Schneider Electric TSXP57 / TSXDEY / DSY / DMY Processors Discrete I/O Quick Reference Guide
Annonce
Annonce
Premium PLCs
TSX P57 / TSX DEY /
DSY / DMY
Processors
Discrete I/O
Quick Reference Guide
General safety advice for users
TSX P57••3/P57••23 Processors
At a Glance
Physical description
Catalog summary
Installation / Mounting
Precautions to be taken when replacing a processor
Auxiliary functions
Diagnostics using the indicator lamps
Characteristics
General introduction to discrete I/O modules
Presentation
Physical description
Catalog
Installation / Mounting
Functions
Connection equipment and wiring rules
Characteristics of input modules with terminal blocks
Characteristics of input modules with connector(s)
Characteristics of output modules with terminal block
Characteristics of output modules with connector(s)
Characteristics of mixed I/O modules with connectors
Maintenance / Diagnostics
Operating conditions
Discrete I/O module connections
Discrete input modules
Discrete output modules
Discrete mixed I/O module
Contents
2
16
16
28
29
30
31
24
25
26
16
17
19
19
22
32
32
36
42
8
12
13
7
8
4
6
4
4
1
General safety advice for users
1 General
This manual is intended for personnel technically qualified to install, operate and maintain the products which are described herein. For advanced use of these products please contact your nearest sales office for additional information.
The contents of this manual are not contractual and cannot under any circumstance extend or restrict contract warranty clauses.
2 Qualification of personnel
Only qualified personnel are authorized to install, operate or maintain the products. Any work performed by an unqualified person or non-observance of the safety instructions contained in this document or attached to the equipment may jeopardize the safety of personnel and/or cause irreparable damage to equipment.
3 Warnings
Warnings serve to prevent specific risks encountered by personnel and/or equipment. They are indicated in the documentation and on the products by different warning symbols:
Caution
Indicates that not following instructions or ignoring the warning may cause serious personal injury, death and/or serious damage to equipment.
Important or !
Indicates that not following a specific instruction may lead to minor injury and/or damage to equipment.
Comment
Highlights important information relating to the product, its operation or its accompanying documentation.
4 Conformity of use
The products described in this manual conform to the European Directives (*) to which they are subject (CE marking). However, they can only be used correctly in the context of the applications for which they are intended (described in the various documents) and when connected to approved third party products.
(*) EMC and LV Directives, concerning Electromagnetic Compatibility and Low Voltage.
5 Installing and setting up equipment
It is important to observe the following rules when installing and starting up equipment. In addition, if the installation includes digital links, it is essential to follow the basic wiring rules, given in the manual “Electromagnetic Compatibility of Industrial Networks and Fieldbuses”, reference TSX
DG KBLF.
• Safety instructions must be followed meticulously. These instructions are in the documentation or on the equipment being installed and set up.
• The type of equipment defines the way in which it should be installed:
- a flush-mountable device (for example, a process control terminal) must be flushmounted,
- a device which is to be built in (for example, a PLC) must be placed in a cabinet or enclosure,
- the casing of a laptop or portable device (for example, a programming terminal or a notebook) must remain closed.
2
General safety advice for users
• If the device is permanently connected, its electrical installation must include a device to isolate it from the power supply and a circuit-breaker to protect it against overcurrents and isolation faults. If this is not the case, the power socket must be grounded and be easily accessible. The
device must be connected to the protective ground.
• If the device is supplied with 24 or 48 VDC, the low voltage circuits must be protected. Only use power supplies which conform to the standards currently in force.
• Check that the supply voltages remain within the tolerance ranges defined in the technical characteristics of the devices.
• All measures must be taken to ensure that any power return (immediate, warm or cold) does not lead to a dangerous state which may place personnel or the installation at risk.
• Emergency stop devices must remain effective in all the device’s operating modes, even those which are abnormal (for example, when a wire becomes disconnected). Resetting these devices must not cause uncontrolled or improper restarts.
• Cables which carry signals must be located where they do not cause interference with the control system functions by capacitative, inductive or electromagnetic interference.
• Control system equipment and their control devices must be installed in such as way as to ensure that they are protected against unintentional operation.
• Appropriate safety measures must be taken for the inputs and outputs, to prevent improper states in the control system device, if no signal is received.
6 Equipment operation
The operational safety and availability of a device is its ability to avoid the appearance of faults and to minimize their effects if they occur.
A fault inside the control system is known as:
• Passive, if it results in an open output circuit (no command is sent to the actuators).
• Active, if it results in a closed output circuit (a command is sent to the actuators).
From the point of view of safety, a given fault may or may not be dangerous depending on the type of command given during normal operation. A passive fault is dangerous if the normal command is the operation of an alarm. An active fault is dangerous if it maintains or activates an undesirable command.
The system designer must use devices external to the PLC to protect against active faults inside the PLC, whether they are indicated or not.
7 Electrical and thermal characteristics
Details of the electrical and thermal characteristics of devices are given in the associated technical documents (installation manuals, service instructions).
8 Maintenance
Troubleshooting procedure
• Control system equipment should only be repaired by qualified personnel (after-sales service engineer, or technician approved by Schneider Automation SA). Only certified replacement parts or components should be used.
• Before performing any operation on equipment, always cut the power supply off and mechanically lock any moving parts.
Replacement and recycling of used batteries
Use batteries of the same type as the originals and dispose of defective batteries in the same way as toxic waste.
3
TSX P57 ••3 and TSX P57 ••23 Processors
At a Glance
A wide range of processors, scalable in terms of performance and capacity, are available to meet the different needs of users.
TSX 57 processors can be installed in TSX RKY•• racks:
TSX P57 103, TSX P57 153, TSX P57 203, TSX P57 253, TSX P57 2623, TSX P 57 2823, TSX P57
303, TSX P57 353, TSX P57 3623, TSX P57 453 and TSX P57 4823 processors.
TSX processors manage the whole PLC station consisting of discrete input/output modules, analog modules and application-specific modules (counting, axis control, stepper control, communication, etc.) located on one or more racks connected to the X Bus.
Each processor includes :
• a protected internal RAM memory which can take the application program and can be extended by a PCMCIA memory extension card (RAM or FLASH EPROM),
• a realtime clock,
• 2 terminal ports (TER and AUX) for connecting several devices simultaneously (programming terminal, human-machine interface terminal, etc),
• a slot for a PCMCIA communication card (Modbus+, FIPWAY, FIPIO Agent, UNI-TELWAY, serial links),
• a master FIPIO link on TSX P57 •53 and TSX P57 •823 processors,
• an Ethernet link on TSX P57 ••23 processors.
The application program is created using PL7 Junior or PL7 Pro software which offers:
• 4 programming languages,
• a multi-task software structure (master and fast tasks, event processing),
• program modification during execution, etc.
Physical description
TSX P57 103/153 TSX P57 203/.../453
Standard format
4
1
2
3
4
5
6
7
1
2
3
4
5
6
7
Double format
TSX P57 ••3 and TSX P57 ••23 Processors
TSX P57 ••23
6
7
4
8
5
9
1
2
3
Double format
(with built-in Ethernet link)
1 Display block with 4 or 5 LEDs depending on the model:
- RUN, ERR, I/O, TER LEDs on all processors,
- FIP LED on processors with a built-in master FIPIO link (TSX P57 •53 and TSX P57 •823).
2 Pencil-point RESET button which is used to activate a PLC cold restart.
3 Terminal port (TER) for connecting a peripheral which may or may not be self-powered
(programming or adjustment terminal, human-machine interface terminal, printer, etc).
4 Human-machine interface port (AUX) for connecting a self-powered peripheral (programming or adjustment terminal, human-machine interface terminal, printer, etc).
5 Slot for a type 1 PCMCIA memory extension card.
If no memory card is installed, this slot is fitted with a cover which must be left in place; as removing it will cause the PLC to stop.
6 Slot for a type 3 PCMCIA communication card for connecting a communication channel to the processor. If no communication card is installed, this slot is fitted with a cover.
7 9-pin SUB D connector for connecting to master FIPIO bus. Connector only featured on TSX
P57 •53 and TSX P57 •823 processors.
8 RJ 45 connector for connecting to Ethernet networks. This connector is only featured on TSX P57 ••23 processors.
9 ETY PORT display block with 6 LEDs:
- RUN (green), ERR (red), COL (red), STS (amber), TX (amber) and RX (amber).
5
TSX P57 ••3 and TSX P57 ••23 Processors
Catalog summary
• TSX 57 Processors
References TSX P57 103 153 203/
2623
253/
2823
303/
3623
353 453/
4823
TSX RKY 12EX racks
TSX RKY 4EX/6EX/8EX Racks
Module slots (1)
In-rack discrete I/O (2)
In-rack analog I/O 24
Application-specific channels (3) 8
Process control loops -
2
4
2
4
8
16
8
16
8
16
8
16
8
16
21 [27] 21 [27] 87 [111] 87 [111] 87 [111] 87 [111] 87 [111]
512 512 1024 1024 1024 1024 2048
24
8
-
80
24
30
80
24
30
128
32
45
128
32
45
256
64
60
-
1
10
1
10
1
15
3
15
3
20
4
Process control channels
Network connection: FIPWAY,
ETHWAY/TCP/IP, Modbus +
Ethernet (4)
-
1
Built-in FIPIO connection
Third party fieldbus connection
AS-i sensor/actuator fieldbus connection
Internal memory (5)
Memory extension
(K16) 32
(K16) 64
-
0
2
63
0
2
32
64
-
1
4
48
160
127
1
4
64
160
-
2
8
64/80
384
127
2
8
80/96
384
127
2
8
96/176
512
(1) With standard format modules, except for processor and power supply modules.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks.
(2) The I/O on the FIPIO bus, the third party bus and AS-i fieldbus are to be counted additionally.
(3) Application-specific channels = counter, axis control, stepper control, communication, etc.
(see characteristics section entitled: Number of different application-specific channels).
(4) The built-in Ethernet link on TSX P57 ••23 processors is included in the number of network connections.
(5) On TSX P57 453 and TSX P57 4823: if application is stored in internal RAM, memory capacity
= 96 KWords; if application is stored in PCMCIA card, internal RAM capacity = 176 KWords.
6
TSX P57 ••3 and TSX P57 ••23 Processors
Installation / Mounting
• Installation of a standard format processor module
The standard format TSX P57 processor module can be installed in a TSX RKY
••
rack in position
00 or 01 depending on the type of power supply module used (standard format or double format):
- If the rack is fitted with a TSX PSY 1610/2600 standard format power supply module, the processor can be installed in position 00 (by way of preference) or in position 01, in which case position 00 is unavailable.
PS 00 01 02 03 04 05 06
- If the rack is fitted with a TSX PSY 3610/5500/
5520, or 8500 double format power supply module, the processor is installed in position
01.
PS 00 01 02 03 04 05 06
The processor module must be mounted on the rack when the rack is
POWERED DOWN.
• Installation of a double format processor module
The double format TSX P57 processor module can be installed in a TSX RKY
••
rack in position
00 and 01 or 01 and 02 depending on the type of power supply module used (standard format or double format):
- If the rack is fitted with a TSX PSY 1610/2600 standard format power supply module, the processor can be installed in position 00 and
01 (by way of preference) or in position 01 and
02, in which case position 00 is unavailable.
PS 00 01 02 03 04 05 06
- If the rack is fitted with a TSX PSY 3610/5500/
5520, or 8500 double format power supply module, the processor is installed in position
01 and 02.
PS 00 01 02 03 04 05 06
The processor module must be mounted on the rack when the rack is
POWERED DOWN.
For inserting modules in the rack, refer to the rack installation instructions.
7
TSX P57 ••3 and TSX P57 ••23 Processors
Precautions to be taken when replacing a processor
If a TSX 57 processor is being replaced by another processor which has already been programmed and contains an application, the power to all the PLC station control devices must be cut off.
Before restoring the power to the control devices, check that the processor contains the required application.
Auxiliary functions
• Terminal port and auxiliary port
Two 8-pin mini-DIN connectors (non-isolated RS 485 link) for connecting the following to these two ports:
- TER: an FTX-type or PC compatible terminal or for connecting the PLC to a UNI-TELWAY bus, via a TSX P ACC 01 isolation box. This port supplies 5 V power to the peripheral connected to it.
- AUX: a human-machine interface terminal or printer. This port does not supply 5 V power.
By default, the “TER” and “AUX” ports offer UNI-TELWAY master communication mode at 19 200 bauds and can be configured for UNI-TELWAY slave mode or ASCII character mode.
• Slot for PCMCIA communication card
This slot, on the front panel of the processor, can take a type 3
PCMCIA communication card:
- TSX SCP 111: RS 232 D multiprotocol
- TSX SCP 112: 20 mA current loop multiprotocol
- TSX SCP 114: RS 485 multiprotocol, compatible
with isolated RS 422
- TSX MBP 100: Modbus+,
- TSX FPP 10 / 20: FIPIO Agent / FIPWAY,
- TSX FPP 200: FIPWAY,
- TSX MDM 10: Modem,
- TSX MBP 100: Modbus+,
- FCS SCP 111: specific protocol on RS 232 support,
- FCS SCP 114: specific protocol on RS 485 support,
- TSX CPP 100: CAN OPEN.
The processor must always be POWERED DOWN prior to inserting or removing a communication card.
PCMCIA communication card
8
TSX P57 ••3 and TSX P57 ••23 Processors
• Internal RAM
This memory takes the application (data, program and constants). Its capacity varies according to the type of processor:
- 32 KWords on TSX P57 103/153 processor,
- 48 KWords on TSX P57 203/2623 processors,
- 64/80 KWords on TSX P57 253/2823/303 processors,
- 80/96 KWords on TSX P57 353/3623 processors,
- 96/176 KWords (1) on TSX P57 453/4823 processors.
If the size of the application is larger than the RAM, the memory can be extended using a
PCMCIA memory extension card. In this case, the program and constants are stored in the
PCMCIA memory extension card, and data is stored in the internal RAM.
The internal RAM can be protected using an optional battery (TSX PLP 01), located in the power supply module. The application is only protected if the power supply and processor
modules are kept in the rack. (See duration of backup of internal RAM.)
(1) When the application is stored in internal RAM, the memory capacity is limited to 96 KWords.
When the application is stored in the PCMCIA card, the memory capacity is extended to
176 KWords.
• Slot for PCMCIA memory extension card
This slot, on the front panel of the processor, can take an optional type 1 PCMCIA memory card. If no card is installed,
the cover must be left in place.
4 families of cards are available:
- Standard memory cards: Two types of card are available:
Protected RAM used during the creation and debugging of the application program. The protection is provided by a removable battery integrated in the card.
FLASH EPROM used when the application program is operational (debugging completed).
- BACKUP type memory card used for loading the program into the internal RAM, without using a terminal. Such a card needs to be loaded beforehand with the application program which must be < 32 KWords in size.
- Application + file type memory cards
As well as the conventional application storage zone, these also have:
- a file zone which can be used to store data by program,
- a zone which can be used to store the application symbols database. This symbols database is compressed to ensure it remains within the allocated zone without restriction.
This zone is only available on some cards.
Two types of card are available:
- Protected RAM card,
- FLASH EPROM + protected RAM card for data storage.
Memory card
9
TSX P57 ••3 and TSX P57 ••23 Processors
A memory card can be inserted/removed while the processor is POWERED UP
(causes a cold start). To be operational, a memory card must be fitted with a handle. If the program stored in the PCMCIA memory card includes the AUTO
RUN option, the processor will automatically start in RUN after the card is inserted.
References of standard and backup PCMCIA memory extension cards
References Type Capacity Compatibility with TSX/TPMX
processors
TSX MRP 032P
TSX MRP 064P
TSX MRP 0128P
TSX MRP 0256P
TSX MFP 032P
TSX MFP 064P
TSX MFP 0128P
RAM
RAM
RAM
RAM
FLASH EPROM 32 K16
FLASH EPROM 64 K16
Yes
Yes
FLASH EPROM 128 K16 No
TSX MFP BAK032P RAM/Backup
32 K16
64 K16
Yes
Yes
128 K16 No
256 K16 No
32 K16 Yes
P57 1•3 P57 2 • 3 P57 3 • 3 P57 453
P57 2•23 P57 3623 P57 4823
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
References of application + file or symbol memory cards
References
TSX MRP 232P
TSX MRP 264P
Type / Capacity
Application zone
Compatible processors
File zone
Symbol zone
(RAM) (RAM)
TSX TSX
P57 1•3 P57 2
•
3
TSX
P57 3
•
3
TSX
P57 453
P57 2•23 P57 3623 P574823
RAM/32 K16
RAM/64 K16
128 K16 -
128 K16 -
Yes
Yes
TSX MRP 2128P RAM/128 K16 128 K16 128 K16 No
TSX MRP 3256P RAM/256 K16 640 K16 128 K16 No
TSX MRP 3384P RAM/384 K16 640 K16 -
TSX MRP 0512P RAM/512 K16 -
TSX MFP 232P Flash/Eprom
No
256 K16 No
128 K16 -
32 K16
TSX MFP 264P Flash/Eprom 128 K16 -
64 K16
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
References of file memory cards
References
TSX MRP DS 2048 P
Type / Capacity
File zone
(RAM)
2048 K16
10
Compatible processors
T S X
P57 2
•
3
P57 2•23
Yes
T S X
P57 3
•
3
P57 3623
Yes
T S X
P57 453
P574823
Yes
TSX P57 ••3 and TSX P57 ••23 Processors
• RESET button
Pressing this pencil point pushbutton triggers a cold start of the application:
- processor operating normally: start in STOP or in RUN depending on the configuration,
- processor faulty: forced start in STOP.
• RUN / STOP function
This is used to start or stop the application program from a programming terminal or a discrete input defined during configuration. A STOP command from this physical input takes priority over a RUN command from a terminal.
• Realtime clock
The realtime clock built into the processor manages the current date and time and the date and time of the last application stop. This continues even when the processor is powered down, as long as it is mounted on the rack with the power supply module, and fitted with a backup battery.
Removing the processor will mean the date and time will be lost after a certain
amount of time. (See below).
• Duration of backup of internal RAM and realtime clock
- Duration of battery backup
Ambient temperature when not operating
Backup PLC switched off 12 hours/day time PLC switched off 1 hour/day
≤
30 °C 40 °C 50 °C 60 °C
5 yrs 3 yrs 2 yrs 1 year
5 yrs 5 yrs 4.5 yrs 4 yrs
- Standby backup while the battery is being changed (PLC powered down) or the processor or power supply module is being removed. Intervention time is limited; after a certain length of time the data in the RAM memory may be lost.
20 °C 30 °C 40 °C 50 °C Ambient temperature when not operating
Backup time 2 h 45 mn 20 mn 8 mn
• Ethernet link on TSX P57 ••23
Some processors have a built-in Ethernet link, making it possible to manage 64 TCP connections using the port 502 messaging service, and to scan up to a maximum of 64 devices using the IO
Scanning service.
A RJ45 port located on the second part of the module can be used to connect it to the Ethernet network via an RJ45 connector.
11
TSX P57 ••3 and TSX P57 ••23 Processors
• Master FIPIO link on TSX P57 •53 and TSX P57 •823 processors
Some processors have a built-in master FIPIO link which is used to manage a FIPIO bus on which 1 to 127 devices can be connected, such as:
TSX P57 153
- Momentum and TBX remote I/O modules
(discrete and analog),
- CCX 17 operator consoles,
TSX P57
253/2823/353/
453/4823
- ATV16 variable speed drives
- Devices which conform to standard profiles, etc.
TSX FP
ACC12
TSX FP
ACC12
A 9-pin SUB D connector on the front panel is used for connecting to the FIPIO bus via a TSX FP ACC12 connector.
Note: The complete installation of the FIPIO bus (type of architecture, type of cable to use, wiring accessories, etc) is described in the FIPIO bus reference manual.
Diagnostics using the display LEDs
4 or 5 LEDs (depending on the type of processor) located on the front panel can be used to rapidly diagnose the state of the PLC:
• RUN (green): state of the application (on: normal operation;
flashing: PLC stopped or has a blocking software fault; off:
PLC not configured, application missing, not valid or incompatible with the type of processor, PLC fault or processor or system fault),
• ERR (red): processor or memory card or PCMCIA communication card faults (on: PLC fault, processor fault or system fault; flashing: PLC not configured, application missing, not valid or incompatible with the type of processor, PLC blocking software fault, memory card battery fault, X Bus fault (1); off: normal operation),
• I/O (red): I/O faults (on: I/O fault, from a module or a channel or configuration fault, flashing: X Bus fault (1); off: normal operation),
• TER (amber): this indicates activity on the terminal port
(flashing: exchange in progress on the terminal port),
RUN
TER
FIP
ERR
I / O
• FIP (amber): only on TSX P57 •53 and TSX P57 •823 processors. This indicates activity on the
FIPIO bus (flashing: exchanges in progress on the FIPIO bus).
(1) A X Bus fault is indicated by simultaneous flashing of the ERR and I/O indicator lamps.
12
TSX P57 ••3 and TSX P57 ••23 Processors
Characteristics
• General characteristics of TSX 57 processors
Processors TSX P57 103 153 203/
2623
253/
2823
Maximum characteristics for the station
TSX RKY 12EX racks
TSX RKY 4EX/6EX/8EX racks
Module slots (1)
In-rack discrete I/O on X Bus
Analog I/O on X Bus
Application-specific channels on X Bus (2)
Number of process control loops
Number of process control channels
UNI-TELWAY connection (terminal port)
Network connection (3)
(FIPWAY, ETHWAY/TCP/IP, Modbus +, Ethernet)
Built-in master FIPIO connection
Third party fieldbus connection
(INTERBUS-S, etc.) (4)
AS-i fieldbus connection
Functions
Realtime clock (can be backed up)
8
0
0
2
1
2
4
2
4
8
16
8
16
21 [27] 21 [27] 87 [111] 87 [111]
512
24
-
0
2
512
24
8
0
0
2
1
63
0
2
1024
80
24
30
10
2
1
-
1
4
1024
80
24
30
10
2
1
127
1
4
Yes Yes Yes Yes
Memory
Internal RAM (5)
Extended memory (maximum)
Maximum memory
Application structure
Master task
Fast task
Event processing (1 event has priority)
(K16)
(K16)
(K16)
32
64
96
1
1
32
32
64
96
1
1
32
48
160
208
1
1
64
64
160
224
1
1
64
Execution time for 1K instructions (6)
Internal RAM
PCMCIA card
Programming software (7)
0.95 ms 0.95 ms 0.28 ms 0.28 ms
1.18 ms 1.18 ms 0.40 ms 0.40 ms
PL7 Junior/PL7 Pro (Windows 95/98/2000 or NT)
Languages Ladder, Grafcet, Structured Text, List
(1) With standard format modules, except for processor and power supply modules.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks.
(2) application-specific channels = counter, axis control, stepper control, communication channels etc. (See definition and numbers of application-specific channels.)
(3) The built-in Ethernet link on TSX P57 ••23 processors is included in the number of network connections.
(4) INTERBUS-S, PROFIBUS-DP.
(5) Can be backed up by a battery located in the power supply module.
(6) 65% Boolean / 35% Numerical.
(7) PL7
≥
V4.3 for TSX P57 ••23 processors.
13
TSX P57 ••3 and TSX P57 ••23 Processors
General characteristics of TSX 57 processors (continued)
Processors TSX P57 303/
3623
Maximum characteristics for the station
TSX RKY 12EX racks
TSX RKY 4EX/6EX/8EX racks
Module slots (1)
In-rack discrete I/O on X Bus
Analog I/O on X Bus
8
16
87 [111]
1024
128
Application-specific channels on X Bus (2)
Number of process control loops
Number of process control channels
UNI-TELWAY connection (terminal port)
Network connection (3)
(FIPWAY, ETHWAY/TCP/IP, Modbus+, Ethernet)
Built-in master FIPIO connection -
Third party fieldbus connection (INTERBUS-S, etc.) (4) 2
AS-i fieldbus connection
Functions
2
3
8
32
45
15
Yes Realtime clock (can be backed up)
Memory
Internal RAM (5)
Extended memory (maximum)
Maximum memory
Application structure
(K16)
(K16)
(K16)
64/80
384
464
Master task
Fast task
Event processing (1 event has priority)
1
1
64
353
8
16
87 [111]
1024
128
32
45
15
2
3
127
2
8
Yes
80/96
384
480
1
1
64
453/
4823
8
16
87 [111]
2048
256
64
60
20
2
4
127
2
8
Yes
96/176
512
688
1
1
64
Execution time for 1K instructions (6)
Internal RAM
PCMCIA card
Programming software (7)
0.21 ms
0.32 ms
0.21 ms
0.32 ms
0.11 ms
0.11 ms
PL7 Junior/PL7 Pro (on Windows 95/98/2000 or NT)
Languages Ladder, Grafcet, Structured Text, List
(1) With standard format modules, except for processor and power supply modules.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks.
(2) Application-specific channels = counter, axis control, stepper control, communication channels, etc., see definition and numbers of application-specific channels.
(3) The built-in Ethernet link on TSX P57 ••23 processors is included in the number of network connections.
(4) INTERBUS-S, PROFIBUS-DP.
(5) Can be backed up by a battery located in the power supply module.
On TSX P57 453: if application is stored in internal RAM, memory capacity = 96 KWords; if application is stored in PCMCIA card, internal RAM capacity = 176 KWords.
(6) 65% Boolean / 35% Numerical.
(7) PL7
≥
V4.3 for TSX P57 ••23 processors.
14
TSX P57 ••3 and TSX P57 ••23 Processors
• Electrical characteristics
Processors
TSX P57 103
TSX P57 153
TSX P57 203
TSX P57 2623
TSX P57 253
TSX P57 2823
TSX P57 303
TSX P57 3623
TSX P57 353
TSX P57 453
TSX P57 4823
5 VDC consumption of power supply module
TSX PSY •
Typical
440 mA
530 mA
750 mA
1110 mA
820 mA
1180 mA
Maximum
610 mA
740 mA
1050 mA
1450 mA
1140 mA
1540 mA
1000 mA
1360 mA
1060 mA
1080 mA
1440 mA
1400 mA
1800 mA
1480 mA
1510 mA
1910 mA
Dissipated power
Typical
2.2 W
2.7 W
3.8 W
5.6 W
4.1 W
5.9 W
5.0 W
6.8 W
5.3 W
5.4 W
7.2 W
Maximum
3.1 W
3.7 W
5.3 W
7.4 W
5.7 W
7.8 W
7.0 W
9.1 W
7.4 W
7.6 W
9.7 W
• Number of different application-specific channels
Application Module/card
Counting
Motion control
Axis
Stepper
TSX CTY 2A
TSX CTY 2C
TSX CTY 4A
TSX CCY 1128
TSX CAY 21/22
TSX CAY 41/42
TSX CAY 33
TSX CSY 84
TSX CFY 11
TSX CFY 21
TSX ISP Y100/101 Weighing
Communication Serial link TSX SCP 11 •• (in processor)
TSX SCP 11
••
(in TSX SCY 21601)
TSX JNP 11
••
(in TSX SCY 21601)
TSX SCY 21601 (built-in channel)
FIPIO Agent TSX FPP10 (in processor)
FIPIO Master built into processor
Modem TSX MDM10
App-spec.
Number channel
Yes 2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2
4
1
2
4
3
32 (1)
1
2
1
No
Yes
Yes
Yes
No
No
Yes
1
1
0 (2)
1
0 (2)
0 (2)
1
Note: Only the configured application-specific channels must be included.
(1) 1 channel minimum.
(2) Channels not to be included when calculating the maximum number of application-specific channels supported by the processor.
15
General introduction to discrete I/O modules
Presentation
Modularity
Connection
HE 10 connectors
64 I or 64 O 32 I or 32 O 32 I or 28 I/O 16 I
Connection
Screw terminal blocks
(Terminal blocks not shown)
64 I or 64 O 32 I or 32 O 8/16 I or 8/16 O 8 or 16 O
Physical description
Modules with HE 10 connectors
1 Display block
2 HE10 connectors protected by a cover. They enable connection of the sensors and preactuators either directly via preformed cables, or via TELEFAST 2 connection subbases.
16
1
2
General introduction to discrete I/O modules
Modules with connection via screw terminal block
1 Display block.
2 Removable screw terminal block for direct connection of the sensors and preactuators.
3 Door providing access to screw terminals and also acting as a reference label holder.
4 Module locating device.
!
The terminal block is supplied separately, under the reference TSX BLY 01.
1
• Reference label
This removable label is supplied with the module, to be placed inside the door (3). Printed on both sides, it displays the following information :
- door closed : module reference and type of channel. In the space provided, the user enters the module address and channel symbols,
- door open : wiring of inputs and/or outputs, with channel numbers and connection terminal numbers.
3
Catalog summary
TSX DEY .. input modules
Reference
DEY 08 D2
DEY 16 D2
DEY 16 D3
DEY 16 A2
DEY 16 A3
DEY 16 A4
DEY 16 A5
DEY 16 FK
DEY 32 D2K
DEY 32 D3K
DEY 64 D2K
Modularity Connect.
Voltage Isolation
8 (1) Ter. block 24 VDC
16 (1) Ter. block 24 VDC
Yes
Yes
16 (1) Ter. block 48 VDC
16 (2) Ter. block 24 VDC
24 VAC
Yes
Yes
Yes
16 (2) Ter. block 48 VAC
16 (2) Ter. block 115 VAC
16 (2) Ter. block 230 VAC
16 (3) HE10 24 VDC
32 (3)
32(1)
64 (3)
HE10
HE 10
HE10
24 VDC
48 VDC
24 VDC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(1) 2 and 3-wire proximity sensor compatibility IEC 947-5-2
(2) 2-wire proximity sensor compatibility IEC 947-5-2 AC
(3) Telemecanique 2 and 3-wire proximity sensor compatibility
Logic
Positive
Positive
Positive
Negative
–
Filtering IEC 1131
4 ms
4 ms
Type 2
Type 2
4 ms Type 2
10 ms –
50/60 Hz Type 2
–
–
50/60 Hz Type 2
50/60 Hz Type 2
– 50/60 Hz Type 1
Positive 0.1..7.5 ms Type 1
Positive
Positive
Positive
4 ms
4 ms
4 ms
Type 1
Type 2
Type 1
4
4
2
17
General introduction to discrete I/O modules
TSX DSY .. output modules
Reference
(5)
DSY 08 T2
DSY 08 T22
DSY 08 T31
DSY 16 T2
DSY 16 T3
DSY 08 R5
(3)
DSY 08 R4D
(3)
DSY 08 R5A
(3)
DSY 16 R5
(3)
DSY 08 S5
(3) (4)
DSY 16 S4
(3) (4)
DSY 16 S5
DSY 32 T2K
DSY 64 T2K
Modularity Connect.
Voltage
8 (T)
8 (T)
8 (T)
8 (R)
8 (R)
8 (R)
Ter. block 24 VDC
Ter. block 24 VDC
Ter. block 48 VDC
16 (T) Ter. block 24 VAC
16 (T) Ter. block 48 VAC
Ter. block 24 VDC
24…240 VAC
Ter. block 24…110 VDC
Ter. block 24…48 VDC
24…240 VAC
16 (R) Ter. block 24 VDC
24…240 VAC
8 (S)
16 (S)
16 (S)
32 (T)
64 (T)
Ter. block 48…220 VAC
Ter. block 24…110 VAC
Ter. block 48…220 VAC
HE10
HE10
24 VDC
24 VDC
Current
0.5 A
2 A
1 A
0.5 A
0.5 A
3 A
5 A
5 A
3 A
2 A
1 A
1 A
0.1 A
0.1 A
Logic Protection Response time
Pos.
Pos.
Pos.
Pos.
Pos.
–
–
–
–
–
–
Yes (1)
Yes (1)
Yes (1)
Yes (1)
Yes (1)
No
Yes (2)
Yes (2)
No
Yes (2)
No
1.2 ms
0.2 ms
0.2 ms
1.2 ms
1.2 ms
0 v 1<8ms
1 v 0<10ms
0
1
0
1 v v v v
1<10ms
0<15ms
1<10ms
0<10ms
–
Pos.
Pos.
Yes (2)
Yes (1)
Yes (1)
1.2 ms
1.2 ms
(1) Outputs have an integrated device for protection against short-circuits and overloads.
Modules are protected against polarity inversions.
(2) Outputs are protected by interchangeable fuses, accessed via the module front panel.
(3) A device automatically cuts off the outputs when the terminal block is unlocked.
(4) The output fallback can be configured for all modules, with the exception of triac output modules.
(5) All outputs are isolated.
( T )Transistor outputs (R) Relay outputs (S)Triac outputs
TSX DMY 28FK/28RFK mixed I/O module
Modularity Connect. Voltage Current Logic ProtectionFiltering Response IEC time 1131
16 inputs HE 10 24 VDC Pos.
0.1..7.5 ms Type 1
12 outputs (T) HE 10 24 VDC 0.5 A Pos.
Yes 0.5 ms Yes
Note : Outputs have an integrated device for protection against short-circuits and overloads.
Modules are protected against polarity inversions.
All inputs and outputs are isolated.
(T)Transistor outputs
18
General introduction to discrete I/O modules
Installation / Mounting
Discrete I/O modules can be positioned anywhere on a TSX RKY ... rack.
For inserting modules in the rack, refer to the rack installation instructions.
!
Modules can be inserted in and removed from the rack when the rack is powered up; however, the sensor and preactuator supply must be off and the terminal block disconnected.
Functions
Current generator inputs
24 VDC and 48 VDC inputs are "current generator" type. Although the input voltage may be higher than 11 V (for 24 VDC inputs) or 20 V (for 48 VDC inputs), the input current is constant.
Protecting DC solid state outputs
All protected solid state outputs have a device which detects the appearance of an overload or a short-circuit when an output is active. Any such fault deactivates the output (tripping) and the fault is signalled (the indicator lamp of the faulty channel flashes and the processor I/O indicator lights up). To use an output after tripping, it must be reactivated.
Reactivating outputs
Reactivation of a tripped output can be automatic or controlled depending on the option selected during configuration. Reactivation is required for solid state DC outputs or for relay and triac outputs protected by interchangeable fuses. It is performed on groups of 8 channels, but has no effect on channels which have not been activated or are not faulty.
• If reactivation is automatic, it is executed every 10 s by the module, until the fault disappears, enabling it to be taken into account.
• If reactivation is controlled by the application program or via an operator terminal, it will be taken into account if the fault has disappeared. The minimum time between two reactivations is 10 s.
Output fallback
On a blocking fault, all module outputs are set to a state determined by the user during configuration : maintain state, fallback to 0 or fallback to 1.
Sharing I/O
Each module is split functionally into groups of 8 channels which may be assigned to the various application tasks (for example, for a module with 16 channels, channels 0 to 7 can be assigned to the MAST task and channels 8 to 15 to the FAST task).
Channels of the same group have common operating modes and function management
(fallback and reactivation of outputs).
Programmable input filtering
TSX DEY 16FK and TSX DMY 28FK/28RFK modules configure the input filter time between 0 and 7.5 ms (4 ms by default).
!
To avoid taking account of bounce when mechanical contacts are closed, it is advisable to use a filter time greater than 3 ms.
19
General introduction to discrete I/O modules
Latching
By means of latching, TSX DEY 16FK and TSX DMY 28 FK modules can use very short pulses which have a shorter duration than the PLC scan time. The change in the input state is taken into account so that it can be processed in the next task scan.
!
The time between the arrival of 2 pulses on the same input must be at least equal to the time of 2 PLC scans.
The minimum duration of the pulse should be greater than the filter time configured.
Event management
TSX DEY 16FK and TSX DMY 28FK modules allow up to 16 inputs to be configured, enabling events to be taken into account and processed immediately by the processor (processing on an interrupt).
Monitoring the presence of the terminal block
All terminal block modules have a device which checks that the terminal block is on the module.
A fault is signalled if the terminal block is missing or if it is not properly attached to the module.
Monitoring short-circuits and overloads
Solid state output modules have a facility which monitor the state of the load. A short-circuit or overload at one or more outputs causes a fault to appear and the relevant outputs to trip.
Monitoring sensor voltage
All input modules include a facility for monitoring that the sensor and module supply voltage is sufficient to ensure correct operation of the input channels. If this voltage drops below a defined threshold, a fault is signalled.
!
The sensor supply must be protected by a 0.5 A fast blow fuse.
Monitoring preactuator voltage
All solid state output modules include a facility for monitoring that the preactuator and module supply voltage is sufficient to ensure correct operation of the output channels. If this voltage falls below a defined threshold, a fault is signalled.
Reflex and timer functions on the TSX DMY 28RFK module
This module can be used to implement applications which require a faster response time than the
FAST task or event processing (<500 ms) by means of automation functions executed at module level, independently of the PLC task, and use the following as input variables :
• the physical inputs of the module (%I),
• the output commands of the module (%Q),
• the channel or module fault data,
• the states of the module physical outputs.
These functions are programmed in configuration mode using PL7 Junior or PL7 Pro software
V
≥
3.3. The configuration screen for each output comprises two main parts :
• one part representing a simplified Ladder rung layout comprising 4 lines of 4 contacts which can be used to execute a combinational logic function for the input variables ,
• one part representing the function used which can either be direct control of the output using the configured combinational logic, or a function block.
(see examples overleaf).
20
Examples
%I5.2
%I5.3
%I5.4
%Q5.20
ERR 2
%I5.8
ERR 3
%I5.7
General introduction to discrete I/O modules
%Q5.25
%I5.2
%I5.3
%I5.4
%Q5.20
Val
Monostable
%Q
5.25
ERR 2
%I5.8
ERR 3
Sel
%I5.7
List of the main function blocks :
• on-delay type timer function block,
• off-delay type timer function block,
• on-delay/off-delay type timer function block,
• 2-value timer function block,
• selectable on-delay/off-delay timer function block,
• retriggerable monostable function block,
• time-delayed non-retriggerable monostable function block,
• 2-value monostable function block,
• oscillator function block,
• Dual threshold counter function block,
• single threshold counter with monostable function block,
• interval counter function block used to measure time or length,
• Burst function block used to generate a defined number of oscillator periods,
• PWM function block used to generate a continuous oscillation with a fixed frequency but a variable cyclic ratio,
• slow speed detection function block,
• speed monitoring function block,
• command/control function blocks used to control an action and to check that it has been executed correctly after a certain period of time :
- type 1command/control function block : (1 command),
- type 2command/control function block : (2 commands : FWD and REV),
• command function block for a number of counting points (simple position control),
• fault indication function block,
• D latch function block, memorisazion of edge,
• T latch function block, division by 2.
A more detailed description of the various function blocks and their installation using software can be found in the application-specific manual TLS DS 57 PL7 33E - Volume 1 - part B).
21
General introduction to discrete I/O modules
Connection equipment and wiring rules
Wiring rules
• External power supplies for sensors and preactuators
These power supplies must be protected against shorts-circuits and overloads, by fast blow
fuses.
!
If the 24 VDC installation does not conform to SELV (Safety Extra Low Voltage) standards, the 0 V of the power supply must be connected to the protective ground, which should be taken to ground as near as possible to the power supply unit.
• Inputs
The use of a TSX DEY 16FK/DMY 28FK fast input module requires the input filter time to be adapted to the desired function : use of sensors with mechanical contact outputs requires a filter time of ≥ 3 ms. In order to achieve faster operation, use DC inputs and sensors which have a response time less than that of AC inputs.
• Outputs
For high currents, it is advisable to segment the terminal connections by protecting each one with a fast blow fuse.
Use wire of a sufficient cross section to avoid voltage drops and temperature rises.
• Cable routing
In order to limit the AC coupling, separate the power cables (power supply, power contactors, etc) and input (sensors) and output (preactuators) cables.
Connection of modules with screw terminal block
Each terminal can accept bare wires or wires fitted with cable ends, or open lugs.
• minimum :
• maximum :
1 wire, 0.2 mm 2 (AWG 24) without cable end.
1 wire, 2 mm 2 without cable end or
1 wire, 1.5 mm 2 with cable end
5.5 mm max.
Connection of modules with HE10 connectors
• 20-wire preformed cable, 22 gauge (0.34 mm 2 )
Used for wire-to-wire connection of I/O to sensors, preactuators or connection terminals.
There are 2 product references : TSX CDP 301 (3 meters) and TSX CDP 501 (5 meters).
Terminal / Wire Terminal / Wire
5
7
1
3 white green gray blue
9
11 black gray-pink
10
12
13 white-green 14
15 white-yellow 16
17 white-gray 18
19 white-pink
6
8
2
4
20 brown yellow pink red purple red-blue brown-green yellow-brown gray-brown pink-brown
Module
Preformed cable
22
General introduction to discrete I/O modules
• Preformed stranded connection cable with sheath, 28 gauge (0.08 mm 2 )
Used to connect I/O to TELEFAST 2 rapid wiring connection and adaptation interfaces.
Bearing in mind the small cross section of the wires, it is recommended that the connection cable is only used for low current inputs or outputs ( ≤ 100 mA).
Module
Preformed cable
There are 3 product references :
TSX CDP 102 (1 meter), TSX CDP 202
(2 meters) and TSX CDP 302 (3 meters).
• Connection cable, 22 gauge (0.34 mm 2 )
Connection cable
Used to connect I/O to TELEFAST 2 rapid wiring connection and adaptation interfaces.
The wire cross section (0.34 mm 2 ) enables higher currents to be carried than when using the preformed connection cable
( ≤ 500 mA).
TELEFAST 2
ABE-7H iiiii
There are 5 product references : TSX CDP 053 (0.5 meters), TSX CDP 103 (1 meter),
TSX CDP 203 (2 meters), TSX CDP 303 (3 meters) and TSX CDP 503 (5 meters).
Maximum tightening torques :
• on screw for fixing the module on the rack :
• on screw for TSX BLY 01 connection terminal block :
• on screw for TSX CDP • cable connectors :
2.0 N.m
0.8 N.m
0.5 N.m
23
General introduction to discrete I/O modules
Characteristics of input modules with terminal blocks
DC inputs
TSX DEY module reference
Nominal input values
Input l i m i t values at state 1
Voltage
Current
Voltage
Current at state 0 Voltage
Current
Sensor supply
(ripple included)
Input impedance (at U nominal)
Logic
IEC 1131-2 conformity
Type of input
Paralleling of inputs current sink
Yes
Compatibility 2-wire/3-wire prox. sensor IEC 947-5-2
Sensor voltage OK > 18 V monitoring threshold Fault < 14 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms
Consumption 5 V typical 55 / 80 mA
(2) typ. sensor supply 25 +(Nx 7) mA
Dissipated power(2)
0 8 D 2 / 1 6 D 2
24 VDC
7 mA
≥
≥
11 V
6.5 mA
(U = 11 V)
≤
5 V
≤
2 mA
19…30 V
(1)
4 k
Ω positive
Type 2
1 6 D 3
48 VDC
7 mA
≥
≥
30 V
6.5 mA
(U = 30 V)
≤
10 V
≤
2 mA
38…60 V
7 k
Ω positive
Type 2 current sink
Yes
IEC 947-5-2
> 36 V
< 24 V
1500 V rms
80 mA
25 +(Nx 7) mA
1 +(Nx 0.15) W 1 +(Nx 0.3) W
1 6 A 2
24 VDC
16 mA
≤
Ual - 14 V
≥
6.5 mA
≥
Ual - 5 V
≤
2 mA
19…30 V
(1)
1.6 k
Ω negative
– resistive
Yes
IEC 947-5-2
> 18 V
< 14 V
1500 V rms
80 mA
15 +(Nx 15) mA
1 +(Nx 0.4) W
AC inputs
TSX DEY module reference
Nominal input Voltage values Current
Input limit values at state 1 Voltage
Current
1 6 A 2
24 VAC
15 mA
10 V
6 mA
1 6 A 3
48 VAC
16 mA
29 V
6 mA
1 6 A 4
12 mA
74 V
6 mA
1 6 A 5
100..120 VAC 200..240 VAC
15 mA
159 V
6 mA
(U = 10 V) (U = 29 V) (U = 74 V) at state 0 Voltage/current 5 V/3 mA 10 V/4 mA 20 V/4 mA
(U = 159 V)
40 V/4 mA
Frequency 47…63 Hz 47…63 Hz 47…63 Hz 47…63 Hz
Sensor supply
Input impedance
Sensor voltage monitoring threshold
OK
Fault
20…26 V
1.6 k
Ω
IEC 1131-2 conformity
Type of input
Type 2 resistive
Compatibility 2-wire/3-wire prox. sensor IEC 947-5-2
> 18 V
< 14 V
40…52 V
3.2 k
Ω
Type 2 capacitive
IEC 947-5-2
> 36 V
< 24 V
85…132 V 170…264 V
9.2 k
Ω
Type 2 capacitive
IEC 947-5-2
> 82V
< 40 V
20 k
Ω
Type 1 capacitive
IEC 947-5-2
> 164V
< 80 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms 1500 V rms 1500 V rms 2000 V rms
Consumption 5 V typical 80 mA 80 mA 80 mA 80 mA
(2) typ. sensor supply (mA) 15 + (Nx15) 16 + (Nx16) 15 + (Nx15) 12 + (Nx12)
Power dissipated per channel (2)
(1) up to 34 V (1 h / 24 h)
1+(0.35xN) W 1+(0.35xN) W 1+(0.35xN) W 1+(0.35xN) W
(2) N = number of channels at 1
24
General introduction to discrete I/O modules
Characteristics of input modules with connector(s)
TSX DEY module reference
Nominal input values
Input limit values at state 1 at state 0
16FK
Voltage 24 VDC
Current
Voltage
Current
Voltage
Current
Sensor supply
3.5 mA
≥
11 V
≥
3 mA
≤
5 V
≤
1.5 mA
19…30 V
Type of input
Logic
(ripple included)
Input impedance (at U nominal)
IEC 1131-2 conformity
(1)
6.3
κΩ current sink positive
Type 1
32D2K
24 VDC
3.5 mA
≥
11 V
≥
3 mA
≤
5 V
≤
1.5 mA
19…30 V
(1)
6.3
κΩ current sink positive
Type 1
No
Yes
64D2K
24 VDC
≤
≤
3.5 mA
≥
11 V
≥
3 mA
5 V
1.5 mA
19…30 V
(1)
6.3
κΩ current sink positive
Type 1
No
Yes
Paralleling of inputs Yes
Compatibility 2-wire/3-wire prox. sensor Yes
Sensor voltage monitoring threshold
OK
Fault
Dielectric strength (50/60 Hz, 1 min)
Consumption
(2)
5 V typical
24 V typ. sensor
> 18 V
< 14 V
1500 V rms
250 mA
> 18 V
< 14 V
1500 V rms
135 mA
> 18 V
< 14 V
1500 V rms
155 mA
20 +(Nx3.4) mA 30 +(Nx3.5) mA 60 +(Nx3.5) mA
Dissipated power(2)
(1) up to 34 V (1 h / 24 h)
1.2 +(Nx0.1) W 1 +(Nx0.1) W 1.5 +(Nx0.1) W
(2) N = number of channels at 1
TSX DEY module reference
Nominal input values
Input limit values at state 1
Voltage
Current
Voltage
Current at state 0 Voltage
Current
Input impedance (at U nominal)
Type of input
Logic
Sensor supply
(ripple included)
IEC 1131-2 conformity
Paralleling of inputs
Compatibility 2-wire/3-wire prox. sensor
Sensor voltage OK monitoring threshold Fault
Dielectric strength (50/60 Hz, 1 min)
Consumption 5 V typical
(2) 24 V typ. sensor
Dissipated power(2)
(1) up to 34 V (1 h / 24 h)
.
32D3K
48 VDC
7 mA
≥
≥
30 V
6.5 mA (when U = 30V)
≤
10 V
≤
2 mA
38…60 V
6.3 k
Ω current sink positive
Type 2
Yes
Yes
> 36 V
< 24 V
1500 V rms
300 mA
50 +(7xN) mA
2.5 +(Nx0.34) W
(2) N = number of channels at 1
25
General introduction to discrete I/O modules
Characteristics of output modules with terminal block
DC solid state outputs (positive logic)
TSX DSY module reference 08T2
16T2
08T22 08T31
Nominal values Voltage
Current
Voltage
24 VDC
0.5 A
24 VDC
2 A
48 VDC
1 A
19…30 V (1) 19…30 V (1) 38…60 V Limit values
(for U
≤
30 or 34 V, ripple included)
Curr. / chan.
0.625 A
Curr./module 4 A / 7 A
6 W Tungsten filament lamp power
Leakage current at state 0 < 0.5 mA
2.5 A
14 A
10 W
< 1 mA
1.25 A
7 A
10 W
< 1 mA
Residual voltage
Min load impedance
Response time
Preactuator voltage monitoring threshold at state 1 < 1.2 V
48
Ω
OK
1.2 ms
> 18 V
Fault < 14 V
< 0.5 V
12
Ω
µ s
> 16 V
< 14 V
< 1 V
48
Ω
300
µ s
> 36 V
< 24 V
16T3
48 VDC
0.25 A
38…60 V
0.31 A
4 A
6 W
0.5 mA
< 1.5 V
192
1.2 ms
> 36 V
< 24 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms 1500 V rms 1500 V rms 1500 V rms
Consumption typically 5 V 55 / 80 mA 55 mA 55 mA 80 mA preactuator supply 30/ 40 mA 30 mA 30 mA 40 mA
Dissipated power (13) 1.1+(0.75xN)W 1.3+(0.2xN)W 2.2 +(0.55xN)W 2.4 +(0.85xN)W
Relay outputs, thermal current 3 A
TSX DSY module reference
Operating voltageD C
A C
Thermal current
AC load Resistive Voltage duty
AC12
Power
Inductive Voltage duty Power
AC14 and
AC15
08R5 / 16R5
10...34 VDC
19...264 VAC
3 A
24 VAC 48 VAC
50 VA (6)
100..120 VAC 200..240 VAC
50 VA (7) 110 VA (7) 220 VA (7)
110 VA (5) 220 VA (5)
24 VAC
24 VA (5)
48 VAC
10 VA (11)
24 VA (9)
100..120 VAC 200..240 VAC
10 VA (12)
50 VA (8)
10 VA (12)
50 VA (10)
110 VA (3) 110 VA (7)
220 VA (2)
DC load Resistive Voltage duty Power
DC12
Inductive Voltage duty Power
24 VDC
24 W (7)
40 W (4)
24 VDC
10 W (9)
Response time
Isolation (50/60 Hz, 1 min)
Consumption
DC13
Switch on
Switch off
5 V typical
24 W (7)
< 8 ms
< 10 ms
2000 V rms
55 / 80 mA
(13) 24 V typical relay (8.5 x N) mA
Dissipated power (13) 0.25 + (0.2 x N) W
26
General introduction to discrete I/O modules
DC relay outputs
TSX DSY module reference
Operating A C voltage limit
Thermal current
DC load
08R4D not allowed
D C 19..143 VDC
5 A
Resistive Voltage 24 VDC duty
DC12
Power 50 W (7)
(max 6 A per common)
48 VDC 100..130 VDC
100 W (7) 220 W (7)
100 W (4) 200 W (4) 440 W (4)
Response time
Inductive Voltage 24 VDC duty Power 20 W (9)
DC13
Switch on
Switch off
50 W (7)
< 10 ms
< 15 ms
Isolation (50/60 Hz, 1 min)
Consumption 5 V typical
(13) 24 V typical relay
Dissipated power (13)
2000 V rms
55 mA
(10 x N) mA
48 VDC
50 W (9)
110 VDC
110 W (9)
100 W (7) 220 W (7)
0.25 + (0.24 x N) W
Relay outputs, thermal current 5 A
TSX DSY module reference
Operating voltage
Thermal current
AC load
D C
AC
08R5A
19...60 VDC
19...264 VAC
5 A
Resistive Voltage 24 VAC
(max. 6 A per common)
48 VAC 100..120 VAC 200..240 VAC
DC load duty
AC12
Power 100 VA (6) 100 VA (7) 220 VA (7) 440 VA (7)
200 VA (5) 440 VA (5)
Inductive Voltage 24 VAC duty Power 50 VA (5)
AC14
48 VAC
20 VA (11)
50 VA (9)
100..120 VAC 200..240 VAC
20 VA (12)
110 VA (8)
20 VA (12)
110 VA (10) and
AC15
Resistive Voltage 24 VDC duty Power 24 W (7)
DC12 50 W (4)
48 VDC
50 W (7)
100 W (4)
220 VA (3) 220 VA (7)
440 VA (2)
Response time
Inductive Voltage 24 VDC duty Power 10 W (9)
DC13
Switch on
Switch off
24 W (7)
< 10 ms
< 15 ms
48 VDC
24 W (9)
50 W (7)
Isolation (50/60 Hz, 1 min)
Consumption 5 V typical
2000 V rms
55 mA
(13) 24 V typical relay (10 x N) mA
Dissipated power (13) 0.25 + (0.24 x N) W
(1) up to 34 V (1 h / 24 h)
(2) 0.1 x 10 6
(3) 0.15 x 10
operations
6 operations
(4) 0.3 x 10 6 operations
(5) 0.5 x 10 6 operations
(6) 0.7 x 10
(7) 1 x 10 6
(8) 1.5 x 10 6
(9) 2 x 10 6
6 operations
operations
operations
operations
(10) 3 x 10 6
(11) 5 x 10 6
operations
operations
(12) 10 x 10 6 operations
(13) N = no. of channels at 1
27
General introduction to discrete I/O modules
Triac outputs
TSX DSY module reference
Operating voltage
Isolation (50/60 Hz, 1 min)
Consumption
5 V typical
TSX DSY 08S5
TSX DSY 16S5
08S5/16S5
41..264 VAC
2000 V rms
125 mA
220 mA
16S4
20..132 VAC
Permissible current
Response time
TSX DSY 08S5 2 A / channel - 12 A / module 1 A / channel - 12 A / module
TSX DSY 16S5 1 A / channel - 12 A / module
Switch on
Switch off
≤
≤
10 ms
10 ms
≤
≤
10 ms
10 ms
2000 V rms
220 mA
Dissipated power TSX DSY 08S5
TSX DSY 16S5
0.5 W + 1 W/A per output 0.85 W + 1 W/A per output
0.85 W + 1 W/A per output
Characteristics of output modules with connector(s)
DC solid state outputs (positive logic)
TSX DSY module reference
Nominal values Voltage
Limit values
(for U
≤
30 or 34 V, ripple included)
Tungsten filament
32T2K
24 VDC
Current
Voltage
0.1 A
19…30 V (1)
Current / channel 0.125 A
Current / module 3.2 A
1.2 W (maximum)
64T2K
24 VDC
0.1 A
19…30 V (1)
0.125 A
5 A
1.2 W (maximum) lamp power
Leakage current
Residual voltage
Min load impedance
Paralleling of outputs at state 0 at state 1
Response time
Preactuator voltage OK
monitoring threshold Fault
< 0.1 mA when U = 30 V < 0.1 mA when U = 30 V
< 1.5 V when I = 0.1 A
220
Ω
Yes : 3 max
< 1.5 V when I = 0.1 A
220
Ω
Yes : 3 max
1.2 ms
> 18 V
< 14 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms
Consumption 5 V typical 135 mA
24 V typ. sensor 30 mA
1.2 ms
> 16 V
< 14 V
1500 V rms
155 mA
60 mA
Dissipated power (2) 1.6 + (0.1 x N) W 2.4 + (0.1 x N) W
(1) up to 34 V (1 h / 24 h) (2) N = number of channels
28
General introduction to discrete I/O modules
Characteristics of mixed I/O module with connectors
Input characteristics
TSX DMY module reference
Nominal input values
Input limit values
Voltage
Current at state 1 Voltage
Current at state 0 Voltage
(ripple included)
Input impedance (at U nominal)
Type of input
Current
Sensor supply
Paralleling of inputs
Compatibility 2-wire/3-wire prox. sensor
Sensor voltage monitoring threshold
OK
Fault
Dielectric strength (50/ 60 Hz, 1 min)
Consumption 5 V typical
24 V typical sensor
Dissipated power (1)
(1) N = number of channels at 1
Output characteristics
TSX DMY module reference
Nominal output values
Voltage
Current
Output limit values
Voltage
Current / channel
Current / module
Tungsten filament lamp power
Leakage current
Residual voltage at state 0 at state 1
Minimum load impedance
Response time
Preactuator voltage monitoring threshold
Dielectric strength (50/60 Hz, 1 min)
Consumption 24 V preactuator
Dissipated power
OK
Fault
28FK / 28RFK
24 VDC
3.5 mA
≥
≥
11 V
3 mA
≤
5 V
≤
1.5 mA
19…30 V
(up to 34 V (1 h / 24 h))
6.3
κΩ current sink
Yes
Yes
> 18 V
< 14 V
1500 V rms
300 mA
20 +(3.5xN) mA
1.2 +(0.1xNb) W
28FK / 28RFK
24 VDC
500 mA
19…30 V (up to 34 V (1 h / 24 h)
0.625 A
4 A
6 W
< 1 mA
< 1.2 V
48
Ω
0.6 ms
> 18 V
< 14 V
1500 V rms
30/40 mA
1 W + 0.75 W per output at 1
29
General introduction to discrete I/O modules
Maintenance / Diagnostics
The status lamps on the front panel of the module, enable fast diagnostics of the following :
• 3 module status lamps provide information on the module operating mode
- RUN (green) : module status (on : normal operation; off : faulty module)
- ERR (red) : internal faults (on : module failure; flashing : communication fault)
- I/O (red) : external faults (on : overload, shortcircuit, sensor/ preactuator voltage fault; flashing : terminal block fault)
!
During the self-tests the RUN, ERR and I/O indicator lamps flash.
• 8, 16 or 32 channel status indicators give information on the status of every input or output (on : channel at state 1; flashing : faulty channel, overload or short-circuit; off : channel at state 0).
In addition, the +32 indicator, found on 64 channel modules, indicates the group of channels displayed (off : channels 0 to 31; on : channels 32 to 63). A pushbutton (only on 64-channel modules) is used to select the group of channels.
8-channel module
RUN ERR
I / O
5
6
7
2
3
0
1
4
For mixed I/O modules with 28 I/O (16I + 12O):
- indicators 0 to 15 display the state of the inputs
- indicators 16 to 27 display the state of the outputs
16-channel module
RUN ERR
I / O
4
5
6
7
2
3
0
1
12
13
14
15
8
9
10
11
28/32/64-channel module
RUN
+ 32
ERR
I / O
4
5
6
7
2
3
0
1
12
13
14
15
8
9
10
11
20
21
22
23
16
17
18
19
28
29
30
31
24
25
26
27
Pushbutton
30
General introduction to discrete I/O modules
Status O n
Lamps
R U N Normal operation
Flashing
-
E R R Internal fault module failure
Communication fault if
RUN lamp on
Module not configured if
RUN lamp off (1)
Terminal block fault I/O External fault : overload, short-circuit, sensor/ preactuator voltage fault
0...i
Channel at state 1 Faulty channel, overload or short-circuit
(1) This state is only available on module versions
≥
V2.0.
Off
Module faulty or switched off
No module fault
No external fault
Channel at state 0
Operating conditions
Operating temperature
Relative humidity
Operating altitude
Withstand to vibrations shocks
Withstand to electrostatic discharge
Immunity to electromagnetic fields rapid transients shock waves damped oscillating waves
Withstand to LF interference
Storage temperature
Mechanical safety
0…60° C
10…95% (without condensation)
0…2000 m
IEC 68-2-6, Fc test, severity 2 g
IEC 68-2-27, Ea test
IEC 1000-4-2, level 3
IEC 1000-4-3, level 3
IEC 1000-4-4, level 3
IEC 1000-4-5
IEC 1000-4-12
IEC 1131-2
-25…+70° C
IP 20 with TSX RKA 01 cover
31
Discrete I/O module connections
Discrete input modules
TSX DEY 08D2
Sensors
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
FU1
+ –
18
0 V
+24 VDC
20
19
Inputs
I 0
1
2
3
4
5
6
7
TSX DEY 16D2
Sensors
FU1
+ –
18
0 V
+24 VDC
20
FU1 = 0.5 A fast blow fuse
2
4
6
8
10
12
14
16
1
3
5
7
9
11
13
15
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
19
TSX DEY 16D3
Sensors
FU1
+ –
18
0 V
+48 VDC
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
15
17
19
TSX DEY 16A2 / 16A3 / 16A4 / 16A5
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Sensors
2
4
6
8
10
12
14
16
24 / 48 / 115 / 230 V
FU1 UVAC 18
20
FU1 = 0.5 A fast blow fuse
19
1
3
5
7
9
11
13
15
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
32
Discrete I/O module connections
TSX DEY 16FK
Sensors
1
3
5
7
9
11
13
A
2
4
6
8
10
12
14
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TSX DEY 32D2K
Sensors
15 16
+24 VDC
FU1
+
–
0 V
17
19
18
20
+24 VDC
FU1
+
–
0 V
FU1 = 0.5 A fast blow fuse
Sensors
1 2
1 3
1 4
15
1 6
7
8
9
10
11
17
18
1 9
2 0
4
5
2
3
6
Pin Wire colors number (HE10) (TSX CDP iiiii 01 cables)
1 White
Brown
Green
Yellow
Gray
Pink
Blue
R e d
Black
Purple
Gray - pink
Red - blue
White - green
Brown - green
White - yellow
Yellow - brown
White - gray
Gray - brown
White - pink
Pink - brown
+24 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
A
2
4
6
8
10
12
14
16
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17 18
19 20
1
3
5
7
9
11
13
15
B
2
4
6
8
10
12
14
16
Inputs
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
17 18
19 20
33
Discrete I/O module connections
TSX DEY 32D3K
(when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Sensors
+48 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
C
2
4
6
8
10
12
14
16
Inputs
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
17
19
18
20
Sensors
+48 VDC
FU1
+
–
0 V
FU1 = 0.5 A fast blow fuse
1
3
5
7
9
11
13
15
A
2
4
6
8
10
12
14
16
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17 18
19 20
34
Discrete I/O module connections
TSX DEY 64D2K (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Sensors Sensors
1
3
5
7
9
11
13
15
C
2
4
6
8
10
12
14
16
Inputs
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
1
3
5
7
9
11
13
15
A
2
4
6
8
10
12
14
16
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+24 VDC
FU1
+
–
0 V
17 18
19 20
+24 VDC
FU1
+
–
0 V
17 18
19 20
Sensors
+24 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
17
19
D
2
4
6
8
10
12
14
16
18
20
Inputs
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
Sensors
+24 VDC
FU1
+
–
0 V
FU1 = 0.5 A fast blow fuse
1
3
5
7
9
11
13
15
B
2
4
6
8
10
12
14
16
Inputs
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
17 18
19 20
35
Discrete I/O module connections
Discrete output modules
TSX DSY 08T2
Preactuators
0
1
2
3
4
5
6
7
2
4
6
8
1
3
5
7
9
10
11
12
13
14
0 V 15
16
–
+
FU1
18
17
19
+24 VDC
20
Outputs
Q0
1
2
3
4
5
6
7
TSX DSY 16T3
Preactuators
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
4
6
8
10
12
14
16
– +
FU1
FU1 = 6.3 A fast blow fuse
18
0 V
+48 VDC
20
1
3
5
7
9
11
13
15
17
19
Outputs
Q0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TSX DSY 16T2
Preactuators
0
1
2
3
4
5
6
7
8
9
10
11
12
14
13
15
– +
FU2
0 V
18
+24 VDC
20
1
2
3
4
5
6
7
8
9
10
12
11
13
14
15
16
17
19
Outputs
Q0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
FU2 = 10 A fast blow fuse
36
TSX DSY 08T22
Preactuators
0 1
2
1 3
4
2 5
6
3 7
8
4 9
10
5 11
12
6 13
14
7 15
16
– +
FU2
18
0 V
+24 VDC
20
FU2 = 16 A fast blow fuse
17
19
Outputs
Q0
5
6
7
3
4
1
2
AC load
DC load
R
0
C
MOV
19...240 VAC
7
– 24 VDC +
Protection must be provided at the preactuator terminals
Discrete I/O module connections
TSX DSY 08T31
Preactuators
0 1
2
1 3
4
2 5
6
3 7
8
4 9
10
5 11
12
6 13
14
7 15
16
– +
FU2
18
0 V
+48 VDC
20
17
19
FU2 = 10 A fast blow fuse
TSX DSY 08R5
Preactuators
Outputs
Q0
1
2
3
4
5
6
7
Outputs
19…240 VAC or 24 VDC
0
2
FU
FU
4
6
5
7
1
3
12
14
2
4
6
8
10
1
3
5
7
9
Q0
1
2
3
C0-3
4
5
6
7
C4-7
11
13
15
16
17
18
19
20
37
Discrete I/O module connections
TSX DSY 16R5
AC load
R
0
C
Preactuators
0
MOV
19...240 VAC 2
1
3
FU
7
4
DC load
5
6
7
FU
– 24 VDC +
Protection must be provided at the preactuator terminals
TSX DSY 08R5A
Preactuators
T0
R0
T1
R1
2
1
Q0
Outputs
8
9
10
11
FU
12
13
14
15
FU
19…240 VAC or 24 VDC
TSX DSY 08R4D
Preactuators
T0
R0
T1
R1
T2
4
6
8
*
3
Q1
C0-1
5
7
*
*(24 V strap)
C2-3
FU
FU
9
Q2
R2 10
T3 11
Q3
R3 12
4
5
6
14
16
18
13
*
15
Q4
C4-5
Q5
17
*
19
Q6
C6-7
Q7
7
19…240 VAC or 24 VDC
20
FU = 6.3 A fast blow fuse
FU
R2
R3
T2
T3
4
5
6
FU
7
24...130 VDC
* make connection if using 24 VAC or 24 VDC
38
2
4
6
8
10
12
14
16
18
20
2
4
6
*
8
10
12
14
16
18
20
Outputs
1
3
5
7
9
11
13
15
17
19
10
11
C8-11
12
13
14
15
C12-15
2
3
Q0
1
5
6
C0-3
4
7
C4-7
8
9
Outputs
1
Q0
3
Q1
5
7
*
C0-1
FU
*(24 V strap)
C2-3
FU
9
Q2
11
Q3
13
*
15
Q4
C4-5
Q5
17
*
19
Q6
C6-7
Q7
FU
FU
FU = 6.3 A fast blow fuse
Discrete I/O module connections
TSX DSY 08S5
Preactuators
0
1
2
1
3
1
Q0
Outputs
2
3
4
5
6
7
4
6
8
10
12
14
16
18
P N
220 VAC
TSX DSY 16S4
Preactuators
0
1
2
3
FU1
20
2
4
4 6
5
6 8
7
FU1
10
8
9 12
10
11
FU1
14
12 16
13
14 18
15
FU1
P N
220 VAC
20
FU1 = 5 A ultra fast blow fuse
5
C0-1
2
7
3
9
11
C2-3
4
13
5
15
C4-5
6
17
7
19
C6-7
FU
FU
FU
FU
FU = interchangeable
5 A ultra fast blow fuse
1
3
5
7
9
11
13
15
17
19
TSX DSY 16S5
Outputs
Q0
1
10
11
C8-11
12
13
14
15
C12-15
5
6
7
2
3
C0-3
4
C4-7
8
9
Preactuators
0
1
2
5
7
9
11
3
4
6
8
10
2
4
6
8
10
12
14
12 16
13
14 18
15
20
P N
48...240 VAC
FU = interchangeable
5 A ultra fast blow fuse
1
3
5
7
9
11
13
15
17
19
4
5
Q0
1
2
3
C0-3
6
7
C4-7
8
9
10
11
C8-11
12
13
14
15
C12-15
Outputs
FU
FU
FU
FU
39
Discrete I/O module connections
TSX DSY 32T2K (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
FU = 4 A
fast blow fuse
0 V
16
17
18
19
20
21
22
23
24
25
26
27
28
30
29
31
Preactuators
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0 V
4A
+
24 VDC
1
3
5
7
9
A
2
4
6
8
10
11 12
13 14
15 16
Outputs
Q0
1
2
3
4
5
6
7
8
9
11
10
13
12
15
14
17 18
19 20
11 12
13 14
15 16
17 18
19 20
B
1
3
5
7
9 10
6
8
2
4
25
24
27
26
29
28
31
30
17
Q16
19
18
21
20
23
22
Connect :
• the + 24VDC to terminals
17 and 19
• the 0V to terminals 18 and 20
40
Discrete I/O module connections
TSX DSY 64T2K (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Preactuators Preactuators
32
34
36
38
40
42
44
46
33
35
37
39
41
43
45
1
3
C
2
Outputs
Q32
33
34
4 35
36
5 6 37
7 8 39
38
40
9 10 41
42
11 12 43
44
13 14 45
46
15 16 47
0
2
4
6
8
10
12
14
1
3
5
7
9
11
13
1
A Outputs
Q0
2 1
2
3 4 3
4
5 6 5
6
7 8 7
8
9 10 9
10
11 12 11
12
13 14 13
14
15 16 15
47 15
0 V
17 18
0 V
17 18
19 20 19 20
4A
+
4A
+
24 VDC 24 VDC
Preactuators
48
50
52
54
56
58
60
62
49
51
53
55
57
59
61
1
3
D Outputs
Q48
2 49
50
4 51
52
5 6 53
54
7 8 55
9 10 57
56
58
11 12 59
60
13 14 61
62
15 16 63
Preactuators
16
18
20
22
24
26
28
30
17
19
21
23
25
27
29
1
B Outputs
Q16
2 17
18
3 4 19
20
5 6 21
22
7 8 23
9 10 25
24
26
11 12 27
28
13 14 29
30
15 16 31
63 31
0 V
17 18
0 V
17 18
19 20
FU = 4 A fast blow fuse
19 20
Connect the + 24VDC to terminals 17 and 19 and the 0V to terminals18 and 20
41
Discrete I/O module connections
Discrete mixed I/O module
TSX DMY 28FK/28RFK (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Preactuators
16
17
18
19
20
21
22
23
24
25
26
27
0 V
–
+
FU2
+24 VDC
1
3
5
7
9
11
13
15
17
19
C
2
4
6
8
10
12
14
16
18
20
Outputs
Q16
17
18
19
20
21
22
23
24
25
26
27
Sensors
+24 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
17
19
A
2
8
10
12
14
16
18
4
6
20
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
FU2 = 2 A fast blow fuse FU1 = 0.5 A fast blow fuse
42
43
44
Schneider Automation Inc.
One High Street
North Andover, MA 01845
Tél.: (1) 978 794 0800
Fax : (1) 978 975 9010
Schneider Automation SAS
245, route des Lucioles - BP 147
F-06903 Sophia Antipolis
Tél. : (33) (0)4 92 38 20 00
Fax : (33) (0)4 93 65 30 31
Schneider Automation GmbH
Steinheimer Straße 117
D-63500 Seligenstadt
Tél. : (49) 61 82 81 29 00
Fax : (49) 61 82 81 21 55
Printed in France September 2002
Download
Annonce