and XBT-
HM007010, 027010
Magelis
XBT-P XBT-PM XBT-E
B - 17
6. Alarms
6. Alarms
Structure of alarm pages
An alarm page has the same characteristics as an application page for :
- the text,
- the field (read only).
Ex.
The additional feature of an alarm page is its event-triggered display. A word bit from the dialog table is assigned to each alarm page. If the bit is at state 1, the page is processed.
A sensor fault occurs. The bit associated with the sensor fault changes to 1.
Sensor fault
Magelis
ATTENTION PRESSURE SENSOR FAULT
CHANGE TO MANUAL
Advantages in running mode
- When a fault appears, it is often as a result of other faults. The priority system of MAGELIS products, enables the most important fault to be displayed . In other words, the one which is most hazardous for the process.
- The occurrence of each fault is time-stamped.
For the XBT-PM, the background picture and the first line blink during an alarm.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The XBT does not support any type of processor nor machine control in association with alarms. It is designer's responsibility to consider programming PLC logic to account for programmed alarms.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
XBT-H, XBT-HM XBT-P XBT-PM
No time stamp for XBT-PM
027010
XBT-E
B - 18 Magelis
6. Alarms
Maintenance advantages
- MAGELIS terminals store the occurence of faults sequentially (log), thereby enabling an investigation into the origin of the fault.
- Several alarms may therefore appear simultaneously in the process.
These are recorded by the XBT in a special memory called the "alarm list".
The actual display of an alarm depends on the priority which it has been allocated (
see "Display priority", Page 22
).
- Alarms appearing in the process are stored in the "Alarm list".
- The "Alarm" indicator lamp continuously informs the operator about the state of the alarm list * :
- Off: the alarm list is empty.
- Blinking: the alarm list contains alarms which have appeared since the alarm list was last viewed.
- On: the alarm list contains alarms which occurred before the alarm list was last viewed.
B
Design using the XBT L1000
The XBT-L1000 software is used to enter the parameters of the following
3 functions for each alarm page :
- Display : the page will be displayed.
- Printing : the page will be printed.(1)
- Storage : the page will be stored.(1)
Magelis XBT-H, XBT-HM
(1) except for .XBT-H/
P/E/HM/PM ***0**
XBT-P XBT-PM XBT-E
Magelis B - 19
6. Alarms
Alarm page parameters
Alarm pages comprise :
- text, the object of which is to indicate :
- the fault,
- actions to correct the fault.
Ex.
Conveyor faults
Turn power off
Remove the part
Restart conveyor
- variable fields,
- a priority,
- request for acknowledgement,
- an alarm relay command (XBT-E).
Design with XBT- L1000
Select the Page menu or the icon
"Create alarm page" is displayed.
New/Alarms and the window
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
B - 20 Magelis
6. Alarms
Assign a bit to the alarm page.
It is possible to change the name.
Confirm with OK.
Open the alarm page.
Assign the priority ( see "Display priority", Page 22 )
Enter the alarm page text.
Authorize or not to display the alarm page.
Authorize or not to print the alarm page.
Authorize or not to memorize the alarm page.
Authorize or not the acknowledgement.
Authorize or not the alarm relay.(1)
Magelis XBT-H, XBT-HM
(1) except for .XBT-H/
P/HM/PM
XBT-P XBT-PM XBT-E
Magelis B - 21
B
6. Alarms
Display priority
With XBT-L1000 a priority can be assigned to each alarm page.
An alarm generally has a higher priority than the display of operating pages. It is lower than the display of an entry which is in progress.
Different alarm pages can have different priorities. 16 levels of priority are possible (the lowest display priority being priority N ° 16).
Special case of priority 0
If priority 0 is assigned to an alarm page, when the alarm appears on the process,
- the alarm page will not be displayed but will be stored in the alarm lists to avoid disturbing the current display.
- the alarm indicator lamp will blink to indicate the alarm.
When an alarm is activated, it is stored by the XBT in the alarm list.
Storage principle :
If of equal priority, alarms are stored in a such a way that
- the oldest is displayed first
- the others are stored one after another in their order of appearance
(FIFO stack).
- If the display is available (in other words not occupied by a higher priority display), the first alarm which occurs is displayed.
If higher priority alarms appear,
- They are stored at the top of the list.
- If the display is available (in other words not occupied by a higher priority display), the highest priority new alarm is displayed.
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
B - 22 Magelis
6. Alarms
Appearance of alarm
The ALARM indicator lamp blinks. The alarm is stored in the alarm list * .
The alarm relay is closed (XBT-E only) if this function is selected.
Entry in progress
No
Yes End of entry or entry abandoned
Higher priority alarm already displayed
No
Yes Acknowledgement or disappearance of the alarm
Display of the higher priority and oldest alarm in the list
B
Magelis XBT-H, XBT-HM
* except for .XBT-
H811050
Magelis
XBT-P XBT-PM XBT-E
B - 23
6. Alarms
Acknowledgement of alarms
When pages are designed, it is possible to define whether the alarm page should be systematically acknowledged or not (acknowlegment).
The management of these two types of alarm is as follows :
1 - Alarms which must be acknowledged
An alarm which must be acknowledged remains in the list of alarms until it is accepted, even if the cause of the fault has disappeared.
Advantage : Picks up transient faults (instability of a discrete sensor for example)
Acknowledgement of alarms
Alarms are accepted on the terminal with the ENTER key. The alarm message changes to fixed display.
2 - Alarms which can optionally be acknowledged
An alarm which is optionally accepted disappears from the list of alarms as soon as the cause of the fault has disappeared, whether the alarm has been accepted or not.
Advantage : Does not monopolize the display unit with the display of faults considered of minor importance to the application.
Design using XBT-L1000
Once the alarm page is displayed, select the "Page/Acknowledgment" menu or the icon.
XBT-P XBT-PM XBT-E Magelis XBT-H, XBT-HM
* except for .XBT-
H021010
.XBT-H022010 and
.XBT-HM027010
B - 24 Magelis
6. Alarms
Control of alarm relay : XBT-E
The alarm relay is closed as soon as an alarm, defined with the "alarm relay" option, is active.
The relay is open as soon as all active alarms, defined with the "alarm relay" option, have been accepted by the operator or have disappeared.
Design using XBT-L1000
Once the alarm page is displayed, select the Page/Alarm relay menu or the icon .
B
Magelis XBT-H, XBT-HM except XBT-H and
XBT-HM
XBT-P except XBT-P
XBT-PM except XBT-
PM
XBT-E
Magelis B - 25
6. Alarms
Alarm display
The dialog table (
see chapter C, "5. Contents of the dialog table",
Page 11 ) is used for dialog between the PLC and the terminal. In this
table, words are reserved for alarm display.
The display is controlled by the PLC by setting a word bit to 1.
The XBT-L1000 software is used to assign a word bit to each alarm page.
Ex.
PLC
(1) Program
Display alarm 3
TERMINAL
Dialog table
1
(2) XBT reads the table
1
(3) Display alarm 3
The terminal reads the dialog table in the PLC (2) and displays the required page (3). It is not necessary to write a program in the PLC to control the communication.
Magelis XBT-H, XBT-HM
B - 26
XBT-P XBT-PM XBT-E
Magelis
6. Alarms
Ex.
When an alarm is displayed, the XBT reserves the first line of the display unit to display :
- the date and time of appearance and acceptance of the alarm,
- the position of the alarm in the alarm list,
- the total number of alarms in the list.
The alarm is displayed in blinking mode.
A 31/01 17:35 3/7
CONVEYOR FAULT
Turn power off.
Remove jammed part.
Restart.
Line time-stamped by the XBT
("A" for Alarm) the alarm text, in blinking mode, becomes steady once the alarm is acknowledged.
Ability to ignore alarms
If an alarm is displayed during operation (for example during debugging), the ESC key can be used to return to running mode, the alarm still remains in the list and the ALARM indicator lamp becomes steady.
Viewing alarms
If there are alarms in the stack, the ALARM indicator lamp lights up. To access the alarm list, press the SHIFT+ENTER key : the highest priority alarm is displayed.
B
Exit viewing of the alarm pages.
Scrolling the alarm page. (except XBT-PM)
Move in the list of alarm pages.
Acceptance.
Ex.
Magelis
A 31/01 17:35 1/7
CONVEYOR FAULT
Turn power off.
Remove jammed part.
Restart.
A 31/01 17:35 2/7
CONVEYOR DEF1
Change to N ° 2.
XBT-H, XBT-HM except XBT-HM
XBT-H021010/022010/H00x/
H012x neither ESC, nor view.
XBT-P
A 31/01 17:35 3/7
MOTOR FAULT
Cut power supply
N ° 5
XBT-PM XBT-E
Magelis B - 27
7. Alarm log
7. Alarm log
Principles
The XBT may control a log of alarm pages.
They store the alarm pages with the text but without the variable values.
The alarms are stored one after another. Once the log is full, the more recent alarms overwrite the older ones.
Each event:
- appearance,
- acknowledgement,
- disappearance, of an alarm is thus recorded and time-stamped.
The following functions may be performed :
- Initiated by the PLC:
- print log,
- clear log ;
- Initiated by the operator:
- display log,
- print log ;
- Initiatid by the PLC and the operator in confidential mode :
- clear log.
Magelis XBT-H, XBT-HM
Printing only XBT-
H012110 and XBT-
HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 28 Magelis
7. Alarm log
Design using the XBT-L1000
For each alarm page, the XBT-L1000 software sets these 3 functions:
- Display: the page will be displayed
- Printing: the page will be printed
- Storing: the page will be stored.
The Alarm page is stored only if the the log.
button has been selected in
B
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
Magelis B - 29
7. Alarm log
Log display
Press "MENU".
Select "ALARM LOG" option in the menu then choose type of display : sequential or statistical.
Change from one alarm to another in the log.
Scrolling to display complete information on an alarm in the log (except
XBT-PM).
Ex.
Display
ALARM LOG ->
Occupancy rate.
ALARM LOG....... %
DISPLAY ->
ERASE ->
A 31/01 17 : 35 1/7
CONVEYOR FAULT
Alarm text (no variable)
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 30 Magelis
7. Alarm log
Ex.
Display principle:
Events for each alarm if any (appearance, acknowledgement, disappearance) are displayed sequentially, grouped according to the status, with the first alarm shown at the first position.
.
Example:
The log contains 4 events 3 of which are related to the same alarm.
Appearance
V 31/01/95 17:35 1/4
CONVEYOR1 FAULT
Alarm text
Acknowledgement
K 31/01/95 17:36 2/4
CONVEYOR1 FAULT
Alarm text
Disappearance
31/01/95 17:55 3/4
CONVEYOR1 FAULT
Alarm text
B
Alarm "CONVEYOR 1 FAULT"
New fault
V 31/01/95 17:38 4/4
VALVE2 FAULT
Alarm text
Alarm "VALVE 2 FAULT"
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
Magelis B - 31
7. Alarm log
Clear log
Clearing initiated by the operator (in confidencial mode)
Press MENU key.
Choose the "ALARM LOG" menu.
Choose "Clear log" (only in "CONFIDENTIAL MODE).
Ex.
ALARM LOG ->
ALARM LOG.
50 %
DISPLAY LOG ->
CLEAR LOG ->
ALARM LOG.
0 %
Clearing initiated by the PLC
The log is cleared using the command word in the dialog table to reset
the log ( see chapter C, "%MWn+18 : Reset log", Page 16
).
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 32 Magelis
7. Alarm log
Print log
Printing initiated by the operator
Press the PRINT key and select the "Alarm log" option.
The following is displayed:
Ex.
PRINTING
HARD COPY
ALARM LOG
FORMS
->
->
->
STOP PRINTING ->
Selecting "Alarm log" option:
The log is printed in sequential mode, the most recent alarm is displayed first.
For each alarm, the following items will be printed on the same line:
- the page name,
- date and time of appearance
- date and time of acknowledgement,
- date and time of disappearance.
Printing initiated by the PLC:
The log is printed in sequential mode (by status), the most recent alarm will be printed first.
For each alarm, these items are printed first and on the same line: name, date of time of appearance (Valid), acknowledgement (ACK), disappearance (Invalid).
B
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
Magelis B - 33
7. Alarm log
Its text cannot be printed in a compact format. The recommended print format is 80 character width. The printed header shows the date and time of the alarm log printing.
Example:
Ex.
ALARM LOG Valid Ack Invalid
05/09/95 11:26
00013: VAT 3 HOT 05/09/95 10:10:05
00011: VAT 1 HOT 05/09/95 09:15:02
00012: VAT 2 HOT 05/09/95 08:58:48 05/09/95 09:02:03
00013: VAT 3 HOT 05/09/95 08:10:05 05/09/95 08:11:02 05/09/95 08:16:75
Alarm 11 is present but not acknowledged.
Alarm 12 is present and acknowledged.
Alarm 13 occurred (twice), was acknowledged and disappeared (once).
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 34 Magelis
8. Process control via function keys
8. Process control via function keys
Ex.
MAGELIS terminals can control the control system via the function keys
(Static or dynamic for the XBT-PM). Two types of control are possible :
Momentary contact command
By pressing a function key, the system is activated. The action stops when the key is released.
Motor command xxxxxxx
B
Ex.
Push on/push off toggle command
The control system is activated by pressing a function key. The action is halted by pressing the function key again.
Forward command for a conveyor
ADVANCE TROLLEY
Magelis
XBT-L1000 software can be used to assign a bit to each function key, as well as to determine the type of control.
XBT-P XBT-PM XBT-E XBT-H, XBT-HM except XBT-H00xxxx,
XBT-H01xxxx, XBT-
H811050, XBT-
HM007010 and 017xxxx
Magelis B - 35
8. Process control via function keys
Ex.
Assigning function keys using XBT-L1000
The dialog table (
see chapter C, "5. Contents of the dialog table",
Page 11 ) is used for dialog between the PLC and the terminal. In this
table, words are reserved for the indication of the state of the function keys in the form of a word bit : bit at 1 = key pressed
%MWn
Bit 15
F16
Bit 0
F1
%MWn+1
Bit 7
F24
Bit 0
F17
PLC TERMINAL
Press key
F1
Dialog table
%MWn,0
1
%MWn,0
Magelis
The terminal writes to the PLC dialog table. It is not necessary to write a program in the PLC to control the communication.
There is no reserved word for dynamic function keys (XBT-PM). So, a word out of the dialog table must be used.
For more informations,
see chapter D, "Displaying a page via a function key", Page 14 .
XBT-P XBT-PM XBT-E XBT-H, XBT-HM except XBT-H00xxxx, XBT-
H01xxxx, XBT-H811050, XBT-
HM007010 and 017xxxx
B - 36 Magelis
9. Locking function keys via the PLC
9. Locking function keys via the PLC
Each of the terminal's keys may be locked by the PLC (except dynamic function keys of XBT-PM). The dialog table (see
dialog between the PLC and the terminal. In this table, words are reserved for locking the various function keys in the form of a word bit : bit at 1= key locked.
Function keys
%MWn-22
Bit 15
F16
Bit 0
F1
Bit 7
F24
Bit 0
F17 %MWn+23
Other keys:
B
%MWn+24
Bit 0: Up arrow
Bit 1: Down arrow
Bit 2: Right arrow
Bit 3: Left arrow
Bit 4: MOD
Bit 5: PRINT
Bit 6: MENU
Bit 7: SYST
Bit 8: ALARM
Bit 9: EXIT
Bit 10: HOME
Bit 11: +1
Bit 12: -1
Bit 13: ENTER
%MWn+25
Bit 0: 0
Bit 1: 1
Bit 2: 2
Bit 3: 3
Bit 4: 4
Bit 5: 5
Bit 6: 6
Bit 7: 7
Bit 8: 8
Bit 9: 9
Bit 10: .
Bit 11: +/-Bit
Bit 12: DEL
Magelis
Magelis
XBT-H, XBT-HM XBT-P XBT-PM XBT-E
B - 37
9. Locking function keys via the PLC
Ex.
PLC
Lock F1
TERMINAL
Press F1 : no action
Dialog table
W21,0
1
W21,0
Magelis
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Pressing the MENU key allows the inexperienced or untrained operator to accidentally display the wrong page, modify the terminal configuration or lose the messages and alarms on the screen. This can lead to confusion, panicking, and, as a consequence, to loss of control over the machine. It is strongly recommended that the PLC be programmed to lock the MENU key as well as the other currently unused keys in order to prevent this from happening.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
The terminal reads the PLC dialog table and locks those keys whose word bit is at 1. It is not necessary to write a program in the PLC to control the communication.
The dynamic function keys (XBT-PM) cannot be locked.
XBT-H, XBT-HM XBT-P XBT-PM XBT-E
B - 38 Magelis
10. Printing
10. Printing
General
The printing of the following information may be :
Initiated by the operator:
Hard copy of the displayed page,
Alarm log,
Forms,
Stop printing.
In all cases the command is executed using the PRINT key.
Initiated by the PLC :
- Alarm log,
- Free format printing,
- Forms,
- Printing "Application page".
General principles (initiated by the operator):
The print process is executed by the PRINT key.
Formatting is performed according to the printing configuration selected using XBT-L1000: "Configuration/Terminal parameters/Printer".
B
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
Magelis B - 39
10. Printing
After pressing the PRINT key, the following is displayed:
PRINTING
HARD COPY
ALARM LOG
FORMS
->
->
->
STOP PRINTING ->
Selection of one of the options.
After selecting one of the options:
- If printing is enabled, transient display of :
PRINTING
ACKNOWLEDGED
- If printing is in progress, transient display of:
ACTION DISABLED
PRINTING IN PROGRESS
- If the printer is faulty, transient display of:
PRINTER FAULT
- If the fault disappears and printing was on progress at the time the fault occurred, printing resumes where it stopped (unless a STOP
PRINTING command has been executed).
Note:
If the printer has been configured with a number of characters less than the requested print format, the printout will be truncated. Characters
>125 and <32 are replaced by '.' on the printout. Except for free format and form printing.
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 40 Magelis
10. Printing
Stop printing
This function is accessible by pressing the "PRINT" key. Any printing in progress (Log, continous…) even though the printer is faulty, will stop without request for confirmation; i.e. the print buffer is cleared as well as any waiting command.
Continous printing of an alarm page
This option must be chosen at the time the page was created using the
XBT-L1000:
The Alarm page must show icon selected.
This function is initiated via the dialog table when the alarm occurs.
At each read cycle of the dialog table, "printable" alarms ("IMP" selected on XBT-L1000), are printed with the page text (25 lines at maximum) and the values for variables.
The printed header shows: the page number, name, date and time of the printing.
B
Ex.
05/09/05 10:26
00015: STOP MOTOR
( Page text)
Note:
Up to 16 "printable" alarms that appear simultaneously are printed.
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
Magelis B - 41
10. Printing
Display Hard Copy
This function is accessible by pressing the "PRINT" key. If the printer is busy, display will be refused and a transient message will be prompted.
The whole page is printed (up to 25 lines) with the variables.
The printed header shows: the page number, name, date and time of the printing.
Ex.
HARD COPY
05/09/05 10:30
00425: STOP MOTOR 2
( Page text with variables)
Log printing
For informations,
Form printing
For informations,
.
Free format printing
Only initiated by the operator;
Accessible via the dialog table using the print command word and via the free format printing table (see
Magelis XBT-H, XBT-HM only XBT-H012110 and XBT-HM017110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 42 Magelis
11. Configuration
11. Configuration
This function, only available in confidential mode, enables the following parameters to be viewed.
- the system language,
- the application language,
- the parameters of the PLC <-> XBT line,
- the terminal date and time,
- the parameters of the Printer <-> XBT line.
Switching to the confidential mode
Press the"MENU" key to display the menu.
Position the cursor on "CONFIGURATION".
B
PAGE NUMBER _ _
LIST OF PAGES
ALARM LOG
CONFIGURATIONS
->
->
->
->
PRODUCT REFERENCES ->
SELFTEST
Access configuration. The configuration menu is displayed.
Magelis
SYSTEM LANGUAGE
APPLICATION LANGUAGE
LINE PARAMETERS
PRINTER PARAMETERS
DATE/TIME
->
->
->
->
->
System language
The language is that in which information messages and terminal menus are expressed. The operator can find out and modify the system language. Position the cursor on the corresponding line using the up and down arrow keys and then access the content using the right arrow key.
To change the language press MOD, choose the language using the up and down arrow keys and confirm with ENTER.
XBT-H, XBT-HM
Except XBT-H and
XBT-HM
XBT-P XBT-PM XBT-E
Magelis B - 43
11. Configuration
Ex.
Application language
In the XBT-L1000 software, application can be entered in 3 different languages. To find out application language, position the cursor on the corresponding line using the up and down arrow keys and access the content using the right arrow key to change the language, press MOD, select the language using the up and down arrow keys and confirm pressing ENTER.
Parameters of the PLC <-> XBT line
To ascertain the parameters of the PLC <-> XBT line, position the cursor on the corresponding line using the up and down arrow keys while in confidential mode and then access the content using the right arrow key.
According to the protocol, some parameters may or may not be modified.
The parameters displayed depend on the protocol :
UNITE protocol:
Speed in bauds,
Parity,
Slave number,
Error counter n ° 1,
Error counter n ° 2,
Error counter n ° 3,
Error counter n ° 4,
Reset the counters (Y/N)
To RESET the counters, Press
Use up and down arrow keys to indicate choice yes (Y) or no (N) to erase counter and confirm with ENTER.
Terminal date and time
To know and modify the terminal date and time, position the cursor on the corresponding line using the up and down arrow keys whilst in confidential mode and then access the content with the right arrow key.
Entry is the same as for the modification of parameters ( see § 4. Page display, Page 14
). The separators / and : may be replaced by full stops.
Magelis XBT-H, XBT-HM
Except XBT-H and
XBT-HM
B - 44
XBT-P XBT-PM XBT-E
Magelis
11. Configuration
Ex.
Access to terminal internal timer:
The DATE and TIME (DD/MM and HH:MM) can be displayed in an application page using XBT internal words.
Example:
DATE: DD/MM/YY TIME: HH:MM:SS
Field No. 1 (DD/MM) defines as follows:
Associated variable: Wi with i = 50000
Equipment:
Format:
XBT
String
Type:
Length:
Access:
ASCII
5 (8 max. for full display)
Read only
Field No. 2 (HH:MM) defines as follows:
Associated variable: Wi with i = 50001
Equipment:
Format:
XBT
String
Type:
Length:
Access:
ASCII
5 (8 max. for full display)
Read only
It is advisable to select a read only access or to use the CONFIDENTIAL mode to change the date and time.
When the timer variables are to be changed, you must use a separator such as "." or the right arrow to insert a SPACE between DD and MM or
HH and MM.
When you change internal words 50000 and 50001, you also change the contents of two words out of the four "Terminal Date and Time words for the controller" (if they have been selected in the dialogue table).
B
XBT-P XBT-PM XBT-E Magelis XBT-H, XBT-HM
Except XBT-H and
XBT-HM
Magelis B - 45
11. Configuration
When you change one of the four "Time Setting" words (if they have been selected in the dialogue table), you also change the contents of internal words 50000 and 50001.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Since all alarms are always time/date stamped and the control program may rely on the XBT's real-time clock, it is important to set or verify the
XBT's date and time after every new installation, repair, disassembly, shipping or battery change.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Parameters of the printer <-> XBT line
Parameters displayed by default:
PRINTER PARAMETERS
SPEED :
PARITY :
FORMAT:
BITSTOP:
LINK:
DUPLEX:
CHARACTERS
FORM FEED:
AUTO LF:
->
9600 BDS
ODD
8 BITS
1 BIT
RS 232
FULL
80
NO
CR LF
Magelis
Adjusting the parameters:
- position the cursor on the corresponding line using the up and down arrow keys, then access the content using the right arrow key.
XBT-H, XBT-HM
Except XBT-H and
XBT-HM
XBT-P XBT-PM XBT-E
B - 46 Magelis
12. Product selftest
12. Product selftest
Permanent selftest:
- Selftest is permanently performed on the program and application memories.
If a malfunction is detected which prevents the product operation, the terminal switches all its indicator lamps and stops running.
Manual selftest*:
- In "Confidential mode" (
see chapter D, "Confidential mode",
Page 10 ), the user may request, via the "system menu" the manual
test of the terminal parts not covered by the permanent test.
Available functions:
- Display test,
- Keyboard test,
- Buzzer test (XBT-E),
- Relay test (XBT-E),
- Serial link test.
Change to confidential mode
Press the "Menu" key to display the menu.
Position the cursor on "Selftests".
B
SELFTEST ->
Accessing the selftests, the menu is displayed
Magelis
SELFTEST
DISPLAY ->
OPERATION LINE ->
KEYBOARD
BUZZER
RELAY
->
->
->
XBT-H, XBT-HM
Except XBT-H and
XBT-HM
XBT-P XBT-PM
Magelis
XBT-E
B - 47
12. Product selftest
Display test:
Test process,
- the display switches off,
- a horizontal line of pixels scrolls up down,
- a vertical line of pixels scrolls from left to right.
To stop the test, press the key.
Serial link tests:
Carefully plug in the test connector on the link to be tested before initiating the test.
Test connectors:
- Operation link type RS 232, connect pins 2-3.
- Operation line type RS 422, connect pins 4-6 and 5-18.
- Printer link type RS 232, connect pins 2-3.
Then, test the link with the test connectors by pressing the key.
If the displayed result is "OK", the link is correct.
Remove the test connector and start the test (pressing the key).
The result must be "NOK".
The link is correct if both tests have had the results shown above.
Magelis XBT-H, XBT-HM
Except XBT-H and
XBT-HM
XBT-P XBT-PM XBT-E
B - 48 Magelis
13. Forms
13. Forms
Purposes
The user may want to print measurement/production monitoring reports, product labels, … Forms that are printed show various widths and lengths.
The example below shows a label whose size, reference, warranty date are variables of the PLC program read by the terminal before printing.
B
Creation using XBT-L1000
EEPROM BOARD [99] KBYTES
REF. [AAAAAAAAAAA]
WARRANTY: [99-99]
Result on printer
EEPROM BOARD [56] KBYTES
REF. XBT-Z800056
WARRANTY: [09-96]
Definition
- The quantity of forms is limited to 255 (N ° 1 to N ° 255).
- One form contains up to 132 characters X 60 lines.
- Forms are created using the XBT-L1000 as application pages or as alarms.
The form takes all from the pages, i.e., as a reminder:
- name of the form on 12 characters,
- number of the form,
- number of variable fields limited to running pages,
- multilanguage,
- protection by a password.
- The forms cannot be viewed from the terminal but only form the printer
(because of format differences between the display with 20 characters and the printer with up to 80 characters).
Magelis XBT-H, XBT-HM only XBT-H012110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
Magelis B - 49
13. Forms
Select "Page/New Page/Form" menu.
Indicate the name and/or the number of the new page.
The form pages can include the following elements:
- printer control codes:
- semi-graphic characters,
- text,
These elements are intended for printing only.
Semi-graphic characters are used to create simple or double frames for highlighting printed data (table of values, etc.).
There are introduced after the semigraphic character is then introduced by clicking on its icon.
The printer control codes {a} (ex : {1}, {2}, etc.) are used to define printer control sequences (printing of bar codes, bold characters, change of colors, etc.).
Selecting and place its position on the screen the printed control codes
({1}, {2}, etc) are then introduced by clicking on its icon.
To configure each control code the menu "configuration / terminal parameters / printers" has to be selected.
The control codes are introduced in hexadecimal format according to the printer manufacturer documentation.
Magelis XBT-H, XBT-HM only XBT-H012110
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 50 Magelis
13. Forms
Utilization
Initiated by the PLC
.
Initiated by the operator
This function is accessible:
- in running mode via function key,
- pressing the "PRINT" key via the selection of the "FORMS" submenu.Then, select the form as you'll do for the list of pages, by the name in the list of forms or by the number that you enter.
Ex.
PRINTING [status]
HARD-COPY
ALARM LOG
FORMS
STOP PRINTING.
->
->
->
->
Form number
Quick access by n °
Number of printed copies
FORMS N °
NBR OF COPIES
00005 LABEL A.
00011 LABEL B
00013 PRODMONIT
[001]
[01]
B
Title of the form
The operator chooses the form by scrolling the pages and using the arrow key .
Variables are read in the PLC then the printing is performed.
Real-time setting is possible via the PLC internal variables: date and time. Moreover, the user can specify the number of printouts via the
"NBR OF COPIES" field which has been previously selected at 1.
Magelis XBT-H, XBT-HM only XBT-H012110
Magelis
XBT-P
only XBT-
P021110 and
XBT-P022110
XBT-PM only XBT-PM
027110
XBT-E only XBT-
E01x110
B - 51
13. Forms
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
B - 52 Magelis
Magelis
Chapter C
PLC and Terminal communications
Dialog
C
C - 1
C - 2 Magelis
Contents
Contents
This chapter includes the following topics:
1. Introduction ______________________________________________________ 5
2. Data exchanged __________________________________________________ 6
Data associated with fields _________________________________________ 7
Command data from the PLC to the terminal ___________________________ 7
Status data from the terminal to the PLC _______________________________ 7
3. Principle of exchanging data associated with fields _______________________ 8
4. Principle of the dialog table __________________________________________ 9
5. Contents of the dialog table _________________________________________ 11
Notation convention for describing the table ___________________________ 11
Detailed description ______________________________________________ 13
C
Magelis C - 3
Contents
C - 4 Magelis
1. Introduction
C
1. Introduction
Man/machine dialog between the Magelis terminal and the PLC consists of an exchange of data between the 2 devices.
In every communication problem, it is advisable to define :
- the data to be exchanged
- the protocol
- etc.
C
Magelis C - 5
2. Data exchanged
2. Data exchanged
Various types of data may be exchanged
Data associated with fields
Command data from the PLC
to the terminal
PLC
Status data from the terminal to the PLC
MAGELIS
TERMINAL
C - 6 Magelis
2. Data exchanged
Data associated with fields
These are variables which may be :
- displayed on the terminal,
- entered or modified via the terminal.
Command data from the PLC to the terminal
Concerns the following commands :
- Display an application page,
- Display alarm pages,
- Lock keys,
- Enter request for a variable field,
- Print command,
- Control of indicator lamps associated with function keys,
- Clear log command,
- Set real-time clock command.
Status data from the terminal to the PLC
Concerns the following states :
- The terminal status
- confidential mode,
- terminal configuration mode,
- confirmation of entries via ENTER key,
- abandon entry via ESC key,
- abandon entry after a time-out,
- printing fault
- Number of displayed page,
- Number of last field entered,
- Image of keypad keys,
- Real-time clock status (date and time),
- Occupancy rate of log as a percentage,
- Communication monitoring,
- Number of last alarm acknowledged.
Magelis C - 7
C
3. Principle of exchanging data associated with fields
3. Principle of exchanging data associated with fields
The exchange principle depends on the protocol chosen according to the type of PLC.
The terminal may be master or slave, client or server of the dialog.
The terminal is most commonly the client, and is responsible for the following exchanges :
- updating of fields (reading values in the PLC)
- entry and modification of fields (writing of values to the PLC)
No communication program needs to be written.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
PLC memory zone allocated for the XBT dialog table must NOT be used for anything else. It is designer's responsibility to program PLC logic properly.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
C - 8 Magelis
4. Principle of the dialog table
4. Principle of the dialog table
To simplify the dialog, all data :
- Commands from the PLC to the terminal
- Status data from the terminal to the PLC are grouped together in a table : the dialog table
Composed of n consecutive words (words of 16 bits), this table has 2 parts:
Status table
Status data from the terminal
to the PLC.
Command table
Commands from the PLC
to the terminal
The number of words in the table depends on the choice of status data and commands that are to be processed via the dialog.
The XBT-L1000 software is used to make this choice.
C
Using the "Authorization" word is a safety check for the PLC.
If this word is not at the correct value, the terminal cannot write any word to the PLC.
- The authorization word is not compulsory.
- It is systematically present in the dialog table offered by XBT-L1000.
- It is strongly advisable to retain the authorization word in the dialog table as long as the table contains at least one word to be written by the
XBT.
Magelis C - 9
4. Principle of the dialog table
PLC
The dialog table is in the PLC (n consecutive words).
The terminal reads and writes the table to the PLC.
There is no PLC program to write for the communication part.
Reading and writing data associated with message fields
TERMINAL
Reading command data
Writing status data
When the terminal is switched on or communication restarted, it reads the command table and writes the status table. In the event of a problem the terminal informs the user via a message.
C - 10 Magelis
5. Contents of the dialog table
5. Contents of the dialog table
The number of words in the table depends on the choice of states and commands that are to be processed via the dialog.
So, the number of available words depends on the PLC type (For example : presence or not of function keys).
Notation convention for describing the table
%MWn word of 16 bits
%MWn, i : bit i of word n
The address n is taken as the start of table address.
C
Word
%MWn+0 to
%MWn+1
%MWn+2
The description below gives the content of the various dialog table words. Refer to the XBT-L1000 software on-line help for more information on the words.
Functions
Static function keys
System keys
Exchange Page
PLC <- XBT
PLC <- XBT
Magelis C - 11
5. Contents of the dialog table
Word
%MWn+3
%MWn+4
%MWn+5 to
%MWn+8
%MWn+9
%MWn+10
%MWn+11
%MWn+12
%MWn+13
%MWn+14
Numeric keys
Set PLC clock
Functions
Communication control
Exchange Page
PLC <- XBT
PLC <- XBT
PLC <- XBT
Number of displayed page
Number of last field entered
Last alarm acknowledged
Confirmation report
Log occupancy rate
Number of page to be processed
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <->XBT
%MWn+15
%MWn+16
Field number to be entered
Print command
%MWn+17
%MWn+18
%MWn+19 to
%MWn+20
%MWn+21
%MWn+22 to
%MWn+23
%MWn+24
Writing table authorization
Reset log
Static function key LED’s command
Dynamic function key LED’s command
Lock static function keys
Lock system keys
Lock numeric keys %MWn+25
%MWn+26 to
%MWn+41
%MWn+42 to
%MWn+46
%MWn+47
Alarm table
Set XBT clock
Printout table in free format (maximum of 40 words on one line of printout)
PLC <->XBT
PLC<->XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
C - 12 Magelis
5. Contents of the dialog table
Detailed description
%MWn+0 to %MWn+3: Images of terminal keypad keys to PLC.
Bit at 1= key pressed.
%MWn
Bit 15
F16
Bit 0
F1
%MWn+1
Bit 7
F24
Bit 0
F17
%MWn+2
Bit 0: Up arrow
Bit 1: Do%MWn arrow
Bit 2: Right arrow
Bit 3: Left arrow
Bit 4: MOD
Bit 5: PRINT
Bit 6: MENU
Bit 7: SYST
Bit 8: ALARM
Bit 9: EXIT
Bit 10: HOME
Bit 11: +1
Bit 12: -14
13: ENTER
Bit 14:Reserved
Bit 15:Reserved
%MWn+3
Bit 0: 0
Bit 1: 1
Bit 2: 2
Bit 3: 3
Bit 4: 4
Bit 5: 5
Bit 6: 6
Bit 7: 7
Bit 8: 8
Bit 9: 9
Bit 10: .
Bit 11: +/-Bit
12: LED
Bit 13:Reserved
Bit 14:Reserved
Bit 15:Reserved
Some bit value are not usable in this range of product.
C
Magelis C - 13
5. Contents of the dialog table
%MWn+4 : Communication control
Word incremented by 1 at each communication request by the terminal.
It is sent to the PLC. This monitors the communication between the terminal and PLC.
%MWn+5 to %MWn+8: Set PLC clock.
C - 14
%MWn+5
%MWn+6
%MWn+7
%MWn+8
Seconds
Hours
Month
Century
Reserved
Minutes
Day of the month
Year
Only XBT-E possesses a protected real-time clock. The XBT writes the time and date periodically to the PLC (approximately every second).
2 coding formats are possible:
Hexadecimal or BCD (option selected with XBT-L1000).
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
If communications between XBT and PLC are lost, operator's control over machine may be lost completely or partially. It is designer's responsibility to program PLC logic to account for this situation. One of the good ways to do that is to monitor %MWn+4 of the dialog table from the PLC program.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
%MWn+9 : Number of page to be displayed
N ° of the page displayed on the terminal and to be sent to the PLC.
It contains H'FFFF' if it is a system page or a displayed alarm.
%MWn+10 : Number of last field entered
N ° of last field entered on the terminal to be sent to the PLC.
%MWn+11 : Last alarm accepted
This information is only present on one PLC scan, it then returns to
H'FFFF'.
Magelis
5. Contents of the dialog table
Magelis
%MWn+12 : Confirmation report
%MWn+12
Bit 0: Confidential mode
Bit 1: Configuration mode
Bit 2: ENTER on entry
Bit 3: ESC on entry
Bit 4: End of entry on TIME-OUT (1mn)
Bit 5: Reserved
Bit 6: Printing fault
Bit 7: Reserved
Bit 8: Reserved
Bit 9: Reserved
Bit 10: Reserved
Bit 11: Current language
Bit 12: Current language
Bit 13: Set terminal clock realised
Bit 14: Reserved
Bit 15: Reserved
%MWn+13 : Log occupancy rate
The occupancy rate of the alarm log as a % on the terminal and to be sent to the PLC.
%MWn+14 : Page number to be processed
To process page 22 insert 22 -> %MWn+14
When %MWn+9 = 22 and %MWn+14 = H'FFFF' the command is OK
When %MWn+9 < > 22 and %MWn+14 = H'FFFF' the command is not OK
Special commands:
Page N°: 65521 normal Brightness
Page N°: 65522 low Brightness
C
%MWn+15 : Field number to enter
If the field 20 is to be entered on page 10 :
* confirm that %MWn+9 = 10
* then 20 -> %MWn+15
When %MWn+10 = 20 and %MWn+15 = H'FFFF' the command is OK.
%MWn+12 then gives more detail : "ENTER on entry".
When %MWn+10 < > 20 and %MWn+15 = H'FFFF' the command is not OK
%MWn+12 then gives more detail : " ESC Time-out".
C - 15
5. Contents of the dialog table
Ex.
%MWn+16 : Print command
MSB : Print code LSB : Long Tab
A code is assigned to each possible print type.
- free format print :
- print sheet :
01 (nb octets)
04 (n° page 0 to 127)
- print log :
- "Hard-copy" Display:
02 (00)
05 (n° page 0 to 127)
For free format printing, the PLC gives the length in bytes of the information to be printed (maximum 40 words) in the LSB. The terminal reads the length given in word table to the end of dialog table address +
1. For sheet print, the LSB represents the N ° of sheets.
The word "Print command" is written by the PLC.
This same word is written to H'FFFF' by the XBT, to acknowledge the end of the command.
%MWn+17 : Writing table authorization
MSB LSB
For a 20 words long table, the PLC can write to the authorization word
H'A514'.( A5= authorization, 14= Nbr of words in dialog table
Hexadecimal value)
%MWn+18 : Reset log
The PLC writes H'00FF' in this word.
- the XBT clears the log and resets the "log occupancy rate" (%MWn+13).
- the PLC must writes H'0000' in the word %MWn+18 to accept a new
Reset Log command .
C - 16 Magelis
5. Contents of the dialog table
%MWn+19 to %MWn+20: Static function key LED’s command
Bit 15
%MWn+19 F16
Bit 0
F1
%MWn+20
Bit 7
F24
Bit 0
F17
%MWn+21 : Dynamic function key LED’s command
%MWn+21
Bit 3
R4
Bit 0
R1
%MWn+22 to %MWn+23 : Lock function keys
Bit 15
%MWn+22 F16
%MWn+23
Bit 7
F24
Bit 0
F1
Bit 0
F17
%MWn+24 : Lock system keys
%MWn+24
Bit 0: Up arrow
Bit 1: Do%MWn arrow
Bit 2: Right arrow
Bit 3: Left arrow
Bit 4: MOD
Bit 5: PRINT
Bit 6: MENU
Bit 7: SYST
Bit 8: ALARM
Bit 9: ESC
Bit 10: HOME
Bit 11: +1
Bit 12: -1
Bit 13: ENTER
Bit 14: Reserved
Bit 15: Reserved
Some bit value are not usable in this range of product.
C
Magelis C - 17
5. Contents of the dialog table
%MWn+25 : Lock numeric keys
%MWn+25
Bit 0: 0
Bit 1: 1
Bit 2: 2
Bit 3: 3
Bit 4: 4
Bit 5: 5
Bit 6: 6
Bit 7: 7
Bit 8: 8
Bit 9: 9
Bit 10: .
Bit 11: +/-Bit
12: LED
Bit 13: Reserved
Bit 14: Reserved
Bit 15: Reserved
%MWn+26 to %MWn+41 : Alarm table
Command to display alarm pages
Bit 15
%MWn+26 AL16
%MWn+27
%MWn+41 AL255
Bit 0
AL0
AL17
C - 18 Magelis
5. Contents of the dialog table
%MWn+42 to %MWn+46 : Set XBT clock.
%MWn+41
%MWn+42
%MWn+43
%MWn+44
Seconds
Hours
Month
Century
Reserved
Minutes
Day of the month
Year
Only the XBT-E has a protected real-time clock.
Each time one of these words is modified, the XBT sets itself to the date and time given in this table.
2 coding formats are possible:
Hexadecimal or BCD (option selected with XBT-L1000).
%MWn+47 : Free format printing table (up to 40 words)
See print command.
C
Magelis C - 19
5. Contents of the dialog table
C - 20 Magelis
Magelis
Chapter D
Operating the terminal D
D - 1
D - 2 Magelis
Contents
Contents
This chapter includes the following topics:
1. Keys and indicator lamps ___________________________________________ 5
2. Operating principle ________________________________________________ 8
Running mode ___________________________________________________ 8
Confidential mode _______________________________________________ 10
3. Page display ____________________________________________________ 12
Display when powered up _________________________________________ 12
Page display via links ____________________________________________ 12
Displaying a page via its number ____________________________________ 13
Displaying a page via its name _____________________________________ 13
Displaying a page via a function key _________________________________ 14
4. Entry and modification of variables ___________________________________ 15
Entry request ___________________________________________________ 15
Entry principle __________________________________________________ 15
5. Alarms _________________________________________________________ 20
Structure of alarm pages __________________________________________ 20
6. Product references _______________________________________________ 21
D
Magelis D - 3
Contents
D - 4 Magelis
1. Keys and indicator lamps
D
1. Keys and indicator lamps
Various terminals have a number of keys and indicator lamps.
gives specific information about the keys and associated indicator lamps for each type of terminal. The table below summarizes the functions of all the keys and indicator lamps.
Key/indicator lamp Function key/indicator lamp
Confirm a choice or entry, acknowledge an alarm page.
Move to page entry, password or variable field.
Move to next field each time MOD is pressed, right to left and top to bottom.
Delete an entry or suspend or stop an action in progress. Move up one level in a menu, exit display alarm.
Accesses the dual function on the keys.
- Change page in a menu.
- Change display (concept of "turning a page" to display the list of alarms, for example).
- Change digits in a variable field :
INDICATOR LAMP STATUS * :
- Off : key inactive.
- On : shows that it is possible to change page in a
menu (active link) or change display.
- Blinking : shows that it is possible to move into the
selected variable field.
Combined with the SHIFT key enable:
- Change the display luminosity.
(only Fluorescent or matrix Display)
(invers video PM)
D
Magelis XBT-H, XBT-HM
* No indicator lamp on
XBT-H811050
XBT-P XBT-PM XBT-E
Magelis D - 5
1. Keys and indicator lamps
Magelis
- Move around a page (activate the page links).
- Select the value of a digit.
- Select a value from a list.
INDICATOR LAMP STATUS :
- Off : key inactive.
- On : shows that moving around a page is possible
- Blinking : shows that it is possible to modify the value of each digit.
Combined with the SHIFT key enable:
- the value of a variable field to be incremented or decremented,
- Access at the top or the bottom page.
INDICATOR LAMP STATUS :
- Off : key inactive.
- On : shows that moving around a page is possible
- Blinking : shows that it is possible to modify the value of each digit.
Deletes the character to the left of the steady digit.
HOME
Inverts the sign of the variable field being entered.
Decimal point.
These keys which are accessible with the keys
give access to the character to the left, the centre, and the right respectively of the alphabetical marking.
SHIFT+ ESC : Return to the point of entry into the current menu.
Example : return to the first application page.
Accesses a menu containing the operating functions which are not directly accessible via keys:
- selection of application pages,
- "secondary" operating functions.
XBT-H, XBT-HM
* No indicator lamp on
XBT-H811050
XBT-P XBT-PM XBT-E
D - 6 Magelis
1. Keys and indicator lamps
SYST
ALARM
SHIFT + MENU : Accesses confidential mode which contains the setup functions (protected by a password) :
- installation and maintenance functions,
- change from running mode to confidential mode.
INDICATOR LAMP STATUS :
- Off : the terminal is in running mode.
- On : the terminal is in confidential mode.
- Blinking : PC<-> XBT transfer is in progress or no application in the terminal.
INDICATOR LAMP STATUS :
- indicator lamp on : no cable or incorrect wiring,
- indicator lamp off : correct cable, no exchange with the
PLC,
- indicator lamp blinking : exchanges with the PLC.
INDICATOR LAMP STATUS * :
- Off : no key pressed.
- On : when any key is pressed.
SHIFT+ ENTER: consult alarms
INDICATOR LAMP STATUS * :
- Off : the current alarm list is empty.
- On : the list contains some alarms which have already been displayed
(ignored).
- Blinking : the alarm list contains some new alarms.
SHIFT+ MOD: print command
INDICATOR LAMP STATUS :
- Off : no printing in progress,
- On : printing in progress.
- Blinking: printing fault.
D
Magelis XBT-H, XBT-HM
* No indicator lamp on
XBT-H811050
XBT-P XBT-E
Magelis D - 7
2. Operating principle
2. Operating principle
Running mode
The running mode is used to control the control system :
- Page display.
- Entry/modification of process parameter values.
- Process control (discrete).
- Printing.
- Viewing and acknowledgement of an alarm.
If the terminal has a MENU key, you can access the following additional functions :
- display of application pages (indirectly),
- consult the alarm log,
- access to the terminal configuration (printer link, real-time clock, link with the control system, languages)
- access to the product references,
- access to the terminal selftest functions (keyboard, display…)
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Pressing the MENU key allows the inexperienced or untrained operator to accidentally display the wrong page, modify the terminal configuration or lose the messages and alarms on the screen. This can lead to confusion, panicking, and, as a consequence, to loss of control over the machine. It is strongly recommended that the PLC be programmed to lock the MENU key as well as the other currently unused keys in order to prevent this from happening.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Magelis XBT-H, XBT-HM
No function menu
XBT-P XBT-PM XBT-E
D - 8 Magelis
2. Operating principle
Ex.
Example : Display of an application page
Solution 1 : once the Menu screen is displayed, press the and the 4 arrow key indicator lamps blink.
PAGE NUMBER _ _ ->
LIST OF PAGES ->
ALARM LOG ->
CONFIGURATIONS ->
Solution 2
LIST OF PAGES
00001 :
00002 :
00003 :
...
Select the required page access the page.
key
Enter the page number and
D
In this mode the SYS indicator lamp is off.
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
Magelis D - 9
2. Operating principle
Confidential mode
Confidential mode enables the running mode functions to be performed and, in addition, the following functions :
- Access to pages protected in running mode,
- Clearing the log,
- Configuration of the MAGELIS terminal and peripherals,
- Terminal selftests.
A password to protect the access to the confidential mode is created using XBT-L1000 : use "Configuration/Terminal parameters" menu.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The XBT should only be installed and used by the authorized personnel that has been assigned the appropriate confidential mode
PASSWORDS by the project manager.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Magelis XBT-H, XBT-HM
No confidential mode
XBT-P XBT-PM XBT-E
D - 10 Magelis
2. Operating principle
Changing to confidential mode
Press the SYST key.
Enter the password using the arrow keys or the numeric keypad, and confirm the entry with ENTER.
The SYST indicator lamp lights.
Exiting confidential mode
Press the SYST key.
Select running mode.
The SYST indicator lamp goes off.
D
Magelis XBT-H, XBT-HM
No confidential mode
XBT-P
Magelis
XBT-PM XBT-E
D - 11
3. Page display
3. Page display
Display when powered up
When it is switched on, the terminal automatically displays the system pages (duration 2 secs) :
- Display of the reference and the sofware version loaded
- Display of the product reference of the terminal
- Display of the reference and the version of software downloaded by
XBT-L1000.
- Display of the reference and the version of the protocol
- Display of the application name.
The terminal then continuously displays the date and time or the default page.
Page display via links
Ex.
A link between pages is indicated by the -> and <- arrows.
PAGE 19 PAGE 11
Automatic operation
<- Pg19
Pg11 ->
Pg23 ->
PAGE 23
If a page is accessible, the -> or <- arrow is displayed blinking in reverse video. Otherwise the display is steady, indicating that the page is protected and therefore accessible only in confidential mode.
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
D - 12 Magelis
3. Page display
Displaying a page via its number
1- Press the MENU key and the XBT displays the following menu :
PAGE NUMBER _ _
LIST OF PAGES ->
Access via page number
Access via page name
2 - Press the "MOD" key.
3 - Enter the page number to be displayed (
4 - Press "ENTER" to confirm and the page is displayed.
Only non-protected pages can be displayed in this way in running mode.
Change to confidential mode to display protected pages.
Displaying a page via its name
Press the MENU key and the XBT displays the following menu :
PAGE NUMBER _ _
LIST OF PAGES -> Access via page name
D
Display of list of pages
LIST OF PAGES
001 PRODUCTION ->
005 QUALITY ->
006 MAINTENANCE ->
- If in running mode, only nonprotected pages are displayed.
- If in confidential mode, both protected and non-protected pages are displayed.
Select the page.
Access the page.
Magelis XBT-H, XBT-HM
No menu function
XBT-P XBT-PM XBT-E
Magelis D - 13
3. Page display
Displaying a page via a function key
It is possible to display a page directly by pressing a function key. (Static or dynamic for XBT-PM).
Example :
Ex.
TEMP Temperature
To configure a function key, use "Configuration/Function key" menu :
Static function keys :
Dynamic function keys :
Magelis XBT-H, XBT-HM
Except XBT-H001010,
002010, 021010,
022010 and XBT-
HM007010, 027010
XBT-P XBT-PM XBT-E
D - 14 Magelis
4. Entry and modification of variables
4. Entry and modification of variables
Entry request
By the operator
Entry mode is accessed with the MOD key.
Entry principle
- If the field contains more than 1 digit, the digit to be entered is displayed in steady mode, while the other digits blink.
- If the field contains 1 digit, the digit to enter blinks.
- The LEDs of the arrow keys blink. Note : when the LEDs are off, the corresponding keys are inactive.
Entry via numeric keypad
Keys 0 to 9 and +/- (toggle function, + is the default sign) are used to enter data.
- Select the digit to be entered using the arrow keys.
- Enter this digit, the following digit (to the right) stops blinking.
- Enter the next digit.
- Enter the other digits and confirm the whole entry with ENTER.
- Entering the first digit of a field without having used the keys
causes the rest of the field to be deleted.
D
Magelis XBT-H, XBT-HM
Except XBT-H001010,
002010, 021010,
022010 and XBT-
HM007010, 027010
XBT-P XBT-PM XBT-E
Magelis D - 15
4. Entry and modification of variables
Entry via the arrow keys
- Select the digit to be entered using the arrow keys.
- Choose the value of the digit using the arrow keys.
- Move to the following digit using the arrow keys.
- Confirm the whole entry with ENTER .
Incrementing/decrementing a value
If you want to adjust a value
(example : adjust around the value 5556)
- Press the SHIFT + up arrow keys to increment the value by 1 point.
- Press the SHIFT + down arrow keys to decrement the value by 1 point.
- Confirm the whole entry with ENTER .
Deleting characters
When an immediate write access or immediate read/write access type is concerned. On each step, the value is sent to the controller.
The DEL key deletes the character to the left of the steady digit.
To delete the last steady digit :
- Move the cursor using the right arrow key until all the digits blink.
- Press the DEL key.
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
D - 16 Magelis
4. Entry and modification of variables
Entry rule
This key is used to move between the various fields of a displayed window and to select the required field.
This key abandons the current entry ; no modification is made.
Rule regarding display of variables
A value which cannot be displayed is represented by ’ ’ characters
(overflow value, unknowed value in a list).
Data type:
D
Display type:
Magelis XBT-H, XBT-HM
Except XBT-H001010, 002010,
021010, 022010 and XBT-
HM007010, 027010
Magelis
XBT-P XBT-PM XBT-E
D - 17
4. Entry and modification of variables
Limits and acces type:
Pushing on the "Option" button open the windows where can be configure limits and acces type of the variable.
A variable which is outside the limits but can be displayed blinks
(alphanumeric field, bar graph or meter).
A value which is not filled in by the PLC is represented by ? characters.
A write-only variable is represented by * characters (example : password).
If the numbered list has no text, the XBT displays ’ ’ throughout the field.
’ ’ = SPACE caracter.
Magelis XBT-H, XBT-HM
Except XBT-H001010, 002010,
021010, 022010 and XBT-
HM007010, 027010
D - 18
XBT-P XBT-PM XBT-E
Magelis
4. Entry and modification of variables
Numbered list
XBT-L1000 software enables a text to be assigned to each value of the variable associated with the field.
- Programming with XBT-L1000 : Access the window defining the characteristics of the field, select Format/Type, click on List and assign a text to each value.
- Operation with the terminal : use the arrow keys.
1. Select the lengh of the string (number of characters) and click on
"LIST" button.
2. Introduce each string and its value associated. A maximum of 255 strings can be associated to the variable field.
Ex.
A field (%MW10) that accepts two values with two associated strings of text (0: CLOSE 1: OPEN).
If you select OPEN using the arrow keys, and confirm by pressing
ENTER, the %MW10 word will take the value 1 in the
PLC.
Inversely, if the PLC writes the value 1 on %MW10 the OPEN text will be displayed.
If the word %MW10 value is neither 0 nor 1, not any text will be displayed. The field became invisible.
D
Magelis XBT-H, XBT-HM
Except XBT-H001010, 002010,
021010, 022010 and XBT-
HM007010, 027010
Magelis
XBT-P XBT-PM XBT-E
D - 19
5. Alarms
5. Alarms
Structure of alarm pages
Appearance of alarm
The ALARM indicator lamp blinks. The alarm is stored in the alarm list * .
The alarm relay is closed (XBT-E only) if this function is selected.
Entry in progress
No
Yes End of entry or entry abandoned
Higher priority alarm already displayed
No
Yes Acknowledgement or disappearance of the alarm
Display of the higher priority and oldest alarm in the list
For more informations,
see chapter B, § 6. Alarms, Page 18
.
Magelis XBT-H, XBT-HM
(1) except for .XBT-H/
P/E/HM/PM ***0**
XBT-P XBT-PM
No time-stamp for XBT-
PM027010
XBT-E
D - 20 Magelis
6. Product references
6. Product references
Push on key to display the menu,
Select "PRODUCT REFERENCES"
PAGE NUMBER _ _
LIST OF PAGES
ALARM LOG
CONFIGURATIONS
->
->
->
->
PRODUCT REFERENCES ->
SELFTEST ->
Accessing the Product Reference menu
Displayed data:
- Name of the downloaded application, date and time of creation of the application.
- Software reference and release.
- Commercial reference of the product.
- Name of the downloaded exe. file.
D
Magelis XBT-H, XBT-HM XBT-P XBT-PM XBT-E
Magelis D - 21
6. Product references
D - 22 Magelis
Magelis
Chapter E
Application development
Example
E
E - 1
E - 2
The objective of the example is to guide you quickly through your first application.
chapter B will give you all the information about the various operations performed.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
This example application will change register contents in remote devices. This may cause unanticipated change in device status. If this example is used in a functioning system, make sure all effects of any register change are fully understood before running this example.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Magelis
Contents
Contents
This chapter includes the following topics :
1. Contents of the application __________________________________________ 5
2. Creation of an application using XBT-L1000 _____________________________ 6
3. Loading the application into the terminal ________________________________ 9
4. PLC application __________________________________________________ 10
5. Entry and modification of parameters _________________________________ 11
Reminder ______________________________________________________ 11
Entry principle __________________________________________________ 11
Entry via numeric keypad _________________________________________ 11
Entry using arrow keys ___________________________________________ 12
Deleting characters ______________________________________________ 12
E
Magelis E - 3
Contents
E - 4 Magelis
1. Contents of the application
E
1. Contents of the application
This application is suitable for any XBT Magelis with a display which has
20 characters per line, and an entry keypad.
It consists of : 2 application pages and 1 alarm page.
Page 1
Quantity :
Production management->
(read/write access to thenumeric field of word %MW1)
(the key calls up page 2)
Page 2
Production management
NB of products : (read-only access to the numeric field of word %MW2)
Magelis
Alarm 1
Output fault Page displayed when bit 0 of word
14 (%MW14) is at 1
For this application, the designer wants the PLC to request the display of an application page, light the function key LEDs and use the function key states (if the Magelis terminal used has them).
Composition of the dialog table (
see chapter A, § Principle of terminal "command and status" exchanges, Page 21 ) between the
terminal and the PLC
Word10 : Static Function keys
Word11 : Page number to process
Word12 : Writing table authorization
Word13 : Static function keys LED’s command
Word14 : Alarm table
The word syntax depends on the protocol used (example : UNITE V2.0
protocol -> word 10=%MW10). The terminal will be able to write these words if the value of word 12 (authorization) is equal in hexa-decimal to
H'A505' (05 = length of the table).
E - 5
E
2. Creation of an application using XBT-L1000
2. Creation of an application using XBT-L1000
1. Start up XBL-L1000 software.
2. Open new application by clicking on the icon
3. Select the XBT type (example : XBT-P022010).
4. Select the protocol (example : UNITELWAY) and confirm with OK
5. When the page editor displays page 1, enter the text of this page :
Quantity :
To enter the accented characters :
- select Edit/Insert characters ,
- double click on the character to be inserted,
- click on copy (the character is placed onto the clipboard),
- close the dialog box then click on the Paste icon (or
CTRL+V), the character is inserted where the cursor is located.
To create a variable field :
- click on the (0..9, A..Z) icon.
- modify the word number by entering 1 in the "i" field for the word
%MW1,
- modify the field length (example : 3),
- confirm with OK.
Enter the following line
Production management->
To create a link with page 2 :
- select "edition/insert link" menu (links to the right by default),
- confirm the dialog box "Create link" with OK
- confirm with OK, the default page number in the window "New application page".
A link with Page 2 can also be create by a funtion key (Static or dynamic with the XBT-PM).
6. Click on "Page 2" in the "Page tree" window in order to enter the contents of page 2.
E - 6 Magelis
2. Creation of an application using XBT-L1000
Production management
No of products :
- To create the variable field :
- click on the (0..9, A..Z) icon.
- modify the word number by entering 2 in the "i" field for word
%MW2,
- modify the field length (example : 3),
- click on Options ,
- select Read in the "access" zone and confirm with OK
- confirm the insertion of the field with OK.
7. Click on the icon to make the "New alarm page" window appear, click on OK to associate the page to bit 0 (selected by default) of the first alarm word n+0 (the word number will be assigned subsequently during configuration of the dialog page).
The window "Appli1-1:ALARM 1" is displayed.
Once the first line of this page has been created and reserved for timestamping the alarms, enter the alarm text from line 2.
Output fault
8. Select the Configuration/Terminal parameters menu .
To display page 1 when the terminal is started up :
- Deselect system page, select Application Page
- Click on 1: page1 . to select page 1
- Check that the language selected is correct and confirm with OK.
9. Configuration of the dialog table .
- Select the Configuration/Dialog table menu
- Click on Number of displayed page in the "Dialog table" zone, then
Delete .
- To declare the start address of the PLC dialog table, click on Modify in the address zone, enter 10 in the " i" field (start of the dialog table in %MW10) and confirm with OK.
E
Magelis E - 7
2. Creation of an application using XBT-L1000
10. Confirm with OK.
To assign a word to the display of the alarm page, click on Alarm table in the "Dialog table" zone, then enter 1 in the "Selected function size" zone and confirm with OK.
11. Save the application with the File/Save menu (default name : appli1.dop).
E - 8 Magelis
3. Loading the application into the terminal
3. Loading the application into the terminal
1. Power up the terminal
2. Connect the PC to the terminal (XBT Z915 cable) then select the
Transfer/Export command to transfer the application to the terminal.
Magelis E - 9
E
4. PLC application
4. PLC application
The dialog table (%MW10 to %MW14) can be used if the authorization word (%MW12) is equal to A505 in hexadecimal.
The designer can use various words from the dialog table.
Word %MW10 contains the image of the function keys (F1 key pressed
: bit %MW10,0=1).
Word %MW11 contains the number of the page to be displayed (1 or 2 in the example).
Word %MW13 controls the display of the function key LEDs (F1 key bit
%MW13,0).
Setting bit %MW14,0 to 1 makes the alarm page appear blinking, press
ENTER to steady the display.
After transferring the application into the terminal, connect the latter to the PLC (see service instructions for wiring : example cable XBT-Z968 for TSX07 with UNITELWAY).
E - 10 Magelis
5. Entry and modification of parameters
5. Entry and modification of parameters
Reminder
A page is composed of texts and fields. A field may correspond to values which have to be filled in (write) or modified (read/write) by the user or to values written by the PLC.
Example :
Ex.
Quantity :
Production management ->
Text Field
Entry principle
Entry mode is accessed using the MOD key.
- If the field contains more than 1 digit, the digit to be entered is displayed in steady mode, while other digits blink.
- If the field contains 1 digit, the digit to be entered blinks.
Entry via numeric keypad
Keys 0 to 9 and +/- (toggle function, + is the default sign) are used to enter data.
- Enter the first digit, the following digit (to the right) stops blinking.
- Enter the second digit.
- Enter the other digits and confirm the whole entry with ENTER.
E
Magelis E - 11
5. Entry and modification of parameters
Entry using arrow keys
- Select position on the digit to be entered using the arrow keys.
- Increment or decrement the value of the digit with the arrow keys.
- Go to the next digit with the arrow keys.
- Confirm the whole entry with ENTER .
Deleting characters
The DEL key deletes the character to the left of the steady digit.
To delete the last steady digit :
- Move the cursor using the right arrow key.
- Press the DEL key.
E - 12 Magelis
Magelis
Chapter F
Appendices
F - 1
F
F - 2 Magelis
Contents
Contents
This chapter includes the following topics :
1. XBT technical sheets _______________________________________________ 5
XBT-H _________________________________________________________ 5
XBT-HM ________________________________________________________ 8
XBT-P ________________________________________________________ 11
XBT-PM _______________________________________________________ 14
XBT-E ________________________________________________________ 17
2. Glossary _______________________________________________________ 19
Alarm page ____________________________________________________ 19
Application page ________________________________________________ 19
Command table _________________________________________________ 19
Confidential mode _______________________________________________ 20
Dialog table ____________________________________________________ 20
JBUS master ___________________________________________________ 20
JBUS slave ____________________________________________________ 20
Links _________________________________________________________ 20
Recording mode ________________________________________________ 20
Status table ____________________________________________________ 20
UTW client _____________________________________________________ 20
UTW server ____________________________________________________ 20
Variable field ___________________________________________________ 20
XBT application _________________________________________________ 21
XBT-L1000 _____________________________________________________ 21
3. Error messages __________________________________________________ 21
F
Magelis F - 3
Contents
F - 4 Magelis
1. XBT technical sheets
F
1. XBT technical sheets
XBT-H
XBT-H002010, XBT-H001010 front panel.
XBT-H021010, XBT-H020010 front panel.
Function keys
F1 F2 F3 F4
Service keys
XBT-H011010, XBT-H012010, XBT-H012110 front panel.
XBT-H811050 front panel.
Service keys
F
Magelis F - 5
1. XBT technical sheets
Display unit types
Serial link
Data exchange protocol
Memory
*XBT-H811050 : no back-lit LCD (5*7 pixels),
XBT-H0.1010 : back-lit LCD (5*7 pixels), height 9 mm.
XBT-H0.2.10 Fluorescent green matrix for each character (5*7 pixels), height 5 mm.
RS232/RS485/RS422 asynchronous serial link.
Can be remotely loaded from diskette protocol using
XBTL-1000 software.
Protocol : UNI-TE, MODBUS, JBUS, Siemens, Allen
Bradley, Omron, KS Modicon...
*XBT-H811050: UNI-TE protocol only.
128 kb Flash EEPROM, capacity of approximately 200 application pages. Up to 256 alarm pages, depending on page distribution. 256 kb
Flash EEPROM on XBT-H01XXXX
*XBT-H811050: 100 application pages,
128 alarm pages.
English, French, Spanish, Italian, German Language version
Weight
Temperature
Power supply
Degree of protection
Mounting and fixing
0.600 Kg / 1,323 lbs
Operation : 0 to 50 ° C (32,0 ° to 122,0 ° F) Humidity
85%
Storage :
- 40 ° + 70 ° C (-40+158 ° F) for a fluorescent display
- 20 ° + 60 ° C (-4,0 ° +140 ° F) for an LCD display
*XBT-H811050: supplied by TSX07 (use XBT-Z968-03 cable ),XBT-H0XXXXX:
24VDC
Limits : 18 to 30 VDC
Ripple : 5% max
Consumption : 10W (XBT-H811050: 1,5 W) .
IP65 according to IEC529 and degree 1 as per
NFC20-010 UL Type 4,4x, Nema 4
Flush mounted, fixed by 4 pressure mounted bolts supplied on a 1 to 6 mm thick panel.
F - 6 Magelis
1. XBT technical sheets
Specific characteristics
Terminal
XBT-H002010
XBT-H001010
XBT-H021010
XBT-H022010
XBT-H011010
XBT-H012010
XBT-H012110
Display
Function
Keys
Service
Keys
Numeric
Keys
Alphanume ric Keys
Signalling
DEL
Printer Link
Real-time clock
0
0
0
2 lines of 20 caracters
4
1
0
0
Communication
0
- Communication
- Return key
- Function key : 4
- Service key : 0
No
0
5
0
0
- Communication
- Return key
- Function key : 0
- Service key : 2
No
RS232 asynchronous serial link for
XBT-H012110
Acces to PLC real time clock
*XBT-
H811050
None
No
0
0
0
5
F
Magelis F - 7
1. XBT technical sheets
XBT-HM
XBT-HM007010 front panel
XBT-HM027010 front panel
Service keys
F1 F2 F3 F4
Function keys
XBT-HM017010 and XBT-HM 017110 front panell
F - 8
Service keys
Magelis
1. XBT technical sheets
Display unit types
Serial link
Data exchange protocol
Memory
Language version
Weight
Temperature
Power supply
Degree of protection
Mounting and fixing
Matrix LCD monochrome (240*64 pixels),
8*40 characters with possibility of:
- 4*40 characters (double height)
- 8*20 characters (double width)
- 4*20 characters (double size)
RS232/RS485/RS422 asynchronous serial link
Can be downloaded from protocol diskette using XBT-
L1000 software.
Protocols : Uni-Telway, Modbus, Jbus, Siemens, Allen
Bradley, Omron, Modicon KS….
384 kb Flash EPROM, giving a capacity of approximately 300 application pages. The maximum number of alarm pages is 256 depending on page distribution.
French, English, Spanish, Italian, German
0.600 Kg / 1.1 lbs
Operation : 0 to 50 ° C (32 to 122 ° F), humidity 0 to 85%
Storage : - 20 ° to + 60 ° C (-40 to +140 ° F)
24 VDC
Limits : 18 to 30 VDC
Ripple : 5% max
Consumption : 15 W
IP65 to IEC529 and degree 1 to NFC20-010 UL Type
4,4x, Nema 4
Flush mounted, attached by 6 spring clips to a 1 to 6 mm thick panel.
F
Magelis F - 9
1. XBT technical sheets
Specific characteristics
Terminal
Function
Keys
Service
Keys
XBT-HM007010
Signalling DEL
Printer Link
-
Real Time Clock
0
0
No
XBT-H027010
4
1
- communication
- return key
- function key: 4
- service key: 0
No
XBT-HM017010
XBT-HM017110
0
5
- communication
- return key
- function key: 0
- service key: 2
RS232 asyncronous serial link for
XBT-H017110
Acces to PLC real time clock
F - 10 Magelis
1. XBT technical sheets
XBT-P
XBT-P011010, XBT-P012010 front panel.
Function keys
Service keys
F1
F3
F2
F4
F5 F6
F7 F8
XBT-P021010, XBT-P022010, XBT-P022110, XBT-P021110 front panel.
F1
F3
F2
F4
F5 F6
F7 F8
F9 F10
F11 F12
F
Magelis F - 11
1. XBT technical sheets
Display unit types
Serial link
Data exchange protocol
Memory
Language version
Weight
Temperature
Power supply
Degree of protection
Mounting and fixing
XBT-P0.1.10 back lit LCD (5*7 pixels), height 9 mm.
XBT-P0.2.10 : Fluorescent green matrix for each character (5*7 pixels), height 5 mm.
RS232/RS485/RS422 asynchronous serial link
Can be remotely loaded from the diskette protocol using XBTL-1000 software.
Protocol : UNI-TE, MODBUS, JBUS, Siemens, Allen
Bradley, Omron... .
256 kb Flash EEPROM, capacity of approximately 400 application pages. Up to 256 alarm pages, depending on page distribution.
English, French, Spanish, Italian, German
0,800 kg / 1,985 lbs
Operation : 0 to 50 ° C (32,0 ° to 122,0 ° F) Humidity 85%
Storage :
-40 ° + 70 ° C (-40+158 ° F) for a fluorescent display
-20 ° + 60 ° C (-4 ° + 140 ° F) for a LCD display
24VDC
Limits : 18 to 30 VDC
Ripple : 5% max
Consumption : 10W
IP65 according to IEC529 and degree 1 as per NFC20-
010 UL Type 4,4x, Nema 4
Flush mounted, fixed by 8 pressure mounted bolts on a
1 to 6 mm panel.
F - 12 Magelis
1. XBT technical sheets
Specific characteristics
Terminal
Display
Function
Keys
Service
Keys
Numeric
Keys
Alphanum eric Keys
XBT-P011010
XBT-P012010
2 lines of 20 characters
8
9
0
Signalling
DEL
0
Communication LED
Return key LED
Function key : 8 LED
Service key : 7 LED
Printer
Link
Real-time clock
No
Access to PLC realtime clock
XBT-P021010
XBT-P022010
2 lines of 20 characters
12
10
XBT-P021110
XBT-P022110
2 lines of 20 characters
12
10
12 12
0
Communication LED
Return key LED
Function key : 12 LED
Service key : 7 LED
No
Access to PLC realtime clock
0
Communication LED
Return key LED
Function key : 12 LED
Service key : 7 LED
RS232 asynchronous serial link
Access to PLC realtime clock
F
Magelis F - 13
1. XBT technical sheets
XBT-PM
XBT-PM027010 and XBT-PM027110 front panel
Dynamic
Function keys
R1
R3
F1
F3
F2
F4
F5 F6
R2
R4
F7 F8
F9 F10
F11 F12
Service keys Static Function keys
F - 14 Magelis
1. XBT technical sheets
Display unit types
Serial link
Data exchange protocol
Memory
Language version
Weight
Temperature
Power supply
Degree of protection
Mounting and fixing
Matrix LCD monochrome (240*64 pixels),
8*40 characters with possibility of:
- 4*40 characters (double height)
- 8*20 characters (double width)
- 4*20 characters (double size)
RS232/RS485/RS422 asynchronous serial link
Can be downloaded from protocol diskette using XBT-
L1000 software.
Protocols : Uni-Telway, Modbus, Jbus, Siemens, Allen
Bradley, Omron, Modicon KS….
512 kb Flash EPROM, giving a capacity of approximately 400 application pages. The maximum number of alarm pages is 256 depending on page distribution.
French, English, Spanish, Italian, German
0.800 Kg / 1,985 Lbs
Operation : 0 to 50 ° C (32 to 122 ° F), humidity 0 to 85%
Storage : - 20 ° to + 60 ° C (-40 to +140 ° F)
24 VDC
Limits : 18 to 30 VDC
Ripple : 5% max
Consumption : 15 W
IP65 to IEC529 and degree 1 to NFC20-010 UL Type
4,4x, Nema 4
Flush mounted, attached by 6 spring clips to a 1 to 6 mm thick panel.
F
Magelis F - 15
1. XBT technical sheets
Specific characteristics
Terminal XBT-PM027010
Function
Keys
Service
Keys
12 Static
4 Dynamic
10
Numeric
Keys
Alphanumer ic Keys
12
0
Signalling
DEL
- Communication LED
- Return key LED
- Dynamic Function key : 4 LED
- Static Function key : 12 LED
- Service key : 7 LED
Printer Link No
Real-time clock
Access to PLC real-time clock
XBT-PM027110
12 Static
4 Dynamic
10
12
0
- Communication LED
- Return key LED
- Dynamic Function key : 4 LED
- Static Function key : 12 LED
- Service key : 7 LED
RS232 asynchronous serial link
Access to PLC real-time clock
F - 16 Magelis
1. XBT technical sheets
XBT-E
XBT-E013010, XBT-E014010, XBT-E013110, XBT-E014110 front panel.l
F1
F3
F2
F4
F5
F7
F6
F8
F9 F10
F11 F12
F13 F14
F15 F16
F17 F18
F19 F20
F21 F22
F23 F24
XBT-E015010, XBT-E016010, XBT-E015110, XBT-E016110 front panel.l
Magelis
F1
F3
F5
F7
F9 F10
F11 F12
F2
F4
F6
F8
F13 F14
F15 F16
F17 F18
F19 F20
F21 F22
F23 F24
F
F - 17
1. XBT technical sheets
Display unit types
Serial link
Data exchange protocol
Memory version
Weight
Language
Temperature
Power supply
Degree of protection
Mounting and fixing
XBT-E013.10, XBT-E015.10 : back lit LCD (5*7 pixels), height 9 mm.
XBT-E014.10,XBT-E016.10 : Fluorescent green matrix for each character (5*7 pixels), height 5 mm.
RS232/RS485/RS422 asynchronous serial link
Can be remotely loaded from the diskette protocol using XBTL-1000 software.
Protocols : UNITE, MODBUS, JBUS, Siemens, Allen
Bradley, Omron...
384 kb Flash EEPROM
-for 2 lines per page, approximately 800 application pages. Up to 256 alarm pages, depending on page distribution.
-for 4 lines per page, approximately 400 application pages. Up to 128 alarm pages, depending on page distribution.
English, French, Spanish, Italian, German
1,3 kg / 2,866 lbs
Operation : 0 to 50 ° C (32,0 ° to 122,0 ° F) Humidity 85%.
Storage :
-40 ° + 70 ° C (-40+158 ° F) for a fluorescent display
-20 ° + 60 ° C (-4 ° +140 ° F) for an LCD display
24VDC
Limits : 18 to 30VDC
Ripple : 5% max
Consumption :
-10 W (LCD display)
-20 W (fluorescent display)
IP65 according to IEC529 and NFC20-010 UL Type
4,4x, Nema 4
Flush mounted, fixed by 10 pressure mounted bolts on a 1 to 6 mm panel.
F - 18 Magelis
2. Glossary
Specific characteristics
Terminal
XBT-E013010
XBT-E014010
XBT-E013110
XBT-E014110
XBT-E015010
XBT-E016010
XBT-E015110
XBT-E016110
Display 2 lines of 40 characters
Function Keys 24
2 lines of 40 characters
Service Keys 10
Numeric Keys 12
Alphanumeric Keys 15
Signalling DEL
Communication LED, return key LED
Function key : 24 LED, service key : 7 LED
Printer Link
XBT-E013110, XBT-E015110
XBT-E014110, XBT-E016110
RS232 asynchronous serial link
Real-time clock Yes
Alarm relay
Mini 1mA/ 5V AC/DC
Maxi 0.5A/24V AC/DC
(
see chapter B, "Control of alarm relay : XBT-E",
)
2. Glossary
Alarm page
Page displayed after a control system fault.
Application page
Page displayed to monitor and control the control system.
Command table
Part of the dialogue table filled in by the PLC (orders passed to the terminal).
F
Magelis F - 19
2. Glossary
Confidential mode
Mode allowing access to all operation functions of the terminal and connected functions.
Dialog table
Table of words containing all the information necessary for control and operation of Magelis terminal.
JBUS master
Device which requests J-BUS functions (write or read).
JBUS slave
Device responding to the requests of a J-BUS master.
Links
Association between application pages.
Recording mode
Mode used for XBT-L1000<-> MAGELIS exchanges.
Status table
Part of the dialog table filled in by the terminal (terminal status).
UTW client
Device which requests UNITE services, i.e. is capable of sending UNITE requests.
UTW server
Device responding to requests for UNI-TE services from client devices.
Variable field
Zone of an XBT display unit configured to display and/or modify a piece
F - 20 Magelis
3. Error messages of information depending on the value of an object in the connected control system.
XBT application
Set of data describing the man/machine dialog with a Magelis terminal.
XBT-L1000
Software for creating man/machine dialog applications.
3. Error messages
System messages generated by the XBT (system messages in English only), which cannot be configured.
WIRING FAULT
SWITCH POWER OFF : Incorrect wiring.
WAITING FOR TRANSFER : Awaiting remote loading.
NO PROGRAM : Product has no application (Version 1.1).
NO APPLICATION : Product has no application (Version 2.1).
DOWNLOAD IN PROGRESS : Download to the XBT in progress.
DOWNLOAD ABORTED : Download to the XBT cancelled by the Op.
DOWNLOAD FAILED : Download to the XBT failed.
DOWNLOAD COMPLETED : Download to the XBT finished.
UPLOAD IN PROGRESS : Upload to the PC in progress.
UPLOAD ABORTED : Upload to the PC cancelled by the operator.
UPLOAD FAILED : Upload to the PC failed.
UPLOAD COMPLETED : Upload to the PC finished.
F
Magelis F - 21
3. Error messages
CONNECTING : Reading the cable and searching for the communication configuration in progress.
APPLICATION FAULT : Application error (incoherence).
OUT OF MEMORY : No more RAM memory available
STACK OVERFLOW N : stack capacity overflow of tast n
CONNECTING FAULT : Configuration error of protocol software
SWITCH POWER OFF : Fatal error of terminal’s Run Time
CS : x IP : x
F - 22 Magelis
3. Error messages
Magelis
System messages generated by the XBT in 5 languages (language selected during configuration).
WRONG PASSWORD : Entry of an incorrect password.
PAGE DOES NOT EXIST: Call-up of a non existent page.
PROTECTED ACCESS PAGE : Call-up of a protected page.
IMPOSSIBLE TO WRITE VARIABLE IN PLC : A variable is written to a protected zone.
OVERFLOW MIN <= VALUE <= MAX : Entry of a value which is outside the limits.
DIALOG TABLE AUTHORIZ. : Authorization word is incorrect.
DIALOG TABLE READING IMPOSSIBLE : Connection problems between XBT <-> PLC.
DIALOG TABLE WRITING IMPOSSIBLE : Writing to a protected zone or XBT <-> PLC connection problems.
PRINTING ACNOWLEDGED : Transient message if after one of the options has been selected, printing is possible.
PRINTING IMPOSSIBLE : Transient message if printing is in progress.
PRINTER FAULT : Transient message if printer is faulty.
LOG EMPTY : Transient message if the log is empty when display or printing log is requested by the operator.
ACCESS PROHIBITED : Fleeting display if the action is prohibited after one of the options has been selected.
DATA NOT ACCESSIBLE : Fleeting display after a non authorized variable has been entered.
PAGE NOT ACCESSIBLE : Fleeting display after a non existent page has been called.
MASTER FAULT : Special case of a server protocol when the client is in fault condition.
F
F - 23
3. Error messages
F - 24 Magelis
INDEX
Magelis I - 1
I
I - 2 Magelis
INDEX
A
Alarm display
Alarm log
Alarm pages
Alarm relay
Alarms
Application
Application pages
Assigning function keys
C
Clear log
Confidential mode
Configuration
Contents of the dialog table
Control of alarm relay
D
I
Dialog table
Display priority
Display when powered up
,
Displaying a page via a function key
Displaying a page via its name
Displaying a page via its number
F
Form pages
Forms
Function keys
G
General characteristics
Indicator lamps
Magelis I - 3
I
INDEX
K
Keys
L
Language
Links
Locking function keys via the PLC
Log display
M
Magelis - PC link
Magelis - PLC/control system link
Magelis - printer link
Modification of variables
Momentary contact command
N
Numbered list
,
P
Page display initiated by the PLC
Page display via links
Parameters entry
,
Password
Print log
Process control
Product references
Push on/push off toggle command
R
Recording mode
Running mode
S
Selftest
Starting up
I - 4 Magelis
INDEX
T
Terminal operating modes
Timer
V
Variable fields
X
XBT-E
XBT-H
XBT-HM
XBT-P
XBT-PM
Magelis I - 5
I
INDEX
I - 6 Magelis
Magelis terminals XBT-H/HM/P/E/PM
A
ALIMENTATION / ALIMENTATION / STROMVERSORGUNG
ALIMENTAZIONE / ALIMENTACION :
24V DC
Sur les produits équipés d'un fusible réarmable, déconnecter l'alimentation pendant plusieurs secondes afin de pouvoir réarmer le fusible.
For the items with a rearming fuse, before rearming, switch off the power supply during several seconds.
Für Produkte mit einer einsteckbaren Sicherung, bitte die Stromversorgung während mehreren Sekunden abschalten, um die Sicherung wieder einstecken zu können.
Sui prodotti attrezzadi di un fusibile riarmado, sconnettere l'alimentazione durante parecchi secondi a fine di pottere riarmare il fusibile.
Sobre los productos equipados con un fusible rearmable, antes de réarmar el fusible, desconectar la alimentación durante unos segundos.
Informations réservées à certaines législations locales.
Information reserved for local legislation.
Diese Informationen sind abhängig vonden Gesetzen des jeweiligen Landes.
Informazioni riservate a talune direttive locali.
Informaciones reservadas a la legislación de su país.
DANGER
HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION.
• This equipment must be installed or servied only by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipement.
• Always use a properly rated voltage to supply this equipment.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR
SERIOUS INJURY.
M
Magelis M - 7
Magelis terminals XBT-H/HM/P/E/PM
Informations réservées à certaines législations locales.
Information reserved for local legislation.
Diese Informationen sind abhängig vonden Gesetzen des jeweiligen Landes.
Informazioni riservate a talune direttive locali.
Informaciones reservadas a la legislación de su país.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter and apply this product.
Failure to observe this precaution can result in death, severe personal injury or equipment damage.
CAUTION
EQUIPMENT DAMAGE HAZARD
The XBT should only be installed and used by the authorized personnel that has been assigned the appropriate confidential mode PASSWORDS by the project manager.
Failure to observe this precaution can result in equipment damage or production loss.
CAUTION
EQUIPMENT DAMAGE HAZARD
Since all alarms are always time/date stamped and the control program may rely on the XBT's real time clock, it is important to set or verify the XBT's date and time after every new installation, repair, disassembly, shipping or battery change.
Failure to observe this precaution can result in equipment damage or production loss.
M - 8 Magelis
Magelis terminals XBT-H/HM/P/E/PM
ENVIRONNEMENT / ENVIRONMENT / UMGEBUNG / AMBIENTE / ENTORNO
- Température de fonctionnement
- Ambient operation temperature
- Betriebstemperatur
- Temperatura ambiente di funzionamento
- Temperatura ambiente de funcionamiento
- Température de stockage
- Storage temperature
- Lagerungstemperatur
- Temperatura ambiente di stoccaggio
- Temp. ambiente de almacenamiento
- Humidité relative (sans condensation)
- Humidity (without condensation)
- Luftfeuchtigkeit (ohne Kondensierung)
- Umidità (senza condensazione)
- Humedad (sin condensación)
LCD / FLUO / Matriciel : 0 °C… +50 °C
FLUO : -40 °C… +70 °C
LCD :• 2 lignes
• 4 lignes
/ 2 lines / 2 Zeilen / 2 linee / 2 líneas /
-20 °C… +70 °C
/ 4 lines / 4 Zeilen / 4 linee / 4 líneas /
-20 °C… +60 °C
Matriciel : - 20 °C...+60 °C
0 … 85 %
IEC 68 - 2 - 6
0,075 mm 10 Hz - 57 Hz
1 g 57 Hz - 150 Hz
_
- Protection (face avant)
- Protection (front face)
- Schutzart (für die Frontseite)
- Protezione (lato anteriore)
- Protección (panel frontal)
- Protection (face arrière)
- Protection (real face)
- Schutzart (für die Rûckseite)
- Protezione (lato posteriore)
- Protección (cara trasera)
IP 65 - Nema 4
(IEC 529 - NF C 20010 - UL Type 4,4x indoor)
IP 20
- Tenue aux décharges électrostatiques
- E.S.D. withstand
- Elektrostatische Verträglichkeit
- Tenuta alle scariche elettrostatiche
- Resistencia a descargas electroestáticas
- Perturbations électromagnétiques
- Electromagnetic interference
- Elektromagnetische Verträglichkeit
- Perturbazioni elettromagnetiche
- Perturbaciones electromagnéticas
- Perturbations électriques
- Electrical interference
- Elektrische Verträglichkeit
- Perturbazioni elettriche
- Perturbaciones eléctricas
IEC 1000 - 4 - 2 niveau 3 / level 3 / Grad 3 / livello 3 / nivel 3
IEC 1000 - 4 - 3
10 V / m
IEC 1000- 4 - 4 niveau 3 / level 3 / Grad 3 / livello 3 / nivel 3
- Chocs / Shocks/
Shockfestigkeit/ Urti/ Impactos
IEC 68 - 2 - 27 impulsion 1/2 sinusoïdale 11 ms, 15 g dans les 3 axes/
1/2 sinusoidal pulse for 11ms, 15 g on 3 axes/
11 ms, 15 g halbsinusförmige Impulse in 3 Achsen / impulso 1/2 sinusoide 11 ms, nei 3 assi 15 g / impulso 1/2 sinusoidal 11 ms, 15 g en los 3 ejes.
- Vibrations / Vibration/
Vibrationsfestigkeit/ Vibrazioni/
Vibraciones
Magelis M - 9
M
Magelis terminals XBT-H/HM/P/E/PM
ETIQUETTES RELEGENDABLES PREDECOUPEES (mise en place) / PERSONNALISABLE
PRE-CUTLABELS (mounting) / VERÄNDERBARE ETIKETTEN (Einsetzen) / ETICHETTE
RINOMINABILI (inserimento) / ETIQUETAS RENOMBRABLES (colocación)
XBT-H•••••• XBT-HM••••••
Ref.: XBL YH4
XBT-P•••••• XBT-PM•••••• Ref.: XBL YHM4
Ref. : XBL YP8
Ref. : XBL YP12
XBT-E••••••
Ref. : XBL YE24
M - 10 Magelis
Magelis terminals XBT-H/HM/P/E/PM
Lors de l'installation du terminal sur son support, bien vérifier que l'extrémité de l'étiquette relégendable n'est pas positionnée entre le support et le joint du terminal.
En effet si l'ensemble est soumis à des projections de liquide, il peut y avoir pénétration du liquide dans le terminal par les étiquettes relégendables. Ce qui peut entraîner des défauts de fonctionnement ou choc électrique.
When installing the terminal on its support, make sure that the end of the re-usable label is not positioned between the support of the terminal and the seal.
If it is and the assembly is subject to splashes of projections of liquid, the liquid may penetrate inside the terminal via the labels. This may cause operating faults or electric shocks.
Beim Installieren des Terminals auf seinem Träger muss dafür gesorgt werden, dass das Ende des
Etiketts, das mit einem neuen Text versehen werden kann, nicht zwischen den Träger und die
Terminaldichtung zu liegen kommt.
Wird die Einheit nämlich Flüssigkeitsspritzern ausgesetzt, kann an der Stelle des Etiketts Flüssigkeit in das Terminal eindringen und Betriebsmängel oder Elektroschock verursachen.
Durante l'installazione del terminale sul rispettivo supporto, verificare bene che l'estremità dell'etichetta leggendaria non sia posizionata tra il supporto e il giunto del terminale.
Infatti se il complesso è soggetto a schizzi di liquido, possono verificarsi penetrazioni del liquido nel terminale attraverso le etichette leggendarie, il che può provocare malfunzionamenti o scosse elettriche.
Al instalar el terminal sobre su soporte, verificar que la extremidad de la etiqueta de personalización no esté entre el soporte y la junta del terminal.
De facto, en caso de exposición del producto a proyecciones de líquido, éste puede penetrar al interior por las etiquetas, lo que pudiera provocar fallos o choque eléctrico.
Magelis M - 11
M
Magelis terminals XBT-H/HM/P/E/PM
ENCOMBREMENTS / DIMENSIONS / ABMESSUNGEN / DIMENSIONI / DIMENSIONES
A G
F
K
D C E
M - 12 Magelis
Magelis terminals XBT-H/HM/P/E/PM
ENCOMBREMENTS / DIMENSIONS / ABMESSUNGEN / DIMENSIONI / DIMENSIONES mm ( inches )
G
H
E
F
C
D
A
B
I
J
K
XBT H
202
(7,952)
102
(4,016)
183,8
(7,236)
12,35
(0,486)
5,85
(0,230)
7
(0,275)
50
(1,968)
6,2
(0,244)
89,6
(3,527)
6,2
(0,244)
120
(4,724)
XBT HM
202
(7,952)
111,3
(4,50)
190,4
(7,630)
5,8
(0,228)
5,8
(0,228)
7,1
(0,279)
57,7
(2,271)
5,8
(0,228)
93,4
(3,66)
12,1
(0,476)
/
( / )
XBT P
253
(9,960)
152
(5,984)
234,5
(9,232)
10
(0,394)
8,5
(0,334)
7
(0,275)
55,4
(2,181)
6,2
(0,244)
133,3
(5,248)
12,5
(0,492)
120
(4,724)
MASSE / WEIGHT / GEWICHT / PESO / PESO
Kg
(lbs)
0,6
(1,321)
0,6
(1,321)
0,8
(1,762)
XBT PM
254
(10)
156
(6,142)
234,5
(9,232)
10
(0,394)
10
(0,394)
7
(0,275)
53
(2,086)
6,2
(0,244)
133,3
(5,248)
16
(0,629)
120
(4,724)
0,8
(1,762)
XBT E
292
(11,456)
202
(7,953)
264
(10,354)
19
(0,748)
9
(0,354)
7
(0,275)
58
(2,283)
7
(0,275)
182,5
(7,185)
12,5
(0,492)
120
(4,724)
1,5
(3,304)
Magelis M - 13
M
Magelis terminals XBT-H/HM/P/E/PM
DECOUPE DU PANNEAU / PANEL CUT-OUT / AUSSCHNITT FÜR TRÄGERPLATTE /
APERTURA NEL PANNELLO / MECANIZADO DEL SOPORTE /
R 3,5 maxi / 2 mini
(0,138 > R > 0,079)
A +/- 0,4
(A +/- 0,015)
A
B
XBT H
184,5
(7,260)
90,5
(3,558)
XBT HM
190,9
(7,508)
99,2
(3,906)
XBT P
235
(9,252)
134
(5,276)
XBT PM
235
(9,252)
134
(5,276)
XBT E
265
(10,433 )
183
(7,205)
EPAISSEUR DU SUPPORT / THICKNESS OF SUPPORT / DICKE DER TRÄGER-PLATTE /
SPESSORE DEL SUPPORTO/ ESPESOR DEL SOPORTE :
1,5…6 mm
(0,06…0,24 inch)
M - 14 Magelis
Magelis terminals XBT-H/HM/P/E/PM
MONTAGE XBT-H/P/E / MOUNTING XBT-H/P/E / EINBAUHINWEISE XBT-H/P/E/
MONTAGGIO XBT-HH/P/E/ MONTAJE XBT-HH/P/E
Les afficheurs XBT-H/P/E se fixent sur le panneau au moyen de 8 ou 10 verrous encliquetables
XBT-H/P/E displays are attached to the panel by means of 8 or 10 rubber screws
Die Displays H/P/E werden an der Frontplatte mit Hilfe von 8 oder 10 elastischen Schlössern befestigt
I display XBT-H si fissano sul pannello mediante 8 o 10 chiusure elastiche
Se fijan los visualizadores XBT-H en el soporte con 8 or 10 pestillos de retención elásticos
!
1
Ancrage
2
CLIC
/ Anchorage / Befestigung /
Ancoraggio / Anclaje /
Pour garantir l'étanchéité, la surface du support doit être plane et rigide /
To ensure tightness, the panel surface must be flat and rigid /
Zur Gewährleistung der Dichtigkeit muß die
Plattenfläche eben und starr sein /
Per garantire la tenuta, la superficie del supporto deve essere piana e rigida /
Para garantizar la estanqueidad, el panel del soporte debe ser plano y rígido /
Verrou encliquetable / Rubber screw /
Elastischer Schloßer / Chiusura elastica /
Pestillo elástico /
8 points d'ancrage / 8 anchorage points /
8 Befestigungspunkte / 8 punti di ancoraggio /
4 puntos de anclaje /
" Encliquetage / Locking /
Sperrung / Arresto / Enclavamiento /
Position des points d'ancrage des verrous en fonction de l'épaisseur du panneau /
Position of rubber anchorage points depending on panel thickness /
Lage der Befestigungspunkte des elastischen Schloßers abhängig von der Dicke der Platte /
Posizione dei punti di ancoraggio della chiusura elastica in funzione dello spessore del pannello /
Posición de los puntos de enclaje del pestillo elástico según el espesor del soporte /
Points d'ancrage avec panneau 1,5 - e - 4 mm /
(0,06 - e - 0,157 inche)
Anchorage point on 1.5 - e 4 mm panel /
Befestigungspunkt für Platte 1,5 - e 4 mm /
Punto di ancoraggio del pannello 1,5 - e 4 mm /
Punto de anclaje con soporte 1,5 - e 4 mm /
Point d'ancrage avec panneau 4 - e - 6 mm /
(0,157 - e - 0,236 inche)
Anchorage point on 4 - e - 6 mm panel /
Befestigungspunkt für Platte 4 - e - 6 mm /
Punto di ancoraggio del pannello 4 - e - 6 mm /
Punto de anclaje con soporte 4 - e - 6 mm /
M
Magelis M - 15
Magelis terminals XBT-H/HM/P/E/PM
MONTAGE XBT-HM/PM / MOUNTING XBT-HM/PM / EINBAUHINWEISE XBT-HM/PM /
MONTAGGIO XBT-HM/PM/ MONTAJE XBT-HM/PM
Les afficheurs XBT-HM/PM se fixent sur le panneau au moyen de 6 agrafes à ressort
XBT-HM/PM displays are attached to the panel by means of 6 rubber screws
Die Displays XBT-HM/PM werden an der Frontplatte mit Hilfe von 6 elastischen Schlössern befestigt
I display XBT-HM/PM si fissano sul pannello mediante 6 chiusure elastiche
Se fijan los visualizadores XBT-HM/PM en el soporte con 6 pestillos de retención elásticos
Attention au sens de montage des agrafes en fonction de l'épaisseur du support /
Caution, when setting the staples, as this depends on the thickness of the holder /
Beachten Sie, deß die Montagerichtung der Schlößer von der Dicke der Stütze abhängig ist/
Attenzione al senso di collegamento delle fibbie in funzione dello spessore del soporte /
Cuidado al sensido de montaje de las grapas, ya que dipende del espesor del suporte /
Pour garantir l'étanchéité, la surface du support doit être plane et rigide /
To ensure tightness, the panel surface must be flat and rigid /
Zur Gewährleistung der Dichtigkeit muß die Plattenfläche eben und starr sein /
Per garantire la tenuta, la superficie del supporto deve essere piana e rigida /
Para garantizar la estanqueidad, el panel del soporte debe ser plano y rígido /
6 points d'ancrage / 6 anchorage points /
6 Befestigungspunkte / 6 punti di ancoraggio / 6 puntos de anclaje /
Ancrage / Anchorage / Befestigung /
Ancoraggio / Anclaje / !
Agrafes à ressort / Rubber screw /
Elastischer Schloßer / Chiusura elastica / Pestillo elástico /
DANG
ER
+
–
Encliquetage / Locking /
Sperrung / Arresto / Enclaviamiento /
"
Déverrouillage / Unlocking /
Lösen / Sblocco / Desbloqueado/
$
CLAC clic
DANG
ER
DANG
ER
M - 16 Magelis
Magelis terminals XBT-H/HM/P/E/PM
MONTAGE XBT-HM/PM / MOUNTING XBT-HM/PM / EINBAUHINWEISE XBT-HMHM/PM /
MONTAGGIO XBT-HMHM/PM / MONTAJE XBT-HMHM/PM
Position des agrafes à ressort en fonction de l'épaisseur du panneau /
Position of rubber screw anchorage points depending on panel thickness /
Lage der Befestigungspunkte des elastischen Schloßers abhängig von der Dicke der Platte /
Posizione dei punti di ancoraggio della chiusura elastica in funzione dello spessore del pannello /
Posición de los puntos de enclaje del pestillo elástico según el espesor del soporte /
panneau 1,5 - e - 4 mm ( 0,06 - e - 0,16 inche )
1,5 - e - 4 mm panel / für Platte 1,5 - e - 4 mm /
pannello 1,5 - e - 4 mm / soporte 1,5 - e - 4 mm /
panneau 4 - e - 6 mm ( 0,14 - e - 0,24 inche )
4 - e - 6 mm panel / für Platte 4 - e - 6 mm /
pannello 4 - e - 6 mm / soporte 4 - e - 6 mm /
Informations réservées à certaines législations locales.
Information reserved for local legislation.
Diese Informationen sind abhängig vonden Gesetzen des jeweiligen Landes.
Informazioni riservate a talune direttive locali.
Informaciones reservadas a la legislacióndu su país.
CAUTION
SPRING LOADED MECHANISM
Do not release mechanism near face.
Failure to follow this instruction can result in injury
Magelis M - 17
M
Magelis terminals XBT-H/HM/P/E/PM
LIAISONS ELECTRIQUES / ELECTRICAL CONNECTIONS /
VERBINDUNGSMÖGLICHKEITEN / COLLEGAMENTI / CONEXIONES
XBT-H
XBT-HM
1
*
3
* Selon modèle / depending on unit
/ je nachModell/ secondo XBT-HM modello/ segùn modelo/
2
*
XBT-P
XBT-PM 3
1 2
XBT-E
1 3
*
2
1 - ALIMENTATION ET SORTIE RELAIS / POWER SUPPLY AND RELAY OUTPUT /
STROMVERSORGUNG UND RELAISAUSGANG / ALIMENTAZIONE E USCITA RELE /
ALIMENTACION Y SALIDA RELE /
XBT-H/ HM
XBT-P/ PM +
24V -
XBT-E
+
24V 4
• ALIMENTATION / POWER SUPPLY / STROMVERSORGUNG / ALIMENTAZIONE /
ALIMENTACION /
- Tension nominale / Nominal voltage / Nennspannung / Tensione nominale / Tensión nominal 24 V DC C
- Limites de tension (ondulation comprise) / Voltage limits (including ripple) /
Spannungsschwankung (einschl. Restwelligkeit) / Limiti di tensione (ondulazione compresa) /
Limites de tensión (ondulación incluida) 18… 30 V
- Consommation maximale / Maximal consumption / Max. Leistungsaufnahme / Consumo maximale / Consumo máximo : XBT-H / P: 10 W - XBT-HM/PM : 15W - XBT-E FLUO : 20W,
LCD:10W.
XBT-E : (3.4) SORTIE RELAIS / RELAY OUTPUT / RELAISAUSGANG / USCITA RELE / RELE DE SALIDA /
Limites d'utilisation / Usage limits / Wertebereich / Limiti d'impiego / Limites de utilización /
1.0 mA / 5V min. AC/DC - 0.5 A / 24V max. AC/DC
M - 18 Magelis
Magelis terminals XBT-H/HM/P/E/PM
2 - LIAISON SERIE / SERIAL COMMUNICATION / SERIELLE SCHNITTSTELLE /
COMMUNICAZIONE SERIALE / UNION SERIE
11
12
13
8
9
10
6
7
4
5
1
2
3
22
23
24
25
19
20
21
14
15
16
17
18
12
13
14
15
16
17
18
10
11
8
9
3
4
1
2
5
6
7
22
23
24
25
19
20
21
PG
TXD
RXD
A
B
A’
OV iso
COM
OV iso
PAR
REG
CONF
B3
B’
B4
B0
B1
B2
TERRE DE PROTECTION / PROTECTIVE GROUND /
GERÄTEMASSE / MASSA MECCANICA / TIERRA DE
PROTECCION /
RS 232 C / V24
2 - TXD : émission / transmission / Senden / emissione / emisión /
3 - RXD : réception / reception / Empfangen / ricezione / recepción /
7 - OV iso :
4 - A
5 - B
6 - A'
18 - B' commun
RS 422 / 485
émission réception
/ common / Gemeinsamer / comune / común /
/ transmission / Senden / emissione / emisión /
/ reception / Empfangen / ricezione / recepción /
7 - OV iso : commun / common / Gemeinsamer / comune / común /
ADRESSAGE MULTIPOINT / MULTIPOINT ADRESS /
MULTIPUNKTBETRIEB / MULTIPUNTO / MULTIPUNTO
(Sauf/ exept / nur bei / salvo / tranne XBT-H811050)
8 - COM (OV) commun / common / Gemeinsamer / comune / común /
14 - B0 : 2
15 - B1 : 2
0
1 actif non connecté / Active if not connected / Aktiv, wenn nicht angeschlossen / Nicht aktiv, wenn angeschlossen / Attivo se non connesso / Activo si no está conectado inactif si connecté à COM (OV) (8) / Inactive if connected to COM (OV) (8) /
Nicht aktiv, wenn angeschlossen an COM (OV) (8) / Inattivo se connesso a COM (OV) (8) / Activo si está conectado con COM (OV) (8)
16 - B2 : 2
2
17 - B3 : 2
3
19 - B4 : 2
4
24 - PAR: parité / parity / Parität / parità / paridad /
Les XBT Magelis se connectent aux principaux automates du marché. Pour les références des câbles et leurs connectiques, reportez vous aux IS protocoles /
The XBT Magelis can be connected to the main PLCs on the market. For wiring details, see the IS protocols /
Die Bedientableaus XBT von Magelis werden an die meisten SPS angeschlossen. Für die
Anschlußbelegung der Kabelstecker siehe IS-Protokolle /
Gli XBT Magelis si collegano ai principali PLC del mercato. Per i riferimenti dei cavi e i loro collegamenti, vedere i protocolli IS. /
Los XBT Magelis se conectan a los principales autómatas del mercado. Para las referencias de cables y sus conexiones, véase las IS protocolos /
M
Magelis M - 19
Magelis terminals XBT-H/HM/P/E/PM
- CONNECTER LA LIAISON SERIE HORS-TENSION / CONNECT THE SERIAL
LINK CONNECTOR WITH POWER OFF / DIE SERIELLE SCHNITTSTELLE
NUR BEI ABGESCHALTETEM GERÄT ANSCHLIESSEN / NON INSERIRE LA
CONNESSIONE SERIALE SOTTO TENSIONE / NO CONECTAR EL
CONECTOR DE LA UNION SERIE EN TENSION /
- NE RACCORDER QU'UN TYPE DE LIAISON SERIE A LA FOIS / CONNECT
ONLY ONE TYPE OFSERIAL COMMUNICATION AT A TIME / NUR JEWEILS
EINE SERIELLE SCHNITTSTELLE BELEGEN / NON UTILIZZARE PIU' DI UN
TIPO DI COLLEGAMENTOCONTEMPORA-NEAMENTE / CONECTAR TAN
SOLO UN TIPO DE UNION A LA VEZ /
- VISSER LES DEUX VERROUS DU CONNECTEUR / TIGHTEN FIXING
SCREWS / DENSCHNITTSTELLENSTECKER UNMIT BEIDEN SCHRAUBEN
BEFESTIGEN / AVVITARE LE DUE VITI DEL CONNETTORE / APRETAR LOS
DOS PESTILLOS DEL CONECTOR /
3 - LIAISON SERIE IMPRIMANTE (RS 232 C) / SERIAL PRINTER LINE (RS 232 C) /
Serielle DRUCKERSCHNITTSTELLE (RS232C) / SERIALE STAMPANTE (RS232C) /
UNION SERIE IMPRESORA (RS232C)
(Selon modèle / depending on unit / je nachModell/ secondo modello/ segùn modelo)
3
2
1
5
4
7
6
9
8
2
3
4
8
9
5
6
7
1 DCD
RXD
TXD
DTR
COM
(OV)
DSR
RTS
CTS
RI
Réservée / Reserved / Reserve /
Riservato / Reservado
Réservée / Reserved / Reserve /
Riservato / Reservado
Emission RS 232 C / RS 232 C transmission / Senden RS 232 C /
Emissione RS 232 C / Emision RS 232 C
XBT sous-tension / Power up XBT / XBT betriebsbereit /
XBT in tensione / XBT en tension
Commun RS 232 C / Common RS 232 C / Gemeinsamer RS 232 C /
Comune RS 232 C / Comun RS 232 C
Imprimante prête / Printer ready / Drucker betriebsbereit /
Stampante pronta / Impresora lista
Demande pour mettre / Request to send / Sendeanforderung XBT /
Rechiesta emissione XBT / Petición de emisión
Imprimante prête à recevoir / Printer ready / Drucker empfangsbereit /
Stampante pronta a ricevere / Impresora lista para recibir
Réservée / Reserved / Reserve /
Riservato / Reservado
M - 20 Magelis
Magelis terminals XBT-H/HM/P/E/PM
XBT-H811050
LIAISONS ELECTRIQUES / ELECTRICAL CONNECTIONS /
VERBINDUNGSMÖGLICHKEITEN / COLLEGAMENTI / CONEXIONES
1
2
A Configuration / Configuration / Konfiguration/
Configurazione / Configuraciòn
B Utilisation / Utilisation / Benutzung /
Utilizzazione / Utilizaciòn
1 ALIMENTATION / POWER SUPPLY / STROMVERSORGUNG / ALIMENTAZIONE /
ALIMENTACION /
- Tension nominale / Nominal voltage / Nennspannung / Tensione nominale /
Tensión nominal : 24 V DC
- Limites de tension (ondulation comprise) / Voltage limits (including ripple) /
Spannungsschwankung (einschl. Restwelligkeit) / Limiti di tensione (ondulazione compresa) /
Limites de tensión (ondulación incluida) : 18… 30 V
- Consommation maximale / Maximal consumption / Max. Leistungsaufnahme / Consumo máximo / Consumo maximale : 5W
+
24V -
Magelis M - 21
M
Magelis terminals XBT-H/HM/P/E/PM
2 Liaison série: alimentation par TSX07 / Serial link:TSX07 power supply /
Serrielle Schnittstelle: Stromversorgung TSX07/ Collegamenti: TSX07 alimentazione /
Conexiones: TSX07 alimentaciòn /
Câble : XBT-Z968 (03) (TSX07 <--> XBT) (l'adresse programmée dans le câble est 4) /
Cable : XBT-Z968 (03) (TSX07 <--> XBT) (Address in the cable is 4) /
Kabel : XBT-Z968 (03) (TSX07 <--> XBT) (Die programmierte Kabel-Adresse ist 4) /
Cable : XBT-Z968 (03) (TSX07 <--> XBT) (L'indirizzo programmaton el cavo è 4) /
Cavo : XBT-Z968 (03) (TSX07 <--> XBT) (La dirección programmada en el cable es 4) /
XBT-H811050
A
A'
1
4
6
B
B'
0VL
5
18
22
B0
B1
B2
B3
B4
14
15
16
17
19
PAR 24
COM ADR
GND
S DOWN
5V TSX
8
7
21
10
2 D -
TSX 07
1 D +
7 0VL
8
+ 5 V
3
6
7
4
8
5
1 2
-XBT-Z968 (03) : 2,4 m (V1.2) - XBT-Z968-1(03): 4,8 m (V1.1)
Câble : XBT-Z915 (V2.2) (PC <---> XBT). Configuration et transfert application
Cable : XBT-Z915 (V2.2) (PC <---> XBT) . Configuration and application transfert
Kabel : XBT-Z915 (V2.2) (PC <---> XBT) .Konfiguration und applikationsübertragung
Cable : XBT-Z915 (V2.2) (PC <---> XBT) . Configurazione e transferimento applicazione
Cavo : XBT-Z915 (V2.2) (PC <---> XBT) . Configuración y transferencia de applicación
Côté / Side / Seite / Lato / Lado XBT
XBT
PG
Emission
Réception
0V
TXD
RXD
SG
Connecteur 25 points mâle
25 pin male connector
25 polige Stiftleiste
Conector 25 puntos macho
Connettore 25 poli maschio
8
13
1
2
3
7
Côté / Side / Seite / Lato / Lado PC
6
4
7
8
2
3
5
1
PC/PS 9 broches / pin /
PG
RXD Réception
TXD Emission
SG 0V
RTS
CTS
DSR
DTR
M - 22 Magelis
Magelis terminal XBT-HM017010A8
XBT-HM
XBT-Z908
TSXSCA62
TSXCSAxxx
TSXSCA62
VW3A58306
VW3A8306
ATV28
ATV58
This is a Magelis operator interface that monitors up to 8 ATV28 and/ or
ATV58 drives .
The main functions are :
- display drive application data
- display faults
- display and modify drive parameters
- save modified parameters into the drive memory
This operator interface is not able to Run or Stop the Drive
Magelis M - 23
M
Magelis terminal XBT-HM017010A8
CONNECTION
- The physical address of TSXSCA62 taps is unimportant, except the address of the tap connected to the terminal which must not be 31.
- The terminal is configured to dialogue with ATV28 or ATV58 speed- drivers, with address 1 to 8.
- To optimize performance, configure drive with consecutive addresses, starting from 1.
- Refer to the ATV28/ 58 manuals for the configuration of their Modbus address.
OPERATION
Navigation principles:
- The ↑ key is used to select an equipment or a function.
- The → key validates the selection.
- ESC is used to return to the previous page.
Variable monitoring pages:
Refer to the ATV28/ 58 manuals for the meaning of the displayed variables.
“Thermal status” page
- The digital value flashes above the 100% threshold.
- The bar graph flashes above the 118% threshold.
“Fault 1/ 2” page
- This page displays the last 4 faults detected by the drive (ATV28 or ATV58).
“Fault 2/ 2” page
- This page displays the 4 previous faults (ATV58 only).
“I/ O” page
- Variables L15, L16, LO, AI3 are meaningful only for an ATV58.
- Analog inputs AI1, AI2, AI3, AO are scaled according to the ATV58 default configuration.
Adjust page:
The ACC, DEC, LSP, HSP parameters can be modified as follows:
- The MOD key is used to select the variable to modify. The selected variable flashes.
- The → key is used to select the value to modify:
the selected value stops flashing.
- The ↑ key increments the selected figure.
- Pressing ENTER validates the input.
- Pressing ESC cancels the input.
The value modified is stored in the volatile memory of drive.
- The → key is used to save modified values in case of power down.
Follow the procedure displayed on the screen.
M - 24 Magelis
Magelis terminal XBT-HM017010A8
DIAGNOSTIC HELP
Problem
Nothing lights up
The screen displays “ ???” and the indicator <=> is steady on
The screen displays
“ CONNECTING…”
Probable cause
The 24VDC power supply is down.
Wiring error
Series link connection wrong.
This value is outside the configured interval [Min., Max.].
The value is not applicable to the for mat scheduled in the configuration.
Normal transient operation: the terminal sets up dialogue with the drives.
Tip
Check that the power supply is compatible with the terminal power rating.
Check 24VDC connection.
Check connections to terminals, speed- drivers and taps TSXSCA62.
Check that the address of the tap connected to the terminal is not 31.
Check connection of the drive and its tap TSXSCA62.
The screen displays “ ???” and the indicator <=> flashes
Some displayed values do not correspond to the drive status.
The drive whose address is given on the displayed page is not correctly connected.
No drive connected has the address indicated on the displayed page.
Several drive are connected with the same Modbus address.
The drive whose address is given on the page is powered down or out-of-service.
This is information specific to an ATV58, whereas the drive used is an ATV28.
The AI3R information is wrong.
A digital value or a bar graph flashes.
The screen displays ###
Check and modify if necessary the Modbus address of the drive.
Check and modify the address of one of the drive.
Check the power supply of the drive.
These are analog inputs of an ATV28
(the terminal is configured to display the analog inputs of an ATV58).
Use an encoder card on ATV58.
If an ATV28 is used, ignore the bracketed information "ATV58". Or, use the XBT- L1000 software to adapt the application to the drives used.
Use the XBT- L1000 to adapt the scaling of these variables to an
ATV28.
Use the XBT- L1000 software to adapt scaling of this variable.
Magelis M - 25
M
Magelis terminal XBT-HM017010A8
Modify the application in order to adapt information of an ATV28 drive
Page concerned : I-O( 2/ 2)
Variables concerned : AI2 / AO
Fields information in the standard application where the scale factor fits the ATV58 drive :
Designation Variable
W480
AI2R
W482
AOR
ATV
Unity
0.002mA
[0 , 10000]
[ 0, 20 mA]
0.002mA
[0 , 10000]
[ 0, 20 mA]
XBT
Unity
%
[ 0 , 100 ]
%
[ 0 , 100 ]
XBT displaying
Numeric : ###
XBT = ATV / 100
Numeric : ###
XBT = ATV / 100
Analog Input image « AI2 »
Analog Input image « AOR »
Fields information to be adapted to the ATV28 drive :
Variable
W480
AI2R
W482
AOR
ATV
Unity
0.001mA
[0 , 20000]
[ 0, 20 mA]
0.001mA
[0 , 20000]
[ 0, 20 mA]
XBT
Unity
%
[ 0 , 100 ]
%
[ 0 , 100 ]
XBT displaying
Numeric : ###
XBT = ATV / 200
Numeric : ###
XBT = ATV / 200
Designation
Analog Input image « AI2 »
Analog Input image « AOR »
For both fields AI2 and AO from page I-O( 2/ 2) to be adapted :
1- Edit the concerned field (double- click on it )
2- Select “ Options …”
3- Modify the conversion parameters and validate the Dialog Boxes
4- Do it again for the fields AI2 and AO from the page I-O( 2/ 2) of each ATV28 drives
5- Do the same thing for all the languages used into the application
Example :
M - 26 Magelis
Telemecanique reserves the right to change the characteristics (presentation, function or utilization) of its products, materials and services at any time in order to incorporate the latest developments. The information in this document is therefore subject to change without notice and cannot be construed as containing any form of contractual obligation.
© Copyright Telemecanique 2003. All reproduction of this document is prohibited.
Copying or reproduction, even partial, by whatever means, photographic, magnetic or other, as well as any other partial or total transcription able to be read by electronic device is strictly forbidden.
XBT X000EN
12 / 2003
W914083610311 A15
Stiahnuť
Reklama