Appendix A. Omron NT-series NT600S-ST211(B)-EV3, NT-series NT600S-ST121(B)-EV3, NT-series NT20S-ST161-EV3, NT-series NT20S-ST121-EV3, NT-series NT20S, NT-series NT20M-DT131, NT-series NT20S-ST168, NT-series NT20S-ST128, NT-series NT20S-ST122-V1
Mainos
Mainos
Specifications Appendix A
APPENDIX A
Specifications
General Specifications
Item
Power supply voltage
Allowable power supply voltage range
Power consumption
Inrush current
Ambient operating temperature
Storage temperature
Ambient operating humidity
Operating environment
Resistance to electrostatic discharge
Electromagnetic field strength
Fast transient/burst noise
Damped oscillatory wave
Vibration resistance
Shock resistance
Dimensions (mm)
Weight
Enclosure ratings
Applicable standards
Specification
24 VDC
20.4 VDC to 26.4 VDC (24 VDC --15% +10%)
10 W max.
3 A max.
0 to +50_C (with no freezing)
--20 to +70_C
35 to 85% RH (with no condensation)
No corrosive gases.
Level 3 (IEC801-2)
In air 8 kV, contact 6 kV, indirect 7 kV
10 V/m (IEC801-3)
Power supply line: 2 kV (IEC801-4)
I/O line: 0.25 kV
Power supply line: 1 kV (IEC255-4)
10 to 22 Hz with 1.5 mm double amplitude for a total of 30 min. in X, Y, and Z directions.
22 to 500 Hz with 1.5 G {14.7 m/s 2 } acceleration in X, Y, and Z directions.
Durability: 30 G, 3 times each in X, Y, and Z directions.
Malfunction: 20 G, 3 times each in X, Y, and Z directions.
190 (W) x 110 (H) x 58 (D) mm
0.7 kg max.
Front panel:
Equivalent to IP65 (front face waterproof construction).
Rear case:
Terminals:
IP20
IP00
IEC1131-2 (1992)
EN50081-2 (1992)
243
Specifications Appendix A
Performance Specifications
Display Specifications
Item
Dot matrix of STN liquid crystal display panel
Backlight
(white cold cathode tube)
Indicators
Specification
Number of dots
(resolution)
128 dots (vertically) x 256 dots (horizontally) (dot size: 0.407 mm)
Effective display area 56 mm (vertically) x 112 mm (horizontally)
Display mode £ 1
View angle
Life expectancy
Life expectancy
Automatic turn-off
Blue mode (NT20S-ST12j)
Monochrome mode (NT20S-ST16j)
Left/right direction: 35_
50,000 hours minimum
10,000 hours minimum
(average: 20,000 hours) £ 2
Can be set to turn off in 10 minutes or 1 hour, or to remain on.
POWER indicator
(Green LED)
RUN indicator
(Green LED)
Lit while power is being supplied.
Lit during operation
£ 1: The contrast in the monochrome mode is five times that in the blue mode.
£ 2: This is the time it takes for the brightness to decline to half its original value under normal temperature and humidity conditions.
Panel Specifications
Touch panel
Item Specification
Number of switches: Max. 72 registerable per screen
(6 vertically x 12 horizontally)
Input: Pressure-sensitive type
Operating force: 100 gf min.
Life expectancy: 1 million operations minimum
244
Specifications Appendix A
Display Capacity p y elements
Character displays
Character string displays
Numeral displays £
Graph displays £
Graphic displays
Lamps
Touch switches
Numeral settings £
Normal screen
Overlapping screens
Continuous screens
Screen attributes
Max. number of registered screens
Screen registration method
Screen saving method
(screen data memory)
Specification
NT20S-ST121-EV3/ST122-V1 NT20S-ST128
Fixed character data (character strings registered for each screen)
128 strings per file (32 bytes per string), 32 positions per screen
50 positions per screen, 8-digit display
50 per screen
Can be displayed wherever required
128 per screen
72 per screen
Max. 256 strings per file
Max. 256 strings per file
Display of set numerical values 50 per screen
Displays screens registered as normal.
A maximum of 8 registered screens can be displayed overlapped with each other.
A maximum of 8 screens can be displayed sequentially by scrolling.
(The screen can be changed by pressing the and touch switches)
Buzzer, numeral setting
495
Transfer screen data created using the support tool to the PT.
Saved to flash memory (recording format unique to NT20S)
£ : Number of numeral memory tables that can be set (number used for numeral display + number used for graphs + number used for numeral settings) ≦ 128
Display Element Specifications
Smoothing processing
Character display attributes
Graphics
Data Quantities
Item
Enlargement function
Specification
Half-size characters (8 x 8 dots): Alphanumerics and symbols
Normal characters (8 x 16 dots): Alphanumerics and symbols
Marks (16 x 16 dots): User-defined pictographs
Horizontal and vertical magnifications of double width,double height,4x, 9x, and
16x
Enlarged characters up to 4x
Normal, inverse, flashing, inverse flashing
Continuous straight lines, circles
Strings
Numeral data
Marks
Touch switches
Lamps
Item Specification
NT20S-ST121-EV3/ST122-V1
128 strings comprising 32 characters each
128 max. (8 digits each)
64 marks
No maximum restriction
No maximum restriction
NT20S-ST128
Max. 256 strings per file
Max. 256 strings per file
245
Specifications Appendix A
Special Features
Buzzer
Item
Maintenance functions
Key input sound setting
Specification
Two types: Continuous sound and intermittent sound
Setting: Set “key press sound” in the “Memory Switch” menu of the
Maintenance Mode ON.
If “ERR ON” is set the buzzer only sounds when an error occurs.
ON: The buzzer sounds on designation from the PC, when a screen with a buzzer-ON specification is called, or on display of an error screen such as for a receive error.
OFF: The buzzer is turned off on designation from the PC, by touch switch input, or when a screen without a buzzer-ON specification is displayed.
Sound pressure: Min. 80 dB, average 87 dB (measured 10 cm from front face)
S
Self-test for memory, switches, etc.
S
Status setting confirmation for communications and other conditions.
S
Simple communications confirmation.
0.2 second input sound when a touch switch is pressed
Setting: Set “key press sound” of the “Memory Switch” menu in the
Maintenance mode ON.
Communications Specifications
[For a Host Link] (NT20S-ST121-EV3)
Item
Communications standard
Communications settings
Connector
Number of units connected
Transmission distance
Communications protocol
EIA RS-232C
Start-stop synchronization
Baud rate: 9600, 19,200 bps
Data length: 7 bits
Stop bit:
Parity:
2 bits
Even
9-pin, D-SUB connector (female)
1 to 1
Max. 15 m
C-series SYSWAY (1:N)
Specification
[For an NT Link (1 to 1)] (NT20S-ST121-EV3)
Item
Communications standard
Connector
Number of units connected
Transmission distance
EIA RS-232C
9-pin D-SUB connector (female)
1 to 1
Max. 15 m
[For an NT Link (1:N)] (NT20S-ST121-EV3)
Item
Communications standard
Connector
Number of units connected
Transmission distance
Specification
Specification
EIA RS-232C
9-pin D-SUB connector (female)
1:1 to 8
S
RS-232C cable : Max. 2 m (*)
S
RS-422A/485 cable : Total length 500 m (*)
(*) When NT-AL001 used
246
Specifications
[For RS-232C] (NT20S-ST128)
Item
Communication standard
Communication settings
Connector
Number of units connected
Transmission distance
Specification
EIA RS-232C
Start-stop synchronization
Baud rate: 2400/4800/9600/19200 (bps)
Data length: 7, 8 bits
Stop bit: 1, 2 bits
Parity: Even/Odd/None
Flow control:RS/CS control
XON/XOFF control
None
9-pin D-SUB female
1-to-1
Max. 15 m
Appendix A