11. Configuration. Schneider Electric XBTH / P / E / HM / PM Alphanumeric and Matrix Terminals
تبلیغات
تبلیغات
11. Configuration
11. Configuration
This function, only available in confidential mode, enables the following parameters to be viewed.
- the system language,
- the application language,
- the parameters of the PLC <-> XBT line,
- the terminal date and time,
- the parameters of the Printer <-> XBT line.
Switching to the confidential mode
Press the"MENU" key to display the menu.
Position the cursor on "CONFIGURATION".
B
PAGE NUMBER _ _
LIST OF PAGES
ALARM LOG
CONFIGURATIONS
->
->
->
->
PRODUCT REFERENCES ->
SELFTEST
Access configuration. The configuration menu is displayed.
Magelis
SYSTEM LANGUAGE
APPLICATION LANGUAGE
LINE PARAMETERS
PRINTER PARAMETERS
DATE/TIME
->
->
->
->
->
System language
The language is that in which information messages and terminal menus are expressed. The operator can find out and modify the system language. Position the cursor on the corresponding line using the up and down arrow keys and then access the content using the right arrow key.
To change the language press MOD, choose the language using the up and down arrow keys and confirm with ENTER.
XBT-H, XBT-HM
Except XBT-H and
XBT-HM
XBT-P XBT-PM XBT-E
Magelis B - 43
11. Configuration
Ex.
Application language
In the XBT-L1000 software, application can be entered in 3 different languages. To find out application language, position the cursor on the corresponding line using the up and down arrow keys and access the content using the right arrow key to change the language, press MOD, select the language using the up and down arrow keys and confirm pressing ENTER.
Parameters of the PLC <-> XBT line
To ascertain the parameters of the PLC <-> XBT line, position the cursor on the corresponding line using the up and down arrow keys while in confidential mode and then access the content using the right arrow key.
According to the protocol, some parameters may or may not be modified.
The parameters displayed depend on the protocol :
UNITE protocol:
Speed in bauds,
Parity,
Slave number,
Error counter n ° 1,
Error counter n ° 2,
Error counter n ° 3,
Error counter n ° 4,
Reset the counters (Y/N)
To RESET the counters, Press
Use up and down arrow keys to indicate choice yes (Y) or no (N) to erase counter and confirm with ENTER.
Terminal date and time
To know and modify the terminal date and time, position the cursor on the corresponding line using the up and down arrow keys whilst in confidential mode and then access the content with the right arrow key.
Entry is the same as for the modification of parameters ( see § 4. Page display, Page 14
). The separators / and : may be replaced by full stops.
Magelis XBT-H, XBT-HM
Except XBT-H and
XBT-HM
B - 44
XBT-P XBT-PM XBT-E
Magelis
11. Configuration
Ex.
Access to terminal internal timer:
The DATE and TIME (DD/MM and HH:MM) can be displayed in an application page using XBT internal words.
Example:
DATE: DD/MM/YY TIME: HH:MM:SS
Field No. 1 (DD/MM) defines as follows:
Associated variable: Wi with i = 50000
Equipment:
Format:
XBT
String
Type:
Length:
Access:
ASCII
5 (8 max. for full display)
Read only
Field No. 2 (HH:MM) defines as follows:
Associated variable: Wi with i = 50001
Equipment:
Format:
XBT
String
Type:
Length:
Access:
ASCII
5 (8 max. for full display)
Read only
It is advisable to select a read only access or to use the CONFIDENTIAL mode to change the date and time.
When the timer variables are to be changed, you must use a separator such as "." or the right arrow to insert a SPACE between DD and MM or
HH and MM.
When you change internal words 50000 and 50001, you also change the contents of two words out of the four "Terminal Date and Time words for the controller" (if they have been selected in the dialogue table).
B
XBT-P XBT-PM XBT-E Magelis XBT-H, XBT-HM
Except XBT-H and
XBT-HM
Magelis B - 45
11. Configuration
When you change one of the four "Time Setting" words (if they have been selected in the dialogue table), you also change the contents of internal words 50000 and 50001.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Since all alarms are always time/date stamped and the control program may rely on the XBT's real-time clock, it is important to set or verify the
XBT's date and time after every new installation, repair, disassembly, shipping or battery change.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Parameters of the printer <-> XBT line
Parameters displayed by default:
PRINTER PARAMETERS
SPEED :
PARITY :
FORMAT:
BITSTOP:
LINK:
DUPLEX:
CHARACTERS
FORM FEED:
AUTO LF:
->
9600 BDS
ODD
8 BITS
1 BIT
RS 232
FULL
80
NO
CR LF
Magelis
Adjusting the parameters:
- position the cursor on the corresponding line using the up and down arrow keys, then access the content using the right arrow key.
XBT-H, XBT-HM
Except XBT-H and
XBT-HM
XBT-P XBT-PM XBT-E
B - 46 Magelis