Schneider Electric TSX P57 / TPMX P57 / TSX DEY / DSY / DMY Processors, Discrete I/O Quick Reference Guide
Reklama
Reklama
Premium PLCs
TSX P57 / TPMX P57
TSX DEY / DSY / DMY
Processors
Discrete I/O
Quick Reference Guide
General safety advice for users
TSX/TPMX P57 1
ii
/P57 2
ii
/P57 3
ii
/P57 4
ii
processors
Presentation
Physical description
Catalog
Installation / Mounting
Precautions to be taken when replacing a processor
Auxiliary functions
Diagnostics using the indicator lamps
Characteristics
General introduction to discrete I/O modules
Presentation
Physical description
Catalog
Installation / Mounting
Functions
Connection equipment and wiring rules
Characteristics of input modules with terminal blocks
Characteristics of input modules with connector(s)
Characteristics of output modules with terminal block
Characteristics of output modules with connector(s)
Characteristics of mixed I/O modules with connectors
Maintenance / Diagnostics
Operating conditions
Discrete I/O module connections
Discrete input modules
Discrete output modules
Discrete mixed I/O module
Contents
2
18
18
30
31
32
33
26
27
28
18
19
21
21
24
34
34
38
44
4
4
8
12
13
7
8
4
5
1
General safety advice for users
1 General
This manual is intended for personnel technically qualified to install, operate and maintain the products which are described herein. For advanced use of these products please contact your nearest sales office for additional information.
The contents of this manual are not contractual and cannot under any circumstance extend or restrict contract warranty clauses.
2 Qualification of personnel
Only qualified personnel are authorized to install, operate or maintain the products. Any work performed by an unqualified person or non-observance of the safety instructions contained in this document or attached to the equipment may jeopardize the safety of personnel and/or cause irreparable damage to equipment.
3 Warnings
Warnings serve to prevent specific risks encountered by personnel and/or equipment.
They are indicated in the documentation and on the products by different warning symbols :
Caution
Indicates that not following instructions or ignoring the warning may cause serious personal injury, death and/or serious damage to equipment.
Important or
!
Indicates that not following a specific instruction may lead to minor injury and/or damage to equipment.
Comment
Highlights important information relating to the product, its operation or its accompanying documentation.
4 Conformity of use
The products described in this manual conform to the European Directives (*) to which they are subject (CE marking). However, they can only be used correctly in the context of the applications for which they are intended (described in the various documents) and when connected to approved third party products.
(*) EMC and LV Directives, concerning Electromagnetic Compatibility and Low Voltage.
5 Installing and setting up equipment
It is important to observe the following rules when installing and starting up equipment.
In addition, if the installation includes digital links, it is essential to follow the basic wiring rules, given in the manual "Electromagnetic Compatibility of Industrial Networks and Fieldbuses", reference TSX DG KBLE
• Safety instructions must be followed meticulously. These instructions are in the documentation or on the equipment being installed and set up.
• The type of equipment defines the way in which it should be installed :
- a flush-mountable device (for example, a process control terminal) must be flush-mounted,
- a device which is to be built in (for example, a PLC) must be placed in a cabinet or enclosure,
- the casing of a laptop or portable device (for example, a programming terminal or a notebook) must remain closed,
2
General safety advice for users
• If the device is permanently connected, its electrical installation must include a device to isolate it from the power supply and a circuit-breaker to protect it against overcurrents and isolation faults. If this is not the case, the power socket must be grounded and be easily accessed. The device must be connected to the protective ground.
• If the device is supplied with 24 or 48 VDC, the low voltage circuits must be protected.
Only use power supplies which conform to the standards currently in force.
• Check that the supply voltages remain within the tolerance ranges defined in the technical characteristics of the devices.
• All measures must be taken to ensure that any power return (immediate, warm or cold) does not lead to a dangerous state which may place personnel or the installation at risk.
• Emergency stop devices must remain effective in all the device's operating modes, even those which are abnormal (for example, when a wire becomes disconnected).
Resetting these devices must not cause uncontrolled or improper restarts.
• Cables which carry signals must be located where they do not cause interference with the control system functions by capacitative, inductive or electromagnetic interference.
• Control system equipment and their control devices must be installed in such as way as to ensure that they are protected against unintentional operation.
• Appropriate safety measures must be taken for the inputs and outputs, to prevent improper states in the control system device, if no signal is received.
6 Equipment operation
The operational safety and availability of a device is its ability to avoid the appearance of faults and to minimize their effects if they occur.
A fault inside the control system is known as :
• passive, if it results in an open output circuit (no command is sent to the actuators).
• active, if it results in a closed output circuit (a command is sent to the actuators).
From the safety point of view, a given fault is dangerous or not depending on the type of command given during normal operation. A passive fault is dangerous if the normal command is the operation of an alarm. An active fault is dangerous if it maintains or activates an undesirable command.
The system designer must use devices external to the PLC to protect against active faults inside the PLC, whether they are indicated or not.
7 Electrical and thermal characteristics
Details of the electrical and thermal characteristics of devices are given in the associated technical documents (installation manuals, service instructions).
8 Maintenance
Troubleshooting procedure
• Control system equipment should only be repaired by qualified personnel (after sales service engineer, or technician approved by Schneider Automation SA). Only certified replacement parts or components should be used.
• Before performing any operation on equipment, always cut the power supply off and mechanically lock any moving parts.
Replacement and recycling of used batteries
Use batteries of the same type as the originals and dispose of defective batteries in the same way as toxic waste.
3
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
Presentation
A wide range of high performance, increased capacity processors is offered to best respond to the various user requirements.
• TSX 57 sequential processors which can be integrated in TSX RKY•• racks :
TSX P57 102, TSX P57 202, TSX P57 252, TSX P57 302, TSX P57 352, TSX P57
402, TSX P57 452 processors
• PMX 57 process control processors which can be integrated in TSX RKY•• racks :
TPMX P57 102, TPMX P57 202, TPMX P57 352, TPMX P57 452 processors
TSX/PMX 57 processors manage an entire PLC station comprising the discrete I/O, analog I/O and application-specific modules (counter, axis control, stepper control, communication, etc) distributed over one or more racks connected on Bus X.
Each processor integrates :
• a protected internal RAM memory which can receive the application program and can be extended by a PCMCIA memory card (RAM or FLASH EPROM)
• a realtime clock
• 2 terminal ports (TER and AUX) which enable simultaneous connection of several devices (programming terminal, man-machine interface terminal, etc)
• a slot for a PCMCIA communication card (Modbus+, FIPWAY, FIPIO Agent, UNI-TELWAY, serial links).
• a FIPIO master link on some processors
The application program is created using PL7 Junior or PL7 Pro software which offers :
• 4 programming languages
• a multitasking software structure (master task and fast task, event processing)
• modification of currently running programs, etc.
Physical description
TSX P57 102/202/252
TSX P57 302/352
TPMX P57 102
1
2
3
4
5
TSX P57 402/452
TPMX P57 202/352
TPMX P57 452
1
2
3
4
5
6
7 6
7
Standard format
4
Double format
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
1 Display block with 4 or 5 indicator lamps depending on the model :
- RUN, ERR, I/O, TER lamps on all processors
- FIP lamp on processors with an integrated FIPIO master link (TSX/TPMX P57 i 52).
2 Pencil-point RESET button which is used to activate a PLC cold restart.
3 TER terminal port for connecting a peripheral which may or may not be self-powered
(programming or adjustment terminal, man-machine interface terminal, printer, etc).
4 AUX man-machine interface port for connecting a self-powered peripheral (programming or adjustment terminal, man-machine interface terminal, printer, etc).
5 Slot for a type 1 PCMCIA memory extension card.
!
If there is no memory card, this slot has a cover which must be left in place; removing it will cause the processor to stop.
6 Slot for type 3 PCMCIA communication card to connect the processor to a communication channel. If no communication card is present, this slot is fitted with a cover.
7 9-pin SUB D connector for connection to the FIPIO master bus. This connector is only available on TSX/TPMX P57 i 52 processors.
5
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
Catalog summary
• TSX 57 processors
References TSX P57 v
102
TSX RKY 12EX racks 2
TSX RKY 4EX/6EX/8EX racks 4
Module slots (1) 21 [27]
16 16 16 16 16 16
87 [111] 87 [111] 87 [111] 87 [111] 87 [111] 87 [111]
I/O profile (2)
In-rack discrete I/O (3)
In-rack analog I/O
Fixed
512
24
Fixed
1024
80
Fixed
1024
80
Fixed
1024
128
Fixed
1024
128
Flexible Flexible
2040
255
2040
255
App-specific channels (4) 8
Network connection : FIPWAY,1
ETHWAY/TCP_IP, Modbus +
Integrated FIPIO connection
Third party fieldbus connection -
-
AS-i sensors/actuators fieldbus connection
Internal memory (5)
Extension memory
2
(K16) 32
(K16) 64
202
8
24
1
-
1
4
48
128
252
8
24
1
1
1
4
64
128
-
2
8
302
8
32
3
64
256
1
2
8
352
8
32
3
80
256
-
2
8
402
8
48
4
96
256
1
2
8
452
8
48
4
96/112
256
• PMX 57 processors
References TPMX P57
TSX RKY 12EX racks v
TSX RKY 4EX/6EX/8EX racks
Module slots (1)
I/O profile (2)
In-rack discrete I/O (3)
In-rack analog I/O
App-specific channels (4)
Control loops
Network connection : FIPWAY,
512
24
8
10
1
102
2
4
21 [27]
Fixed
202
8
16
87 [111]
Fixed
1024
80
24
10
1
352
8
16
87 [111]
Fixed
1024
128
32
10
3
452
8
16
87 [111]
Flexible
2040
255
48
10
4
ETHWAY/TCP_IP, Modbus +
Integrated FIPIO connection
Third party fieldbus connection
AS-i sensors/actuators fieldbus connection
Internal memory (5)
Extension memory
(K16)
(K16)
-
-
2
-
1
4
1
2
8
1
2
8
48
64
48
128
80
128
96/112
256
(1) For standard format modules, except power supply module and processor.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks,
(2) Fixed I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels are cumulative
Flexible I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels are not cumulative, distribution is defined by a formula (see characteristics section).
(3) I/O on the FIPIO bus, third party fieldbus and AS-i fieldbus are to be counted additionally.
(4) Application-specific channels = counter, axis control, stepper control, communication, etc (see characteristics section : Number of various application-specific channels).
(5) On TSX/TPMX P57 452 : if the application is stored in the internal RAM, memory capacity = 96 Kwords; if the application is stored in the PCMCIA card, internal RAM memory capacity = 112 Kwords.
6
Installation/Mounting
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
• Installing a standard format processor module
TSX 57 and PMX 57 processor modules are installed in a TSX RKY ii rack, in position 00 or 01 depending on the type of power supply module used (standard or double format) :
- If the rack is fitted with a TSX PSY 1610/2600 standard format power supply module, the processor is installed in position 00 (preferred position) or in position 01 if position 00 is not available.
PS 00 01 02 03 04 05 06
- If the rack is fitted with a TSX PSY 3610/5500/
5520 double format power supply module, the processor is installed in position 01.
PS 00 01 02 03 04 05 06
!
The rack power supply must always b e P O W E R E D D O W N p r i o r t o mounting a processor module.
• Installing a double format processor module
TSX 57 and PMX 57 double format processor modules are installed in a TSX RKY ii rack, in positions 00 and 01 or 01 and 02 depending on the type of power supply module used (standard format or double format) :
- If the rack has a TSX PSY 1610/2600 standard format power supply module, the processor is installed in positions 00 and 01 (preferred positions) or in positions 01 and 02 if position
00 is not available.
PS 00 01 02 03 04 05 06
- If the rack has a TSX PSY 3610/5500/5520 double format power supply module, the processor is installed in positions 01 and 02.
!
The rack power supply must always be
POWERED DOWN prior to mounting a processor module.
PS 00 01 02 03 04 05 06
For mounting modules in the rack, refer to the rack installation guide.
7
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
Precautions to be taken when replacing a processor
!
When replacing a TSX/PMX 57 processor with another processor which has already been used (processor already programmed and containing an application), it is essential to cut power to all PLC station control devices.
Before restoring power to the control devices, check that the processor actually contains the required application.
Auxiliary functions
• Terminal port and auxiliary port
Two 8-pin mini-DIN connectors (non-isolated RS 485 link) are used to connect :
- TER : an FTX terminal / PC compatible or to connect the
PLC to the UNI-TELWAY bus via the TSX P ACC 01 isolation box. This port supplies 5 V to power the peripheral which is connected to it.
- AUX : a man-machine interface terminal or a printer. This port does not supply the 5 V power.
The default setting for the terminal ports is UNI-TELWAY master communication mode at 19200 bauds. They can also be configured for UNI-TELWAY slave mode or ASCII characters.
• Slot for PCMCIA communication card
This slot, on the front panel of the processor, can take a type 3
PCMCIA communication card :
- TSX SCP 111 : RS 232 D multiprotocol
- TSX SCP 112 : 20 mA current loop multiprotocol
- TSX SCP 114 : RS 485 multiprotocol, compatible with
isolated RS 422
- TSX MBP 100 : Modbus +
- TSX FPP 10 / 20 : FIPIO Agent / FIPWAY
- TSX MDM 10 : Modem
!
The processor must always be POWERED DOWN prior to inserting or removing a communication card.
PCMCIA communication card
8
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
• Internal RAM memory
This memory holds the application (data, program and constants) and its capacity varies according to the type of processor :
- 32 Kwords on TSX P57 102 processor
- 48 Kwords on TSX P57 202/TPMX P57 102/202 processors
- 64 Kwords on TSX P57 252/302 processors
- 80 Kwords on TSX /TPMX P57 352 processors
- 96 Kwords on TSX P57 402 processor)
- 96/112 Kwords (1) on TSX /TPMX P57 452 processors
If the size of the application is greater than that of the RAM, it is possible to extend the memory by using a PCMCIA memory extension card. In this case, the program and the constants are memorized in the PCMCIA memory extension card and the data in the RAM memory.
The internal RAM memory can be protected by an optional battery (TSX PLP 01), located in the power supply module. The protection is only effective as long as the power
supply and processor modules remain in the rack (see duration of internal RAM memory protection).
(1) When the application is stored in the internal RAM, memory capacity is limited to
96 Kwords.
When the application is in the card, the capacity of the internal RAM memory is
112 Kwords.
• PCMCIA memory card slot
This slot, on the front panel of the processor, can accept an optional type 1 PCMCIA memory card. If the card is not
present the cover must be kept in place.
3 families of cards are offered :
- Standard memory cards : Two types are available
Protected RAM used during creation and debugging of the application program. The memory is protected by a removable battery integrated in the memory card.
FLASH EPROM when the application program is operational
(debug completed)
- BACKUP memory card for loading the application program into the internal RAM memory, without using a terminal. This card must be loaded beforehand with the application program, which should be less than 32 Kwords in size.
- Application + file memory cards
Memory card
As well as the conventional application storage zone, these also have :
- a file zone which can be used to store data by program
- a zone which can be used to store the application symbols database. This symbols database is compressed to ensure it remains within the allocated zone without restriction. This zone is only available on some cards.
Two types of card are available :
Protected RAM
FLASH EPROM + protected RAM for data storage
9
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
!
A memory card can be inserted or removed with the POWER ON (causes a cold start). To become operational, a memory card must be fitted with a handle.
If the program contained in the PCMCIA memory card includes the RUN AUTO option, the processor will start automatically in RUN after the card has been inserted.
References for standard and backup PCMCIA memory extension cards
References Type Capacity Compatibility with TSX/TPMX processors
TSX MRP 032P
TSX MRP 064P
TSX MRP 0128P
RAM
RAM
RAM
32 K16
P 57 102
Yes
64 K16 Yes
128 K16 No
TSX MRP 0256P
TSX MFP 032P
TSX MFP 064P
RAM 256 K16
FLASH EPROM 32 K16
FLASH EPROM 64 K16
No
Yes
Yes
TSX MFP 0128P FLASH EPROM 128 K16 No
TSX MFP BAK032P RAM/Backup 32 K16 Yes
P 57 2 i 2 P 57 3 i 2 P 57 4 i 2
Yes Yes Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
References for application + file memory cards
References Type / Capacity
Application zone
File zone
(RAM)
Compatibility with processors
Symbols T S X zone P57102
T S X
P572•2
TSXP573•2
TSXP574•2
(RAM) TPMX TPMX TPMXP57352
P57102 P57202 TPMXP57452
TSX MRP 232P
TSX MRP 264P
RAM/32 K16
RAM/64 K16
Flash/Eprom
64 K16
128 K16
128 K16
TSX MRP 2128P RAM/128 K16 128 K16
TSX MRP 3256P RAM/256 K16 640 K16
TSX MFP 232P Flash/Eprom
32 K16
(5x128K16)
128 K16
TSX MFP 264P 128 K16
–
–
Yes
Yes
128 K16 No
128 K16 No
–
–
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
10
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
• RESET button
Using a pencil point to push this button causes the application to cold-start :
- processor functioning normally : start in STOP or in RUN according to configuration,
- processor faulty : forced start in STOP.
• RUN / STOP function
This is used to start or stop the application program, from a programming terminal or from a discrete input defined during configuration. A stop command from this physical input takes priority over a run command from a terminal.
• Realtime clock
The realtime clock integrated in the processor manages the current date and time as well as the date and time of the last application stop. This continues even when the processor is powered down, as long as it is mounted on the rack with the power supply module, and protected by a battery.
!
If the processor is removed the date and time information will be lost after a certain
length of time (see below).
• Duration of backup for the internal RAM and realtime clock
- Battery backup period
Ambient temperature when not operating
Backup period
PLC off 12 hours/day
PLC off 1 hour/day
≤
30°C 40°C 50°C 60°C
5 years 3 years 2 years 1 year
5 years 5 years 4, 5 years 4 years
- Standby backup while the battery is being replaced (PLC off) or while a power supply module or processor is removed. Intervention time is limited; after a certain time, the data in the RAM memory may be lost.
20°C 30°C 40°C 50°C Ambient temperature during power down
Backup period 2 h 45 min 20 min 8 min
11
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
• FIPIO master link on certain processors
Some processors have an integrated FIPIO master link which can manage a FIPIO bus to which 1 to 127 devices can be connected, such as :
TSX P57
252/352
- Momentum and TBX type distributed I/O modules (discrete and analog)
- CCX 17 operator panels
- ATV16 variable speed controllers
TSX FP
TSX P57 452
TPMX P57 352
TPMX P57 452
TSX FP
ACC12
A 9-pin SUB D connector on the front panel provides connection to the FIPIO bus using a TSX
FP ACC12 connector.
Note : complete installation of a FIPIO bus (architecture type, type of wiring to be used, wiring accessories, etc) is described in the FIPIO bus reference manual.
Diagnostics using the indicator lamps
There are 4 or 5 indicator lamps on the front panel depending on the type of processor. These enable the state of the PLC to be diagnosed quickly :
• RUN (green) : application status (on : normal operation;
flashing : PLC stopped or software blocking fault; off : PLC not configured, application missing, invalid or incompatible with the type of processor, PLC error, processor or system fault)
• ERR (red) : processor or memory card or PCMCIA communication card fault (on : PLC fault, processor or system fault; flashing :
PLC not configured, application missing, invalid or incompatible with the type of processor, PLC software blocking fault, memory card battery fault, Bus X fault (1); off : normal operation)
• I/O (red) : I/O faults (on : I/O fault, (module, channel or configuration), flashing : Bus X fault (1); off : normal operation)
• TER (yellow) : this indicates activity on the terminal port
(flashing : exchange taking place on the terminal port).
RUN
TER
ERR
I / O
• FIP (yellow) : only on TSX/TPMX P57 i 52 processors, it FIP indicates activity on the FIPIO bus (flashing : exchanges taking place on the FIPIO bus).
(1) A fault on Bus X is signalled by the ERR and I/O indicator lamps flashing simultaneously.
12
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
Characteristics
• General characteristics of TSX 57 processors
Processors TSX P57 v
Maximum characteristics for the station
TSX RKY 12EX racks
TSX RKY 4EX/6EX/8EX racks
Module slots (1)
In-rack discrete I/O on Bus X
Analog I/O on Bus X
App-specific channels on Bus X (2)
UNI-TELWAY connection (terminal port)
Network connection (FIPWAY, ETHWAY/TCP_IP, Modbus +)
Integrated master FIPIO connection
Third party fieldbus connection (INTERBUS-S, etc) (3)
AS-i fieldbus connection
Functions
I/O profile (4)
Protectable realtime clock
Memory
Internal RAM (5)
Max. extension memory
Maximum memory
Application structure
Master task
Fast task
Event processing
(1 event has priority)
Execution time for 1K instructions (6)
Internal RAM
PCMCIA card
Programming software
(K16)
102
2
2
1
-
202 252
4 16 16
21 [27] 87 [111]87 [111]
512 1024 1024
-
2
24
8 fixed
Yes
32
(K16) 64
(K16) 96
1
1
32
8
80
24
2
1
-
1
4 fixed
Yes
48
128
176
1
1
64
8
80
24
2
1
1
1
4 fixed
Yes
64
128
192
1
1
64
1.39 ms 0.78 ms0.78 ms
1.39 ms 0.98ms 0.98 ms
PL7 Junior/PL7 Pro
(under Windows 95/98 or Windows NT)
Languages Ladder, Grafcet,
Structured Text, List
(1) For standard format modules, except power supply module and processor.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks,
(2) Application-specific channels = counter, axis control, stepper control, communication, etc (see characteristics section : Number of various application-specific channels).
(3) INTERBUS-S, PROFIBUS-DP
(4) Fixed I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels is cumulative.
Flexible I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels is not cumulative (see characteristics section).
(5) Protected by battery located in the power supply module.
(6) 65% Boolean / 35% Numerical.
13
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
Characteristics
Processors TSX P57
Maximum characteristics for the station v
TSX RKY 12EX racks
TSX RKY 4EX/6EX/8EX racks
Module slots (1)
In-rack discrete I/O on Bus X
Analog I/O on Bus X
App-specific channels on Bus X (2)
UNI-TELWAY connection (terminal port)
302
Network connection (FIPWAY, ETHWAY/TCP_IP, Modbus+) 3
Integrated master FIPIO connection -
Third party fieldbus connection (INTERBUS-S, etc) (3) 2
AS-i fieldbus connection 8
Functions
I/O profile (4)
Protectable realtime clock
Memory
Internal RAM (5)
Max. extension memory
(K16)
(K16) fixed
Yes
64
256
(K16) 320 Maximum memory
Application structure
Master task
Fast task
Event processing (1 event has priority)
1
1
64
352 402 452
8
16
8
16
8
16
8
16
87 [111] 87 [111] 87 [111] 87[111]
1024 1024 2040 (7) 2040 (7)
128
32
2
128
32
2
255 (7) 255 (7)
48 (7)
2
48 (7)
2
2
8
3
1
2
8
4
-
2
8
4
1 fixed
Yes
80
256
336
1
1
64 flexible flexible
Yes
96
256
352
1
1
64
Yes
96/112
256
368
1
1
64
Execution time for 1K instructions (6)
Internal RAM
PCMCIA card
Programming software
Languages
0.78 ms 0.78 ms 0.5 ms 0.5 ms
0.98 ms 0.98 ms 0.68 ms 0.68 ms
PL7 Junior/PL7 Pro (under
Windows 95/98 or Windows NT)
Ladder, Grafcet, Structured Text,
List
(1) For standard format modules, except power supply module and processor.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks.
(2) Application-specific channels = counter, axis control, stepper control, communication, etc (see characteristics section : Number of various application-specific channels).
(3) INTERBUS-S, PROFIBUS-DP
(4) Fixed I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels is cumulative
Flexible I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels is not cumulative (see characteristics section).
(5) Protected by battery located in the power supply module.
On TSX P57 452 : if the application is stored in the internal RAM , memory capacity = 96 Kwords; if the application is stored in the PCMCIA card, internal RAM memory capacity = 112 Kwords.
(6) 65% Boolean / 35% Numerical.
(7) Maximum non-cumulative numbers.
14
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
• General characteristics of PMX 57 processors
Processors TPMX P57
Maximum characteristics for the station v
TSX RKY 12EX racks
TSX RKY 4EX/6EX/8EX racks
Module slots (1)
In-rack discrete I/O on Bus X
Analog I/O on Bus X
App-specific channels on Bus X (2)
Control loops
102 202 352 452
2
16
8
16
8
16
8
16
21 [27] 87 [111] 87 [111] 87[111]
512 1024 1024 2040 (7)
24
8
10
80
24
10
128
32
10
255 (7)
48 (7)
10
UNI-TELWAY connection (terminal port) 2
Network connection (FIPWAY, ETHWAY/TCP_IP, Modbus +)1
Integrated FIPIO master connection
Third party fieldbus connection (3)
AS-i fieldbus connection 2
-
-
Functions
I/O profile (4)
Protectable realtime clock
Memory
Internal RAM (5)(K16)
Max. extension memory
Maximum memory
Application structure
Master task
Fast task
(K16)
(K16) fixed
Yes
48
64
112
1
1
32 Event processing (1 event has priority)
Execution time for 1K instructions (6)
Internal RAM
PCMCIA card
Execution time (in ms) for
2
1
-
1
4 fixed
Yes
48
128
176
1
1
64
0.78 ms 0.5 ms
2
3
1
2
8 fixed
Yes
80
256
336
1
1
64
2
4
1
2
8 flexible
Yes
96/112
256
368
1
1
64
0.5 ms 0.5 ms
0.98ms 0.68 ms 0.68 ms 0.68 ms
Process loop
Cascaded loop
4 to 9.5 0.4 to 1 0.4 to 1 0.4 to 1
8 to 16 0.8 to 1.6 0.8 to 1.6 0.8 to 1.6
Programming software
PL7 Junior/PL7 Pro (under Windows 95/98 or Windows NT)
Languages Ladder, Grafcet, Structured Text, List
(1) For standard format modules, except power supply module and processor.
21 slots with 2 TSX RKY 12EX racks, 27 slots with 4 TSX RKY 8EX racks,
87 slots with 8 TSX RKY 12EX racks, 111 slots with 16 TSX RKY 8EX racks.
(2) Application-specific channels = counter, axis control, stepper control, communication, etc. See definition and number of the various application-specific channels.
(3) INTERBUS-S, PROFIBUS-DP
(4) Fixed I/O profile : the no. of discrete and analog I/O and application-specific channels is cumulative.
Flexible I/O profile : the number of in-rack discrete I/O, analog I/O, application-specific channels is not cumulative (see characteristics section).
(5) Protected by battery located in the power supply module.
On TSX P57 452 : when the application is stored in the internal RAM, memory capacity = 96 Kwords; when the application is in the PCMCIA card, internal RAM memory capacity = 112 Kwords.
(6) 65% Boolean / 35% Numerical .
(7) Maximum non-cumulative numbers.
15
TSX/TPMX P57 1 i /P57 2 i /P57 3 i /P57 4 i processors
• Electrical characteristics
Processors TSX PSY i power supply module consumption on 5VDC
Typical
440 mA
450 mA
Maximum
600 mA
650 mA
TSX P57 102
TSX P57 202/302
TPMX P57 102
TSX P57 252/352
TSX P57 402
TPMX P57 202
TSX P57 452
TPMX P57 352/452
500 mA
1300 mA
1350 mA
750 mA
1700 mA
1750 mA
Dissipated power
Typical
2.2 W
2.25 W
2.5 W
6.5 W
6.75 W
Maximum
3 W
3.25 W
3.75 W
8.5 W
8.75 W
• Number of application-specific channels
Application
Counting
Module/card
TSX CTY 2A
TSX CTY 2C
TSX CTY 4A
TSX CAY 21 Motion control
Axis
Stepper
TSX CAY 41
TSX CFY 11
TSX CFY 21
Yes
Yes
Yes
Weighing
Communication Serial link
TSX ISP 100
TSX SCP 11 ii (in the processor)
TSX SCP 11
TSX JNP 11 ii ii
(in TSX SCY 21601)
(in TSX SCY 21601)
Yes
No
Yes
Yes
TSX SCY 21601 (integrated channel) Yes
FIPIO Agent TSX FPP10 (in the processor)
FIPIO Master integrated in the processor
No
No
Modem TSX MDM 10 Yes
Appli-spec. Number channel
Yes
Yes
Yes
Yes
2
2
4
2
4
1
2
1
0 (*)
1
1
1
0 (*)
0 (*)
1
(*) channels not to be taken into account when calculating the maximum number of application-specific channels supported by the processor.
16
• I/O profiles
- Fixed I/O profile : the maximum number of in-rack discrete I/O, analog I/O and application-specific channels shown in the various characteristics tables is cumulative.
- Flexible I/O profile : the maximum number of in-rack discrete I/O, analog I/O and application-specific channels shown in the various characteristics tables for TSX/TPMX P57
4•2 processors is not cumulative.
Each channel and group of channels (discrete, analog, application-specific) occupies space in the internal RAM and system RAM memory; the latter is limited to 8800 bytes. The user must check the system RAM usage in the various modules and application-specific channels used in the station to ensure that system RAM usage is less than 8800 bytes.
Note : If system RAM usage is greater than 8800 bytes, the processor will be in
NOT CONFIGURED state after the application has been loaded.
The table below lists the level of system RAM usage for each type of module.
Type of module
Discrete I/O 8 or 16 channels : TSX DEY• / DSY•
Discrete I/O 28 channels : TSX DMY•
System RAM usage (in bytes)
Per module Per channel
40
120
Discrete I/O 32 or 64 channels (1) : TSX DEY• / DSY• 80
–
–
–
Security : TSX PAY•
Remote Bus X : TSX REY 200
Analog 4,8,16 channels : TSX AEY•/ASY•
Counting 1,2,4 channels : TSX CTY•
Axis control 2,3,4 channels : TSX CAY•
40
–
–
–
–
–
–
21
85
30
Stepper motor control 1,2 channels : TSX CFY•
Weighing : TSX ISP Y100
Serial links : TSX SCP 11•
Serial link : TSX SCP 2160•
Modem : TSX MDM 10
AS-i fieldbus : TSX SAY 100
FIPIO Agent bus : TSX FPP10
60
–
Third party fieldbus INTERBUS-S : TSX IBY100 25
PROFIBUS-DP : TSX PBY 100 25
Network : ETHWAY : TSXETY110/120/210, 25
Modbus + : TSX MBP 100
FIPWAY : TSX FPP20
–
–
–
–
–
–
–
30
95
25
25
–
–
–
–
–
–
–
–
(1) Combining tasks (MAST, FAST) in a group or groups of channels in a 64-channel discrete I/O module generates system RAM memory usage equivalent to 20 additional bytes per group of channels.
17
General introduction to discrete I/O modules
Presentation
Modularity
Connection
HE 10 connectors
64 I or 64 O 32 I or 32 O 32 I or 28 I/O 16 I
Connection
Screw terminal blocks
(Terminal blocks not shown)
64 I or 64 O 32 I or 32 O 8/16 I or 8/16 O 8 or 16 O
Physical description
Modules with HE 10 connectors
1 Display block
2 HE10 connectors protected by a cover. They enable connection of the sensors and preactuators either directly via preformed cables, or via TELEFAST 2 connection subbases.
18
1
2
General introduction to discrete I/O modules
Modules with connection via screw terminal block
1 Display block.
2 Removable screw terminal block for direct connection of the sensors and preactuators.
3 Door providing access to screw terminals and also acting as a reference label holder.
4 Module locating device.
!
The terminal block is supplied separately, under the reference TSX BLY 01.
1
• Reference label
This removable label is supplied with the module, to be placed inside the door (3). Printed on both sides, it displays the following information :
- door closed : module reference and type of channel. In the space provided, the user enters the module address and channel symbols,
- door open : wiring of inputs and/or outputs, with channel numbers and connection terminal numbers.
3
Catalog summary
TSX DEY .. input modules
Reference
DEY 08 D2
DEY 16 D2
DEY 16 D3
DEY 16 A2
DEY 16 A3
DEY 16 A4
DEY 16 A5
DEY 16 FK
DEY 32 D2K
DEY 32 D3K
DEY 64 D2K
Modularity Connect.
Voltage Isolation
8 (1) Ter. block 24 VDC
16 (1) Ter. block 24 VDC
Yes
Yes
16 (1) Ter. block 48 VDC
16 (2) Ter. block 24 VDC
24 VAC
Yes
Yes
Yes
16 (2) Ter. block 48 VAC
16 (2) Ter. block 115 VAC
16 (2)
16 (3)
Ter. block 230 VAC
HE10 24 VDC
32 (3)
32(1)
64 (3)
HE10
HE 10
HE10
24 VDC
48 VDC
24 VDC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(1) 2 and 3-wire proximity sensor compatibility IEC 947-5-2
(2) 2-wire proximity sensor compatibility IEC 947-5-2 AC
(3) Telemecanique 2 and 3-wire proximity sensor compatibility
Logic
Positive
Positive
Positive
Negative
–
Filtering IEC 1131
4 ms
4 ms
Type 2
Type 2
4 ms Type 2
10 ms –
50/60 Hz Type 2
–
–
50/60 Hz Type 2
50/60 Hz Type 2
– 50/60 Hz Type 1
Positive 0.1..7.5 ms Type 1
Positive
Positive
Positive
4 ms
4 ms
4 ms
Type 1
Type 2
Type 1
4
4
2
19
General introduction to discrete I/O modules
TSX DSY .. output modules
Reference
(5)
DSY 08 T2
DSY 08 T22
DSY 08 T31
DSY 16 T2
DSY 16 T3
Modularity Connect.
Voltage
8 (T)
8 (T)
8 (T)
Ter. block
Ter. block
Ter. block
24 VDC
24 VDC
48 VDC
16 (T) Ter. block 24 VAC
16 (T) Ter. block 48 VAC
DSY 08 R5
(3)
DSY 08 R4D 8 (R)
(3)
DSY 08 R5A
(3)
DSY 16 R5
(3)
DSY 08 S5
(3) (4)
8 (R)
8 (R)
Ter. block 24 VDC
24…240 VAC
Ter. block 24…110 VDC
Ter. block 24…48 VDC
24…240 VAC
16 (R) Ter. block 24 VDC
24…240 VAC
8 (S) Ter. block 48…220 VAC
DSY 16 S4
(3) (4)
DSY 16 S5
DSY 32 T2K
DSY 64 T2K
16 (S)
16 (S)
32 (T)
64 (T)
Ter. block 24…110 VAC
Ter. block 48…220 VAC
HE10
HE10
24 VDC
24 VDC
Current
0.5 A
2 A
1 A
0.5 A
0.5 A
3 A
5 A
5 A
3 A
2 A
1 A
1 A
0.1 A
0.1 A
Logic
Pos.
Pos.
Pos.
Pos.
Pos.
–
–
–
–
–
–
Protection Response time
Yes (1)
Yes (1)
Yes (1)
Yes (1)
Yes (1)
No
Yes (2)
Yes (2)
No
Yes (2)
No
1.2 ms
0.2 ms
0.2 ms
1.2 ms
1.2 ms
0 v
1<8ms
1 v
0<10ms
0
1
0
1 v v v v
1<10ms
0<15ms
1<10ms
0<10ms
–
Pos.
Pos.
Yes (2)
Yes (1)
Yes (1)
1.2 ms
1.2 ms
(1) Outputs have an integrated device for protection against short-circuits and overloads.
Modules are protected against polarity inversions.
(2) Outputs are protected by interchangeable fuses, accessed via the module front panel.
(3) A device automatically cuts off the outputs when the terminal block is unlocked.
(4) The output fallback can be configured for all modules, with the exception of triac output modules.
(5) All outputs are isolated.
( T )Transistor outputs (R) Relay outputs (S)Triac outputs
TSX DMY 28FK/28RFK mixed I/O module
Modularity Connect. Voltage Current Logic ProtectionFiltering Response IEC time 1131
16 inputs HE 10 24 VDC Pos.
0.1..7.5 ms Type 1
12 outputs (T) HE 10 24 VDC 0.5 A Pos.
Yes 0.5 ms Yes
Note : Outputs have an integrated device for protection against short-circuits and overloads.
Modules are protected against polarity inversions.
All inputs and outputs are isolated.
(T)Transistor outputs
20
General introduction to discrete I/O modules
Installation / Mounting
Discrete I/O modules can be positioned anywhere on a TSX RKY ... rack.
For inserting modules in the rack, refer to the rack installation instructions.
!
Modules can be inserted in and removed from the rack when the rack is powered up; however, the sensor and preactuator supply must be off and the terminal block disconnected.
Functions
Current generator inputs
24 VDC and 48 VDC inputs are "current generator" type. Although the input voltage may be higher than 11 V (for 24 VDC inputs) or 20 V (for 48 VDC inputs), the input current is constant.
Protecting DC solid state outputs
All protected solid state outputs have a device which detects the appearance of an overload or a short-circuit when an output is active. Any such fault deactivates the output (tripping) and the fault is signalled (the indicator lamp of the faulty channel flashes and the processor I/O indicator lights up). To use an output after tripping, it must be reactivated.
Reactivating outputs
Reactivation of a tripped output can be automatic or controlled depending on the option selected during configuration. Reactivation is required for solid state DC outputs or for relay and triac outputs protected by interchangeable fuses. It is performed on groups of 8 channels, but has no effect on channels which have not been activated or are not faulty.
• If reactivation is automatic, it is executed every 10 s by the module, until the fault disappears, enabling it to be taken into account.
• If reactivation is controlled by the application program or via an operator terminal, it will be taken into account if the fault has disappeared. The minimum time between two reactivations is 10 s.
Output fallback
On a blocking fault, all module outputs are set to a state determined by the user during configuration : maintain state, fallback to 0 or fallback to 1.
Sharing I/O
Each module is split functionally into groups of 8 channels which may be assigned to the various application tasks (for example, for a module with 16 channels, channels 0 to 7 can be assigned to the MAST task and channels 8 to 15 to the FAST task).
Channels of the same group have common operating modes and function management
(fallback and reactivation of outputs).
Programmable input filtering
TSX DEY 16FK and TSX DMY 28FK/28RFK modules configure the input filter time between 0 and 7.5 ms (4 ms by default).
!
To avoid taking account of bounce when mechanical contacts are closed, it is advisable to use a filter time greater than 3 ms.
21
General introduction to discrete I/O modules
Latching
By means of latching, TSX DEY 16FK and TSX DMY 28 FK modules can use very short pulses which have a shorter duration than the PLC scan time. The change in the input state is taken into account so that it can be processed in the next task scan.
!
The time between the arrival of 2 pulses on the same input must be at least equal to the time of 2 PLC scans.
The minimum duration of the pulse should be greater than the filter time configured.
Event management
TSX DEY 16FK and TSX DMY 28FK modules allow up to 16 inputs to be configured, enabling events to be taken into account and processed immediately by the processor (processing on an interrupt).
Monitoring the presence of the terminal block
All terminal block modules have a device which checks that the terminal block is on the module.
A fault is signalled if the terminal block is missing or if it is not properly attached to the module.
Monitoring short-circuits and overloads
Solid state output modules have a facility which monitor the state of the load. A short-circuit or overload at one or more outputs causes a fault to appear and the relevant outputs to trip.
Monitoring sensor voltage
All input modules include a facility for monitoring that the sensor and module supply voltage is sufficient to ensure correct operation of the input channels. If this voltage drops below a defined threshold, a fault is signalled.
!
The sensor supply must be protected by a 0.5 A fast blow fuse.
Monitoring preactuator voltage
All solid state output modules include a facility for monitoring that the preactuator and module supply voltage is sufficient to ensure correct operation of the output channels. If this voltage falls below a defined threshold, a fault is signalled.
Reflex and timer functions on the TSX DMY 28RFK module
This module can be used to implement applications which require a faster response time than the
FAST task or event processing (<500 ms) by means of automation functions executed at module level, independently of the PLC task, and use the following as input variables :
• the physical inputs of the module (%I),
• the output commands of the module (%Q),
• the channel or module fault data,
• the states of the module physical outputs.
These functions are programmed in configuration mode using PL7 Junior or PL7 Pro software
V
≥
3.3. The configuration screen for each output comprises two main parts :
• one part representing a simplified Ladder rung layout comprising 4 lines of 4 contacts which can be used to execute a combinational logic function for the input variables ,
• one part representing the function used which can either be direct control of the output using the configured combinational logic, or a function block.
(see examples overleaf).
22
Examples
%I5.2
%I5.3
%I5.4
%Q5.20
ERR 2
%I5.8
ERR 3
%I5.7
General introduction to discrete I/O modules
%Q5.25
%I5.2
%I5.3
%I5.4
%Q5.20
Val
Monostable
%Q
5.25
ERR 2
%I5.8
ERR 3
Sel
%I5.7
List of the main function blocks :
• on-delay type timer function block,
• off-delay type timer function block,
• on-delay/off-delay type timer function block,
• 2-value timer function block,
• selectable on-delay/off-delay timer function block,
• retriggerable monostable function block,
• time-delayed non-retriggerable monostable function block,
• 2-value monostable function block,
• oscillator function block,
• Dual threshold counter function block,
• single threshold counter with monostable function block,
• interval counter function block used to measure time or length,
• Burst function block used to generate a defined number of oscillator periods,
• PWM function block used to generate a continuous oscillation with a fixed frequency but a variable cyclic ratio,
• slow speed detection function block,
• speed monitoring function block,
• command/control function blocks used to control an action and to check that it has been executed correctly after a certain period of time :
- type 1command/control function block : (1 command),
- type 2command/control function block : (2 commands : FWD and REV),
• command function block for a number of counting points (simple position control),
• fault indication function block,
• D latch function block, memorisazion of edge,
• T latch function block, division by 2.
A more detailed description of the various function blocks and their installation using software can be found in the application-specific manual TLS DS 57 PL7 33E - Volume 1 - part B).
23
General introduction to discrete I/O modules
Connection equipment and wiring rules
Wiring rules
• External power supplies for sensors and preactuators
These power supplies must be protected against shorts-circuits and overloads, by fast blow
fuses.
!
If the 24 VDC installation does not conform to SELV (Safety Extra Low Voltage) standards, the 0 V of the power supply must be connected to the protective ground, which should be taken to ground as near as possible to the power supply unit.
• Inputs
The use of a TSX DEY 16FK/DMY 28FK fast input module requires the input filter time to be adapted to the desired function : use of sensors with mechanical contact outputs requires a filter time of ≥ 3 ms. In order to achieve faster operation, use DC inputs and sensors which have a response time less than that of AC inputs.
• Outputs
For high currents, it is advisable to segment the terminal connections by protecting each one with a fast blow fuse.
Use wire of a sufficient cross section to avoid voltage drops and temperature rises.
• Cable routing
In order to limit the AC coupling, separate the power cables (power supply, power contactors, etc) and input (sensors) and output (preactuators) cables.
Connection of modules with screw terminal block
Each terminal can accept bare wires or wires fitted with cable ends, or open lugs.
• minimum :
• maximum :
1 wire, 0.2 mm 2 (AWG 24) without cable end.
1 wire, 2 mm 2 without cable end or
1 wire, 1.5 mm 2 with cable end
5.5 mm max.
Connection of modules with HE10 connectors
• 20-wire preformed cable, 22 gauge (0.34 mm 2 )
Used for wire-to-wire connection of I/O to sensors, preactuators or connection terminals.
There are 2 product references : TSX CDP 301 (3 meters) and TSX CDP 501 (5 meters).
Terminal / Wire Terminal / Wire
5
7
1
3 white green gray blue
6
8
2
4 brown yellow pink red
9
11 black gray-pink
10
12 purple red-blue
13 white-green 14 brown-green
15 white-yellow 16 yellow-brown
17 white-gray 18 gray-brown
19 white-pink 20 pink-brown
Module
Preformed cable
24
General introduction to discrete I/O modules
• Preformed stranded connection cable with sheath, 28 gauge (0.08 mm 2 )
Used to connect I/O to TELEFAST 2 rapid wiring connection and adaptation interfaces.
Bearing in mind the small cross section of the wires, it is recommended that the connection cable is only used for low current inputs or outputs ( ≤ 100 mA).
Module
Preformed cable
There are 3 product references :
TSX CDP 102 (1 meter), TSX CDP 202
(2 meters) and TSX CDP 302 (3 meters).
• Connection cable, 22 gauge (0.34 mm 2 )
Connection cable
Used to connect I/O to TELEFAST 2 rapid wiring connection and adaptation interfaces.
The wire cross section (0.34 mm 2 ) enables higher currents to be carried than when using the preformed connection cable
( ≤ 500 mA).
TELEFAST 2
ABE-7H iiiii
There are 5 product references : TSX CDP 053 (0.5 meters), TSX CDP 103 (1 meter),
TSX CDP 203 (2 meters), TSX CDP 303 (3 meters) and TSX CDP 503 (5 meters).
Maximum tightening torques :
• on screw for fixing the module on the rack :
• on screw for TSX BLY 01 connection terminal block :
• on screw for TSX CDP • cable connectors :
2.0 N.m
0.8 N.m
0.5 N.m
25
General introduction to discrete I/O modules
Characteristics of input modules with terminal blocks
DC inputs
TSX DEY module reference
Nominal input values
Input l i m i t values at state 0
Voltage
Voltage
Current
24 VDC at state 1
Current 7 mA
Voltage
Current
≥
11 V
≥
6.5 mA
(U = 11 V)
≤
5 V
≤
2 mA
Sensor supply
(ripple included)
Input impedance (at U nominal)
Logic
IEC 1131-2 conformity
19…30 V
(1)
4 k
Ω positive
Type 2
Type of input
Paralleling of inputs
Consumption 5 V typical
0 8 D 2 / 1 6 D 2
Compatibility 2-wire/3-wire prox. sensor IEC 947-5-2
Sensor voltage monitoring threshold
Dielectric strength (50/60 Hz, 1 min) 1500 V rms
(2) typ. sensor supply
Dissipated power(2)
OK
Fault current sink
Yes
> 18 V
< 14 V
55 / 80 mA
25 +(Nx 7) mA
1 6 D 3
48 VDC
7 mA
≥
≥
30 V
6.5 mA
(U = 30 V)
≤
10 V
≤
2 mA
38…60 V
7 k
Ω positive
Type 2 current sink
Yes
IEC 947-5-2
> 36 V
< 24 V
1500 V rms
80 mA
25 +(Nx 7) mA
1 +(Nx 0.15) W 1 +(Nx 0.3) W
1 6 A 2
24 VDC
16 mA
≤
Ual - 14 V
≥
6.5 mA
≥
Ual - 5 V
≤
2 mA
19…30 V
(1)
1.6 k
Ω negative
– resistive
Yes
IEC 947-5-2
> 18 V
< 14 V
1500 V rms
80 mA
15 +(Nx 15) mA
1 +(Nx 0.4) W
AC inputs
TSX DEY module reference
Nominal input Voltage values Current
Input limit values at state 1 Voltage
Current
1 6 A 2
24 VAC
15 mA
10 V
6 mA
1 6 A 3
48 VAC
16 mA
29 V
6 mA
1 6 A 4
12 mA
74 V
6 mA
1 6 A 5
100..120 VAC 200..240 VAC
15 mA
159 V
6 mA
(U = 10 V) (U = 29 V) (U = 74 V) at state 0 Voltage/current 5 V/3 mA 10 V/4 mA 20 V/4 mA
(U = 159 V)
40 V/4 mA
Frequency 47…63 Hz 47…63 Hz 47…63 Hz 47…63 Hz
Sensor supply
Input impedance
Sensor voltage monitoring threshold
OK
Fault
20…26 V
1.6 k
Ω
IEC 1131-2 conformity
Type of input
Type 2 resistive
Compatibility 2-wire/3-wire prox. sensor IEC 947-5-2
> 18 V
< 14 V
40…52 V
3.2 k
Ω
Type 2 capacitive
IEC 947-5-2
> 36 V
< 24 V
85…132 V 170…264 V
9.2 k
Ω
Type 2 capacitive
IEC 947-5-2
> 82V
< 40 V
20 k
Ω
Type 1 capacitive
IEC 947-5-2
> 164V
< 80 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms 1500 V rms 1500 V rms 2000 V rms
Consumption 5 V typical 80 mA 80 mA 80 mA 80 mA
(2) typ. sensor supply (mA) 15 + (Nx15) 16 + (Nx16) 15 + (Nx15) 12 + (Nx12)
Power dissipated per channel (2)
(1) up to 34 V (1 h / 24 h)
1+(0.35xN) W 1+(0.35xN) W 1+(0.35xN) W 1+(0.35xN) W
(2) N = number of channels at 1
26
General introduction to discrete I/O modules
Characteristics of input modules with connector(s)
TSX DEY module reference
Nominal input values
Input limit values
Voltage
Current at state 1 Voltage
Current at state 0 Voltage
Current
Sensor supply
(ripple included)
Input impedance (at U nominal)
Type of input
Logic
IEC 1131-2 conformity
16FK
24 VDC
3.5 mA
≥
11 V
≥
3 mA
≤
5 V
≤
1.5 mA
19…30 V
(1)
6.3
κΩ current sink positive
Type 1
Paralleling of inputs Yes
Compatibility 2-wire/3-wire prox. sensor Yes
Sensor voltage monitoring threshold
OK
Fault
Dielectric strength (50/60 Hz, 1 min)
Consumption
(2)
5 V typical
24 V typ. sensor
> 18 V
< 14 V
1500 V rms
32D2K
24 VDC
3.5 mA
≥
11 V
≥
3 mA
≤
5 V
≤
1.5 mA
19…30 V
(1)
6.3
κΩ current sink positive
Type 1
No
Yes
> 18 V
< 14 V
1500 V rms
64D2K
24 VDC
3.5 mA
≥
11 V
≥
3 mA
≤
5 V
≤
1.5 mA
19…30 V
(1)
6.3
κΩ current sink positive
Type 1
No
Yes
> 18 V
< 14 V
1500 V rms
250 mA 135 mA 155 mA
20 +(Nx3.4) mA 30 +(Nx3.5) mA 60 +(Nx3.5) mA
Dissipated power(2)
(1) up to 34 V (1 h / 24 h)
1.2 +(Nx0.1) W 1 +(Nx0.1) W 1.5 +(Nx0.1) W
(2) N = number of channels at 1
TSX DEY module reference
Nominal input values
Input limit values
Voltage
Current at state 1 Voltage
Current at state 0 Voltage
Current
Input impedance (at U nominal)
Type of input
Logic
Sensor supply
(ripple included)
IEC 1131-2 conformity
Paralleling of inputs
Compatibility 2-wire/3-wire prox. sensor
Sensor voltage OK monitoring threshold Fault
Dielectric strength (50/60 Hz, 1 min)
Consumption 5 V typical
(2) 24 V typ. sensor
Dissipated power(2)
(2) N = number of channels at 1
.
32D3K
48 VDC
7 mA
≥
≥
30 V
6.5 mA (when U = 30V)
≤
10 V
≤
2 mA
38…60 V
6.3 k
Ω current sink positive
Type 2
Yes
Yes
> 36 V
< 24 V
1500 V rms
300 mA
50 +(7xN) mA
2.5 +(Nx0.34) W
27
Characteristics of output modules with terminal block
DC solid state outputs (positive logic)
TSX DSY module reference 08T2
16T2
08T22 08T31
Nominal values Voltage
Current
Voltage
24 VDC
0.5 A
24 VDC
2 A
48 VDC
1 A
19…30 V (1) 19…30 V (1) 38…60 V Limit values
(for U
≤
30 or 34 V, ripple included)
Curr. / chan.
0.625 A
Curr./module 4 A / 7 A
6 W Tungsten filament lamp power
Leakage current at state 0 < 0.5 mA
2.5 A
14 A
10 W
< 1 mA
1.25 A
7 A
10 W
< 1 mA
Residual voltage
Min load impedance
Response time
Preactuator voltage monitoring threshold at state 1 < 1.2 V
48
OK
1.2 ms
> 18 V
Fault < 14 V
< 0.5 V
12
µ s
> 16 V
< 14 V
< 1 V
48
µ s
> 36 V
< 24 V
16T3
48 VDC
0.25 A
38…60 V
0.31 A
4 A
6 W
0.5 mA
< 1.5 V
192
1.2 ms
> 36 V
< 24 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms 1500 V rms 1500 V rms 1500 V rms
Consumption typically 5 V 55 / 80 mA 55 mA 55 mA 80 mA preactuator supply 30/ 40 mA 30 mA 30 mA 40 mA
Dissipated power (12) 1.1+(0.75xN)W 1.3+(0.2xN)W 2.2 +(0.55xN)W2.4 +(0.85xN)W
Relay outputs, thermal current 3 A
TSX DSY module reference
Operating voltageD C
A C
Thermal current
AC load Resistive Voltage duty
AC12
Power
Inductive Voltage duty Power
AC14 and
AC15
08R5 / 16R5
10...34 VDC
19...264 VAC
3 A
24 VAC 48 VAC
50 VA (5)
100..120 VAC 200..240 VAC
50 VA (6) 110 VA (6) 220 VA (6)
110 VA (4) 220 VA (4)
24 VAC
24 VA (4)
48 VAC
10 VA (10)
24 VA (8)
100..120 VAC 200..240 VAC
10 VA (11)
50 VA (7)
10 VA (11)
50 VA (9)
110 VA (2) 110 VA (6)
220 VA (1)
DC load Resistive Voltage duty Power
DC12
Inductive Voltage duty Power
24 VDC
24 W (6)
40 W (3)
24 VDC
10 W (8)
Response time
Isolation (50/60 Hz, 1 min)
Consumption
DC13
Switch on
Switch off
5 V typical
24 W (6)
< 8 ms
< 10 ms
2000 V rms
55 / 80 mA
(12) 24 V typical relay (8.5 x N) mA
Dissipated power (12) 0.25 + (0.2 x N) W
28
General introduction to discrete I/O modules
General introduction to discrete I/O modules
DC relay outputs
TSX DSY module reference
Operating A C voltage limit
Thermal current
DC load
08R4D not allowed
D C 19..143 VDC
5 A
Resistive Voltage 24 VDC duty
DC12
Power 50 W (6)
(max 6 A per common)
48 VDC 100..130 VDC
100 W (6) 220 W (6)
100 W (3) 200 W (3) 440 W (3)
Response time
Inductive Voltage duty Power
DC13
Switch on
Switch off
Isolation (50/60 Hz, 1 min)
Consumption 5 V typical
(12) 24 V typical relay
Dissipated power (12)
24 VDC
20 W (8)
50 W (6)
< 10 ms
< 15 ms
48 VDC
50 W (8)
110 VDC
110 W (8)
100 W (6) 220 W (6)
2000 V rms
55 mA
(10 x N) mA
0.25 + (0.24 x N) W
Relay outputs, thermal current 5 A
TSX DSY module reference
Operating D C
AC voltage
Thermal current
AC load
08R5A
19...60 VDC
19...264 VAC
5 A (max. 6 A per common)
Resistive Voltage 24 VAC duty Power 100 VA (5)
48 VAC
100 VA (6)
100..120 VAC 200..240 VAC
220 VA (6) 440 VA (6)
AC12 200 VA (4) 440 VA (4)
DC load
Inductive Voltage duty Power
AC14 and
AC15
24 VAC
50 VA (4)
Resistive Voltage 24 VDC duty Power 24 W (6)
48 VAC
48 VDC
50 W (6)
100..120 VAC 200..240 VAC
20 VA (10) 20 VA (11) 20 VA (11)
50 VA (8) 110 VA (7) 110 VA (9)
220 VA (2) 220 VA (6)
440 VA (1)
DC12 50 W (3) 100 W (3)
Inductive Voltage 24 VDC duty Power 10 W (8)
DC13
Switch on
24 W (6)
< 10 ms
48 VDC
24 W (8)
50 W (6)
Response time Switch off
Isolation (50/60 Hz, 1 min)
Consumption 5 V typical
< 15 ms
2000 V rms
55 mA
(12) 24 V typical relay (10 x N) mA
Dissipated power (12) 0.25 + (0.24 x N) W
(1) 0.1 x 10 6
(2) 0.15 x 10
operations
6 operations
(3) 0.3 x 10
(4) 0.5 x 10
6
6
operations
operations
(5) 0.7 x 10
(6) 1 x 10 6 operations
(7) 1.5 x 10
(8) 2 x 10 6
6
6
operations
operations
operations
(9) 3 x 10 6
(10) 5 x 10
operations
6 operations
(11) 10 x 10 6 operations
(12) N = no. of channels at 1
29
General introduction to discrete I/O modules
Triac outputs
TSX DSY module reference
Operating voltage
Isolation (50/60 Hz, 1 min)
Consumption
5 V typical
TSX DSY 08S5
TSX DSY 16S5
08S5/16S5
41..264 VAC
2000 V rms
125 mA
220 mA
16S4
20..132 VAC
Permissible current
Response time
TSX DSY 08S5 2 A / channel - 12 A / module 1 A / channel - 12 A / module
TSX DSY 16S5 1 A / channel - 12 A / module
Switch on
Switch off
≤
≤
10 ms
10 ms
≤
≤
10 ms
10 ms
2000 V rms
220 mA
Dissipated power TSX DSY 08S5
TSX DSY 16S5
0.5 W + 1 W/A per output 0.85 W + 1 W/A per output
0.85 W + 1 W/A per output
Characteristics of output modules with connector(s)
DC solid state outputs (positive logic)
TSX DSY module reference
Nominal values Voltage
Limit values
(for U
≤
30 or 34 V, ripple included)
Tungsten filament
32T2K
24 VDC
Current
Voltage
0.1 A
19…30 V (1)
Current / channel 0.125 A
Current / module 3.2 A
1.2 W (maximum)
64T2K
24 VDC
0.1 A
19…30 V (1)
0.125 A
5 A
1.2 W (maximum) lamp power
Leakage current
Residual voltage
Min load impedance
Paralleling of outputs at state 0 at state 1
Response time
Preactuator voltage OK
monitoring threshold Fault
< 0.1 mA when U = 30 V < 0.1 mA when U = 30 V
< 1.5 V when I = 0.1 A
220
Yes : 3 max
< 1.5 V when I = 0.1 A
220
Yes : 3 max
1.2 ms
> 18 V
< 14 V
Dielectric strength (50/60 Hz, 1 min) 1500 V rms
Consumption 5 V typical 135 mA
24 V typ. sensor 30 mA
1.2 ms
> 16 V
< 14 V
1500 V rms
155 mA
60 mA
Dissipated power (2) 1.6 + (0.1 x N) W 2.4 + (0.1 x N) W
(1) up to 34 V (1 h / 24 h) (2) N = number of channels
30
General introduction to discrete I/O modules
Characteristics of mixed I/O module with connectors
Input characteristics
TSX DMY module reference
Nominal input values
Input limit values
Voltage
Current at state 1 Voltage
Current at state 0 Voltage
(ripple included)
Input impedance (at U nominal)
Type of input
Current
Sensor supply
Paralleling of inputs
Compatibility 2-wire/3-wire prox. sensor
Sensor voltage monitoring threshold
OK
Fault
Dielectric strength (50/ 60 Hz, 1 min)
Consumption 5 V typical
24 V typical sensor
Dissipated power (1)
(1) N = number of channels at 1
Output characteristics
TSX DMY module reference
Nominal output values
Voltage
Current
Output limit values
Voltage
Current / channel
Current / module
Tungsten filament lamp power
Leakage current
Residual voltage at state 0 at state 1
Minimum load impedance
Response time
Preactuator voltage monitoring threshold
Dielectric strength (50/60 Hz, 1 min)
Consumption 24 V preactuator
Dissipated power
OK
Fault
28FK / 28RFK
24 VDC
3.5 mA
≥
≥
11 V
3 mA
≤
5 V
≤
1.5 mA
19…30 V
(up to 34 V (1 h / 24 h))
6.3
κΩ current sink
Yes
Yes
> 18 V
< 14 V
1500 V rms
300 mA
20 +(3.5xN) mA
1.2 +(0.1xNb) W
28FK / 28RFK
24 VDC
500 mA
19…30 V (up to 34 V (1 h / 24 h)
0.625 A
4 A
6 W
< 1 mA
< 1.2 V
48
Ω
0.6 ms
> 18 V
< 14 V
1500 V rms
30/40 mA
1 W + 0.75 W per output at 1
31
General introduction to discrete I/O modules
Maintenance / Diagnostics
The status lamps on the front panel of the module, enable fast diagnostics of the following :
• 3 module status lamps provide information on the module operating mode
- RUN (green) : module status (on : normal operation; off : faulty module)
- ERR (red) : internal faults (on : module failure; flashing : communication fault)
- I/O (red) : external faults (on : overload, shortcircuit, sensor/ preactuator voltage fault; flashing : terminal block fault)
!
During the self-tests the RUN, ERR and I/O indicator lamps flash.
• 8, 16 or 32 channel status indicators give information on the status of every input or output (on : channel at state 1; flashing : faulty channel, overload or short-circuit; off : channel at state 0).
In addition, the +32 indicator, found on 64 channel modules, indicates the group of channels displayed (off : channels 0 to 31; on : channels 32 to 63). A pushbutton (only on 64-channel modules) is used to select the group of channels.
8-channel module
RUN ERR
I / O
5
6
7
2
3
0
1
4
For mixed I/O modules with 28 I/O (16I + 12O):
- indicators 0 to 15 display the state of the inputs
- indicators 16 to 27 display the state of the outputs
16-channel module
RUN ERR
I / O
4
5
6
7
2
3
0
1
12
13
14
15
8
9
10
11
28/32/64-channel module
RUN
+ 32
ERR
I / O
4
5
6
7
2
3
0
1
12
13
14
15
8
9
10
11
20
21
22
23
16
17
18
19
28
29
30
31
24
25
26
27
Pushbutton
32
General introduction to discrete I/O modules
Status O n
Lamps
R U N Normal operation
Flashing
-
E R R Internal fault module failure
Communication fault if
RUN lamp on
Module not configured if
RUN lamp off (1)
Terminal block fault I/O External fault : overload, short-circuit, sensor/ preactuator voltage fault
0...i
Channel at state 1 Faulty channel, overload or short-circuit
(1) This state is only available on module versions
≥
V2.0.
Off
Module faulty or switched off
No module fault
No external fault
Channel at state 0
Operating conditions
Operating temperature
Relative humidity
Operating altitude
Withstand to vibrations shocks
Withstand to electrostatic discharge
Immunity to electromagnetic fields rapid transients shock waves damped oscillating waves
Withstand to LF interference
Storage temperature
Mechanical safety
0…60° C
10…95% (without condensation)
0…2000 m
IEC 68-2-6, Fc test, severity 2 g
IEC 68-2-27, Ea test
IEC 1000-4-2, level 3
IEC 1000-4-3, level 3
IEC 1000-4-4, level 3
IEC 1000-4-5
IEC 1000-4-12
IEC 1131-2
-25…+70° C
IP 20 with TSX RKA 01 cover
33
Discrete I/O module connections
Discrete input modules
TSX DEY 08D2
Sensors
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
FU1
+ –
18
0 V
+24 VDC
20
19
Inputs
I 0
1
2
3
4
5
6
7
TSX DEY 16D2
Sensors
FU1
+ –
18
0 V
+24 VDC
20
FU1 = 0.5 A fast blow fuse
2
4
6
8
10
12
14
16
1
3
5
7
9
11
13
15
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
19
TSX DEY 16D3
Sensors
FU1
+ –
18
0 V
+48 VDC
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
15
17
19
TSX DEY 16A2 / 16A3 / 16A4 / 16A5
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Sensors
2
4
6
8
10
12
14
16
24 / 48 / 115 / 230 V
FU1 UVAC 18
20
FU1 = 0.5 A fast blow fuse
19
1
3
5
7
9
11
13
15
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
34
Discrete I/O module connections
TSX DEY 16FK
Sensors
1
3
5
7
9
11
13
A
2
4
6
8
10
12
14
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TSX DEY 32D2K
Sensors
15 16
+24 VDC
FU1
+
–
0 V
17
19
18
20
+24 VDC
FU1
+
–
0 V
FU1 = 0.5 A fast blow fuse
Sensors
1 2
1 3
1 4
15
1 6
7
8
9
10
11
17
18
1 9
2 0
4
5
2
3
6
Pin Wire colors number (HE10) (TSX CDP i 01 cables)
1 White
Brown
Green
Yellow
Gray
Pink
Blue
R e d
Black
Purple
Gray - pink
Red - blue
White - green
Brown - green
White - yellow
Yellow - brown
White - gray
Gray - brown
White - pink
Pink - brown
+24 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
A
2
4
6
8
10
12
14
16
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17 18
19 20
1
3
5
7
9
11
13
15
B
2
4
6
8
10
12
14
16
Inputs
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
17 18
19 20
35
Discrete I/O module connections
TSX DEY 32D3K
(when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Sensors
+48 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
C
2
4
6
8
10
12
14
16
Inputs
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
17
19
18
20
Sensors
+48 VDC
FU1
+
–
0 V
FU1 = 0.5 A fast blow fuse
1
3
5
7
9
11
13
15
A
2
4
6
8
10
12
14
16
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17 18
19 20
36
Discrete I/O module connections
TSX DEY 64D2K (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Sensors Sensors
1
3
5
7
9
11
13
15
C
2
4
6
8
10
12
14
16
Inputs
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
1
3
5
7
9
11
13
15
A
2
4
6
8
10
12
14
16
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+24 VDC
FU1
+
–
0 V
17 18
19 20
+24 VDC
FU1
+
–
0 V
17 18
19 20
Sensors
+24 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
17
19
D
2
4
6
8
10
12
14
16
18
20
Inputs
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
Sensors
+24 VDC
FU1
+
–
0 V
FU1 = 0.5 A fast blow fuse
1
3
5
7
9
11
13
15
B
2
4
6
8
10
12
14
16
Inputs
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
17 18
19 20
37
Discrete I/O module connections
Discrete output modules
TSX DSY 08T2
Preactuators
0
1
2
3
4
5
6
7
2
4
6
8
1
3
5
7
9
10
11
12
13
14
0 V 15
16
–
+
FU1
18
17
19
+24 VDC
20
Outputs
Q0
1
2
3
4
5
6
7
TSX DSY 16T3
Preactuators
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
4
6
8
10
12
14
16
– +
FU1
FU1 = 6.3 A fast blow fuse
18
0 V
+48 VDC
20
1
3
5
7
9
11
13
15
17
19
Outputs
Q0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TSX DSY 16T2
Preactuators
0
1
2
3
4
5
6
7
8
9
10
11
12
14
13
15
– +
FU2
0 V
18
+24 VDC
20
1
2
3
4
5
6
7
8
9
10
12
11
13
14
15
16
17
19
Outputs
Q0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
FU2 = 10 A fast blow fuse
38
TSX DSY 08T22
Preactuators
0 1
2
1 3
4
2 5
6
3 7
8
4 9
10
5 11
12
6 13
14
7 15
16
– +
FU2
18
0 V
+24 VDC
20
FU2 = 16 A fast blow fuse
17
19
Outputs
Q0
5
6
7
3
4
1
2
AC load
DC load
R
0
C
MOV
19...240 VAC
7
– 24 VDC +
Protection must be provided at the preactuator terminals
Discrete I/O module connections
TSX DSY 08T31
Preactuators
0 1
2
1 3
4
2 5
6
3 7
8
4 9
10
5 11
12
6 13
14
7 15
16
– +
FU2
18
0 V
+48 VDC
20
17
19
FU2 = 10 A fast blow fuse
TSX DSY 08R5
Preactuators
Outputs
Q0
1
2
3
4
5
6
7
Outputs
19…240 VAC or 24 VDC
0
2
FU
FU
4
6
5
7
1
3
12
14
2
4
6
8
10
1
3
5
7
9
Q0
1
2
3
C0-3
4
5
6
7
C4-7
11
13
15
16
17
18
19
20
39
Discrete I/O module connections
TSX DSY 16R5
AC load
R
0
C
Preactuators
0
MOV
19...240 VAC 2
1
3
FU
7
4
DC load
5
6
7
FU
– 24 VDC +
Protection must be provided at the preactuator terminals
TSX DSY 08R5A
Preactuators
T0
R0
T1
R1
2
1
Q0
Outputs
8
9
10
11
FU
12
13
14
15
FU
19…240 VAC or 24 VDC
TSX DSY 08R4D
Preactuators
T0
R0
T1
R1
T2
4
6
8
*
3
Q1
C0-1
5
7
*
*(24 V strap)
C2-3
FU
FU
9
Q2
R2 10
T3 11
Q3
R3 12
4
5
6
14
16
18
13
*
15
Q4
C4-5
Q5
17
*
19
Q6
C6-7
Q7
7
19…240 VAC or 24 VDC
20
FU = 6.3 A fast blow fuse
FU
R2
R3
T2
T3
4
5
6
FU
7
24...130 VDC
* make connection if using 24 VAC or 24 VDC
40
2
4
6
8
10
12
14
16
18
20
2
4
6
*
8
10
12
14
16
18
20
Outputs
1
3
5
7
9
11
13
15
17
19
10
11
C8-11
12
13
14
15
C12-15
2
3
Q0
1
5
6
C0-3
4
7
C4-7
8
9
Outputs
1
Q0
3
Q1
5
7
*
C0-1
FU
*(24 V strap)
C2-3
FU
9
Q2
11
Q3
13
*
15
Q4
C4-5
Q5
17
*
19
Q6
C6-7
Q7
FU
FU
FU = 6.3 A fast blow fuse
Discrete I/O module connections
TSX DSY 08S5
Preactuators
0
1
2
1
3
1
Q0
Outputs
2
3
4
5
6
7
4
6
8
10
12
14
16
18
P N
220 VAC
TSX DSY 16S4
Preactuators
0
1
2
3
FU1
20
2
4
4 6
5
6 8
7
FU1
10
8
9 12
10
11
FU1
14
12 16
13
14 18
15
FU1
P N
220 VAC
20
FU1 = 5 A ultra fast blow fuse
5
C0-1
2
7
3
9
11
C2-3
4
13
5
15
C4-5
6
17
7
19
C6-7
FU
FU
FU
FU
FU = interchangeable
5 A ultra fast blow fuse
1
3
5
7
9
11
13
15
17
19
TSX DSY 16S5
Outputs
Q0
1
10
11
C8-11
12
13
14
15
C12-15
5
6
7
2
3
C0-3
4
C4-7
8
9
Preactuators
0
1
2
5
7
9
11
3
4
6
8
10
2
4
6
8
10
12
14
12 16
13
14 18
15
20
P N
48...240 VAC
FU = interchangeable
5 A ultra fast blow fuse
1
3
5
7
9
11
13
15
17
19
4
5
Q0
1
2
3
C0-3
6
7
C4-7
8
9
10
11
C8-11
12
13
14
15
C12-15
Outputs
FU
FU
FU
FU
41
Discrete I/O module connections
TSX DSY 32T2K (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
FU = 4 A
fast blow fuse
0 V
16
17
18
19
20
21
22
23
24
25
26
27
28
30
29
31
Preactuators
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0 V
4A
+
24 VDC
11 12
13 14
15 16
17 18
19 20
B
1
3
5
7
9 10
6
8
2
4
1
3
5
7
9
A
2
4
6
8
10
11 12
13 14
15 16
Outputs
Q0
1
2
3
4
5
6
7
8
9
11
10
13
12
15
14
17 18
19 20
!
Connect :
• the + 24VDC to terminals
17 and 19
• the 0V to terminals 18 and 20
25
24
27
26
29
28
31
30
17
Q16
19
18
21
20
23
22
42
Discrete I/O module connections
TSX DSY 64T2K (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Preactuators Preactuators
32
34
36
38
40
42
44
46
33
35
37
39
41
43
45
1
3
C
2
Outputs
Q32
33
34
4 35
36
5 6 37
7 8 39
38
40
9 10 41
42
11 12 43
44
13 14 45
46
15 16 47
0
2
4
6
8
10
12
14
1
3
5
7
9
11
13
1
A Outputs
Q0
2 1
2
3 4 3
4
5 6 5
6
7 8 7
8
9 10 9
10
11 12 11
12
13 14 13
14
15 16 15
47 15
0 V
17 18
0 V
17 18
19 20 19 20
4A
+
4A
+
24 VDC 24 VDC
Preactuators
48
50
52
54
56
58
60
62
49
51
53
55
57
59
61
1
3
D Outputs
Q48
2 49
50
4 51
52
5 6 53
54
7 8 55
9 10 57
56
58
11 12 59
60
13 14 61
62
15 16 63
Preactuators
16
18
20
22
24
26
28
30
17
19
21
23
25
27
29
1
B Outputs
Q16
2 17
18
3 4 19
20
5 6 21
22
7 8 23
9 10 25
24
26
11 12 27
28
13 14 29
30
15 16 31
63 31
0 V
17 18
0 V
17 18
19 20
FU = 4 A fast blow fuse
19 20
!
Connect the + 24VDC to terminals 17 and 19 and the 0V to terminals18 and 20
43
Discrete I/O module connections
Discrete mixed I/O module
TSX DMY 28FK/28RFK (when using a TSX CDP i 01 preformed cable, the correspondence between the HE10 connector pins and the wire colors is shown on page 35)
Preactuators
16
17
18
19
20
21
22
23
24
25
26
27
0 V
–
+
FU2
+24 VDC
1
3
5
7
9
11
13
15
17
19
C
2
4
6
8
10
12
14
16
18
20
Outputs
Q16
17
18
19
20
21
22
23
24
25
26
27
Sensors
+24 VDC
FU1
+
–
0 V
1
3
5
7
9
11
13
15
17
19
A
2
8
10
12
14
16
18
4
6
20
Inputs
I 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
FU2 = 2 A fast blow fuse FU1 = 0.5 A fast blow fuse
44
Schneider Automation Inc.
One High Street
North Andover, MA 01845
Tél.: (1) 978 794 0800
Fax : (1) 978 975 9010
Schneider Automation S.A.
245, route des Lucioles - BP 147
F-06903 Sophia Antipolis
Tél. : (33) (0)4 92 38 20 00
Fax : (33) (0)4 93 65 30 31
Schneider Automation GmbH
Steinheimer Straße 117
D-63500 Seligenstadt
Tél. : (49) 6182 81 2584
Fax : (49) 6182 81 2860
Printed in France January 2000