V1.2-2026-03-16
Copyright Statement
Copyright Statement
Copyright© GoodWe Technologies Co., Ltd. 2026. All rights reserved.
Without the authorization of GoodWe Technologies Co., Ltd., no part of this manual may be
reproduced, distributed, or uploaded to third-party platforms such as public networks in any form.
Trademark Authorization
GOODWE and other GOODWE trademarks used in this manual are owned by GoodWe Technologies
Co., Ltd. All other trademarks or registered trademarks mentioned in this manual belong to their
respective owners.
NOTICE
Due to product version upgrades or other reasons, the content of this document is updated
periodically. Unless otherwise agreed, the content of this document cannot replace the safety
precautions on the product label. All descriptions in the document are for guidance only.
1
About This Manual
Overview
This document primarily introduces the product information, installation wiring,
configuration and commissioning, troubleshooting, and maintenance content for the
energy storage system composed of inverters, Battery system, and smart meters.
Please read this manual carefully before installing and using the product to
understand the product safety information and familiarize yourself with the
product's functions and features. The document may be updated periodically; please
obtain the latest version of the materials and more product information from the
official website.
Applicable Model
The energy storage system includes the following products:
Product
Type
Product
Information
Description
Inverter
GW5K-ETA-G20
GW6K-ETA-G20
GW8K-ETA-G20
GW9.999K-ETAG20
GW10K-ETA-G20
GW12K-ETA-G20
GW15K-ETA-G20
GW20K-ETA-G20
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Nominal output power: 5kW-30kW
2
Product
Type
Product
Information
Description
Battery
system
GW5.1-BAT-D-G20
GW5.1-BAT-D-G21
Rated energy 5.12kWh
GW8.3-BAT-D-G20
GW8.3-BAT-D-G21
Rated energy 8.32kWh
Meter
GMK330
GM330
Monitoring module in the energy storage system,
capable of detecting operating voltage, current, and
other information in the system.
smart
dongle
WiFi/LAN Kit-20
Can upload system operation information to the
monitoring platform via WiFi or LAN signals.
Symbol Definition
DANGER
Indicates a highly potential danger that, if not avoided, will result in death or
serious injury.
WARNING
Indicates a moderately potential danger that, if not avoided, may result in death or
serious injury.
CAUTION
Indicates a low potential danger that, if not avoided, may result in moderate or
minor injury.
NOTICE
Emphasizes and supplements the content, and may also provide tips or tricks for
optimizing product use, helping you solve a problem or save your time.
3
Table of Contents
1 Safety Precautions
9
1.1 General Safety
9
1.2 personnel requirements
10
1.3 System Safety
11
1.3.1 PV String Safety
13
1.3.2 Inverter Safety
14
1.3.3 Battery Safety
15
1.3.4 Smart Meter Safety
18
1.4 Safety Symbols and Certification Marks
18
1.5 EU Declaration of Conformity
20
1.5.1 Equipment with Wireless Communication Modules
20
1.5.2 No Equipment with Wireless Communication Modules (except Battery) 20
1.5.3 Battery
21
2 System Introduction
22
2.1 System Overview
22
2.2 Product Overview
33
2.2.1 Residential All-in-One System
33
2.2.2 Smart Meter
39
2.2.3 smart dongle
40
2.3 Supported Grid Types
41
2.4 System Working Mode
41
4
2.5 Features
51
3 Check and Storage
55
3.1 Check Before Receiving
55
3.2 deliverables
55
3.2.1 Inverter Deliverables
55
3.2.2 Batteries Deliverables
58
3.2.2.1 Cluster Expansion Basedeliverables
59
3.2.2.2 Wall-Mounted Bracket
61
3.2.3 Smart Meter DeliverablesGM330 & GMK330
3.2.3.1 Attachment List
61
61
3.3 Storage
62
4 Installation
65
4.1 Installation Requirements
65
4.1.1 Installation Environment Requirements
65
4.1.2 Installation Space Requirements
67
4.1.3 Tool Requirements
68
4.2 Equipment Handling
70
4.3 Installation equipment
71
4.4 Installing the Smart Meter
77
5 System Wirings
78
5.1 System Wiring Electrical Block Diagram
79
5.2 Detailed System Wiring Diagram
83
5
5.3 Preparing Materials
93
5.3.1 Preparing Breakers
94
5.3.2 Preparing Cables
97
5.4 Connecting the PE cable
99
5.5 Connecting the PV Cable
100
5.6 Connecting the Battery Cable
102
5.7 Connecting the AC Cable
103
5.8 Connecting the Meter Cable
105
5.9 Connecting the Inverter Communication Cable
107
6 System Commissioning
113
6.1 Check Before Power ON
113
6.2 Power ON
113
6.3 InstallationProtective coverP
116
6.4 Indicators
116
6.4.1 Inverter Indicators
116
6.4.2 Battery Indicators
119
6.4.3 Smart Meter IndicatorGM330 & GMK330
119
6.4.3.1 indicator Description
119
6.4.4 Smart Dongle Indicator
120
7 System Commissioning
123
7.1 Set Inverter parameters via the App
7.1.1 Download the Installation SEMS+ App
6
123
123
7.2 Power Plant Monitoring is performed via SEMS+ WEB
8 Maintenance
124
125
8.1 Power OFF the System
125
8.2 Removing the Equipment
126
8.3 Disposing of the Equipment
127
8.4 Routine Maintenance
127
8.5 fault
131
8.5.1 Viewing Fault/Alarms Information
131
8.5.2 Fault Information and Troubleshooting
131
8.5.2.1 Inverter fault
133
8.5.2.2 Batteryfault
203
9 technical parameter
222
9.1 Inverter Parameters
222
9.2 Battery Technical Data
247
9.3 Smart Meter Technical Data
250
9.3.1 GM330
250
9.3.2 GMK330
251
9.4 Smart Dongle Technical Data
252
9.4.1 WiFi/LAN Kit-20
252
10 Appendix
254
10.1 FAQ
254
10.1.1 How to perform Meter/CT Auxiliary Detection?
7
254
10.1.2 How to Upgrade the Device Version
254
10.2 Abbreviations
255
10.3 Explanation of Terms
258
10.4 Battery SN code meaning
259
11 Contact Information
261
8
1 Safety Precautions
The safety precautions information contained in this document must always be
followed when operating the device.
WARNING
The device has been strictly designed and tested in accordance with safety
regulations, but as an electrical device, before performing any operations on the
device, relevant safety instructions must be followed. Improper operation may lead
to serious injury or property damage.
1.1 General Safety
NOTICE
9
• Due to product version upgrades or other reasons, the document content will be
updated periodically. Unless otherwise agreed, the document content cannot
replace the safety precautions on product labels. All descriptions in the
document are for guidance only.
• Please read this document carefully before installing the device to understand
the product and precautions.
• All operations of the device must be performed by professional and qualified
electrical technicians who are familiar with the relevant standards and safety
regulations at the project location.
• When operating the device, use insulated tools and wear personal protective
equipment to ensure personal safety. When handling electronic components,
wear anti-static gloves, anti-static wrist straps, anti-static clothing, etc., to protect
the device from electrostatic damage.
• Unauthorized disassembly or modification may cause device damage, and such
damage is not covered by the warranty.
• Device damage or personal injury caused by not installing, using, or configuring
the device according to the requirements of this document or the corresponding
user manual is beyond the manufacturer’s liability. For more product warranty
information, please obtain it through the official website:
https://en.goodwe.com/warrantyrelated.html.
1.2 personnel requirements
10
NOTICE
To ensure safety, compliance, and efficiency throughout the entire process of
equipment transportation, Installation, wiring, operation, and maintenance,
operations must be performed by qualified personnel.
1. Qualified personnel include:
• Personnel who have mastered knowledge of equipment working principles,
system structure, risks and hazards, and have received professional operation
training or possess extensive practical experience.
• Personnel who have received relevant technical and safety training, possess
certain operational experience, are aware of potential dangers specific tasks
may pose to themselves, and can take protective measures to minimize risks to
themselves and others.
• Qualified electrical technicians meeting the regulatory requirements of the
country/region.
• Personnel holding a degree in electrical engineering/an advanced diploma in
electrical discipline or equivalent/possessing professional qualifications in the
electrical field, with at least 2/3/4 years of experience in testing and
supervision work using electrical equipment safety standards.
2. Personnel involved in special tasks such as electrical work, work at heights, and
special equipment operation must hold valid qualification certificates as required
by the equipment's location.
3. Medium-voltage equipment operation must be performed by certified highvoltage electricians.
4. Equipment and component replacement is only permitted to be performed by
authorized personnel.
1.3 System Safety
DANGER
11
• Before performing electrical connections, disconnect all upstream switches of
the device to ensure it is powered off. Working on live circuits is strictly
prohibited, as it may lead to hazards such as electric shock.
• To prevent personal injury or equipment damage caused by working on live
circuits, a circuit breaker must be added to the voltage input side of the device.
• All operations including transportation, storage, installation, operation, use, and
maintenance must comply with applicable laws, regulations, standards, and
specifications.
• The specifications of cables and components used for electrical connections must
comply with local laws, regulations, standards, and specifications.
• Use the cable connectors provided in the package to connect the device cables. If
other models of connectors are used, any resulting equipment damage is not
within the manufacturer's liability.
• Ensure all cables of the device are correctly connected, securely fastened, and
free from looseness. Improper wiring may cause poor contact or damage the
equipment.
• The equipment's protective grounding wire must be firmly connected.
• To protect the equipment and its components from damage during
transportation, ensure that transport personnel are professionally trained.
Record the operation steps during transportation and keep the equipment
balanced to avoid dropping.
• The equipment is heavy. Assign personnel according to the equipment's weight
to prevent it from exceeding the human lifting capacity and causing injury from
falling.
• Ensure the equipment is placed stably and not tilted. Equipment tipping over
may cause equipment damage and personal injury.
WARNING
12
• During equipment installation, avoid having the terminals bear weight, as this
may cause terminal damage.
• If the cable is subjected to excessive tension, it may lead to poor connections.
When wiring, leave a certain length of cable slack before connecting it to the
equipment's terminal ports.
• Cables of the same type should be bundled together. Different types of cables
should be routed at least 30mm apart and must not be intertwined or crossrouted.
• Using cables in high-temperature environments may cause insulation aging and
damage. Maintain a distance of at least 30mm between cables and heatgenerating components or the periphery of heat source areas.
1.3.1 PV String Safety
13
WARNING
• Ensure the component frame and mounting system are properly grounded.
• After connecting the DC cables, ensure the cable connections are tight and
secure with no looseness. Improper wiring may cause poor contact or high
impedance, and damage the inverter.
• Use a multimeter to measure the positive and negative poles of the DC cables to
ensure correct polarity, with no reverse connection; and that the voltage is within
the permissible range.
• Use a multimeter to measure the DC cables to ensure correct polarity, with no
reverse connection; the voltage should be lower than the maximum DC input
voltage. Damage caused by reverse connection and overvoltage is not covered
by the equipment manufacturer's warranty.
• The PV string output does not support grounding. Before connecting the PV
string to the inverter, ensure the minimum insulation resistance to ground of the
PV string meets the minimum insulation resistance requirement (R=Max. Input
Voltage (V)/30mA).
• Do not connect the same PV string to multiple inverters, as this may damage the
inverters.
• The PV modules used with the inverter must comply with IEC 61730 Class A
standards.
• When the PV string input voltage or input current is high, it may cause the
inverter output power to derate.
1.3.2 Inverter Safety
14
WARNING
• Ensure the voltage and frequency at the grid connection point comply with the
inverter's grid-connection specifications.
• It is recommended to install protective devices such as circuit breakers or fuses
on the AC side of the inverter. The rating of the protective device must be greater
than 1.25 times the maximum AC output current of the inverter.
• If the inverter triggers an arc fault alarm less than 5 times within 24 hours, the
alarm can be cleared automatically. After the 5th arc fault alarm, the inverter will
shut down for protection. The inverter can resume normal operation only after
the fault is cleared.
• If a battery is not configured in the photovoltaic system, it is not recommended
to use the BACK-UP function, as it may cause a system power outage risk.
• Grid voltage and frequency fluctuations may cause the inverter output power to
derate.
1.3.3 Battery Safety
DANGER
15
• Before operating any devices in the system, ensure that the devices are powered
off to avoid the risk of electric shock. During device operation, strictly adhere to
all safety precautions in this manual and the safety labels on the devices.
• Do not disassemble, modify, or repair the battery without official authorization
from the device manufacturer. Otherwise, it may cause electric shock or device
damage, and any losses incurred are beyond the manufacturer’s liability.
• Do not impact, pull, drag, squeeze, or step on the device, and do not place the
battery in fire, as the battery may explode.
• Do not place the battery in high-temperature environments. Ensure there are no
heat sources near the battery and that it is not exposed to direct sunlight. If the
ambient temperature exceeds 60°C, it may cause a fire.
• Do not use the battery if it has obvious defects, cracks, damage, or other
conditions. Battery damage may lead to electrolyte leakage.
• Do not move the battery system while it is operating. If battery replacement or
addition is needed, contact the after-sales service center.
• Battery short circuits may cause personal injury. The instantaneous high current
from a short circuit can release a large amount of energy, which may lead to a
fire.
• To protect the battery pack and its components from damage during
transportation, ensure that transport personnel are professionally trained.
Record the operating steps during transportation and keep the device balanced
to avoid dropping.
• The battery device is heavy. Assign personnel according to the device's weight to
prevent it from exceeding the weight range that can be manually handled, which
could cause injury to personnel.
WARNING
16
• Battery current may be affected by factors such as temperature, Humidity,
weather conditions, etc., which may cause current limiting and affect load
capacity.
• If the battery cannot start, contact the after-sales service center as soon as
possible. Otherwise, the battery may be permanently damaged.
• Regularly inspect and maintain the battery according to its maintenance
requirements.
• Ensure that the battery system is not damaged during transportation and
storage. Ensure that the device is placed stably and not tilted, as tipping may
cause device damage and personal injury.
Emergency Response Measures
• Battery electrolyte leakage
If a battery module leaks electrolyte, avoid contact with the leaking liquid or gas.
Electrolyte is corrosive and contact may cause skin irritation and chemical burns. If
accidental contact with the leaked substance occurs, take the following actions:
inhalation: Evacuate from the contaminated area and seek medical help
immediately.
Eye contact: Rinse with clean water for at least 15 minutes and seek medical help
immediately.
Skin contact: Wash the affected area thoroughly with soap and water and seek
medical help immediately.
Ingestion: Induce vomiting and seek medical assistance immediately.
○
○
○
○
• Fire
When the battery temperature exceeds 150°C, there is a risk of fire. A battery fire
may release toxic and harmful gases.
To prevent fire, ensure carbon dioxide or water fire extinguishing equipment is
available near the device.
When extinguishing a fire, do not use ABC dry powder fire extinguishers.
Firefighters must wear protective clothing and self-contained breathing
apparatus.
• Battery triggers fire protection
For batteries equipped with optional fire protection functionality, after the fire
protection function is triggered, perform the following actions:
Immediately cut off the main power switch to ensure no current flows through
the battery system.
○
○
○
○
17
○
○
○
Conduct a preliminary visual inspection of the battery for any damage,
deformation, leakage, or unusual odor. Check the battery casing, connectors,
and cables.
Use a temperature sensor to detect the battery and its ambient temperature to
ensure there is no risk of overheating.
Isolate and label the damaged battery, and dispose of it properly according to
local regulations.
1.3.4 Smart Meter Safety
WARNING
If the grid voltage fluctuation exceeds 265V, long-term overvoltage operation may
cause damage to the meter. It is recommended to add a fuse with a rated current
of 0.5A on the voltage input side of the meter to protect it.
1.4 Safety Symbols and Certification Marks
DANGER
• After equipment installation, labels and warning signs on the enclosure must
remain clearly visible. Do not cover, alter, or damage them.
• The following enclosure warning label descriptions are for reference only. Please
refer to the actual labels used on the equipment.
No.
Symbol
Meaning
1
Potential hazard exists during equipment operation. Please
take protective measures when operating the equipment.
2
High voltage hazard. High voltage is present during
equipment operation. Please ensure the equipment is
powered off before performing any operations.
18
No.
Symbol
Meaning
3
The inverter surface is at high temperature. Do not touch
during operation to avoid burns.
4
Use the equipment properly. There is a risk of explosion
under extreme conditions.
5
Battery contains flammable materials. Beware of fire.
6
The equipment contains corrosive electrolyte. Avoid
contact with leaked electrolyte or volatile gases.
7
Delayed discharge. After powering off the equipment,
please wait 5 minutes for it to discharge completely.
8
Keep the equipment away from open flames or ignition
sources.
9
Keep the equipment out of reach of children.
10
Do not extinguish with water.
11
Please read the product manual carefully before operating
the equipment.
12
Personal protective equipment must be worn during
installation, operation, and maintenance.
13
This equipment must not be disposed of as household
waste. Please dispose of it according to local laws and
regulations, or return it to the manufacturer.
19
No.
Symbol
Meaning
14
Grounding point.
15
Recycling symbol.
16
CE certification mark.
17
TUV mark.
18
RCM mark.
1.5 EU Declaration of Conformity
1.5.1 Equipment with Wireless Communication Modules
Equipment with wireless communication modules sold in the European market must
comply with the following directives:
• Radio Equipment Directive 2014/53/EU (RED)
• Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863
(RoHS)
• Waste Electrical and Electronic Equipment 2012/19/EU
• Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No
1907/2006 (REACH)
1.5.2 Equipment without Wireless Communication Modules (Except
Battery)
Equipment without wireless communication modules that can be sold in the
European market meets the requirements of the following directives:
• Electromagnetic compatibility Directive 2014/30/EU (EMC)
20
• Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
• Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863
(RoHS)
• Waste Electrical and Electronic Equipment 2012/19/EU
• Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No
1907/2006 (REACH)
1.5.3 Battery
Batteries sold in the European market must comply with the following directives:
• Electromagnetic compatibility Directive 2014/30/EU (EMC)
• Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
• Battery Directive 2006/66/EC and Amending Directive 2013/56/EU
• Waste Electrical and Electronic Equipment 2012/19/EU
• Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No
1907/2006 (REACH)
For more EU Declarations of Conformity, please visit the official website.
21
2 System Introduction
2.1 System Overview
The All-in-One Home Energy Storage Solution integrates devices such as inverters,
batteries, Smart Meters, and smart communication sticks. In a photovoltaic system, it
converts solar energy into electricity to meet household power demands. The energy
IoT devices in the system manage electrical appliances by identifying the overall
power situation, thereby achieving intelligent management of electricity for
supplying loads, storing to batteries, or exporting to the grid.
WARNING
• The energy storage system is not suitable for connecting devices that rely on
stable power supply, such as life-sustaining medical equipment, etc. Please
ensure that when the system is powered off, it does not cause personal injury..
• If the all-in-one home storage unit is in a high-temperature or BMS currentlimiting condition, it may cause the battery charging power to be limited, leading
to system overvoltage triggering overvoltage protection.
• In microgrid scenarios, it is recommended that the PV open-circuit voltage of the
all-in-one home storage unit be < 0.85*PV maximum input voltage to avoid
system overvoltage triggering overvoltage protection under harsh operating
conditions.
• In microgrid scenarios, please ensure that the over-frequency power reduction
point of the grid-tied inverter is consistent with that of the all-in-one home
storage unit.
• If the grid-tied inverter needs to limit output power, please connect a meter or
CT device separately.
• Please ensure that the over-frequency power reduction curve of the grid-tied
inverter is set as follows:
Set the end power to 0%Pn
○
○
Set the response delay time to 0, and disable the hysteresis function
• In a system where the inverter operates completely off-grid, if the battery is in
low light or rainy weather for a long time and cannot be replenished in time, it
may lead to over-discharge, causing battery performance degradation or
damage. To ensure long-term stable operation of the system, avoid completely
22
WARNING
draining the battery. Recommended measures are as follows:
When operating off-grid, set the minimum SOC protection threshold. It is
recommended to set the off-grid battery SOC lower limit to 30%.
When the SOC approaches the protection threshold, the system will
automatically enter power limitation or protection mode.
If there is insufficient light for several consecutive days and the battery SOC is
too low, promptly replenish the battery with external energy sources (such as
a generator or grid-assisted charging).
Regularly check the battery status to ensure it is within the safe operating
range.
It is recommended to fully charge and discharge the battery every six months
to calibrate SOC accuracy.
• Due to product version upgrades or other reasons, the document content will be
updated periodically. For the compatibility relationship between inverters and
IoT products, please refer to:
https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_Compatibilitylist-of-GoodWe-inverters-and-IoT-products-EN.pdf
• For detailed networking and wiring schemes for each scenario, please refer to:
5.2.Detailed System Wiring Diagram(Page 83).
○
○
○
○
○
When the energy storage system is in off-grid mode, it can normally supply the
following loads:
BACK-UP Port Off-Grid Load Capacity Specification
Inverter Model
GW5K-ETA-G20
GW6K-ETA-G20
GW8K-ETA-G20
GW9.999K-ETA-G20
GW10K-ETA-G20
GW12K-ETA-G20
GW15K-ETA-G20
GW20K-ETA-G20
GW25K-ETA-G20
GW29.999K-ETA-G20
GW30K-ETA-G20
Load Type
Singlephase
Singlephase
23
Threephase
Threephase
BACK-UP Port Off-Grid Load Capacity Specification
Single Motor Load Rated Power
(kVA)
1.1
3.3
2.2
6.6
Total Rated Power of Multiple
Motor Loads (kVA)
0.4*Pn/3
0.4*Pn
0.4*Pn/3
0.4*Pn
Capacitive Load (kVA)
0.33*Pn/3
0.33*Pn
0.33*Pn/
3
0.33*Pn
Half-wave Load (kW)
2
-
3
-
Note:
• Pn: Inverter rated output power.
• Half-wave Load: Some old or non-EMC compliant household appliances (such as
hair dryers, small heaters using half-wave rectification).
• If the total power of multiple motor loads calculated based on rated power is less
than the rated power of a single motor load, then the total rated power of
multiple motor loads equals the rated power of a single motor load.
General Scenario
24
Device
Type
model
hybrid
inverter
GW5K-ETA-G20
GW6K-ETA-G20
GW8K-ETA-G20
GW9.999K-ETAG20
GW10K-ETA-G20
GW12K1-ETA-G20
GW15K-ETA-G20
GW20K-ETA-G20
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Description
• Can be connected to a GOODWE rgingpile.
• Supports generator control and generator
charging of the battery. If a generator
connection is required, please use the GMK330
or GM330 Smart Meter.
25
Device
Type
Battery
system
model
Description
GW5.1-BAT-D-G20
GW5.1-BAT-D-G21
GW8.3-BAT-D-G20
GW8.3-BAT-D-G21
• Different models of battery modules support
mixed use.
• The system supports 5-96kWh, meeting
different power and energy matching
requirements.
• When mixing GW5.1-BAT-D-G20, GW8.3-BAT-DG20 with GW5.1-BAT-D-G21, GW8.3-BAT-D-G21,
the operating environment temperature
requirement shall be based on GW5.1-BAT-DG21, GW8.3-BAT-D-G21.
• If the system has requirements for split-type
expansion, please ensure the BMS and DCDC
software versions are V04 or above.
Inverter built-in
meter
Smart
Meter
GMK330
(purchased from
GOODWE)
GM330 (purchased
from GOODWE)
• Built-in meter: Please use the CT shipped with
the box to connect to the inverter.
CT ratio is 120A:40mA.
○
When the inverter's built-in meter does not
meet the usage requirements, you can
contact dealers or others to purchase a
GMK330 or GM330 Smart Meter.
• GMK330: CT cannot be replaced, CT ratio is
120A:40mA
• GM330: CT can be purchased from GOODWE
or independently, CT ratio is nA: 5A.
○
26
Device
Type
Smart
dongle
model
Description
WiFi/LAN Kit-20
• Uses Bluetooth signals for local configuration
of device parameters and viewing device
operation information, and uses WiFi or LAN to
upload system operation information to the
monitoring platform.
• Please ensure the Smart Dongle's firmware
version is 06 or above.
Microgrid Scenario
When a grid-tied inverter is connected to the hybrid inverter's BACK-UP port, it
constitutes a Microgrid Scenario.
27
Device
Type
model
Description
hybrid
inverter
GW5K-ETA-G20
GW6K-ETA-G20
GW8K-ETA-G20
GW9.999K-ETA-G20
GW10K-ETA-G20
GW12K-ETA-G20
GW15K-ETA-G20
GW20K-ETA-G20
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
• In a microgrid scenario, only one hybrid inverter
is supported in the system.
• In a microgrid scenario, connecting a generator
is not supported.
Battery
system
GW5.1-BAT-D-G20
GW5.1-BAT-D-G21
GW8.3-BAT-D-G20
GW8.3-BAT-D-G21
• Battery modules of different models can be
mixed.
• The system supports 5-96kWh, meeting
different power and energy matching
requirements.
• When GW5.1-BAT-D-G20, GW8.3-BAT-D-G20 are
mixed with GW5.1-BAT-D-G21, GW8.3-BAT-DG21, the operating ambient temperature
requirement shall follow that of GW5.1-BAT-DG21 and GW8.3-BAT-D-G21.
• If the system requires split-type expansion,
ensure the BMS and DCDC software version is
V04 or higher.
Smart
Meter
Inverter Built-in
Meter
GMK330 (Purchase
from GoodWe)
28
Device
Type
model
Description
• Built-in meter: Use the CT shipped with the
inverter to connect to the inverter.
CT ratio is 120A:40mA
○
If the inverter's built-in meter does not meet
the requirements, contact your dealer to
purchase a GMK330 or GM330 Smart Meter.
• GMK330: CT cannot be replaced; CT ratio is
120A:40mA
• GM330: CT can be purchased from GoodWe or
elsewhere; CT ratio is nA:5A
○
GM330 (Purchase
from GoodWe)
Smart
dongle
WiFi/LAN Kit-20
• Uses Bluetooth signals for local configuration of
device parameters and viewing device
operation information. Uses WiFi or LAN to
upload system operation information to the
monitoring platform.
• Ensure the firmware version of the Smart
dongle is 06 or higher.
29
Device
Type
grid-tied
PV
inverter
model
Description
• It is recommended to use GoodWe brand gridtied PV inverters; third-party grid-tied PV
inverters are also supported.
• In a microgrid scenario, ensure the rated output
power of the grid-tied PV inverter ≤ the rated
output power of the hybrid inverter.
• When the microgrid system is in grid-connected
mode, if power limitation is required, ensure:
For the hybrid inverter, set it in the Grid
Power Limitation interface of the ShineCloud+
App. For the grid-tied PV inverter, set it
according to the actual tool used.
To ensure the grid-tied PV inverter can
continue generating power, adjust the output
power of the hybrid inverter in the Microgrid
Mode interface of the ShineCloud+ App.
○
-
○
Note: The output power control precision varies
among different grid-tied PV inverters. Set the
grid power limitation parameter value according
to the actual situation.
Coupled Scenario
When a grid-tied inverter is connected to the hybrid inverter's GRID port, it
constitutes a Coupled Scenario.
30
Device
Type
model
hybrid
inverter
GW5K-ETA-G20
GW6K-ETA-G20
GW8K-ETA-G20
GW9.999K-ETA-G20
• Can be connected to GoodWe AC charging pile.
GW10K-ETA-G20
• Supports generator control and generator
GW12K-ETA-G20
charging the battery.If you need to connect a
GW15K-ETA-G20
generator, please use GMK330 or GM330
GW20K-ETA-G20
Smart Meter.
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Description
31
Device
Type
Battery
system
model
Description
GW5.1-BAT-D-G20
GW5.1-BAT-D-G21
GW8.3-BAT-D-G20
GW8.3-BAT-D-G21
• Battery modules of different models can be
mixed.
• The system supports 5-96kWh, meeting
different power and energy matching
requirements.
• GW5.1-BAT-D-G20, GW8.3-BAT-D-G20 and
GW5.1-BAT-D-G21, GW8.3-BAT-D-G21 can be
mixed. When mixing, the operating
environment temperature requirements
should follow GW5.1-BAT-D-G21 and GW8.3BAT-D-G21.
• If the system requires split expansion, ensure
that the BMS and DCDC software versions are
V04 or above.
Inverter built-in
meter
Smart
Meter
GMK330
(purchased from
GoodWe)
GM330 (purchased
from GoodWe)
• Built-in meter: Please use the CT shipped with
the box to connect to the inverter.
CT ratio is 120A:40mA
○
If the built-in meter of the inverter does not
meet the requirements, you can contact
dealers to purchase GMK330 or GM330
Smart Meter.
• GMK330: CT cannot be replaced, CT ratio is
120A:40mA.
• GM330: CT can be purchased from GoodWe or
independently, CT ratio is nA:5A.
○
32
Device
Type
Smart
dongle
grid-tied
PV
inverter
model
Description
WiFi/LAN Kit-20
• Uses Bluetooth signals for local configuration
of device parameters and viewing device
operation information, and uploads system
operation information to the monitoring
platform via WiFi or LAN.
• Ensure that the firmware version of the Smart
dongle is 06 or above.
-
• It is recommended to use GoodWe brand gridtied PV inverters, and third-party grid-tied PV
inverters are supported.
• In coupling scenarios, ensure that the rated
output power of the grid-tied PV inverter is ≤
the rated output power of the hybrid inverter.
• When the coupling system is in grid-connected
state, if power limitation is required, ensure:
the hybrid inverter should be set through the
SEMS+ App grid-connected power limitation
interface, and the grid-tied PV inverter should
be set according to the actual tools used.
Note: The output power control accuracy of
different grid-tied PV inverters varies, please set
the grid-connected power limitation parameter
values according to the actual situation.
2.2 Product Overview
2.2.1 Residential Three-Phase All-in-One
Residential Three-Phase All-in-One:
The Residential Three-Phase All-in-One uses a blind plug stacking connection method
and integrates the Inverter and Battery units through modular design.
33
The energy storage system supports Battery capacity expansion. The total Battery
capacity is determined by the number and specifications of Battery modules.
Configuration must strictly adhere to the restrictions specified in this section. Overall
system configuration description:
Mounting Method
Total Number of
Batteries
Expansion Group
Count
Stacking per
Group
Away from wall ≤4
Floor Installation
≤12 units
≤3 groups
units
Against wall ≤6
units
Wall-mounted
Installation (5kWh
model)
Wall-mounted
Installation
(8kWh/5kWh+8kWh
model)
≤9 units
≤3 groups
≤3 units
≤6 units
≤3 groups
≤2 units
34
Mounting Method
Total Number of
Batteries
Expansion Group
Count
Stacking per
Group
Note: Expansion Group Count × Stacking per Group ≤ Total System Battery Count
Wall-mounted Installation
Floor-standing Installation
• Against-wall installation
• Away-from-wall installation
35
Cluster Expansion Installation
• Floor-standing installation
• Wall-mounted installation
Inverter:
The Inverter controls and optimizes the energy flow in the photovoltaic system
through an integrated energy management system. It can supply the electricity
generated in the photovoltaic system to loads, store it in the Battery, or output it to
the grid, etc.
36
No.
Component/Sil
kscreen
Description
1
indicator
Indicates the operating status of the inverter.
2
heat sink
Dissipates heat for the inverter.
3
Connector
Power and Communication Port for connecting the
inverter to the battery.
4
• Can connect to smart communication sticks, such as
Smart
WiFi/LAN communication modules. Please select the
Communication
module type according to actual needs.
Stick
• Supports connecting a USB flash drive for local
Connection Port
inverter software version upgrade.
5
Ventilation
valve
-
6
STS
Communication
Interface
Reserved
• Can connect to DC input cables from PV modules.
7
PV Input
Terminals
• The number of PV input terminals is as follows:
GW5K-ETA-G20, GW6K-ETA-G20, GW8K-ETA-G20,
GW6K-EHA-G20: 3
GW9.999K-ETA-G20, GW10K-ETA-G20, GW12K-ETAG20, GW15K-ETA-G20, GW20K-ETA-G20, GW25K-ETAG20, GW29.999K-ETA-G20, GW30K-ETA-G20: 4
○
○
8
BACK-UP Port
Connects to AC cables, connecting to critical loads or
grid-tied inverters.
9
Battery
Mounting Holes
Secures the inverter and the battery.
37
No.
Component/Sil
kscreen
Description
10
Communication
Port
Can connect communication cables for load control, CT,
RS485, Remote Shutdown/Rapid Shutdown, DRED
(Australia)/RCR (Europe), etc.
11
Lifting Handle
Mounting Holes
Used for installing the lifting handle.
Used when moving the inverter.
12
DC Switch
Controls the connection or disconnection of the DC
input.
13
GRID Port
Connects to AC cables, connecting the inverter to the
grid.
14
Grounding
terminal
Connects the chassis protective ground wire.
Battery:
The Battery system can store and release electricity according to the requirements of
the photovoltaic energy storage system. The input and output ports of this energy
storage system are high-voltage direct current.
No.
Part
Description
1
Connector
Power and Communication Port for connections
between batteries, and between battery and inverter.
38
No.
Part
Description
2
Anti-tip bracket
mounting hole
Used for fixing the battery to the wall.
• Indicates the battery operating status.
• Battery black start function: When there is no PV
power generation in the photovoltaic system and the
grid is abnormal, the inverter cannot work normally;
you can press and hold the multi-function button for 2
seconds to start the battery system, activate the
inverter, so that the inverter enters off-grid mode
operation, and the battery discharges to power the
load.
• Battery power-off function: Press and hold the multifunction button for >5 seconds to power off the
battery system.
3
Multi-function
button
indicator light
4
Battery
isolation switch
Battery power input and output switch.
5
Battery interfixing hole
For fixing between two batteries.
6
heat sink
Battery heat dissipation
7
Battery
hoisting hole
Used for hoisting the battery.
When stacking more than three batteries, use hoisting
tools for installation.
8
Battery or
inverter fixing
hole
Used for fixing between batteries or between inverter
and battery.
9
Lifting rod
mounting hole
Used for installing the lifting rod.
Used during manual handling of the battery.
2.2.2 Smart Meter
The Smart Meter measures and monitors electrical data in the photovoltaic energy
39
storage system, such as: voltage, current, frequency, Power Factor, power, etc.
GM330&GMK330&CT
No.
model
Applicable Scenarios
CT can be purchased from GoodWe or separately. CT ratio
requirement: nA: 5A
1
GM330
• nA: CT primary side input current, n range is 200-5000
• 5A: CT secondary side output current
CT is shipped with the meter. CT ratio:
2
GMK330
• 120A: 40mA
2.2.3 smart dongle
The smart dongle is mainly used for real-time transmission of various power
generation data from inverters to remote monitoring platforms, and for connecting
the smart dongle via the SEMS+ App for proximal device debugging.
40
No.
1
model
Signal Type
Applicable Scenario
WiFi/LAN Kit-20
WiFi, LAN,
Bluetooth
Can upload system operation
information to the monitoring
platform via WiFi or LAN signals
2.3 Supported Grid Types
2.4 System Working Mode
Self-consumption
• The basic operating mode of the system.
• PV generation first supplies power to the loads, excess energy charges the battery,
and any remaining energy is sold to the grid. When PV generation cannot meet the
41
load demand, the battery supplies power to the loads; when the battery power is
also insufficient to meet the load demand, the grid supplies power to the loads.
Backup Mode
• Recommended for use in areas with unstable grids.
• When the grid fails, the inverter switches to off-grid working mode, and the battery
discharges to supply power to the loads, ensuring uninterrupted power for the
BACK-UP Loads. When the grid is restored, the inverter switches its working mode
back to grid-connected operation.
• To ensure the battery SOC is sufficient to maintain normal system operation during
off-grid periods, the system will charge the battery using PV or by purchasing
electricity from the grid to the backup power SOC during grid-connected operation.
If purchasing electricity from the grid to charge the battery, please ensure
compliance with local grid laws and regulations.
42
43
TOU Mode
In compliance with local laws and regulations, buy and sell electricity during different
time periods based on the difference between peak and valley grid electricity prices.
For example: During valley price periods, set the battery to charging mode to
purchase electricity from the grid for charging; during peak price periods, set the
battery to discharging mode to supply power to the loads via the battery.
44
45
Delayed Charging Mode
• Suitable for areas with grid-connected power output limits.
• Setting a peak power limit can use PV generation exceeding the grid connection
limit to charge the battery; or setting a PV charging period to utilize PV generation
for charging the battery during that period.
46
47
48
Demand Control Mode
• Primarily applicable to commercial and industrial scenarios.
• When the total load power consumption exceeds the electricity quota within a
short period, battery discharge can be used to reduce the portion of consumption
exceeding the quota.
• When the battery SOC is lower than the reserved SOC for demand control, the
system purchases electricity from the grid based on the time period, load
consumption, and peak purchase power limit.
49
Off-grid Mode
NOTICE
When the inverter is not connected to the battery system, do not operate in pure
off-grid mode.
When the grid fails, the inverter switches to off-grid working mode.
• During the day, PV generation first supplies power to the loads, and excess energy
charges the battery.
• At night, the battery discharges to supply power to the loads, ensuring
uninterrupted power for the BACK-UP Loads.
50
2.5 Features
NOTICE
Specific features are subject to the actual product configuration.
AFCI
The inverter integrates an AFCI circuit protection device, used to detect arc faults and
quickly cut off the circuit when detected, thereby preventing electrical fires.
Causes of arc generation:
• Damage to connector connections in the photovoltaic system.
• Incorrect or damaged cable connections.
• Aging of connectors and cables.
51
Fault handling methods:
1. When the inverter detects an arc occurrence, the fault type can be viewed through
the App.
2. If the inverter triggers a fault less than 5 times within 24 hours, after waiting for 5
minutes, the machine will automatically restore grid connection protection. After
the 5th arc fault, the fault must be cleared before the inverter can operate
normally. For specific operations, please refer to the 'SEMS+ App User Manual'.
model
Label
Description
F(Full coverage):Full coverage of
inverter PV input ports
I(Integrated):Integrated within the
inverter
GW5K-ETA-G20
GW6K-ETA-G20
GW8K-ETA-G20
AFCI:F-I-AFPE-1-2/1-2
AFPE(arc fault protection equipment):
Combines both AFD and AFI arc detection
functions
1: One pair of PV input ports (PV+, PV-)
connects to one PV input string
2/1: One arc detection channel has 2
MPPT inputs; one arc detection
channel has 1 MPPT input;
2: There are 2 arc detection channels
F(Full coverage):Full coverage of
inverter PV input ports
I(Integrated):Integrated within the
GW9.999K-ETAG20
GW10K-ETA-G20
GW12K-ETA-G20
GW15K-ETA-G20
GW20K-ETA-G20
inverter
AFCI:F-I-AFPE-1-2/2-2
52
AFPE(arc fault protection equipment):
Combines both AFD and AFI arc detection
functions
1: One pair of PV input ports (PV+, PV-)
connects to one PV input string
2/2: Each arc detection channel has 2
MPPT inputs;
2: There are 2 arc detection channels
model
Label
Description
F(Full coverage):Full coverage of
inverter PV input ports
I(Integrated):Integrated within the
inverter
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
AFCI:F-I-AFPE-1-2/4-2
AFPE(arc fault protection equipment):
Combines both AFD and AFI arc detection
functions
1: One pair of PV input ports (PV+, PV-)
connects to one PV input string
2/4: One arc detection channel has 2
MPPT inputs; one arc detection
channel has 4 MPPT inputs;
2: There are 2 arc detection channels
Three-phase unbalanced output
Both the grid connection end and the BACK-UP end of the inverter support threephase unbalanced output, and each phase can be connected to loads of different
power. The maximum output power per phase for different models is shown in the
table below:
No.
model
Single-Phase Maximum Output Power
1
GW5K-ETA-G20
2.5kW
2
GW6K-ETA-G20
3kW
3
GW8K-ETA-G20
4kW
4
GW9.999K-ETA-G20
5kW
5
GW10K-ETA-G20
5kW
6
GW12K-ETA-G20
6kW
7
GW15K-ETA-G20
7.3kW
8
GW20K-ETA-G20
7.3kW
9
GW25K-ETA-G20
11kW
53
No.
model
Single-Phase Maximum Output Power
10
GW29.999K-ETA-G20
11kW
11
GW30K-ETA-G20
11kW
Rapid Shutdown (RSD) Rapid Shutdown
In the Rapid Shutdown system, the Rapid Shutdown transmitter and receiver are
used together to achieve rapid system shutdown. The receiver maintains component
output by receiving signals from the transmitter. The transmitter can be external or
built into the inverter. In case of an emergency, by enabling the external trigger
device, the transmitter can be stopped, thereby shutting down the components.
• External transmitter
Transmitter models: GTP-F2L-20, GTP-F2M-20
https://en.goodwe.com/Ftp/Installation-instructions/RSD2.0-transmitter.pdf
Receiver models: GR-B1F-20, GR-B2F-20
https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_RSD-20_QuickInstallation-Guide-POLY.pdf
• Built-in transmitter
External trigger device: external switch
○
○
○
○
Receiver models: GR-B1F-20, GR-B2F-20
https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_RSD-20_QuickInstallation-Guide-POLY.pdf
54
3 Check and Storage
3.1 Check Before Receiving
Before receiving the product, please carefully check the following:
1. Check if the outer packaging is damaged, such as deformation, holes, cracks, or
other signs that could cause damage to the equipment inside the box. If damaged,
do not open the packaging and contact your dealer.
2. Check if the device model is correct. If it does not match, do not open the
packaging and contact your dealer.
3.2 deliverables
WARNING
Check if the type and quantity of the delivered items are correct, and if there is any
damage to the appearance. If there is any damage, please contact your dealer.
After removing the delivered items from the packaging, do not place them on
rough, uneven, or sharp surfaces to avoid paint chipping.
3.2.1 Inverter Deliverables
Component
Description
Component
Description
Inverter x 1
Decorative cover top x
1
Decorative cover left
x1
Decorative cover right
x1
55
Component
Description
Component
Description
AC terminal kit x 2
• AC wiring terminal
x2
• PIN terminal x N
5-20kW:
4mm² x 5
○
■
or
○
■
6mm² x 5
■
10mm² x 5
■
16mm² x 5
Handle x 2
25-30kW:
10mm² x 5
■
■
16mm² x 5
■
25mm² x 5
OT grounding
terminal x 1
6PIN communication
terminal x 2
2PIN communication
terminal x 2
PIN terminal x 16
CT connection cable
x1
CT x 1
56
Component
Description
Component
Description
Battery base x 1
Adjustable feet x 4
Anti-tip bracket x 4
M5*16 screw x 9
M5*60 expansion
screw x 4
Drilling template
paper x 2
PV terminal unlocking
tool x N
N:China region x
0;Other regions x 1。
57
Component
Description
Component
Description
PV terminal and PV
terminal anti-tamper
cover
• GW5K-ETA-G20
,GW6K-ETAG20 ,GW8K-ETAG20,GW6K-EHAG20:3
• GW9.999K-ETAG20,GW10K-ETAG20,GW12K-ETAG20,GW15K-ETAG20,GW20K-ETAG20,GW25K-ETAG20,GW29.999KETA-G20,GW30KETA-G20:4
Smart dongle x 1
Manual transfer
switch (Australia only)
x1
Product
documentation x 1
3.2.2 Batteries Deliverables
Part
Description
Part
Battery x 1
Silicone cap x 2
Description
M5*16 screw x 2
-
Bracket Installation (Optional)
58
-
Part
Description
Part
M10 expansion bolt x
6
Bracket x 2
M10 screw x 4
Description
-
-
3.2.2.1 Battery Expansion Kit Deliverables
NOTICE
The system supports 5-96kWh. A single column can stack up to 6 batteries, with a
maximum energy of 48kWh. For scenarios requiring more energy, needing to
reduce the single-column stacking height due to installation constraints, or other
expansion needs, please contact GoodWe or distributors to purchase a battery
expansion kit.
Part
Description
Part
Base x 1
Description
locking bracket x 4
59
Part
Description
Part
M5 Screw x 7
Description
M6 Expansion Screw x
4
Adjustable Feet x 4
OT Grounding
Terminal x 1
Terminal resistor x 1
Battery Decorative
Cover x 1
Drilling Marking
Paper x 2
Battery Expansion
Cluster Harness x 1
PIN terminal x 8
Battery Expansion
Cluster Positive
Connection Harness x
1
Battery Expansion
Cluster Negative
Connection Harness
x1
Battery Expansion
Cluster Network Cable
x1
60
Part
Description
Part
Description
Silicone Cap x 2
Handle x 2
Hex Key x 1
Product
Documentation x 1
3.2.2.2 Wall-Mount Bracket Delivery Kit
Part
Description
Part
Wall-mount bracket
x2
M5 fixing screw x 4
Description
M6 expansion bolt x 4
-
3.2.3 Smart Meter Delivery Set GM330&GMK330
3.2.3.1 Attachment List
61
-
Component
Description
Component
Description
Smart meter x1
2PIN communication
terminal x1
6PIN
communication
terminal x1
7PIN communication
terminal x1
Meter
communication
terminal
screwdriver x1
PIN terminal x 6
Product documentation
x1
3.3 Storage
• If the inverter has been stored for more than two years or has not been in
operation for more than six months after installation, it is recommended to have it
inspected and tested by professionals before putting it into use.
• To ensure the good electrical performance of the internal electronic components
of the inverter, it is recommended to power it on every six months during storage;
if it has not been powered on for more than six months, it is recommended to have
it inspected and tested by professionals before putting it into use.
• To protect battery performance and service life, it is recommended to avoid longterm idle storage. Prolonged storage may cause deep discharge of the battery,
leading to irreversible chemical damage, resulting in capacity衰减 or even
complete failure, it is advised to use it promptly. If the battery needs to be stored
for a long time, please maintain it according to the following requirements:
62
NOTICE
[1] The storage time is calculated from the SN date on the battery's outer
packaging. After exceeding the storage period, charge and discharge maintenance
is required. (Battery maintenance time = SN date + charge/discharge maintenance
cycle). For how to view the SN date, refer to: 10.4.Battery SN Code Meaning(Page
259).
[2] After passing the charge and discharge maintenance, if the outer box has a
Maintaining Label, please update the maintenance information on the Maintaining
Label. If there is no Maintaining Label, please record the maintenance time and
battery SOC yourself and keep the data securely for maintaining maintenance
records.
Battery Model
Initial
SOC
Range
for
Battery
Storage
Recom
mended Charge/Discharg
e Maintenance
Storage
Cycle[1]
Temper
ature
GW5.1-BAT-D-G20
GW8.3-BAT-D-G20
GW5.1-BAT-D-G21
GW8.3-BAT-D-G21
-20~35℃,12
35~45%
0~35℃
months
35~45℃,6
months
Battery
Maintenance
Method[2]
Please consult the
distributor or aftersales service center
for maintenance
methods.
Packaging Requirements:
Ensure that the outer packaging box is not removed and the desiccant inside the box
is not lost.
Environmental Requirements:
1. Ensure that the device is stored in a cool place, avoiding direct sunlight.
2. Ensure the storage environment is clean, with appropriate temperature and
humidity ranges, and no condensation. If there is condensation on the device
ports, do not install the device. Battery storage humidity range: 5%-95%.
3. Ensure that the device is stored away from flammable, explosive, corrosive, and
63
other hazardous materials.
Stacking Requirements:
1. Ensure that the stacking height and direction of the device are arranged according
to the instructions on the packaging box label.
2. Ensure that there is no risk of tipping after the devices are stacked.
64
4 Installation
DANGER
When performing equipment installation and electrical connections, please use the
delivery items shipped with the box. Otherwise, any resulting equipment damage
will not be covered under warranty.
4.1 Installation Requirements
4.1.1 Installation Environment Requirements
NOTICE
• Inverter operating temperature range: -35℃ to 60℃.
• GW5.1-BAT-D-G20, GW8.3-BAT-D-G20: Charging temperature range: -18℃ to
55°C; Discharging temperature range: -20℃ to 55°C. If installed in an
environment below -18℃, the battery will be unable to recharge and restore
energy after being depleted, resulting in battery undervoltage protection.
• GW5.1-BAT-D-G21, GW8.3-BAT-D-G21: Charging temperature range: 2℃ to 55°C;
Discharging temperature range: -20℃ to 55°C. If installed in an environment
below 2℃, the battery will be unable to recharge and restore energy after being
depleted, resulting in battery undervoltage protection.
1. The equipment must not be installed in flammable, explosive, corrosive, or similar
environments.
2. The temperature and humidity of the installation environment must be within a
suitable range.
3. The installation location must be out of reach of children and avoid easily
accessible positions.
4. The equipment surface may become hot during operation to prevent burns.
5. The equipment must be installed away from direct sunlight, rain, snow
accumulation, etc. It is recommended to install in a sheltered location; a sunshade
can be built if necessary.
6. The installation space must meet the equipment's ventilation, heat dissipation, and
65
operational space requirements.
7. The installation environment must meet the equipment's protection rating. The
Inverter, battery, and smart communication stick are suitable for indoor and
outdoor installation; the meter is suitable for indoor installation.
8. The installation height of the equipment should facilitate operation and
maintenance, ensuring the indicator lights, all labels are easily visible, and the
wiring terminals are easy to operate.
9. The installation altitude of the equipment should be lower than the maximum
operating altitude.
10. For outdoor installation in salt damage areas, please consult the equipment
manufacturer. Salt damage areas mainly refer to regions within 500m of the coast.
The affected area is related to sea wind, precipitation, terrain, and other
conditions.
11. The equipment generates noise during operation. The installation location should
be away from areas highly sensitive to noise, such as residential living areas,
schools, hospitals, etc., to avoid disturbance to people living nearby caused by
operational noise.
12. Keep away from strong magnetic field environments to avoid electromagnetic
interference. If there are radio stations or wireless communication equipment
below 30MHz near the installation site, install the equipment according to the
following requirements:
• Inverter: Add ferrite cores with multiple turns on the DC input or AC output lines of
the Inverter, or add a low-pass EMI filter; or maintain a distance of over 30m
between the Inverter and the wireless electromagnetic interference equipment.
• Other equipment: Maintain a distance of over 30m between the equipment and the
wireless electromagnetic interference equipment.
66
4.1.2 Installation Space Requirements
When installing equipment in the system, sufficient space should be reserved around
the equipment to ensure adequate installation and heat dissipation space.
• CAT 5E or above shielded network cable is required for CT installation, with a cable
distance not exceeding 30 meters.
• The RS485 twisted-pair shielded cable for communication between the inverter and
the electric meter should not exceed 100 meters in length.
Cable Specifications
67
Cable Specifications
68
4.1.3 Tool Requirements
NOTICE
During installation, it is recommended to use the following installation tools. If
necessary, other auxiliary tools may be used on-site.
Installation Tools
Tool Type
Description
Tool Type
Description
diagonal plier
RJ45 connector
crimping tool
wire stripper
Level bar
open-end wrench
PV terminal
crimping tool
PV-CZM-61100
hammer drill (drill bit
Φ12mm)
torque wrench
M4, M5, M6, M10
rubber hammer
socket wrench
marker pen
multimeter
Range ≤ 1000V
heat shrink tubing
heat gun
69
Tool Type
Description
Tool Type
cable tie
Description
vacuum cleaner
Personal Protective Equipment
Tool Type
Description
Tool Type
Description
Insulated gloves, protective gloves
Dust mask
goggle
Safety shoes
4.2 Equipment Handling
70
CAUTION
• During operations such as transportation, handling, and installation, all relevant
national/regional laws, regulations, and standards must be complied with.
• Before installation, the equipment must be moved to the installation site. To
avoid personal injury or equipment damage during handling, please note the
following:
1. Ensure an adequate number of personnel is assigned based on the
equipment's weight to prevent it from exceeding the safe lifting capacity and
causing injury.
2. Wear safety gloves to prevent injury.
3. Ensure the equipment remains balanced during handling to avoid dropping.
4. The battery system can be transported to the installation site using hoisting
methods.
5. When using hoisting methods to move the equipment, use flexible slings or
straps. The load-bearing capacity per single strap must meet the following
requirements:
GW5.1-BAT-D-G20, GW5.1-BAT-D-G21 ≥180KG
○
○
GW8.3-BAT-D-G20, GW8.3-BAT-D-G21 ≥240KG
4.3 Equipment Installation
71
CAUTION
• When drilling holes, ensure the drilling location avoids water pipes, cables, etc.,
inside the wall to prevent danger.
• When drilling, please wear safety goggles and a dust mask to prevent dust from
being inhaled into the respiratory tract or falling into the eyes.
• The inverter must be installed above the battery; do not install the battery above
the inverter.
• When installing the battery system, ensure it is level and secure. When placing
the battery base, battery, and inverter, confirm that the holes on the upper and
lower layers are aligned; the anti-tipping bracket should be vertical and tightly
attached to the ground, wall, or battery system surface.
• When using an impact drill to make holes, use cardboard or other coverings to
shield the battery system to prevent foreign objects from entering the
equipment and causing damage.
• For wall-mounted installation, to ensure the safety of your life and property, be
sure to assess the wall's load-bearing capacity.
72
NOTICE
• The battery must be installed on the base, which can be floor-mounted or
bracket-mounted.
• For floor installation, a maximum of 4 batteries can be stacked when away from
the wall, and a maximum of 6 batteries can be stacked when against the wall.
• The maximum stacking quantities for bracket installation are as follows:
Same capacity stacking:
GW5.1-BAT-D-G20 and GW5.1-BAT-D-G21: Maximum of 3 units.
○
■
■
GW8.3-BAT-D-G20 and GW8.3-BAT-D-G21: Maximum of 2 units.
Mixed capacity stacking:
When GW5.1-BAT-D-G20,GW5.1-BAT-D-G21 are mixed with GW8.3-BAT-DG20,GW8.3-BAT-D-G21 for stacking, the system supports a maximum of
2 units per group.
• When installing against a wall, the base, bracket, and top battery must be
secured to the wall using an anti-tip bracket.
• When marking drilling positions for bracket installation, have one person steady
the base while another uses a marker to mark the drilling spots.
• When installing batteries and the inverter, remove the protective covers from the
blind-mate connectors before stacking.
○
■
Wall Mounting
Step 1: Install the base onto the wall bracket.
Step 2: Place the wall bracket flush against the wall. Ensure the bracket is securely
positioned, observing the level bubble in the center of the base.
Step 3: After adjusting the position and level of the wall bracket, use a marker to
mark the drilling positions. After marking, remove the wall bracket. (A: PACK fixing
hole positions; B: Bracket fixing hole positions.)
Step 4: Drill holes and install expansion bolts.
1. Use an impact drill to drill holes.
2. Clean the holes.
3. Use a rubber mallet to install the expansion bolts into the holes.
4. Use a hex wrench to tighten the nut clockwise to expand the bolt.
5. Rotate the nut counterclockwise to remove it.
6. Use a torque screwdriver to secure the anti-tipping bracket to the wall.
73
Step 5: Use a hex wrench to secure the wall bracket to the wall.
Floor Installation
Installation Against Wall
Step 1: Install the adjustable feet onto the bottom of the base, and secure the antitipping bracket to the base.
Step 2: Place the base 50-60mm away from the wall, keeping it parallel to the wall.
Observe the level bubble in the center of the base; if it is not centered, use the
adjustable feet to level it.
Step 3: After adjusting the position and level of the base, use drilling marking paper
to mark the drilling positions. After marking, remove the base. (A: PACK fixing hole
positions; B: Bracket fixing hole positions.)
Step 4: Use an impact drill to drill holes, and clean the holes.
Step 5: Use a Phillips screwdriver to secure the anti-tipping bracket to the wall.
a: Surface fixed to the base; b: Surface fixed to the wall.
74
Freestanding Installation (Away from Wall)
Step 1: Install the adjustable feet onto the bottom of the base. Observe the level
bubble in the center of the base; if it is not centered, use the adjustable feet to level
it.
Step 2: After adjusting the position and level of the base, secure the freestanding
installation bracket to the base. Choose a suitable location to mark the drilling
positions. After marking, remove the base.
Step 3: Drill holes and install expansion bolts.
1. Use an impact drill to drill holes.
2. Clean the holes.
3. Use a rubber mallet to install the expansion bolts into the holes.
4. Use a hex wrench to tighten the nut clockwise to expand the bolt.
5. Rotate the nut counterclockwise to remove it.
6. Use a torque screwdriver to secure the anti-tipping bracket (for freestanding) to
the floor.
Step 4: Use a hex wrench to secure the base to the floor.
75
Installing Battery and Inverter
NOTICE
When wall-mounted, the topmost battery must be secured to the wall using an
anti-tipping bracket.
Step 1: Remove the protective cover from the blind-mate connector on the bottom of
the inverter or battery.
Step 2: Install the handle (optional), and stack the battery onto the base.
If installing more than 3 batteries, use lifting equipment.
Step 3: Tighten the screws between the battery and the base or between batteries.
If installing multiple batteries, repeat Step1 and Step2 to complete the installation of
all batteries. The number of stacked batteries must comply with the "2.2.1.System
Overall Configuration Description(Page 33)".
Step 4: (Optional) Secure the topmost battery to the wall using an anti-tipping
bracket.
Step 5: Install the inverter or battery decorative cover.
• Integrated Installation: Lift the inverter, align it, and stack it on top of the battery.
Tighten the screws between the inverter and the battery. If the system is an
integrated configuration, the installation is now complete.
• Split-type Expansion: Repeat the battery installation steps. After completing the
electrical connections, place the battery decorative cover on top of the battery and
tighten the side screws.
a: Surface fixed to the PACK; b: Surface fixed to the wall.
76
4.4 Installing the Smart Meter
WARNING
In areas with lightning danger, if the meter cable length exceeds 10m and the
cable is not laid with grounded metal conduit, it is recommended to install external
lightning protection devices.
GM330&GMK330
77
5 System Wirings
DANGER
• The installation, routing, and connection of cables must comply with local laws,
regulations, and code requirements.
• All operations during electrical connection, as well as the specifications of cables
and components used, must meet local legal and regulatory requirements.
• Before performing electrical connections, disconnect the DC switch and AC
output switch of the equipment to ensure it is powered off. Live working is
strictly prohibited, as it may lead to hazards such as electric shock.
• Cables of the same type should be bundled together and arranged separately
from different types of cables. Intertwining or cross-routing is prohibited.
• If cables are subjected to excessive tension, poor connections may result. During
wiring, leave a certain length of cable slack before connecting to the inverter
terminals.
• When crimping terminals, ensure the conductor part of the cable makes full
contact with the terminal. Do not crimp the cable insulation together with the
terminal, as this may cause the equipment to malfunction, or lead to overheating
and damage to the inverter terminal block due to unreliable connections during
operation.
• The inverter is not tested to AS/NZS 4777.2:2020 for combinations and/or
multiple phase inverter combinations so that combpinations should not be used.
• Unused cable entry holes and ports (including communication ports) must be
reliably sealed using the dedicated terminal blocks or plugs provided in the
accessory kit. Failure to do so may result in the following risks:
Electric Shock Hazard: Open electrical ports may allow direct contact with live
parts, leading to electric shock accidents.
Protection Failure: Open ports can allow dust, moisture, or foreign objects to
enter, potentially causing short circuits, fires, or equipment failure.
○
○
78
NOTICE
• When performing electrical connections, wear personal protective equipment
such as safety shoes, protective gloves, and insulating gloves as required.
• Only qualified personnel are permitted to perform electrical connection
operations.
• The cable colors shown in the graphics in this document are for reference only.
Actual cable specifications must comply with local regulations.
5.1 System Wiring Electrical Block Diagram
NOTICE
• Depending on regional regulatory requirements, the wiring methods for the N
and PE lines of the inverter's GRID and BACK-UP ports may differ. Please comply
with local regulations.
• The inverter has a built-in energy meter and can be directly connected to a CT for
use. The CT network cable included in the shipment is 10 meters. For longer
distances, you can use shielded network cable of CAT5E or higher grade to
extend it up to 30 meters.
• CT accuracy will decrease when the connection length to the inverter exceeds
30m. For higher accuracy requirements, an external smart meter can be
connected.
• The inverter's GRID AC port has a built-in relay. When the inverter is in off-grid
mode, the built-in GRID relay is open; when the inverter is in grid-connected
mode, the built-in GRID relay is closed.
• When the inverter is powered on, the BACK-UP AC port is live. If maintenance on
the BACK-UP Loads is required, please power down the inverter to avoid electric
shock.
• In a whole-house backup scenario, if the total power of the connected loads
exceeds 1.1 times the inverter's rated power, the inverter will stop outputting
due to overload protection after a grid outage. In this case, please turn off some
non-essential loads to ensure the total load power is less than 1.1 times the
inverter's rated power.
N and PE lines are connected together in the distribution box
79
NOTICE
• To maintain neutral integrity, the neutral lines of the grid-connected side and the
off-grid side must be connected together; otherwise, the off-grid function cannot
operate normally.
• The diagram below illustrates the grid system for regions such as Australia and
New Zealand:
Whole-house backup power
Partial backup power
80
N and PE lines are wired separately in the distribution box
NOTICE
• Please ensure that the protective ground wire of BACK-UP is correctly and
securely connected; otherwise, the BACK-UP function may malfunction when a
grid fault occurs.
• Other regions except Australia, New Zealand, etc. are applicable to the following
wiring methods:
Whole-house backup power
81
Partial backup power
82
5.2 Detailed System Wiring Diagram
When all loads in the photovoltaic system cannot consume the electricity generated
by the system, the surplus electricity will be fed into the grid. In this case, a smart
meter or CT monitoring system can be used to monitor the system's power
generation and control the amount of electricity fed into the grid.
• Connecting a smart meter enables output power limiting and load monitoring
functions.
• After connecting the smart meter, please enable the "Export power limit" function
via the SEMS+ App.
The Detailed System Wiring Diagram only shows wiring examples using some model
devices. Please refer to the corresponding wiring guide chapter for the actual devices
you are using for wiring.
83
WARNING
The common contact of the manual transfer switch must be at the Inverter's BACKUP load side, do not connect to the GRID grid side. If connected to the GRID grid
side, the Inverter's off-grid mode and bypass mode operate simultaneously, when
the grid power is out, the distribution cabinet connected to the Inverter's GRID port
still has high voltage electricity, there may be a risk of electric shock.
84
NOTICE
• In microgrid and coupling scenarios, if grid-tied inverter power generation
monitoring and load monitoring functions are required, dual-meter networking
must be used.
Meter 1 or the built-in meter is used to monitor the system's grid-connected
power.
Meter 2 is used to monitor the grid-tied inverter's power generation.
○
○
By integrating data from Meter 1 and Meter 2, the monitoring platform can
achieve real-time monitoring of load power consumption.
• If output power limitation is required for the grid-tied inverter, please connect
separate equipment such as a meter or CT.
• In microgrid and coupling scenarios configured with dual meters, the meter
wiring method is the same.
• When not using the inverter's built-in meter, do not connect to the inverter's CT
port.
• The manual transfer switch is shipped as an optional accessory; please decide
whether to install it based on the actual usage scenario. If using a self-provided
ATS or STS switch, this switch must have an interlock function.
○
Dual Meter Configuration Scenarios
Meter 1 (Grid Side)
Meter 2 (Grid-tied Inverter AC Side)
Built-in Meter
GMK330
Built-in Meter
GM330
GMK330
GMK330
GM330
GM330
GMK330
GM330
GM330
GMK330
General Scenario
Scenario with Built-in Meter
The scenario with a built-in meter does not support connecting a generator.
85
Scenario with GM330 Meter
Scenario with GMK330 Meter
86
Microgrid Scenario Network Diagram
• The Microgrid Scenario does not support connecting a generator.
• The manual transfer switch is optional. Please choose whether to install it based on
the actual usage scenario.
Built-in Meter + GM330 Meter Network Diagram
87
GMK330 + GMK330
88
Microgrid Scenario, Grid-tied Inverter Export Power Limit Network Diagram
If output power limiting is required for grid-tied inverters in a Microgrid Scenario,
please connect a meter or CT device separately.
GM330 + GMK330
89
Coupled Scenario Dual Meter Network Diagram
• The manual transfer switch is optional. Please choose whether to install it based on
the actual usage scenario.
• The scenario with a built-in meter does not support connecting a generator.
Built-in Meter + GMK330
90
GM330 + GM330 Network Diagram
91
Coupled Scenario, Grid-tied Inverter Export Power Limit Network Diagram
If output power limiting is required for grid-tied inverters in a Coupled Scenario,
please connect a meter or CT device separately.
GMK330 + GM330
92
5.3 Preparing Materials
WARNING
93
• Do not connect loads between the inverter and the AC switch directly connected
to the inverter.
• Each inverter must be equipped with an AC output circuit breaker. Multiple
inverters cannot be connected to one AC circuit breaker simultaneously.
• To ensure that the inverter can safely disconnect from the grid in case of
abnormalities, please connect an AC circuit breaker on the AC side of the
inverter. Select a suitable AC circuit breaker according to local regulations.
• When the inverter is powered on, the BACK-UP AC port is live. If maintenance is
required on the BACK-UP Loads, please power off the inverter; otherwise, it may
cause electric shock.
• For cables used in the same system, it is recommended that the following cable
conductor material, cross-sectional area, length, etc., be consistent.
Inverter's BACK-UP AC cable
○
○
Inverter's GRID AC cable
• The inverter supports connecting to a generator via an ATS switch to achieve
switching between grid and generator power supply. The ATS switch is by default
connected to the grid.
5.3.1 Preparing Breakers
No.
breaker
Recommended
Specifications
Acquisitio
n Method
Remarks
Selfprovided
In actual
selection, you
can also
choose a
breaker that
meets local
installation
regulations
based on the
actual working
current.
For partial backup power
scenarios, the
recommendations are as
follows:
1
GRID breaker
BACK-UP
breaker
• Nominal Voltage ≥230Vac
• Nominal current
requirements are as
follows:
GW5K-ETA-G20: 20A
○
○
GW6K-ETA-G20: 20A
○
GW8K-ETA-G20: 20A
94
No.
breaker
Recommended
Specifications
Acquisitio
n Method
○
GW9.999K-ETA-G20: 32A
○
GW10K-ETA-G20: 32A
○
GW12K-ETA-G20: 40A
○
GW15K-ETA-G20: 50A
○
GW20K-ETA-G20: 50A
○
GW25K-ETA-G20: 63A
○
GW29.999K-ETA-G20: 80A
○
GW30K-ETA-G20: 80A
For whole-house backup
power scenarios, the
recommendations are as
follows:
• Nominal Voltage ≥230Vac
• Nominal current
requirements are as
follows:
GW5K-ETA-G20: 63A
○
○
GW6K-ETA-G20: 63A
○
GW8K-ETA-G20: 63A
○
GW9.999K-ETA-G20: 80A
○
GW10K-ETA-G20: 80A
○
GW12K-ETA-G20: 80A
○
GW15K-ETA-G20: 100A
○
GW20K-ETA-G20: 100A
○
GW25K-ETA-G20: 125A
○
○
GW29.999K-ETA-G20:
125A
GW30K-ETA-G20: 125A
Note: If the inverter BACK-UP
95
Remarks
No.
breaker
Recommended
Specifications
Acquisitio
n Method
Remarks
port is not used, the GRID
breaker can be selected
based on the maximum gridconnected current.
2
3
ATS switch
The specifications of the ATS
switch and GRID breaker for
the same model are
consistent.
Selfprovided
RCD
RCD device installation and
RCD specification selection:
It is recommended to
connect a Type A RCD with a
residual current trip level
≥300mA to the AC output side of
the inverter (for inverter capacity
<30kVA, select the residual current
action level as 300mA; for inverter
capacity ≥30kVA, select the residual
current action level as 10mA/kVA).
Alternatively, select an appropriate
RCD specification based on local
regulatory requirements.
Selfprovided
96
-
No.
breaker
Recommended
Specifications
Acquisitio
n Method
Remarks
• Selfprovided
• Shipped
with the
inverter
(Australi
a only)
In actual
selection, you
can also
choose an
appropriate
manual
transfer switch
based on local
regulations.
Nominal Voltage ≥230Vac
Nominal current
requirements are as follows:
4
(Optional)
Manual
transfer
switch
• GW5K-ETA-G20, GW6K-ETAG20, GW8K-ETA-G20,
GW9.999K-ETA-G20,
GW10K-ETA-G20, GW12KETA-G20, GW15K-ETA-G20,
GW20K-ETA-G20: 63A
• GW25K-ETA-G20,
W29.999K-ETA-G20,
GW30K-ETA-G20, GW25KBTA-G20: 80A
5.3.2 Preparing Cables
No.
Cable
Recommended Specification
Source
• Single-core outdoor copper cable
• Conductor cross-sectional area:
GW5K-ETA-G20, GW6K-ETA-G20,
GW8K-ETA-G20: 4-6mm2
GW9.999K-ETA-G20, GW10K-ETAG20, GW12K-ETA-G20, GW15KETA-G20, GW20K-ETA-G20: 6-10
mm2
GW25K-ETA-G20, GW29.999K-ETAG20, GW30K-ETA-G20, GW25KBTA-G20: 10-16 mm2
○
1
Inverter
Chassis
Protective
Ground Cable
○
○
97
User-provided
No.
2
Cable
Recommended Specification
Source
PV DC Cable
• Industry-standard outdoor
photovoltaic cable
• Conductor cross-sectional area:
4mm²-6mm²
• Cable outer diameter: 5.9mm8.8mm
User-provided
AC Cable
• Inverter AC input/output cable
(BACK UP/GRID):
• Conductor cross-sectional area:
GW5K-ETA-G20, GW6K-ETA-G20,
GW8K-ETA-G20: 4-6mm2
GW9.999K-ETA-G20, GW10K-ETAG20, GW12K-ETA-G20: 6-10mm2
GW15K-ETA-G20, GW20K-ETA-G20:
10-16mm2
GW25K-ETA-G20, GW29.999K-ETAG20, GW30K-ETA-G20: 16-25mm2
• Multi-core outdoor copper cable
outer diameter:
GW5K-ETA-G20, GW6K-ETA-G20,
GW8K-ETA-G20, GW9.999K-ETAG20, GW10K-ETA-G20, GW12KETA-G20: 10-26mm
GW15K-ETA-G20, GW20K-ETA-G20:
18-30mm
User-provided
○
○
○
3
○
○
○
4
5
Smart Meter
Power Cable
Meter RS485
Communicatio
n cable
• Outdoor copper cable
• Conductor cross-sectional area:
1mm²
• Shielded twisted pair
• Conductor cross-sectional area:
0.2mm²-0.4mm²
98
User-provided
User-provided
No.
6
7
8
9
10
Cable
EMS or
Charging Pile
RS485
Communicatio
n cable
Remote
Shutdown
Load Control
and Generator
Control DO
Communicatio
n cable
RCR/DRED/14
a Signal Cable
CT
Communicatio
n cable
Recommended Specification
Source
• Shielded cable meeting local
standards
• Conductor cross-sectional area:
0.2mm²-0.4mm²
• Cable outer diameter: 5mm-8mm
User-provided
standard network cable: CAT 5E or
above standard shielded network
cable and RJ45 connector
User-provided
5.4 Connecting the PE cable
WARNING
• The protective grounding of the chassis cannot replace the protective ground
wire of the AC output port. When wiring, ensure the protective ground wires at
both locations are reliably connected.
• To improve the corrosion resistance of the terminal, it is recommended to apply
silicone or paint over the external part of the grounding terminal for protection
after the protective ground wire connection installation is completed.
• When installing the equipment, the protective ground wire must be installed
first; when removing the equipment, the protective ground wire must be
removed last.
• The battery grounding is integrated into the blind-mating connector connected
to the inverter. The system is uniformly grounded through the inverter, so no
separate grounding operation is required for the battery during installation. If
there is a requirement for split expansion, please separately ground the
expansion battery pack.
99
Energy storage system grounding:
Expansion battery pack grounding:
5.5 Connecting the PV Cable
DANGER
• Do not connect the same PV string to multiple inverters, as this may cause
inverter damage.
• Before connecting the PV string to the inverter, confirm the following
information. Failure to do so may cause permanent damage to the inverter, and
in severe cases, may lead to fire causing personal injury and property damage.
1. Ensure the maximum short-circuit current and Max. Input Voltage for each
MPPT are within the inverter's allowable range.
2. Ensure the positive pole of the PV string is connected to the inverter's PV+, and
the negative pole of the PV string is connected to the inverter's PV-.
WARNING
100
• PV string output does not support grounding. Before connecting the PV string to
the inverter, ensure the minimum insulation resistance to ground of the PV
string meets the minimum insulation resistance requirement (R=Max. Input
Voltage/30mA).
• After completing the DC cable connection, ensure the cable connections are tight
and secure, with no looseness.
• Use a multimeter to measure the positive and negative poles of the DC cables to
ensure correct polarity (no reverse connection) and that the voltage is within the
allowable range.
NOTICE
• The two PV strings within each MPPT must use the same model, the same
number of panels, and the same tilt and azimuth angles to ensure maximum
efficiency.
To disassemble the PV terminal, please refer to the following steps:
101
5.6 Connecting the Battery Expansion Cable
DANGER
• Do not connect loads between the inverter and the battery.
• When connecting battery cables, use insulated tools to prevent accidental electric
shock or battery short circuit.
• Ensure the battery open-circuit voltage is within the inverter's allowable range.
• Select whether to configure a DC switch between batteries according to local
laws and regulations.
• Do not route wires on the surface or surrounding area of the inverter heat sink
to prevent overheating damage to the wiring harness.
Energy Storage System Expansion Overview
A1: Base shipped with the inverter
A2: Installation base with parallel port
102
Battery System Expansion Cable Harness Manufacturing Method
5.7 Connecting the AC Cable
WARNING
103
• The inverter integrates a Residual Current Monitoring Unit (RCMU) internally to
prevent residual current from exceeding the specified value. When the inverter
detects a leakage current greater than the allowable value, it will quickly
disconnect from the grid.
• During wiring, ensure the AC cables fully match the "BACKUP" and "GRID"
ground ports of the AC terminals. Incorrect cable connection will cause
equipment damage.
• Ensure the wire cores are fully inserted into the terminal wiring holes with no
exposed parts.
• Ensure the insulation plate at the AC terminals is securely fastened and not
loose.
• Ensure the cable connections are tight. Otherwise, during operation, overheating
of the terminals may occur, leading to equipment damage.
If you need to disassemble the AC terminal, please refer to the following steps:
104
5.8 Connecting the Meter Cable
NOTICE
• If there is a need for multiple inverters to be connected in parallel for
networking, please consult the manufacturer to purchase a meter separately.
• Please ensure that the CT connection direction and phase sequence are correct;
otherwise, it may lead to incorrect monitoring data.
• Ensure that all cables are connected correctly, tightly, and without looseness.
Improper wiring may cause poor contact or damage to the meter.
• In areas with lightning risks, if the meter cable length exceeds 10m and the
cables are not laid with grounded metal conduits, it is recommended to install
external lightning protection devices.
GM330 Meter Wiring
105
GMK330 Meter Wiring
Wiring Steps
Install CT (Type One)
106
Install CT (Type Two)
5.9 Connecting the Inverter Communication Cable
107
NOTICE
• To ensure the meter and CT function properly, please ensure the following: the
CT must be correctly matched and connected to the phase line—CT1 to L1, CT2 to
L2, and CT3 to L3.
• When using the Inverter's built-in meter, please use the CT shipped with the unit.
• If you need to use the DRED, RCR, or remote shutdown function, please enable it
in the SEMS+
App after wiring is completed.
• Do not enable this function in the SEMS+
App if the Inverter is not connected
to a DRED device or remote shutdown device, otherwise the Inverter will not be
able to operate on-grid.
• To maintain the Inverter's waterproof rating, do not remove the waterproof
plugs from any unused communication ports on the Inverter.
• The Inverter's DO signal communication port can connect to a dry contact signal
with the following specifications: Max≤24Vdc, 1A.
• The Inverter's communication functions are optional; please select according to
the actual usage scenario.
• The Inverter supports connecting via Bluetooth, WiFi, or LAN to a mobile phone
or WEB interface to set device parameters, view device operation information
and error messages, and stay informed about system status.
Communication Function Description
108
Port (Silkscreen)
A
PAR1
B
PAR2
C
CT
Function
Description
Reserved
-
CT Connection
Port
Only when using the inverter's built-in
meter, it is necessary to connect the CT
communication cable.
109
Port (Silkscreen)
Function
DRM/RCR
RCR, DRED or
EnWG 14a
Function
Connection Port
D
E
METER
• RCR (Ripple Control Receiver): Provides
RCR signal control port to meet the grid
dispatch requirements in European
regions.
• DRED (Demand Response Enabling
Device): Provides DRED signal control port
to meet the DERD certification
requirements in regions like Australia.
• EnWG (Energy Industry Act) 14a: All
controllable loads need to accept
emergency dimming from the grid. Grid
operators can temporarily reduce the
maximum grid purchase power of
controllable loads to 4.2kW.
Meter
Connection Port
Use RS485 communication to connect to an
external smart meter.
Remote
Shutdown /
Rapid Shutdown
• External Remote Shutdown device,
default is off.
• In a Rapid Shutdown system, the Rapid
Shutdown transmitter and receiver are
used together to achieve rapid system
shutdown. The receiver maintains
component output by receiving signals
from the transmitter. The transmitter can
be external or built into the inverter. In
case of an emergency, by enabling an
external trigger device, the transmitter
can be stopped, thereby shutting down
the components.
F
DI
Description
110
Port (Silkscreen)
LOAD
GEN
G
EMS
H
SW1
I
SW2
Function
load control
Generator
Control Port
Description
• Supports connection to dry contact
signals to achieve functions such as load
control. The DO contact capacity is 24V
DC@1A, NO/COM normally open contacts.
• Supports SG Ready heat pump access,
controlling the heat pump via dry contact
signals.
Supports connecting generator control
signals to control generator start/stop. In
microgrid scenarios, connecting a
generator is not supported.
EMS/Charging
Pile
Communication
Port
Connect to third-party EMS devices for
energy control or connect to GoodWe
charging piles.
-
-
Method for Connecting the Communication Cable
111
112
6 System Commissioning
6.1 Check Before Power ON
No.
Check Item
1
The equipment is securely installed, the installation location facilitates
operation and maintenance, the installation space allows for ventilation and
heat dissipation, and the installation environment is clean and tidy.
2
The PE cable, DC cable, AC cable, and communication cable are connected
correctly and securely.
3
Cable bundling meets wiring requirements, is reasonably distributed, and
shows no damage.
4
For unused cable entry holes and ports, please use the terminals provided
with the accessories for reliable connection, and ensure they are sealed.
5
Ensure that all used cable entry holes have been sealed.
6
The voltage and frequency at the inverter grid connection point meet the
grid interconnection requirements.
6.2 Power ON
113
WARNING
• Battery black start: When there is no PV power generation in the photovoltaic
system and the grid is abnormal, if the inverter cannot work normally, the
battery black start function can be used to force battery discharge to start the
inverter. The inverter can enter off-grid mode operation, and the battery supplies
power to the load.
• After the battery system is started, please ensure that the communication
between the inverter and the battery system is normal within 15 minutes. If the
inverter and the battery system cannot communicate normally, the battery
system switch will automatically disconnect, cutting off power to the battery
system.
• When the inverter is working normally, and the load is powered by the inverter's
BACK-UP port. When the inverter ispowered down for maintenance or in case of
a fault, to ensure normal operationof the load, and the load ispowered by the
grid.
NOTICE
When the system is powered on for the first time, it is recommended to perform a
battery black start. Close the battery power switch and briefly press the
multifunction button on one of the batteries. Observe whether the inverter SOC
indicator lights up. If the indicator lights up, it indicates the battery is connected
properly, and you can proceed to close the DC switch of the inverter.
power on
114
1. Close the battery power switch and briefly press the multifunction button on the
battery. If there are multiple batteries in the system, close the power switch on all
batteries. Briefly pressing the multifunction button on any one battery will start all
batteries.
2. Close the DC switch of the inverter.
3. (Optional) Close the circuit breaker between the PV module and the inverter.
4. Close the GRID circuit breaker.
5. Close the BACK-UP circuit breaker.
Battery Black Start
1. Close the battery power switch. If there are multiple batteries in the system, close
the power switch on all batteries.
115
2. Close the DC switch of the inverter.
3. (Optional) Close the circuit breaker between the PV module and the inverter.
4. Close the GRID circuit breaker.
5. Close the BACK-UP circuit breaker.
6. After all batteries are powered on separately, wait for 15 seconds, then press and
hold the multifunction button on any battery for 2 seconds to force the battery to
discharge and activate the inverter.
6.3 Install Protective Cover
6.4 Indicators
6.4.1 Inverter Indicators
116
Breathing Light:
• When the system is upgrading: The breathing light is a green running light; the
head of the running light is the brightest and the tail is the dimmest, the length of
the running light and the upgrade percentage are affected by the SEMS+ App
settings and the device's operational status.
• Except for inverter upgrade, system fault, and inverter power-off status, the
breathing light status is affected by the App settings on the SEMS+ App.
For setup instructions, please refer to the SEMS+ App User Manual.
indicat
or
Indicator
Status
Breathing Light Status
• 3min/Always on: Bluepurple chasing light
stays on
• Always off: Not lit
Description
The inverter is powered on and
in standby mode
The inverter is starting up and
in self-test mode
• 3min: Blue-purple
breathing for 3min
then off
• Always on in App: Bluepurple breathing stays
on
• Always off in App: Not
lit
The inverter is operating
normally in grid-tied power
generation or off-grid mode
Red flashing
System fault
Off
The inverter is powered off
/
Inverter monitoring module is
resetting
Inverter and communication
terminal are not connected
117
indicat
or
Indicator
Status
Breathing Light Status
Description
Communication failure
between communication
terminal and cloud server
Inverter monitoring is normal
Inverter monitoring module is
not started
Grid abnormal, inverter BACKUP port power supply normal
Grid normal, inverter BACK-UP
port power supply normal
BACK-UP port has no power
supply
System upgrade
System fault
Battery has no charge
Constantly lit: Charge
Flashing: Discharge
Battery SOC: 0% < SOC ≤ 25%
Constantly lit: Charge
Flashing: Discharge
Battery SOC: 25% < SOC ≤ 50%
118
indicat
or
Indicator
Status
Breathing Light Status
Description
Constantly lit: Charge
Flashing: Discharge
Battery SOC: 50% < SOC ≤ 75%
Constantly lit: Charge
Flashing: Discharge
Battery SOC: 75% < SOC ≤ 100%
6.4.2 Battery Indicators
Button Indicator Light
No.
1
2
Green
Light
Steady
On
Blinking1
time/S
Blinking3
times/S
Red
Light
--
--
Battery System
Status
Description
System operating
normally
Run
System ready
Standby
PCS communication
lost
--
3
Blinking1
time/2S
--
System alarm
4
--
Steady
On
System fault
Includes Level 2 faults from
the fault list, where undervoltage fault is at Level 2, 3,
or 4
Level 3 and above faults in
the fault list (steady on when
under-voltage fault is Level 5)
6.4.3 Smart Meter Indicator Lights GM330&GMK330
6.4.3.1 Indicator Light Description
119
Type
Power Light
Comm Light
Buy/Sell
Power Light
Buy/Sell
Power Light
(GMK360
only)
Status
Description
Steady On
The meter is powered on, with no RS485
communication.
Blinking
The meter is powered on, with normal RS485
communication.
Off
The meter is powered off.
Off
Reserved.
Blinking
Press and hold the Reset button for ≥5s, and the Power
Light and Buy/Sell Power Light blink: The meter is resetting.
Steady On
buy power from the grid.
Blinking
Selling power to the grid.
Off
Not buying or selling power.
Steady On
buy power from the grid.
Blinking
Selling power to the grid.
Off
Not buying or selling power.
6.4.4 Smart Dongle Indicator
• WiFi/LAN Kit-20
120
NOTICE
• After double-clicking the Reload button to turn on Bluetooth, the communication
indicator light will switch to a single-blink state. Please connect to the SEMS + App
within 5 minutes, otherwise Bluetooth will automatically
turn off.
• The communication indicator light's single-blink state only appears after doubleclicking the Reload button to turn on Bluetooth.
Indicator
Status
Description
Steady on: The Smart Communication Stick is
powered on.
Off: The Smart Communication Stick is not
powered on.
Steady on: Communication is normal in WiFi
mode or LAN mode.
Single blink: The Smart Communication Stick's
Bluetooth signal is enabled, waiting to connect
to the SEMS + App.
Two blinks: The Smart Communication Stick has
not connected to the router.
Four blinks: The Smart Communication Stick
communicates normally with the router but has
not connected to the server.
Six blinks: The Smart Communication Stick is
identifying connected devices.
Off: The Smart Communication Stick is
undergoing a software reset or is not powered
on.
Power
indicator
Communi
cation
indicator
Indicator
Color
Green
Status
Steady on
Description
100Mbps wired network connection is
normal.
121
Indicator
Color
LAN port
communica
tion
indicator
Status
• Network cable is not connected.
Off
Steady on
Yellow
Flashing
Off
Button
Reload
Description
• 100Mbps wired network connection is
abnormal.
• 10Mbps wired network connection is
normal.
10/100Mbps wired network connection is
normal, with no communication data
being transmitted or received.
Communication data is being transmitted
or received.
Network cable is not connected.
Description
Hold for 0.5 to 3 seconds to reset the Smart Communication
Stick.
Hold for 6 to 20 seconds to restore the Smart Communication
Stick to factory settings.
Double-click quickly to enable Bluetooth signal (maintained for
only 5 minutes).
122
7 System Commissioning
7.1 Setting Inverter Parameters via App
SEMS + App is a software used for remote power station monitoring or local device
debugging. It supports installers or owners:
• Remotely monitor the operation of power stations and set parameters for stations
and equipment.
• Locally connect to devices, view device operation status, and set device
parameters.
For detailed functions, please refer to the "SEMS + App User Manual ".
The user manual can be obtained from the official website or by scanning the QR
code below.
SEMS+ App User Manual
7.1.1 Download and Install SEMS + App
Phone Requirements:
• Operating System: Android 7.0 or above, iOS 15.1 or above.
• Phone must support a web browser and connect to the Internet.
• Phone must support WLAN/Bluetooth functionality.
Download Methods:
Method 1:
Search for "SEMS +" in Google Play, App Store, Huawei, Honor,
Xiaomi, OPPO, or vivo app stores to download and install.
123
Method 2:
Scan the QR code below to download and install.
7.2 Power Plant Monitoring via SEMS+ WEB
SEMS+ WEB is a monitoring platform that communicates via WiFi or LAN. The
following are the common functions of SEMS+ WEB:
1. Manage organization or user information, etc.
2. Add and monitor power plant information, etc.
3. Maintain equipment.
For detailed functions, please refer to the SEMS+ WEB User Manual.
"SEMS+ WEB User Manual"
124
8 Maintenance
8.1 Power OFF the System
DANGER
• When performing operation and maintenance on devices in the system, please
power off the system. Operating devices with power on may cause device
damage or electric shock DANGER.
• After the device is powered off, internal components require some time to
discharge. Please wait until the device is completely discharged according to the
label time requirements.
• Restarting the battery should be done using the air switch power-on method.
• When shutting down the battery system, strictly adhere to the battery system
power-off requirements to prevent damage to the battery system.
NOTICE
• To ensure effective protection of the battery system, keep the cover plate of the
battery system switch closed. If the battery system switch is not used for an
extended period, secure it with screws.
power off
125
1. Disconnect the BACK-UP circuit breaker.
2. Disconnect the GRID circuit breaker.
3. Press and hold any battery's multifunction button for 5 seconds to power off the
battery system. If the system contains multiple batteries, this operation will power
off all batteries; there is no need to operate them individually. Finally, disconnect
the battery system switch.
4. (Optional) Disconnect the circuit breaker between the PV components and the
inverter.
5. Disconnect the inverter's DC switch.
8.2 Removing the Equipment
126
DANGER
• Ensure the device is powered off.
• When operating the device, please wear personal protective equipment.
• When removing wiring terminals, use standard disassembly tools to avoid
damaging the terminals or device.
• Unless otherwise specified, the device disassembly method is the reverse order
of the installation method, and this document will not elaborate further.
1. Power down the system.
2. Label the cables connected in the system to indicate their types.
3. Disconnect the cables from the Inverter, Battery, and smart meter in the system,
such as DC cables, AC cables, Communication cable, and PE cable.
4. Remove equipment such as the smart communication stick, Inverter, Battery, and
smart meter.
5. Store the equipment properly. If it will be put into use again later, ensure the
storage conditions meet the requirements.
8.3 Disposing of the Equipment
When the equipment can no longer be used and needs to be disposed of, please
handle it according to the electrical waste disposal requirements of the regulations in
the country/region where the equipment is located. The equipment must not be
disposed of as general household waste.
8.4 Routine Maintenance
WARNING
127
• If any issues that may affect the battery or energy storage inverter system are
found, contact after-sales personnel. Disassembly by unauthorized persons is
prohibited.
• If exposed copper wires inside the conductive wires are found, do not touch
them. High voltage danger. Contact after-sales personnel. Disassembly by
unauthorized persons is prohibited.
• In case of other emergencies, contact after-sales personnel immediately.
Operate under the guidance of after-sales personnel or wait for on-site operation
by after-sales personnel.
Maintenan
ce Item
Maintenance Method
Maintenanc
e Cycle
Maintenance
Purpose
System
Cleaning
Check the heat sink and air
inlet/outlet for foreign objects
or dust.
Check if the installation space
meets requirements and if
there is debris accumulation
around the equipment.
Once every
6 months
Prevent cooling
failures.
Once every
6 months to
once a year
Confirm equipment
installation stability.
Once every
6 months to
once a year
Confirm electrical
connection
reliability.
System
Installation
Electrical
Connection
s
Fan
Check if the equipment
installation is secure and if
fastening screws are loose.
Check the equipment exterior
for damage or deformation.
Check electrical connections
for looseness, inspect cable
exteriors for damage or
exposed copper.
Check the fan for abnormal
noise;
Check fan blades for cracks;
Check the fan for abnormal
blockage/stalling;
128
Once every 6
Prevent fan failure.
months
Maintenan
ce Item
Sealing
Battery
Maintenanc
e
Maintenance Method
Check if the sealing of
equipment cable entry holes
meets requirements. If gaps
are too large or unsealed,
reseal them.
If the battery has not been
used or fully charged for an
extended period, it is
recommended to charge it
regularly.
Maintenanc
e Cycle
Maintenance
Purpose
Once a year
Confirm machine
sealing and
waterproof integrity.
Once every
15 days
Protect battery
service life.
For fan maintenance, refer to the following steps:
The inverter has a fan module on the outside. To better clean the fan module, please
remove it from the machine before cleaning. The specific steps are as follows:
1. Power off the inverter. You can refer to 8.1.Power OFF the System(Page 125).
2. Wait for the system residual voltage to be completely discharged and the fan
module to completely stop running.
3. Use a screwdriver to remove the module mounting screws and take out the entire
fan module.
4. Use a soft brush, cloth, or vacuum cleaner to clean the fan.
After cleaning is completed, reinstall the fan module back into the machine.
129
130
8.5 fault
8.5.1 Viewing Fault/Alarms Information
Detailed information for all faults and alarms in the energy storage system is
displayed in the SEMS+ App and SEMS+ WEB .
If your product experiences an abnormality and no related fault information is seen in
the SEMS+ App or SEMS+ WEB, please contact the after-sales service center.
• In SEMS+ App
1. Open the SEMS+ App and log in with any account.
2. On the homepage, click "Alarms" to view alarm information for all power plants
under the account.
• SEMS+ WEB
1. Open the SEMS+ WEB and log in with any account.
2. On the power plant details interface, click "Alarms" to view all alarm information
for the current power plant.
8.5.2 Fault Information and Troubleshooting
Please perform troubleshooting according to the following methods. If the
troubleshooting methods cannot help you, please contact the after-sales service
center.
When contacting the after-sales service center, please collect the following
information to facilitate a quick resolution.
1. Product information, such as: serial number, software version, device installation
time, fault occurrence time, fault frequency, etc.
2. Device installation environment, such as: weather conditions, whether components
are blocked, have shadows, etc. It is recommended to provide photos, videos, and
131
other files to assist in problem analysis.
3. Grid conditions.
If the system experiences a problem not listed, or if following the instructions still
cannot prevent the problem or abnormality, immediately stop system operation and
contact your dealer immediately.
No.
1
fault
Resolution
Unable to
search for the
Smart
Communication
Stick's wireless
signal
1. Ensure no other devices are connected to the Smart
Communication Stick's wireless signal.
2. Ensure the Smart Communication Stick is powered
normally, with the blue signal light flashing or steady
on.
3. Ensure the smart device is within the communication
range of the Smart Communication Stick.
4. Refresh the App device list again.
5. Restart the inverter.
2
Unable to
connect to the
Smart
Communication
Stick's wireless
signal
1. Ensure no other devices are connected to the Smart
Communication Stick's wireless signal.
2. Restart the inverter or the communication stick, then
try connecting to the Smart Communication Stick's
wireless signal again.
3. Ensure Bluetooth pairing and encryption were
successful.
3
Unable to find
the router's
SSID
1. Place the router closer to the Smart Communication
Stick, or add a WiFi repeater to enhance the WiFi signal.
2. Reduce the number of devices connected to the router.
132
No.
fault
Resolution
1. Restart the inverter.
4
After all
configuration is
complete, the
Smart
Communication
Stick fails to
connect to the
router
5
After all
configuration is
complete, the
Smart
Communication
Stick fails to
connect to the
server
2. Check if the network name, encryption method, and
password in the WiFi configuration match those of the
router.
3. Restart the router.
4. Place the router closer to the Smart Communication
Stick, or add a WiFi repeater to enhance the WiFi signal.
Restart the router and the inverter.
8.5.2.1 Inverter fault
fault
code
F01
F02
fault name
fault cause
Troubleshooting
recommendation
Grid Power Outage
1. Utility grid power
outage.
2. AC line or AC
Switch
disconnected.
1. The alarm automatically
disappears after Grid
connected recovery.
2. Check if the AC line or
AC Switch is disconnected.
Utility gridvoltage
exceeds the
allowable range, or
the high voltage
Duration surpasses
the high voltage
ride-through
setting value.
1. If it occurs occasionally,
it may be due to a
temporary abnormality in
the Utility grid. The
Inverter will resume
normal operation after
detecting that the Utility
grid is functioning
properly, without requiring
Grid Overvoltage
Protection
133
fault
code
fault name
fault cause
Troubleshooting
recommendation
manual intervention.
2. If it occurs frequently,
check whether Utility grid
and voltage are within the
allowable range.
• If Utility gridvoltage
exceeds the permissible
range, please contact
the local power
operator.
• If the Utility gridvoltage
is within the allowable
range, it is necessary to
modify the InverterGrid
Overvoltage Protection
point after obtaining
consent from the local
power
operator,HVRTEnable or
disable the Grid
Overvoltage Protection
function.
3. If the issue persists for
an extended period,
please check whether the
breaker on the AC side and
the output cables are
properly connected.
134
fault
code
fault name
fault cause
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. The Inverter
will resume normal
operation after detecting
that Utility grid is
functioning properly,
without requiring manual
intervention.
F03
Grid Undervoltage
Protection
Utility gridvoltage
is below the
allowable range, or
the low-voltage
Duration exceeds
the Low Voltage
ride-through
setting value.
2. If it occurs frequently,
check whether the Utility
grid and voltage are within
the allowable range.
• If Utility gridvoltage
exceeds the permissible
range, please contact
the local power
operator.
• If the Utility gridvoltage
is within the allowable
range, it is necessary to
modify the InverterGrid
Undervoltage Protection
point after obtaining
consent from the local
power
operator.LVRTEnable or
disable the Grid
Undervoltage Protection
function.
3. If the issue persists for
an extended period,
135
fault
code
fault name
fault cause
Troubleshooting
recommendation
please check whether the
AC-side breaker and
output cables are properly
connected.
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
F04
Grid Rapid
Overvoltage
Protection
Utility gridvoltage
detection shows
abnormality or
ultra-high voltage
triggers fault.
136
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
please check whether
Utility grid and voltage are
within the allowable range.
• If Utility gridvoltage
exceeds the permissible
range, please contact
the local power
operator.
• If Utility gridvoltage is
within the allowable
range, it is necessary to
modify the InverterGrid
Undervoltage Protection
point after obtaining
approval from the local
power
operator.LVRTEnable or
disable the Grid
Undervoltage Protection
fault
code
fault name
fault cause
Troubleshooting
recommendation
function.
3. If the issue persists for
an extended period,
please check whether the
AC-side breaker and
output cables are properly
connected.
137
fault
code
F05
fault name
10minOvervoltage
Protection
fault cause
In10minThe sliding
average of Utility
gridvoltage
exceeds the safety
regulation limits.
138
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal
operation after
detecting that Utility grid
is functioning properly,
without requiring
manual intervention.
2. Check if Utility
gridvoltage is operating
at a high voltage for an
extended period. If this
occurs frequently, verify
whether Utility
gridvoltage is within the
allowable range.
• If Utility gridvoltage
exceeds the permissible
range, please contact
the local power
operator.
• If the Utility gridvoltage
is within the allowable
range, it is necessary to
obtain approval from
the local power operator
before modifying the
Utility
grid.10minOvervoltage
Protection point.
fault
code
F06
fault name
Grid Overfrequency
fault cause
Utility grid
anomaly: Utility
grid actual
Frequency exceeds
local Utility grid
standard
requirements.
139
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary abnormality in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
check whether Utility grid
and Frequency are within
the allowable range.
• If the Utility
gridFrequency exceeds
the permissible range,
please contact the local
power operator.
• If Utility gridFrequency is
within the allowable
range, the Grid
Overfrequency point
needs to be modified
after obtaining consent
from the local power
operator.
fault
code
F07
fault name
Grid
Underfrequency
fault cause
Utility grid
anomaly: Utility
grid actual
Frequency is lower
than local Utility
grid standard
requirement.
140
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
upon detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
check whether Utility grid
and Frequency are within
the allowable range.
• If the Utility
gridFrequency exceeds
the permissible range,
please contact the local
power operator.
• If the Utility
gridFrequency is within
the permissible range,
the Grid Overfrequency
point needs to be
modified after obtaining
consent from the local
power operator.
fault
code
F08
fault name
Grid Frequency
Instability
fault cause
Utility grid
anomaly: Utility
grid actual
Frequency variation
rate does not
comply with local
Utility grid
standard.
141
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
check whether Utility grid
and Frequency are within
the allowable range.
• If the Utility
gridFrequency exceeds
the permissible range,
please contact the local
power operator.
• If the Utility grid
Frequency is within the
allowable range, please
contact your dealer or
after-sales service
center.
fault
code
F163
fault name
Grid Phase
Instability
fault cause
Utility grid
anomaly: Utility
grid voltage phase
variation rate does
not comply with
local Utility grid
standards.
142
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
please check whether
Utility grid and Frequency
are within the allowable
range.
• If Utility gridFrequency
exceeds the permissible
range, please contact
the local power
operator.
• If the Utility
gridFrequency is within
the allowable range,
please contact your
dealer or after-sales
service center.
fault
code
F09
F10
fault name
Anti-islanding
Protection
Undervoltage ridethrough
fault cause
Utility grid has
been disconnected,
maintaining Utility
grid voltage due to
the presence of
load. According to
safety regulation
Protection, on-grid
has been stopped.
Utility grid
anomaly: Grid
Voltage Abnormal
duration exceeds
the specified highlow transition time.
143
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
check whether the Utility
grid and Frequency are
within the allowable range.
• If the Utility
gridFrequency exceeds
the permissible range,
please contact the local
power operator.
• If the Utility grid
Frequency is within the
allowable range, please
contact your dealer or
after-sales service
center.
fault
code
F11
fault name
HVRT Overvoltage
F43
Grid Waveform
Abnormal
F44
Grid Phase Loss
fault cause
Utility grid
anomaly: The
duration of Grid
Voltage Abnormal
exceeds the
specified high-low
transition time.
Utility grid
anomaly: Utility
grid voltage
detection triggered
fault due to
abnormality.
Utility grid
anomaly: Utility
gridvoltage has a
single-phase dip.
144
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If it occurs frequently,
please check whether
Utility grid, voltage, and
Frequency are within the
allowable range and
stable. If not, contact the
local power operator; if
yes, contact your dealer or
after-sales service center.
fault
code
F45
F46
fault name
Grid Voltage
Imbalance
Grid Phase
Sequence Failure
fault cause
Utility grid phase
voltage deviation is
excessive.
Inverter and Utility
grid wiring
abnormality: wiring
is not in positive
sequence
145
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be due to a
temporary anomaly in
Utility grid. Inverter will
resume normal operation
after detecting that Utility
grid is functioning
properly, without requiring
manual intervention.
2. If this occurs frequently,
please check whether
Utility grid, voltage, and
Frequency are within the
allowable range and
stable. If not, contact the
local power operator; if
yes, contact your dealer or
after-sales service center.
1. Check whether the
wiring of Inverter and
Utility grid is in positive
sequence. After the wiring
is corrected (e.g., by
swapping any two live
wires), the fault will
automatically disappear.
2. If the wiring is correct
and fault persists, please
contact the dealer or aftersales service center.
fault cause
Troubleshooting
recommendation
Quickly shut down
the output upon
detecting the Grid
Power Outage
operating
condition.
1. Grid connected
automatically disappears
after fault is restored
Grid Neutral Wire
Loss
Phase splitting
1. The alarm automatically
disappears after Grid
connected recovery.
2. Check if the AC line or
AC Switch is disconnected.
F160
EMS/Forced off-grid
EMSIssue forced
off-grid command,
but the off-grid
function is not
enabled.
Enable off-grid function
F161
Passive Antiislanding Protection
-
-
Grid Type Fault
Actual Type of
Electrical Supply
System (two-phase
or split-phase) does
not match the set
safety regulations.
Switch the corresponding
safety regulations
according to the actual
Type of Electrical Supply
System.
fault
code
F47
F48
F162
fault name
Grid Rapid
Shutdown
Protection
146
fault
code
F12
fault name
30mAGfciProtection
fault cause
During operation,
the input-toground insulation
resistance becomes
low.
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be caused by
temporary external line
abnormalities. The system
will resume normal
operation after the fault is
cleared, without requiring
manual intervention.
2. If it occurs frequently or
cannot be restored for a
long time, please check
whether the PV String
ground impedance is too
low.
F13
60mAGfciProtection
During operation,
the input-toground insulation
resistance becomes
low.
147
1. If it occurs occasionally,
it may be caused by
temporary abnormalities
in the external circuit. The
fault will resume normal
operation after clearing
without manual
intervention.
2. If the issue occurs
frequently or cannot be
resolved for an extended
period, please check
whether the PV String
ground impedance is too
low.
fault
code
F14
fault name
150mAGfciProtectio
n
fault cause
During operation,
the input-toground insulation
resistance becomes
low.
Troubleshooting
recommendation
1. If it occurs occasionally,
it may be caused by
temporary abnormalities
in the external circuit. The
system will resume normal
operation after the fault is
cleared, without requiring
manual intervention.
2. If the issue occurs
frequently or cannot be
resolved for an extended
period, please check
whether the PV String
ground impedance is too
low.
F15
Gfcislowly varying
Protection
During operation,
the input-toground insulation
resistance becomes
low.
148
1. If it occurs occasionally,
it may be caused by
temporary abnormalities
in the external circuit. The
fault will clear
automatically and resume
normal operation without
manual intervention.
2. If the issue occurs
frequently or cannot be
resolved for an extended
period, please check
whether the PV String
ground impedance is too
low.
fault
code
F16
F17
fault name
DCIPrimary
Protection
DCIsecondary
Protection
fault cause
The High DC
Component of the
inverter output
current is outside
the safety
regulations or the
default permissible
range of the
machine.
The current of the
inverter output is
outside the safety
regulations or the
default permissible
range of the
machine.
149
Troubleshooting
recommendation
1. If the abnormality is
caused by an external
fault, the Inverter will
automatically resume
normal operation after the
fault disappears, without
requiring manual
intervention.
2. If this alarm occurs
frequently and affects the
normal power generation
of the power station,
please contact the dealer
or after-sales service
center.
1. If the abnormality is
caused by an external
fault, the Inverter will
automatically resume
normal operation after the
fault disappears, without
requiring manual
intervention.
2. If this alarm occurs
frequently and affects the
normal power generation
of the power station,
please contact the dealer
or after-sales service
center.
fault
code
F18
fault name
Low Insulation
Resistance
fault cause
1. PV String is
short-circuited to
ground with
Protection.
2. The environment
of PV
StringInstallation is
consistently humid
with poor line-toground insulation.
3. Batteryport lineto-ground Low
Insulation
Resistance.
150
Troubleshooting
recommendation
1. Check the impedance
between PV String/Battery
port and ground
Protection. A resistance
value greater than 80kΩ is
normal. If the measured
resistance is less than
80kΩ, locate and rectify
the short circuit point.
2. Check whether the PE
cable of the Inverter is
properly connected.
3. If it is confirmed that the
impedance is indeed lower
than the default value in
rainy weather, please reset
the Inverter "insulation
resistanceProtection
point" via the App.
In the Australian and New
Zealand markets, when
Inverter occurs, alarms
can also be triggered
through the following
methods:
1. Inverter is equipped
with a buzzer, which will
sound continuously for 1
minute when a fault
occurs; if the fault is not
resolved, the buzzer will
sound again every 30
minutes.
fault
code
fault name
fault cause
Troubleshooting
recommendation
2. If Inverter is added to
the monitoring platform
and the alarm notification
method is configured,
alarm information can be
sent to customers via
email.
1. The PE cable of
Inverter Not
Connected.
F19
F49
Grounding
Abnormal
L-PE Short Circuit
2. When the
output of PV String
is grounded, the
output side of
Inverter is not
connected with an
isolation
transformer.
Output phase line
toPELow
impedance or short
circuit
151
1. Please confirm whether
the Inverter of PE cable is
functioning normally.
2. In the scenario where
the output of PV String is
grounded, please confirm
whether the output side of
Inverter is connected to an
isolation transformer.
Detect output phase line
toPEImpedance, identify
Locations with low
impedance and repair
them.
fault
code
F50
fault name
DCVPrimary
Protection
fault cause
Abnormal load
fluctuation
Troubleshooting
recommendation
1. If the abnormality is
caused by an external
fault, the Inverter will
automatically resume
normal operation after the
fault disappears, without
requiring manual
intervention.
2. If this alarm occurs
frequently and affects the
normal power generation
of the power station,
please contact the dealer
or after-sales service
center.
F51
DCVSecondary
Protection
Abnormal load
fluctuation
152
1. If the abnormality is
caused by an external
fault, the Inverter will
automatically resume
normal operation after the
fault disappears, without
requiring manual
intervention.
2. If this alarm occurs
frequently and affects the
normal power generation
of the power station,
please contact the dealer
or after-sales service
center.
fault
code
F20
fault name
Hardware Export
Limit Protection
fault cause
Abnormal load
fluctuation
Troubleshooting
recommendation
1. If the abnormality is
caused by an external
fault, the Inverter will
automatically resume
normal operation after the
fault disappears, without
requiring manual
intervention.
2. If this alarm occurs
frequently and affects the
normal power generation
of the power station,
please contact the dealer
or after-sales service
center.
F21
F52
Internal Comm Loss
Reference specific
subcode reason
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the dealer or aftersales service center.
Leakage
currentGFCIMultiple
fault shutdowns
North American
safety standards
require that after
multiple fault, the
system must not
recover
automatically and
requires manual
intervention or
waiting.24hPostrecovery
1. Please check if the PV
String ground
impedance is too low.
153
fault
code
F53
F54
F55
fault name
DC Arc
FailureAFCIMultiple
fault shutdowns
External
communication link
failure
Back-upport
Overload fault
fault cause
North American
safety regulations
require that after
multiple fault, the
system must not
recover
automatically and
requires manual
intervention or
waiting.24hPostrecovery
External device
communication
lost, possibly due
to peripheral
power supply
issues,
Communication
Protocols
mismatch, or
unconfigured
corresponding
peripherals.
1. Prevent Inverter
from continuous
Overload output.
154
Troubleshooting
recommendation
1. After the machine is reon-grid, check whether the
voltage current of each
circuit abnormally
decreases to zero;
2. Check if the DC side
terminal is securely
connected.
Judgment is made based
on the actual model and
detection enable bits;
peripherals not supported
by certain models will not
be detected.
1. Disconnect some offgrid loads to reduce the
Inverter off-grid output
Power.
fault
code
F56
fault name
Back-upport
overvoltage fault
fault cause
Troubleshooting
recommendation
2. Prevent damage
to the load caused
by overvoltage in
the Inverter output.
1. If it occurs occasionally,
it may be caused by load
switching and does not
require manual
intervention.
2. If it occurs frequently,
please contact the dealer
or after-sales service
center.
1Check if the
On-grid PWM Sync
Failure
Abnormal
occurrence in
carrier
synchronization ongrid
F57
External
connectionBoxfault
waiting for Switch
On-Grid to OffGridBoxExcessive
relay switching
time
-
Generator Failure
F107
155
synchronization line
connection is normal.
2Check if the master-slave
settings are normal.
3Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
1. InspectionBoxIs it
functioning properly;
2. InspectionBoxIs the
communication wiring
correct;
fault
code
F22
F23
F24
F25
F26
F27
F109
F58
fault name
fault cause
Generator waveform
1. In the case of a
detection fault
Not Connected
generator, this
Abnormal generator
fault will always
connection
be displayed.
Generator voltage
2. During
low
generator
Generator voltage
operation, failure
high
to meet generator
Generator
safety regulations
Frequency low
will trigger this
fault.
Generator
Frequency high
Troubleshooting
recommendation
1. When the generator is
not connected, ignore
this fault;
2. The occurrence of this
fault when the generator
experiences fault is
normal. After the
generator recovers, wait
for a period of time, and
the fault will automatically
clear.
3. The fault does not affect
the normal operation of
the off-grid mode.
4. The generator and
Utility grid are connected
simultaneously and meet
safety requirements. Utility
grid takes priority on-grid
and will operate in the
Utility grid on-grid state.
External
connectionSTSfault
Inverter
andSTSAbnormal
connection cable
Check the Inverter
andSTSIs the wiring
sequence of the harness
connection between them
one-to-one and
sequentially
corresponding?
CTMissing fault
CTConnection wire
disconnected
(Japanese safety
regulation
requirement)
InspectionCTIs the wiring
correct.
156
fault
code
fault name
fault cause
Troubleshooting
recommendation
1. Check if there are any
other error messages in
Inverter. If so, perform
targeted
troubleshooting.
2. InspectionmeterIs the
connection reliable?
3. If this alarm occurs
frequently and affects
the normal power
generation of the power
station, please contact
the dealer or after-sales
service center.
F110
Export Limit
Protection
1. Fault report and
grid disconnection
2. meterUnstable
communication
3. Reverse power
flow condition
occurs
F111
BypassOverload
-
-
F112
Black Start Failure
-
-
F28
Parallel
operationIOSelf-test
abnormality
F59
Parallel
operationCANComm
unication
abnormality
Parallel
communication line
is not securely
connected or
parallel
operationIOChip
damage
Parallel
communication
cable is not
securely connected
or some units are
offline.
157
Check if the parallel
communication cable is
securely connected, and
then recheck.IOCheck if
the chip is damaged, and if
so, replace it.IOChip.
Check whether all
machines are power on
and ensure the parallel
communication cables are
securely connected.
fault
code
fault name
F29
Paralell Grid Line
Reversed
F60
Parallel
operationBackupreverse
connection
F61
Inverter Soft Start
Failure
F113
Offgrid AC Ins Volt
High
Troubleshooting
recommendation
fault cause
Some machines
have the Utility grid
line connected in
reverse with
others.
Partial
machinesbackupLi
ne reversed with
other connections
Off-grid cold start
Inverter Soft Start
Failure
-
Reconnect the Utility grid
line.
reconnectionbackupLine.
Check whether the
inverter module of the
machine is damaged.
-
F30
AC HCT check
Abnormal
AC sensor sampling
anomaly
F62
AC HCT Failure
HCTSensor
anomaly detected
158
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
fault name
fault cause
F31
GFCI HCT Check
Abnormal
Leakage current
sensor has
sampling
abnormality
F63
GFCI HCT Failure
Leakage current
sensor is abnormal
Relay Check
Abnormal
Relay abnormality,
cause:
1Relay abnormality
(relay short circuit)
2Relay sampling
circuit abnormality.
3Abnormal AC side
wiring (possible
loose connection or
short circuit)
F32
159
Troubleshooting
recommendation
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
F64
F164
F165
F33
fault cause
Troubleshooting
recommendation
Relay Failure
1Relay abnormality
(relay short circuit)
2Relay sampling
circuit abnormality.
3Abnormal AC side
wiring (possible
loose connection or
short circuit)
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
String (array)17~32)
1DC side
connection
terminal loose;
2DC side
connection
terminal loose
contact;
3Core damage and
poor contact
1After the machine is reon-grid, check whether the
voltage current of each
circuit is abnormally
reduced to zero;
2Check if the DC-side
terminal is securely
connected.
String33~48)
1DC side
connection
terminal loose;
2DC side
connection
terminal loose
contact;
3Core damage and
poor contact
1After the machine is reon-grid, check whether the
voltage current of each
circuit is abnormally
reduced to zero.
2Check if the DC-side
terminal is securely
connected.
FlashRead/Write
Error
Possible causes:
flashContent has
been
changed;flashEnd
of life
1. Upgrade to the latest
version of the program
2. Contact the dealer or
after-sales service center.
fault name
160
fault
code
F42
F34
F65
fault name
fault cause
Troubleshooting
recommendation
String (string)1~16)
1DC side
connection
terminal loose;
2DC side
connection
terminal loose
contact;
3Core damage and
poor contact
1After the machine is reon-grid, check whether the
voltage current of each
circuit is abnormally
reduced to zero;
2Check if the DC-side
terminal is securely
connected.
AFCI Check Failure
During the Arc
Failure self-test
process, the Arc
Failure module
failed to detect Arc
Failure.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
AC Terminal
Overtemperature
AC Terminal
Overtemperature,
possible causes:
1Inverter
Installation
Location Nonventilated.
2Ambient
Overtemperature
3Internal fan
operation
abnormal.
161
fault
code
F35
F66
fault name
Cabinet
Overtemperature
INVModule
temperature too
high
fault cause
Troubleshooting
recommendation
Cabinet
Overtemperature,
Possible causes:
1InverterInstallatio
n Location nonventilated.
2Ambient
Overtemperature
3Internal fan
operation
1Check whether the
ventilation of the
InverterInstallation
Location is adequate and
whether the ambient
temperature exceeds the
maximum permissible
ambient temperature
range.
2If there is no ventilation
abnormal.
or Ambient
Overtemperature, please
improve the ventilation
and heat dissipation
conditions.
3If ventilation and ambient
temperature are both
normal, please contact the
dealer or after-sales
service center.
Inverter module
temperature is too
high, possible
causes:
1InverterInstallatio
n Location nonventilated.
2Ambient
Overtemperature
3Internal fan
operation
abnormal.
162
fault
code
F67
fault name
BoostModule
temperature too
high
fault cause
BoostModule
temperature too
high, possible
causes:
1InverterInstallatio
n Location nonventilated.
2Ambient
Overtemperature
3Internal fan
operation
abnormal.
F68
AC Capacitor
Overtemperature
Output filter
capacitor
temperature is too
high, possible
causes:
1InverterInstallatio
n Location not
ventilated.
2Ambient
Overtemperature
3Internal fan
operation
abnormal.
163
Troubleshooting
recommendation
fault
code
F114
F69
F70
fault name
Relay Failure2
fault cause
Troubleshooting
recommendation
Relay abnormality,
cause:
1Relay abnormality
(relay short circuit)
2Relay sampling
circuit abnormality.
3Abnormal AC side
wiring (possible
loose connection or
short circuit)
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
PV IGBT short circuit
Possible causes:
1. IGBTshort circuit
2Abnormal
sampling circuit
PV IGBTopen circuit
voltage
1. Software issue
caused no wave
transmission.
2. Drive circuit
abnormality:
3. IGBTOpen Circuit
164
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
fault name
fault cause
F71
NTCabnormall
NTCTemperature
sensor abnormality
detected
F72
PWM Abnormal
PWMAbnormal
waveform detected
F73
CPUInterruption
anomaly
CPUInterruption
anomaly occurred
F74
Microelectronics
fault
Function Safety
anomaly detected
165
Troubleshooting
recommendation
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
fault name
fault cause
F75
PV HCTfault
boostcurrent
sensor abnormality
F76
1. 5VBenchmark
anomaly
Reference circuit
F77
0. 3VBaseline
anomaly
Reference circuit
F78
CPLDVersion
identification error
CPLDVersion
identification error
F79
CPLDCommunicatio
n fault
CPLDandDSPComm
unication content
error or timeout
166
Troubleshooting
recommendation
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
fault name
fault cause
Troubleshooting
recommendation
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
F80
Model Identification
Model Recognition
Error's fault
regarding
F115
SVGPrecharge
Disabled
SVGPrecharge
hardware failure
Contact the dealer or aftersales service center.
F116
nighttimeSVG
PIDPrevention of
fault
PIDPrevent
hardware
anomalies
Contact the dealer or aftersales service center.
F117
DSPVersion
identification error
F36
Bus Overvoltage
F81
P-Bus Overvoltage
F82
N-Bus Overvoltage
F83
Bus
Overvoltage(Deputy
CPU1)
F84
DeputyCPU1)
DSPSoftware
version
identification error
167
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
fault name
F85
DeputyCPU1)
F86
Bus
Overvoltage(Deputy
CPU2)
F87
DeputyCPU2)
F88
N-Bus
Overvoltage(Deputy
CPU2)
F89
P-Bus
Overvoltage(CPLD)
F90
Complex
Programmable
Logic Device (CPLD)
F118
MOSContinuous
Overvoltage
fault cause
Troubleshooting
recommendation
BUSOvervoltage,
possible causes:
1. PVvoltage too
high
2InverterBUSSampl
ing anomaly
3The poor isolation
effect of the rearend double
splitting causes
mutual
interference
between the two
Inverteron-grid,
resulting in DC
overvoltage when
one of the
Inverteron-grid
occurs.
1. Software issue
causes the inverter
drive to shut down
earlier than the
flyback drive.
2. Inverter drive
circuit abnormality
prevents turn-on.
3. PVvoltage too
high
4. MosSampling
anomaly
168
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
fault name
fault cause
F119
Busbar short circuit
1. Hardware
damage
F120
Abnormal bus
sampling
1. BusSampling
hardware
DCLateral sampling
abnormality
1. Bus sampling
hardware
2. Battery Voltage
Sampling
Hardware fault
3. DcrlyRelay
Failure
F121
169
Troubleshooting
recommendation
In case of
occurrenceBUSAfter a
short circuit fault, the
Inverter remains in an offgrid state. Please contact
the dealer or after-sales
service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
F37
fault name
PVInput overvoltage
fault cause
PVvoltage input too
high, possible
causes:
Incorrect PV array
configuration, with
too many PV
Battery panels
connected in
series, causing the
open-circuit
voltage of the
string to exceed
the maximum
operating voltage
of the Inverter.
F38
F39
F91
PVContinuous
Hardware
Overcurrent
1. Unreasonable
module
configuration
2. Hardware
damage
PVContinuous
software
overcurrent
1. Unreasonable
module
configuration
2. Hardware
damage
FlyCap Software
Overvoltage
Flying capacitor
overvoltage,
possible causes:
1. PVvoltage too
high
2Inverter Flying
Capacitor voltage
Sampling Anomaly
170
Troubleshooting
recommendation
Check the series
configuration of the
corresponding PV array
strings to ensure that the
open-circuit voltage of the
strings does not exceed
the maximum working
voltage of the Inverter.
Once the PV array is
correctly configured, the
Inverter alarm will
automatically disappear.
Disconnect the AC output
side switch and the DC
input side switch.5After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
fault
code
F92
fault name
FlyCap Hardware
Overvoltage
fault cause
Troubleshooting
recommendation
Flying capacitor
overvoltage,
possible causes:
1. PVvoltage too
high
2InverterFlying
capacitorvoltagesa
mpling anomaly
Disconnect the AC output
side switch and the DC
input side switch.5After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
FlyCap
Undervoltage,
F93
FlyCap
Undervoltage
possible causes:
1. PVEnergy
deficiency;
2Flying capacitor
sampling anomaly
FlyCap Precharge
Failure
FlyCap Precharge
Failure, Possible
causes:
1. PVEnergy
deficiency;
2InverterFlying
CapacitorvoltageSa
mpling Anomaly
F95
FlyCap Precharge
Abnormal
1. Unreasonable
control loop
parameters
2. Hardware
damage
F96
String
overcurrent(String1
~16)
F94
171
fault
code
fault name
fault cause
Troubleshooting
recommendation
Possible causes:
1. String
Overcurrent
2. String current
sensor anomaly
F97
String
overcurrent(String1
7~32)
F40
String reverse
connection(String1~
16)
PVString reverse
connection
Check if the strings are
reversed.
F98
String reverse
connection(String17
~32)
PVString reverse
connection
Check if the string is
reverse connected.
F99
String
loss(String1~16)
String fuse
disconnected (if
applicable)
Check if the fuse is blown.
F100
String
loss(String17~32)
String fuse
disconnected (if
applicable)
Check if the fuse is blown.
172
fault
code
F122
fault name
PVAccess Mode
setting error
fault cause
Troubleshooting
recommendation
PVAccess Mode has
three modes, with
four
channelsMPPTFor
example:
1. Parallel mode:
that
isAAAAMode(homol
ogous mode),PV1PV4Homologous,4R
InspectionPVIs Access
Mode correctly set
(ABCD、AACC、AAAAReset
oadPVConnect the
same photovoltaic
panel
2. Partial Parallel
Mode:
i.e.AACCMode,PV1a
ndPV2Homologous
connection,PV3and
PV4homologous
connection
3. Stand-alone
mode:
i.e.ABCDMode(nonhomologous),PV1、
check the current
settingsPVAccess Mode"
corresponds to the actual
Access Mode.
3. If the currently
setPVAccess Mode" does
not match the actual
Access Mode and requires
adjustment.Appor the
screen willPVAccess Mode
is set to a mode consistent
with actual conditions.
After the setting is
completed,PVandACPower
supply disconnection and
restart.
4. After the setup is
completed, if the
currentPVAccess Mode
matches the actual Access
Mode, but this fault is still
reported. Please contact
the dealer or after-sales
PV2、PV3、
PV4Independent
connection,4RoadP
VEach connected to
a photovoltaic
panel
IfPVThe actual
Access Mode and
the equipment
173
in the correct
mannerPVAccess Mode
1. Confirm the actual
connected circuitsPVIs the
connection correct.
2. IfPVCorrectly connected,
passedAppor screen to
fault
code
fault name
fault cause
Troubleshooting
recommendation
settingsPVThis fault
will be reported if
Access Mode does
not match.
service center.
-
String reverse
connection(String33
~48)
PVString reverse
connection
Check if the strings are
reversed.
-
String
loss(String33~48)
String fuse
disconnected (if
applicable)
String
overcurrent(String3
3~48)
Possible causes:
1. String
Overcurrent
2. String current
sensor anomaly
-
174
Check if the fuse is blown.
fault
code
F123
fault name
Multi-channel PV
phase error
fault cause
PV input mode
setting error
175
Troubleshooting
recommendation
Check if the PVAccess
Mode is correctly set
(ABCD, AACC, AAAA), and
reset the PVAccess Mode in
the correct manner.
Verify that each connected
PV string is correctly wired.
2. If the PV is correctly
connected, check via the
App or screen whether the
currently set "PVAccess
Mode" corresponds to the
actual Access Mode.
3. If the currently set "PV
Access Mode" does not
match the actual Access
Mode, it is necessary to
use the App or screen to
set the "PV Access Mode"
to the mode consistent
with the actual situation.
After the setting is
completed, disconnect the
PV and AC power supply
and restart.
4. After the setup is
completed, if the current
"PVAccess Mode" matches
the actual Access Mode but
this fault still appears,
please contact the dealer
or after-sales service
center.
fault
code
fault name
fault cause
Troubleshooting
recommendation
Check if the pre-Charge
circuit is in good condition,
ensure that only the
Battery power on matches
the Battery Voltage and
busbar voltage. If they do
not match, please contact
the dealer or after-sales
service center.
After Battery power on,
check whether the Battery
relay operates and if the
closing sound is heard. If it
does not function, please
contact the dealer or aftersales service center.
F101
Battery1Precharge
fault
Battery1Pre-Charge
circuit fault (such
as pre-Charge
resistance burnout,
etc.)
F102
Battery1Relay
Failure
Battery1The relay
fails to operate
normally.
Battery1overvoltage
at connection point
Battery1The
voltage access
exceeds the rated
range of the
machine.
Verify if Battery Voltage is
within the machine's rated
range.
Battery2Pre-Charge
circuit fault (such
as pre-Charge
resistor burnout,
etc.)
Check whether the preCharge circuit is in good
condition, and verify that
the Battery power on postBattery Voltage matches
the busbar voltage. If they
do not match, please
contact the dealer or aftersales service center.
F103
F104
Battery2Precharge
fault
176
fault
code
F105
F106
fault name
Battery2Relay
Failure
Battery2overvoltage
at connection point
F124
Battery1Reverse
connection
F125
Battery2Reverse
polarity fault
F126
Abnormal Access
-
BMS Status Bit Error
fault cause
Troubleshooting
recommendation
Battery2The relay
fails to operate
normally.
After Batterypower on,
check if the Battery relay
operates and if the closing
sound is heard. If it does
not function, please
contact the dealer or aftersales service center.
Battery2The input
voltage exceeds
the rated range of
the machine.
Battery1Reverse
polarity of positive
and negative
terminals
Battery2Reverse
polarity of positive
and negative
terminals
Abnormal
connection of
Battery
BMS Module
177
Verify if Battery Voltage is
within the machine's rated
range.
Check whether the polarity
of Battery and the
machine terminal is
consistent.
Check whether the polarity
of Battery and the
machine terminals is
consistent.
Check if the Battery is
functioning properly.
Disconnect the AC output
side switch and DC input
side switch, then close the
AC output side switch and
DC input side switch after 5
minutes. If fault persists,
please contact the
distributor or after-sales
service center.
fault
code
F127
fault name
BAT
Overtemperature
fault cause
Troubleshooting
recommendation
Battery
temperature is too
high, possible
causes:
1InverterInstallatio
n Location nonventilated.
2Ambient
Overtemperature
3Internal fan
operation
abnormal.
F128
F129
Ref Voltage
Abnormal
Reference circuit
Cabinet Under
Temperature
Cabinet Under
Temperature,
Possible causes:
1. The ambient
temperature is too
low.
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
ACFailure of lateral
lightning
protection device
DCFailure of lateral
lightning
protection device
ReplacementACLateral
lightning protection
device.
ReplacementDCSide
lightning protection
device.
F130
ACsideSPDfault
F131
DCsideSPDfault
178
fault
code
F132
fault name
Internal Fan
Abnormal
fault cause
Internal Fan
Abnormal, possible
causes:
1Abnormal fan
power supply;
2Mechanical
fault(Locked rotor);
3Fan aging and
damage.
Troubleshooting
recommendation
Disconnect the AC output
side switch and the DC
input side switch.5 After a
few minutes, close the AC
output side switch and the
DC input side switch. If
fault persists, please
contact the distributor or
after-sales service center.
External Fan
F133
F134
External Fan
Abnormal
PIDDiagnose
abnormality
Abnormal, Possible
causes:
1Abnormal fan
power supply;
2Mechanical
fault(Locked rotor);
3Fan aging and
damage.
PIDHardware fault
orPVvoltage too
highPIDPause
179
PVOvervoltage caused by
voltagePIDSuspend
WARNING without
processing,PIDHardware
fault can be turned
off.PIDSwitch Reopen
ClearPIDfault,
replacementPIDdevice
fault
code
F135
fault name
Trip-Switch Trip
Warning
fault cause
Possible causes:
Overcurrent
orPVReverse
connection causes
the trip switch to
trip.
180
Troubleshooting
recommendation
Please contact the dealer
or after-sales service
center. The reason for
disconnection is due to a
fault occurrence.PVShort
circuit or reverse
connection, need to check
if there is a history.PVShort
circuit WARNING or
historyPVReverse
connection of WARNING. If
present, maintenance
personnel should inspect
the corresponding
component.PVSituation.
After confirming there is
no fault, manually close
the trip switch and
proceed withAppInterface
Clear History fault
Operation Clears This
WARNING.
fault
code
fault name
F136
HistoryPV
IGBT short circuit
F137
HistoryPVReverse
connection
WARNING(String1~1
6)
fault cause
Troubleshooting
recommendation
Please contact the dealer
or after-sales service
center. Maintenance
personnel should follow
the historicalPVShort
circuit WARNING subcode,
Possible causes:
check for short circuit
Overcurrent caused
occurrenceBoostCheck if
the trip switch to
there is any fault in the
open.
hardware and external
string; after confirming
there is no fault, it can
pass.AppInterface Clear
History fault Operation
Clears This WARNING.
Contact the dealer or aftersales service center.
Maintenance personnel
should follow the
historicalPVReverse
polarity WARNING
subcode, check whether
Possible causes:
the corresponding string
occurrencePVRever
has reverse polarity,
se connection
inspectPVIs there a voltage
causes the trip
difference in the panel
switch to trip.
configuration? After the
inspection is completed
and no fault is found, it
can be
passed.AppInterface Clear
History fault Operation
Clears This WARNING.
181
fault
code
F138
F139
fault cause
Troubleshooting
recommendation
HistoryPVReverse
connection(String17
~32)
Possible causes:
occurrencePVRever
se connection
causes the trip
switch to trip.
Contact the dealer or aftersales service center.
Maintenance personnel
must follow the
historicalPVReverse
connection WARNING
subcode, check whether
the corresponding string
has a reverse connection,
inspectPVIs there a voltage
difference in the panel
configuration? After
checking and confirming
no fault, it can be
passed.AppInterface Clear
History fault Operation
Clears This WARNING.
FlashRead/write
error
Possible causes:
flashContent has
been
changed;flashEnd
of life
1. Upgrade to the latest
version of the program.
2. Contact the dealer or
after-sales service center.
fault name
182
fault
code
F140
fault name
Meter Comm Loss
fault cause
This WARNING may
only be reported
after enabling the
Power Limit
function. Possible
causes:
1. Meter not
connected;
2. The
communication line
connection
between the meter
and Inverter is
incorrect.
F141
PVPanel type
identification failed
PVPanel
identification
hardware anomaly
PVPV String
Mismatch, same
circuitMPPTThe
configurations of
the next two
strings open-circuit
voltage are
different.
Troubleshooting
recommendation
Check the meter wiring
and ensure the meter is
correctly connected. If
fault persists after
inspection, please contact
the dealer or after-sales
service center.
Contact the dealer or aftersales service center.
Check the two strings
open-circuit voltage and
configure the strings with
the same open-circuit
voltage to the same
circuit.MPPTProlonged PV
String Mismatch poses
safety hazards.
F142
PV String Mismatch
F143
CTNot connected
CTNot connected
InspectionCTWiring.
F144
CTReverse
connection
CTReverse
connection
InspectionCTWiring.
F145
PE Loss/PE Loss
Ground wire not
connected
Check the ground wire.
183
fault
code
F146
F147
F148
fault name
String terminal
temperature
high(String1~8)
String terminal
temperature
high(String9~16)
String terminal
temperature
high(String17~20)
Troubleshooting
recommendation
fault cause
37176RegisterPVter
minal temperature
alarm subcode1Set
37177RegisterPVter
minal temperature
alarm subcode2Set
37178registerPVter
minal temperature
alarm subcode3Set
position
-
-
-
F149
HistoryPVReverse
connection
WARNING(String33~
48)
Possible causes:
occurrencePVRever
se connection
causes the trip
switch to trip.
Please contact the dealer
or after-sales service
center; maintenance
personnel must follow the
history.PVReverse
connection WARNING
subcode, check whether
the corresponding string
has a reverse connection,
inspectPVIs there a voltage
difference in the panel
configuration? After
checking and confirming
no fault, it can be
passed.AppInterface Clear
History fault Operation
Clears This WARNING.
F150
Battery1voltage low
Battery Voltage is
below the set value
-
F151
Battery2voltage low
Battery Voltage is
below the set value
-
F152
Low Voltage of
Battery Power
Non-Charge mode,
voltage below
shutdown voltage
-
184
Troubleshooting
recommendation
fault
code
fault name
F153
BAT1 Voltage High
-
-
F154
Battery2voltageHigh
-
-
PV String is shortcircuited to ground
with Protection.
2. The environment
of PV
StringInstallation is
consistently humid
with poor line-toground insulation.
1. Check the impedance
between PV String and
ground. If a short circuit is
found, rectify the short
circuit point.
2. Check whether the PE
cable of the Inverter is
properly connected.
3. If it is confirmed that the
impedance is indeed lower
than the default value
under rainy or cloudy
conditions, please reset
the "insulation
resistanceProtection
point".
F155
Online Low
Insulation
Resistance
fault cause
F156
Micro-grid Overload
Warning
Excessive input at
the backup end
Occasional occurrences
require no action; if this
alarm appears frequently,
please contact the dealer
or after-sales service
center.
F157
Manual Reset
-
-
F158
Generator Phase
Sequence Abnormal
-
-
185
fault
code
fault name
Troubleshooting
recommendation
fault cause
Multiplexed Port
Configuration
Abnormal
Reuse (Generator)
port configured as
Use the App to modify the
a microgrid or large
reuse (generator) port
load, but actually
configuration.
connected to a
generator.
F41
Generator Port
Overload
1. Off-grid side
output exceeds
the requirements
specified in the
specification.
2. Off-grid side
short circuit
3. Off-grid terminal
voltage too low
4. When used as a
high-power load
port, the load
exceeds the
specifications
stated in the
datasheet.
By verifying the data,
confirm the output
parameters such as
voltage, current, and
Power on the off-grid side
to identify the cause of the
issue.
F108
DSP Communication
Failure
-
-
F159
186
fault name
Troubleshooting
recommendation
fault cause
Check whether the
parallel communication
Parallel Comm In parallel operation, if the slave unit
harness is securely
Timeout
exceeds400No communication from the connected and verify
Shutdown
host within seconds
that there are no
duplicate slave
addresses.
One-key
shutdown and
stop
Check if the one-touch shutdown
function is enabled via the App.
Deactivate one-touch
shutdown.
Offline
Shutdown
-
-
Remote
shutdown
-
-
Child Node
Communicatio Internal Comm Abnormal
n Failure
Restart the machine and
observe whether fault is
eliminated.
DG
Abnormal communication link between
Communicatio the control board and the diesel
n Failure
generator
1. Check the link
communication harness
and observe whether
fault is eliminated.
2. Attempt to restart the
machine and observe
whether the fault is
eliminated;
3. If the fault persists
after restarting, please
contact the after-sales
service center.
Battery Over
Voltage
1. The voltage of a single cell is too
high.
2. Abnormal voltage collection line
187
fault name
fault cause
Record the fault
phenomenon, restart
the Battery, wait for a
1. Single cell voltage too low
few minutes, and
2. voltage Acquisition Line Anomaly
confirm whether the
fault disappears. If the
1. Battery Total pressure too low
problem persists after
2. Abnormal voltage collection line
restarting, please
1. Charging Current is too large, Battery contact the after-sales
current limiting is abnormal:
service center.
temperature and voltage value
suddenly change
2. Inverter response anomaly
Battery total pressure too high
2. Abnormal voltage collection line
Battery
Undervoltage
Battery
Overcurrent
Battery dischargecurrent is too large
Battery
Overtemperat
ure
1. Ambient Overtemperature
2. Temperature sensor abnormality
1. Ambient Overtemperature
2. Temperature sensor abnormality
1. Ambient temperature is too low
Battery
2. Temperature sensor abnormality
Undertempera
1. Ambient temperature is too low
ture
2. Temperature sensor abnormality
Battery
Terminal
Overtemperat
ure
Troubleshooting
recommendation
Pole temperature too high
188
fault name
Battery
Imbalance
fault cause
1. Excessive temperature difference in
different stages. Battery will impose
restrictions on Battery Power, that is,
limit the charging of Discharge current.
Therefore, this issue is generally
unlikely to occur.
2. The capacity of the battery cell
degrades, leading to excessive internal
resistance, resulting in significant
temperature rise and large
temperature differences during
Overcurrent.
3. Poor welding of battery cell tabs,
leading to excessive temperature rise in
the Overcurrent cell.
4. Temperature sampling issue;
5. Loose power cable connection
1. Inconsistent aging levels of battery
cells
2. Issues with the board chips can also
lead to excessive voltage differences in
the battery cells.
3. Imbalance issues in the battery pack
can also lead to excessive voltage
differences between cells.
4. Harness issues leading to
1. Inconsistent aging levels of battery
cells
2. Issues with the board chips can also
lead to excessive voltage differences
between battery cells.
3. Imbalance issues in the board can
also lead to excessive voltage
differences between cells.
4. Harness issue causing
189
Troubleshooting
recommendation
fault name
Insulation
Resistance
Pre-charging
Failurefault
fault cause
Troubleshooting
recommendation
Insulation resistance failure
Check if the ground wire
is properly connected
and restart the Battery.
If the issue persists after
restarting, please
contact the after-sales
service center.
Pre-charging Failure
It indicates that during
the precharge process,
the voltage across the
precharge MOS always
exceeds the specified
threshold. After
restarting the system,
observe whether this
fault persists, and check
whether the wiring is
correct and whether the
precharge MOS is
damaged.
Collection line Battery is disconnected
or broken
Check the wiring and
restart the Battery. If
the issue persists after
restarting, please
contact the after-sales
service center.
Harvesting
line
Single voltage collection line poor
contact or disconnected
Single cell temperature acquisition line
poor contact or disconnected
Dual-channel current comparison error
is too large, or current acquisition line
circuit is abnormal.
190
Check the wiring and
restart the Battery. If
the issue persists after
restarting, please
contact the after-sales
service center.
fault name
fault cause
Troubleshooting
recommendation
Dual-channel voltage comparison error
is too large, or the comparison error
between MCU and AFE voltage is too
large, or the voltage acquisition line
loop is abnormal.
Temperature acquisition line circuit
abnormal or poor contact, disconnected
Relay or
MOSFET
overtemperat
ure
Shunt Overtemperature
Overvoltage level 5 or overtemperature
level 5, fuse the three-terminal fuse
To replace the threesection fuse, please
contact the after-sales
service center to replace
the main control board.
Relay or MOSFET overtemperature
The fault indicates that
the MOSFET
temperature has
exceeded the specified
threshold. Power off
and let it stand for 2
hours to allow
temperature recovery.
Shunt Over-temperature
The fault indicates that
the shunt tube
temperature has
exceeded the specified
threshold. Power off
and allow it to stand for
2 hours to wait for
temperature recovery.
191
fault name
BMS1 Other
fault1
(Residential
Storage
Category)
fault cause
Troubleshooting
recommendation
Relay or MOS open circuit
1. Upgrade the
software, power off and
let it sit for 5 minutes,
then check if fault
persists after restarting.
2. If the issue persists,
replace the Battery
package.
Relay or MOSFET short circuit
1. Upgrade the
software, power off and
let it sit for 5 minutes,
then check if fault
persists after restarting.
2. If the issue persists,
replace the Battery
package.
Communication abnormality between
the master cluster and slave cluster, or
inconsistency of battery cells between
clusters.
1. Check the Battery
information and
software version of the
slave unit, as well as
whether the
communication line
connection with the
master unit is normal.
2. Upgrade the software
Abnormal circuit harness in Battery
system, resulting in no loop formation
in interlocking signal
Check if Terminal
resistorInstallation is
correct
192
fault name
fault cause
Abnormal communication between
BMS and PCS
Troubleshooting
recommendation
1. Verify that the
communication line
interface definition
between Inverter and
Battery is correct.
2. Please contact the
after-sales service
center to check the
backend data and verify
whether the Inverter
and Battery software
are correctly matched.
Abnormal communication harness
between BMS master and slave control
Communication loss between main and
auxiliary chips
Circuit breaker, shunt trip abnormality
193
1. Check the wiring and
restart the Battery;
2. Upgrade the Battery.
If the issue persists after
restarting, please
contact the after-sales
service center.
Let the system stand
powered off for 5
minutes, then restart
and check if fault
persists.
2. Check whether the
blind mating connectors
and communication pins
at the bottom of the
PACK and PCU are loose
or misaligned.
fault name
fault cause
Troubleshooting
recommendation
Upgrade the software
and restart the Battery.
If the issue persists after
restarting, contact the
after-sales service
center.
MCU self-test failed
1. Upgrade the software
1. The software version is too low or the and observe whether
BMS board is damaged.
fault persists.
2. The number of Inverter parallel units 2. In the case of parallel
is large, and the Battery experiences
operation, perform a
excessive impact during pre-charging.
black start on Battery
before starting Inverter.
Internal fault of MCU
Upgrade the software
and restart the Battery.
Typically, this issue is
caused by a damaged
MCU or external
component. If the
problem persists after
restarting, please
contact the after-sales
service center.
Total control current exceeds the
specified threshold
1. Let the system stand
idle for 5 minutes,
then restart and check
if fault persists.
2. Check if the Inverter is
set with an excessively
large Power, causing
it to exceed the bus
load.
194
fault name
Air
Conditioner
Failure
fault cause
Troubleshooting
recommendation
Cell inconsistency in parallel clusters
Confirm whether the
cells in the cluster
Battery are consistent.
Cluster Battery reverse polarity of
positive and negative terminals
Check whether the
positive and negative
terminals of the string
combiner Battery are
reversed.
Severe overheating or overvoltage
triggers the fire protection system.
Contact the after-sales
service center.
Abnormal failure of air conditioning
Try restarting the
system. If the fault
persists, please contact
the after-sales service
center.
Cabinet door not closed
Check whether the
cabinet door is properly
closed.
Power supply voltage overvoltage
Insufficient power supply
No voltage input
Unstable power supply voltage
Compressor instability
Sensor poor contact or damaged
Abnormal air conditioning fan
195
Verify that the power
supply voltage value
meets the air
conditioning input
voltage requirements,
and proceed with repower on only after
confirmation.
Try restarting the
system. If the fault
persists, please contact
the after-sales service
center.
fault name
fault cause
BMS1 Other
fault2
(Residential
Storage
Category)
There is an internal voltage or current
abnormality in the DCDC.
DCDCOverload or heat sink
temperature too high
Troubleshooting
recommendation
Please refer to the
specific DC Failure
content.
Abnormal cell acquisition or
inconsistent aging levels
Please contact the aftersales service center.
Fan operation not executed properly
Please contact the aftersales service center.
1. Battery Shut down,
check the wiring and
output port screw status
2. After confirmation,
Output port screw loose or poor contact restart the Battery and
observe whether the
fault persists. If it does,
please contact the aftersales service center.
Battery has been used for too long or
the battery cell is severely damaged.
Please contact the aftersales service center to
replace the pack.
The software version is too low or the
BMS board is damaged.
2. A large number of Inverter parallel
units result in excessive impact during
Battery pre-charging.
Upgrade the software
and observe whether
fault persists.
2. In the case of parallel
operation, perform a
black start on Battery
first, then start Inverter.
Heating film damaged
Please contact the aftersales service center.
196
fault name
fault cause
Troubleshooting
recommendation
The three-terminal fuse of the heating
film is blown, rendering the heating
function unusable.
Please contact the aftersales service center.
Software model, Cell Type, and
hardware model mismatch.
Check whether the
software model, serial
number (SN), Cell Type,
and hardware model are
consistent. If they are
inconsistent, please
contact the after-sales
service center.
Thermal management board
communication disconnection
Let the system stand
powered off for 5
minutes, then restart to
check if fault persists.
2. If the fault is not
restored, contact aftersales service to replace
the pack.
Thermal management board
communication disconnection
Let the system stand
powered off for 5
minutes, then restart
and check if fault
persists.
2. If the fault is not
restored, contact aftersales service to replace
the pack.
197
fault name
fault cause
Troubleshooting
recommendation
Thermal management board
communication disconnection
Let the system stand
powered off for 5
minutes, then restart
and check if fault
persists.
2. If the fault is not
restored, contact aftersales service to replace
the pack.
pack fan fault signal trigger
Let the system stand
powered off for 5
minutes, then restart
and check if fault
persists.
2. If the fault is not
restored, contact aftersales service to replace
the pack.
Output portvoltage too high
Check the output
portvoltage. If the
output portvoltage is
normal and the fault still
cannot be resolved after
restarting Battery,
please contact the aftersales service center.
DC combiner
box
198
fault name
fault cause
Troubleshooting
recommendation
Stop Charge and
Discharge until SOC
drops below 90% or
The DCDC module detected that the
remains idle for 2 hours.
Battery Voltage exceeded the maximum If the issue persists and
Charge voltage.
restarting fault does not
resolve it, please contact
the after-sales service
center.
Radiator temperature too high
Let it stand for 1 hour
until the radiator
temperature decreases.
If the issue persists and
restarting the fault does
not resolve it, please
contact the after-sales
service center.
Battery dischargecurrent is too large
Check if the load
exceeds the Battery's
Discharge capability.
Turn off the load or stop
the PCS for 60 seconds.
If the issue persists after
restarting fault, please
contact the after-sales
service center.
Turn off the Battery
Output port power harness positive and manual switch, check if
negative poles are reversed with the
the output port wiring is
combiner box Battery or PCS.
correct, and restart the
Battery.
199
fault name
Battery Rack
Circulating
Current
Failure
Troubleshooting
recommendation
fault cause
The output Power relay cannot close.
Check whether the
output port wiring is
correct and if there is a
short circuit. If the issue
persists after restarting
fault, please contact the
after-sales service
center.
Power device temperature too high
Let the Battery stand for
1 hour to allow the
internal Power
components of the
Battery to cool down. If
the issue persists and
restarting the fault does
not resolve it, please
contact the after-sales
service center.
Relay sticking
Restart fault still exists.
Please contact the aftersales service center.
1. Cell imbalance
2. First power on undercharge
correction
-
200
fault name
BMS1 Other
fault3 (Large
Storage
Category)
fault cause
Troubleshooting
recommendation
Communication exception with Linux
module
1. Check if the
communication link is
functioning properly.
2. Upgrade the
software, restart the
Battery, and observe
whether the fault
persists. If it does,
please contact the aftersales service center.
Excessive temperature rise of the
battery cell
Abnormal battery cell,
contact after-sales
service to replace the
pack.
SOC below 10%
Perform Charge on
Battery.
SN writing does not comply with the
rules
Check whether the SN
digits are normal. If
abnormal, please
contact the after-sales
service center.
1. Battery Intra-cluster daisy chain
communication anomaly
2. Inconsistent aging levels of battery
cells within Battery clusters
1. Check the contact
condition of a single
Battery pack.
2. Confirm the usage of
each cluster Battery,
such as cumulative
charge Discharge
capacity, number of
cycles, etc.
3. Please contact the
after-sales service
center.
201
fault name
Troubleshooting
recommendation
fault cause
Excessive Humidity within the pack
-
Fuse blown
Contact after-sales
service to replace the
pack.
Low battery power
Perform Charge on
Battery.
Circuit breaker anomaly
Contact after-sales
service to replace the
pack.
External device abnormality
Contact after-sales
service to replace the
pack.
Contactor
Failure 1
-
-
Contactor
Failure 2
-
-
Jinggui
Continuous Overload (over 690KVA) for
10s
Please contact the aftersales service center.
BMS1 Other
fault4 (Large
Storage
Category)
OverloadProte
Continuous Overload (exceeding
ction(Smart
690kVA) for 10s
port
Please contact the aftersales service center.
Master AC On
Meter Comm
Error
1. The meter may not be connected to
the host.
2. Possible loose communication cable
of the electric meter.
1. Check if the meter is
connected to the main
unit.
2. Check if the meter
communication cable is
loose.
Parallel Slave
Meter Error
The meter is connected to the slave
unit.
The meter connection
machine is set as the
master unit.
202
fault name
Slave AC On
Timeout with
Master
fault cause
1. Incorrect slave address setting
2. Slave communication line is loose
Troubleshooting
recommendation
1. Check if the slave
address is duplicated.
2. Check if the parallel
communication cable is
loose.
8.5.2.2 Battery Fault
No.
1
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1 Total
voltage is too high
warning
1. Battery system
voltage is too high.
2. Voltage
acquisition line is
abnormal.
1. Discharge the battery and
observe if the fault persists.
2. If the fault does not
recover, contact the aftersales service center.
203
No.
2
3
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1 Total
voltage is too low
warning
1. Battery system
voltage is too low.
2. Voltage
acquisition line is
abnormal.
1. Charge the battery, let it
rest, and observe if the fault
persists.
2. Check the inverter's
working condition to see if it
is not charging the battery
due to issues like working
mode. Try charging the
battery via the inverter and
observe if the fault recovers.
3. If the fault does not
recover, contact the aftersales service center.
BMS1 RACK1 Cell
voltage is too high
warning
1. Single cell voltage
is too high.
2. Voltage
acquisition line is
abnormal.
1. Discharge the battery, let it
rest, and observe if the fault
persists.
2. If the fault does not
recover, contact the aftersales service center.
204
No.
4
5
Fault Name
BMS1 RACK1 Cell
voltage is too low
warning
BMS1 RACK1
Charging
temperature is too
high warning
Fault Cause
Fault Handling Suggestion
1. Single cell voltage
is too low.
2. Voltage
acquisition line is
abnormal.
1. Charge the battery, let it
rest, and observe if the fault
persists.
2. Check the inverter's
working condition to see if it
is not charging the battery
due to issues like working
mode. Try charging the
battery via the inverter and
observe if the fault recovers.
3. If the fault does not
recover, contact after-sales.
1. Ambient
Overtemperature
2. Temperature
sensor is abnormal.
1. Stop charging/discharging,
let it rest, and observe if the
fault persists.
2. If the fault does not
recover, contact the aftersales service center.
205
No.
Fault Name
Fault Cause
Fault Handling Suggestion
6
BMS1 RACK1
Discharging
temperature is too
high warning
1. Ambient
Overtemperature
2. Temperature
sensor is abnormal.
1. Stop charging/discharging,
let it rest, and observe if the
fault persists.
2. If the fault does not
recover, contact after-sales.
1. Ambient
temperature is too
low.
2. Temperature
sensor is abnormal.
1. Check the cell temperature
in the background. If the
minimum temperature is
above -20°C, set the battery
to discharge to increase the
cell temperature.
2. If the temperature is below
-20°C, power off the battery
and place it in a warm
environment. Use it after the
cell temperature rises.
3. If none of the above works,
contact the after-sales service
center.
7
BMS1 RACK1
Charging
temperature is too
low warning
206
No.
8
9
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1
Discharging
temperature is too
low warning
1. Ambient
temperature is too
low.
2. Temperature
sensor is abnormal.
1. Check the cell temperature
in the background. If the
minimum temperature is
above -20°C, set the battery
to discharge to increase the
cell temperature.
2. If the temperature is below
-20°C, power off the battery
and place it in a warm
environment. Use it after the
cell temperature rises.
3. If none of the above works,
contact the after-sales service
center.
BMS1 RACK1 Charge
overcurrent warning
1. Charging current
is too high, battery
current limiting is
abnormal: sudden
changes in
temperature and
voltage values.
2. Inverter response
is abnormal.
1. Stop charging, let it rest,
and observe if the fault
persists.
2. Check if the inverter is set
to a power output that
exceeds the battery's rated
operating current.
3. If overcurrent persists,
contact the after-sales service
center.
207
No.
10
11
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1
Discharge
overcurrent warning
1. Discharging
current is too high,
battery current
limiting is abnormal:
sudden changes in
temperature and
voltage values.
2. Inverter response
is abnormal.
1. Stop discharging, let it rest,
and observe if the fault
persists.
2. Check if the inverter is set
to a power output that
exceeds the battery's rated
operating current.
3. If overcurrent persists,
contact the after-sales service
center.
BMS1 RACK1
Insulation resistance
is too low warning
Check if the ground wire is
properly connected, restart
Insulation resistance
the battery. If the problem
is damaged or
persists after restarting,
contact is abnormal.
please contact the after-sales
service center.
208
No.
12
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1 Cell
excessive
temperature
differentials warning
1. At different stages
of excessive
temperature
differential, the
battery will limit the
battery power, i.e.,
limit the
charge/discharge
current. Therefore,
this problem is
generally difficult to
occur.
2. Cell capacity
degradation leads to
excessive internal
resistance, causing
large temperature
rise during
overcurrent,
resulting in large
temperature
differential.
3. Poor welding of
cell tabs leads to
rapid cell
temperature rise
during overcurrent.
4. Temperature
sampling issue.
5. Power line
connection is loose.
Power off, restart the battery,
wait for 2 hours. If the
problem is not resolved,
contact the after-sales service
center.
209
No.
Fault Cause
Fault Handling Suggestion
BMS1 RACK1 Post
temperature is too
high warning
Post temperature is
too high.
1. Stop charging/discharging,
let it rest, and observe if the
fault persists.
2. If the fault does not
recover, contact the aftersales service center.
14
BMS1 RACK1 Cell
excessive voltage
differentials warning
1. Inconsistent cell
aging levels.
2. Issues with the
slave board chip can
also cause excessive
cell voltage
differential.
3. Slave board
balancing issues can
also cause excessive
cell voltage
differential.
4. Caused by wiring
harness issues.
1. Stop charging/discharging,
let it rest, and observe if the
fault persists.
2. If the fault does not
recover, contact the aftersales service center.
15
BMS1 RACK1 PCS
communication loss
warning
Communication
between BMS and
PCS is abnormal.
Check if the communication
cable connection between the
battery and the inverter is
intact.
16
BMS1 RACK1 DCDC
warning
Internal voltage or
current abnormality
exists in the DCDC.
Upgrade the software, restart
the battery. If the problem
persists after restarting,
please contact the after-sales
service center.
17
BMS1 RACK1 Heat
film MOS adhesion
warning
Heating film MOS is
damaged.
Please contact the after-sales
service center.
13
Fault Name
210
No.
Fault Name
Fault Cause
Fault Handling Suggestion
18
BMS1 RACK1 Heat
film MOS open
warning
Heating circuit is
abnormal.
Please contact the after-sales
service center.
BMS1 RACK1 Total
voltage is too high
fault
1. Battery system
voltage is too high.
2. Voltage
acquisition line is
abnormal.
1. Discharge the battery and
observe if the fault persists.
2. If the fault does not
recover, please contact the
after-sales service center.
BMS1 RACK1 Total
voltage is too low
fault
1. Battery system
voltage is too low.
2. Voltage
acquisition line is
abnormal.
1. Charge the battery, let it
rest, and observe if the fault
persists.
2. Check the inverter's
working condition to see if it
is not charging the battery
due to issues like working
mode. Try charging the
battery via the inverter and
observe if the fault recovers.
3. If the fault does not
recover, please contact the
after-sales service center.
BMS1 RACK1 Cell
voltage is too high
fault
1. Single cell voltage
is too high.
2. Voltage
acquisition line is
abnormal.
1. Discharge the battery, let it
rest, and observe if the fault
persists.
2. If the fault does not
recover, please contact the
after-sales service center.
19
20
21
211
No.
22
23
Fault Name
BMS1 RACK1 Cell
voltage is too low
fault
BMS1 RACK1
Charging
temperature is too
high fault
Fault Cause
Fault Handling Suggestion
1. Single cell voltage
is too low.
2. Voltage
acquisition line is
abnormal.
1. Charge the battery, let it
rest, and observe if the fault
persists.
2. Check the inverter's
working condition to see if it
is not charging the battery
due to issues like working
mode. Try charging the
battery via the inverter and
observe if the fault recovers.
3. If the fault does not
recover, please contact the
after-sales service center.
1. Ambient
Overtemperature
2. Temperature
sensor is abnormal.
1. Place the battery in a cool
place, power it off and let it
rest for 30 minutes, then
restart and observe if the
fault persists.
2. If the fault persists, please
contact the after-sales service
center.
212
No.
24
25
Fault Name
BMS1 RACK1
Discharging
temperature is too
high fault
BMS1 RACK1
Charging
temperature is too
low fault
Fault Cause
Fault Handling Suggestion
1. Ambient
Overtemperature
2. Temperature
sensor is abnormal.
1. Place the battery in a cool
place, power it off and let it
rest for 30 minutes, then
restart and observe if the
fault persists.
2. If the fault persists, please
contact the after-sales service
center.
1. Ambient
temperature is too
low.
2. Temperature
sensor is abnormal.
1. Check the cell temperature
in the background. If the
minimum temperature is
above -20°C, set the battery
to discharge to increase the
cell temperature.
2. If the temperature is below
-20°C, power off the battery
and place it in a warm
environment. Use it after the
cell temperature rises.
3. If none of the above works,
contact the after-sales service
center.
213
No.
26
27
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1
Discharging
temperature is too
low fault
1. Ambient
temperature is too
low.
2. Temperature
sensor is abnormal.
1. Check the cell temperature
in the background. If the
minimum temperature is
above -20°C, set the battery
to discharge to increase the
cell temperature.
2. If the temperature is below
-20°C, power off the battery
and place it in a warm
environment. Use it after the
cell temperature rises.
3. If none of the above works,
contact the after-sales service
center.
BMS1 RACK1 Charge
overcurrent fault
1. Charging current
is too high, battery
current limiting is
abnormal: sudden
changes in
temperature and
voltage values.
2. Inverter response
is abnormal.
1. Power off and let it rest for
5 minutes, restart and
observe if the fault persists.
2. Check if the inverter is set
to a power output that
exceeds the battery's rated
operating current.
3. If overcurrent persists,
contact the after-sales service
center.
214
No.
28
29
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1
Discharge
overcurrent fault
1. Discharging
current is too high,
battery current
limiting is abnormal:
sudden changes in
temperature and
voltage values.
2. Inverter response
is abnormal.
1. Power off and let it rest for
5 minutes, restart and
observe if the fault persists.
2. Check if the inverter is set
to a power output that
exceeds the battery's rated
operating current.
3. If overcurrent persists,
contact the after-sales service
center.
BMS1 RACK1
Insulation resistance
is too low fault
1. Check if the ground wire is
properly connected, restart
Insulation resistance the battery.
is damaged or
2. Upgrade the software. If
contact is abnormal. the problem persists, please
contact the after-sales service
center.
215
No.
30
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1 Cell
excessive
temperature
differentials fault
1. At different stages
of excessive
temperature
differential, the
battery will limit the
battery power, i.e.,
limit the
charge/discharge
current. Therefore,
this problem is
generally difficult to
occur.
2. Cell capacity
degradation leads to
excessive internal
resistance, causing
large temperature
rise during
overcurrent,
resulting in large
temperature
differential.
3. Poor welding of
cell tabs leads to
rapid cell
temperature rise
during overcurrent.
4. Temperature
sampling issue.
5. Power line
connection is loose.
Power off, restart the battery,
wait for 2 hours. If the
problem is not resolved,
contact the after-sales service
center.
216
No.
31
32
33
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1 Post
temperature is too
high fault
Post temperature is
too high.
1. Power off and let it rest for
30 minutes, restart and
observe if the fault persists.
2. If the fault persists, please
contact the after-sales service
center.
BMS1 RACK1 Cell
excessive voltage
differentials fault
1. Inconsistent cell
aging levels.
2. Issues with the
slave board chip can
also cause excessive
cell voltage
differential.
3. Slave board
balancing issues can
also cause excessive
cell voltage
differential.
4. Caused by wiring
harness issues.
Power off, restart the battery,
wait for 2 hours. If the
problem is not resolved,
contact the after-sales service
center.
MOS short-circuit.
1. Upgrade the software,
power off and let it rest for 5
minutes, restart and observe
if the fault persists.
2. If it persists, contact the
after-sales service center.
BMS1 RACK1 Relay or
MOS short-circuit
fault
217
No.
34
35
36
37
Fault Name
Fault Cause
Fault Handling Suggestion
MOS open-circuit.
1. Upgrade the software,
power off and let it rest for 5
minutes, restart and observe
if the fault persists.
2. If it persists, contact the
after-sales service center.
BMS1 RACK1 The
precharge failed fault
The voltage across
the precharge MOS
always exceeds the
specified threshold.
1. Upgrade the software,
power off and let it rest for 5
minutes, restart and observe
if the fault persists.
2. If it persists, contact the
after-sales service center.
BMS1 RACK1
Acquisition line fault
Battery acquisition
line has poor
contact or is
disconnected.
Power off, check the wiring,
restack the battery. If the
problem persists after
restarting, please contact the
after-sales service center.
Relay or MOS
overtemperature.
1. Upgrade the software,
power off and let it rest for 30
minutes, restart and observe
if the fault persists.
2. If it persists, contact the
after-sales service center.
BMS1 RACK1 Relay or
MOS open-circuit
fault
BMS1 RACK1 Relay or
MOS temperature is
too high fault
218
No.
38
39
40
41
Fault Name
Fault Cause
Fault Handling Suggestion
Diverter
overtemperature.
1. Upgrade the software,
power off and let it rest for 30
minutes, restart and observe
if the fault persists.
2. If it persists, contact the
after-sales service center.
BMS1 RACK1 Slave
MCU communication
fault
Communication loss
between master and
slave chips.
1. Check the wiring, restart
the battery.
2. Upgrade the battery. If the
problem persists after
restarting, please contact the
after-sales service center.
BMS1 RACK1 BMU
communication fault
1. Check the wiring, restart
the battery.
BMS master and
2. Upgrade the battery. If the
slave control wiring
problem persists after
harness is abnormal.
restarting, please contact the
after-sales service center.
BMS1 RACK1 Microelectronics fault
Upgrade the software, restart
the battery. If the problem
persists after restarting,
please contact the after-sales
service center.
BMS1 RACK1 Diverter
temperature is too
high fault
Internal MCU fault.
219
No.
42
43
44
45
46
Fault Name
Fault Cause
Fault Handling Suggestion
BMS1 RACK1
Hardware
overcurrent fault
1. Software version
is too low or BMS
board is damaged.
2. Large number of
parallel inverters,
causing excessive
inrush current
during battery
precharge.
1. Upgrade the software,
observe if the fault persists.
2. In case of parallel
operation, start the battery
with a black start first, then
start the inverter.
BMS1 RACK1
Application software
fault
MCU self-test failed.
Upgrade the software, restart
the battery. If the problem
persists after restarting,
please contact the after-sales
service center.
BMS1 RACK1 Parallel
RACK fault
Communication
abnormality
between the main
RACK and slave
RACKs, or
inconsistency of cells
between RACKs.
1. Check the slave battery
information and software
version, and whether the
communication cable
connection to the master is
normal.
2. Upgrade the software.
BMS1 RACK1 DCDC
fault
DCDC overload or
heat sink
temperature is too
high, etc.
Upgrade the software, restart
the battery. If the problem
persists after restarting,
please contact the after-sales
service center.
BMS1 RACK1
Inconsistent cell fault
1. Cell identification
is abnormal.
2. Different types of
cells are stacked.
Check the cell type.
220
No.
Fault Name
Fault Cause
Fault Handling Suggestion
Output port screws
are loose or have
poor contact.
1. Power off the battery,
check the wiring and the
condition of the output port
screws.
2. After confirmation, restart
the battery, observe if the
fault persists. If it exists,
contact the after-sales service
center.
47
BMS1 RACK1 The
output port over
temperature fault
48
Battery has been
BMS1 RACK1 SOH too used for too long or
low fault
cells are severely
damaged.
Replace the pack.
49
BMS1 RACK1 Heating
film MOS Threeterminal fault
Please contact the after-sales
service center.
Heating film MOS is
damaged.
221
9 technical parameter
9.1 Inverter Parameters
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Battery Type
Li-Ion
Li-Ion
Li-Ion
Li-Ion
Nominal
Voltage (V)
750
750
750
750
Voltage Range
(V)
700-950
700-950
700-950
700-950
Start-up
Voltage (V)
720
720
720
720
Number of
Battery Inputs
1
1
1
1
Max.
Continuous
Charging
Current (A)
6.7
8.1
10.7
13.4
Max.
Continuous
Discharging
Current (A)
7.4
8.9
11.8
14.7
Max. Charging
Power (kW)
5
6
8
10
Max.
Discharging
Power (kW)
5.5
6.6
8.8
11
Battery Side
PV Side
222
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Max. Input
Power (kW)
10
12
16
20
Max. Input
Voltage (V)*1
1000
1000
1000
1000
MPPT
Operating
Voltage Range
(V)*2
120~950
120~950
120~950
120~950
MPPT Voltage
Range at
Nominal
Power (V)
185~850
225~850
300~850
250~850
Start-up
Voltage (V)
150
150
150
150
Nominal Input
Voltage (V)
750
750
750
750
Max. MPPT
Current(A)
21/21/21
21/21/21
21/21/21
21/21/21/21
Max. MPPT
Short Circuit
Current (A)
26/26/26
26/26/26
26/26/26
26/26/26/26
Number of
MPPTs
3
3
3
4
Number of
Strings per
MPPT
1/1/1
1/1/1
1/1/1
1/1/1/1
6
8
9.999
AC Side (On-Grid)
Rated Power
(kW)
5
223
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Max. Power
(kW)
5
6
8
9.999
Rated
Apparent
Power to Grid
(kVA)
5
6
8
9.999
Rated
Apparent
Power from
Grid (kVA)
5
6
8
9.999
Max. Apparent
Power to Grid
(kVA)
5
6
8
9.999
Max. Apparent
Power from
Grid (kVA)
43.5
43.5
43.5
43.5
Nominal
Voltage (V)
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
Voltage Range
(V)
180~260
(According to
local standard)
180~260
(According to
local standard)
180~260
(According to
local standard)
180~260
(According to
local standard)
Nominal Frequ
ency (Hz)
50/60
50/60
50/60
50/60
Frequency
Range (Hz)
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
Rated Current
to Grid (A)
7.6 at 380V
7.3 at 400V
9.1 at 380V
8.7 at 400V
12.2 at 380V
11.6 at 400V
15.2 at 380V
14.5 at 400V
Rated Current
fromGrid (A)
7.6 at 380V
7.3 at 400V
9.1 at 380V
8.7 at 400V
12.2 at 380V
11.6 at 400V
15.2 at 380V
14.5 at 400V
224
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Max. Current
to Grid (A)
7.6 at 380V
7.3 at 400V
9.1 at 380V
8.7 at 400V
12.2 at 380V
11.6 at 400V
15.2 at 380V
14.5 at 400V
Max. Current
from Grid (A)
63.0
63.0
63.0
63.0
Max. Output
Fault Current
(Peak and
Duration) (A)
46.7@4μs
46.7@4μs
46.7@4μs
74.6@4μs
Inrush Current
(Peak and
Duration) (A)
21.3@5ms
21.3@5ms
21.3@5ms
25.4@5ms
Power Factor
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
THDi
<3%
<3%
<3%
<3%
Maximum
Output
Overcurrent
Protection (A)
46.7
46.7
46.7
74.6
Type of
Voltage
a.c.
a.c.
a.c.
a.c.
Rated Output
Apparent
Power (kVA)
5
6
8
10
Max. Output
Apparent
Power (kVA)
Off-grid: 5.5
(10.0, 10s),
on-grid: 43.5
Off-grid:
6.6(12, 10s),
on-grid: 43.5
Off-grid: 8.8
(16.0, 10s),
on-grid: 43.5
Off-grid:
11(20.0, 10s),
on-grid: 43.5
Back-up Side
225
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Nominal
Output
Voltage (V)
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
Nominal
Output
Frequency (Hz)
50/60
50/60
50/60
50/60
Frequency
Range (Hz)
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
Rated Output
Current (A)
7.6 at 380V
7.3 at 400V
9.1 at 380V
8.7 at 400V
12.2 at 380V
11.6 at 400V
15.2 at 380V
14.5 at 400V
Max. Output
Current (A)*3
Off-grid: 11.4,
on-grid: 63
Off-grid: 13.7,
on-grid:63
Off-grid: 18.2,
on-grid: 63
Off-grid: 22.8,
on-grid:63
Max. Output
Fault Current
(Peak and
Duration) (A)
46.7@4μs
46.7@4μs
46.7@4μs
74.6@4μs
Inrush Current
(Peak and
Duration) (A)
21.3@5ms
21.3@5ms
21.3@5ms
25.4@5ms
Maximum
Overcurrent
Protection (A)
46.7
46.7
46.7
74.6
THDv (@Linear
Load)
<3%
<3%
<3%
<3%
On/Off-grid
Switching
Time(ms)
<4
<4
<4
<4
98.00%
98.00%
98.00%
98.10%
Efficiency
Max. Efficiency
226
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
European
Efficiency
96.40%
96.90%
97.10%
97.20%
Max. Battery
to AC
Efficiency
98.00%
98.00%
98.00%
98.00%
PV String
Current
Monitoring
Integrated
Integrated
Integrated
Integrated
PV Insulation
Resistance
Detection
Integrated
Integrated
Integrated
Integrated
Residual
Current
Monitoring
Integrated
Integrated
Integrated
Integrated
PV Reverse
Polarity
Protection
Integrated
Integrated
Integrated
Integrated
Battery
Reverse
Polarity
Protection
Integrated
Integrated
Integrated
Integrated
Anti-islanding
Protection
Integrated
Integrated
Integrated
Integrated
AC
Overcurrent
Protection
Integrated
Integrated
Integrated
Integrated
AC Short
Circuit
Protection
Integrated
Integrated
Integrated
Integrated
Protection
227
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
AC
Overvoltage
Protection
Integrated
Integrated
Integrated
Integrated
DC Switch
Integrated
Integrated
Integrated
Integrated
DC Surge
Protection
Type II(Type
I+II optional)
Type II(Type
I+II optional)
Type II(Type
I+II optional)
Type II(Type
I+II optional)
AC Surge
Protection
Type II
Type II
Type II
Type II
Rapid
Shutdown
Optional
Optional
Optional
Optional
AFCI
Optional
Optional
Optional
Optional
Remote
Shutdown
Integrated
Integrated
Integrated
Integrated
Operating
Temperature
Range (℃)
-35~+60
-35~+60
-35~+60
-35~+60
Operating
Environment
Indoor/Outdo
or
Indoor/Outdo
or
Indoor/Outdo
or
Indoor/Outdo
or
Relative
Humidity
0~100%
0~100%
0~100%
0~100%
Max.
Operating
Altitude (m)
4000 (>2000
derating)
4000 (>2000
derating)
4000 (>2000
derating)
4000 (>2000
derating)
Cooling
Method
Smart Fan
Cooling
Smart Fan
Cooling
Smart Fan
Cooling
Smart Fan
Cooling
User Interface
LED,
WLAN+APP
LED,
WLAN+APP
LED,
WLAN+APP
LED,
WLAN+APP
General Data
228
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Communicatio
n with BMS
CAN
CAN
CAN
CAN
Communicatio
n
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
Communicatio
n Protocols
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Weight (kg)
34
34
34
34
Dimension
(W×H×D mm)
800*340*270
800*340*270
800*340*270
800*340*270
Noise Emission
≤35
(dB)
≤35
≤35
≤40
Topology
Non-isolated
Non-isolated
Non-isolated
Non-isolated
Selfconsumption
at Night (W)
≤10
≤10
≤10
≤10
Ingress
Protection
Rating
IP66
IP66
IP66
IP66
DC Connector
MC4, VACONN
Terminal
MC4, VACONN
Terminal
MC4, VACONN
Terminal
MC4, VACONN
Terminal
AC Connector
VACONN
Terminal
VACONN
Terminal
VACONN
Terminal
VACONN
Terminal
Environmental
Category
4K4H
4K4H
4K4H
4K4H
229
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
Pollution
Degree
IV
IV
IV
IV
Overvoltage
Category
DC II / AC III
DC II / AC III
DC II / AC III
DC II / AC III
Protective
Class
I
I
I
I
Storage
Temperature
(℃)
-40~+70
-40~+70
-40~+70
-40~+70
Battery: C
Battery: C
Battery: C
Battery: C
PV: C
PV: C
PV: C
PV: C
AC: C
AC: C
AC: C
AC: C
Com: A
Com: A
Com: A
Com: A
Mounting
Method
Wall/Floor
Mounted
Wall/Floor
Mounted
Wall/Floor
Mounted
Wall/Floor
Mounted
Active Antiislanding
Method
SMS(Slip-mode SMS(Slip-mode SMS(Slip-mode SMS(Slip-mode
frequency)
frequency)
frequency)
frequency)
+AFD*4
+AFD*4
+AFD*4
+AFD*4
Type of
Electrical
Supply System
three phase
three phase
three phase
three phase
Country of
Manufacture
China
China
China
China
The Decisive
Voltage Class
(DVC)
Certification
Grid Standard
Please refer to the official website
Safety
Regulation
230
Technical
Data
GW5K-ETAG20
GW6K-ETAG20
GW8K-ETAG20
GW9.999KETA-G20
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Battery Type
Li-Ion
Li-Ion
Li-Ion
Li-Ion
Nominal
Voltage (V)
750
750
750
750
Voltage Range
(V)
700-950
700-950
700-950
700-950
Start-up
Voltage (V)*1
720
720
720
720
Number of
Battery Inputs
1
1
1
1
Max.
Continuous
Charging
Current (A)
13.4
16.1
20.1
26.7
Max.
Continuous
Discharging
Current (A)
14.7
17.7
22.1
29.4
Max. Charging
Power (kW)
10
12
15
20
Max.
Discharging
Power (kW)
11
13.2
16.5
22
EMC
Technical
Data
Battery Side
PV Side
231
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Max. Input
Power (kW)
20
24
30
40
Max. Input
Voltage (V)*1
1000
1000
1000
1000
MPPT
Operating
Voltage Range
(V)*2
120~950
120~950
120~950
120~950
MPPT Voltage
Range at
Nominal
Power (V)
250~850
300~850
360~850
400~850
Start-up
Voltage (V)
150
150
150
150
Nominal Input
Voltage (V)
750
750
750
750
Max. MPPT
Current(A)
21/21/21/21
21/21/21/21
21/21/21/21
21/21/21/21
Max. MPPT
Short Circuit
Current (A)
26/26/26/26
26/26/26/26
26/26/26/26
26/26/26/26
Number of
MPPTs
4
4
4
4
Number of
Strings per
MPPT
1/1/1/1
1/1/1/1
1/1/1/1
1/1/1/1
12
15
20
AC Side (On-Grid)
Rated Power
(kW)
10
232
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Max. Power
(kW)
10
12
15
20
Rated
Apparent
Power to Grid
(kVA)
10
12
15
20
Rated
Apparent
Power from
Grid (kVA)
10
12
15
20
Max. Apparent
Power to Grid
(kVA)
10
12
15
20
Max. Apparent
Power from
Grid (kVA)
43.5
43.5
43.5
43.5
Nominal
Voltage (V)
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
Voltage Range
(V)
180~260
(According to
local standard)
180~260
(According to
local standard)
180~260
(According to
local standard)
180~260
(According to
local standard)
Nominal Frequ
ency (Hz)
50/60
50/60
50/60
50/60
Frequency
Range (Hz)
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
Rated Current
to Grid (A)
15.2 at 380V
14.5 at 400V
18.2 at 380V
17.4 at 400V
22.8 at 380V
21.8 at 400V
30.4 at 380V
29.0 at 400V
Rated Current
fromGrid (A)
15.2 at 380V
14.5 at 400V
18.2 at 380V
17.4 at 400V
22.8 at 380V
21.8 at 400V
30.4 at 380V
29.0 at 400V
233
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Max. Current
to Grid (A)
15.2 at 380V
14.5 at 400V
18.2 at 380V
17.4 at 400V
22.8 at 380V
21.8 at 400V
30.4 at 380V
29.0 at 400V
Max. Current
from Grid (A)
63.0
63.0
63.0
63.0
Max. Output
Fault Current
(Peak and
Duration) (A)
74.6@4μs
74.6@4μs
83.3@4μs
83.3@4μs
Inrush Current
(Peak and
Duration) (A)
25.4@5ms
25.4@5ms
29.1@5ms
29.1@5ms
Power Factor
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
THDi
<3%
<3%
<3%
<3%
Maximum
Output
Overcurrent
Protection (A)
74.6
74.6
83.3
83.3
Type of
Voltage
a.c.
a.c.
a.c.
a.c.
Rated Output
Apparent
Power (kVA)
10
12
15
20
Max. Output
Apparent
Power (kVA)
Off-grid:
11(20.0, 10s),
on-grid: 43.5
Off-grid:
13.2(24, 10s),
on-grid: 43.5
Off-grid:
16.5(30, 10s),
on-grid:43.5
Off-grid:
22(30.0, 10s),
on-grid:43.5
Back-up Side
234
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Nominal
Output
Voltage (V)
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
220/380,
230/400,
3L/N/PE
Nominal
Output
Frequency (Hz)
50/60
50/60
50/60
50/60
Frequency
Range (Hz)
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
Rated Output
Current (A)
15.2 at 380V
14.5 at 400V
18.2 at 380V
17.4 at 400V
22.8 at 380V
21.8 at 400V
30.4 at 380V
29.0 at 400V
Max. Output
Current (A)*3
Off-grid: 22.8,
on-grid: 63
Off-grid: 27.3,
on-grid: 63
Off-grid: 33.4,
on-grid: 63
Off-grid: 33.4,
on-grid: 63
Max. Output
Fault Current
(Peak and
Duration) (A)
74.6@4μs
74.6@4μs
83.3@4μs
83.3@4μs
Inrush Current
(Peak and
Duration) (A)
25.4@5ms
25.4@5ms
29.1@5ms
29.1@5ms
Maximum
Overcurrent
Protection (A)
74.6
74.6
83.3
83.3
THDv (@Linear
Load)
<3%
<3%
<3%
<3%
On/Off-grid
Switching
Time(ms)
<4
<4
<4
<4
98.10%
98.10%
98.10%
98.10%
Efficiency
Max. Efficiency
235
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
European
Efficiency
97.20%
97.20%
97.30%
97.30%
Max. Battery
to AC
Efficiency
98.00%
98.00%
98.00%
98.00%
PV String
Current
Monitoring
Integrated
Integrated
Integrated
Integrated
PV Insulation
Resistance
Detection
Integrated
Integrated
Integrated
Integrated
Residual
Current
Monitoring
Integrated
Integrated
Integrated
Integrated
PV Reverse
Polarity
Protection
Integrated
Integrated
Integrated
Integrated
Battery
Reverse
Polarity
Protection
Integrated
Integrated
Integrated
Integrated
Anti-islanding
Protection
Integrated
Integrated
Integrated
Integrated
AC
Overcurrent
Protection
Integrated
Integrated
Integrated
Integrated
AC Short
Circuit
Protection
Integrated
Integrated
Integrated
Integrated
Protection
236
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
AC
Overvoltage
Protection
Integrated
Integrated
Integrated
Integrated
DC Switch
Integrated
Integrated
Integrated
Integrated
DC Surge
Protection
Type II(Type
I+II optional)
Type II(Type
I+II optional)
Type II(Type
I+II optional)
Type II(Type
I+II optional)
AC Surge
Protection
Type II
Type II
Type II
Type II
Rapid
Shutdown
Optional
Optional
Optional
Optional
AFCI
Optional
Optional
Optional
Optional
Remote
Shutdown
Integrated
Integrated
Integrated
Integrated
Operating
Temperature
Range (℃)
-35~+60
-35~+60
-35~+60
-35~+60
Operating
Environment
Indoor/Outdo
or
Indoor/Outdo
or
Indoor/Outdo
or
Indoor/Outdo
or
Relative
Humidity
0~100%
0~100%
0~100%
0~100%
Max.
Operating
Altitude (m)
4000 (>2000
derating)
4000 (>2000
derating)
4000 (>2000
derating)
4000 (>2000
derating)
Cooling
Method
Smart Fan
Cooling
Smart Fan
Cooling
Smart Fan
Cooling
Smart Fan
Cooling
User Interface
LED,
WLAN+APP
LED,
WLAN+APP
LED,
WLAN+APP
LED,
WLAN+APP
General Data
237
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Communicatio
n with BMS
CAN
CAN
CAN
CAN
Communicatio
n
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
RS485,
WiFi+LAN+Blue
tooth,
4G+Bluetooth(
Optional)
Communicatio
n Protocols
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Weight (kg)
34
34
34
34
Dimension
(W×H×D mm)
800*340*270
800*340*270
800*340*270
800*340*270
Noise Emission
≤40
(dB)
≤40
≤40
≤40
Topology
Non-isolated
Non-isolated
Non-isolated
Non-isolated
Selfconsumption
at Night (W)
≤10
≤10
≤10
≤10
Ingress
Protection
Rating
IP66
IP66
IP66
IP66
DC Connector
MC4, VACONN
Terminal
MC4, VACONN
Terminal
MC4, VACONN
Terminal
MC4, VACONN
Terminal
AC Connector
VACONN
Terminal
VACONN
Terminal
VACONN
Terminal
VACONN
Terminal
Environmental
Category
4K4H
4K4H
4K4H
4K4H
238
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
Pollution
Degree
IV
IV
IV
IV
Overvoltage
Category
DC II / AC III
DC II / AC III
DC II / AC III
DC II / AC III
Protective
Class
I
I
I
I
Storage
Temperature
(℃)
-40~+70
-40~+70
-40~+70
-40~+70
Battery: C
Battery: C
Battery: C
Battery: C
PV: C
PV: C
PV: C
PV: C
AC: C
AC: C
AC: C
AC: C
Com: A
Com: A
Com: A
Com: A
Mounting
Method
Wall/Floor
Mounted
Wall/Floor
Mounted
Wall/Floor
Mounted
Wall/Floor
Mounted
Active Antiislanding
Method
SMS(Slip-mode SMS(Slip-mode SMS(Slip-mode SMS(Slip-mode
frequency)
frequency)
frequency)
frequency)
+AFD*4
+AFD*4
+AFD*4
+AFD*4
Type of
Electrical
Supply System
three phase
three phase
three phase
three phase
Country of
Manufacture
China
China
China
China
The Decisive
Voltage Class
(DVC)
Certification
Grid Standard
Please refer to the official website
Safety
Regulation
239
Technical
Data
GW10K-ETAG20
GW12K-ETAG20
GW15K-ETAG20
GW20K-ETAG20
EMC
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Battery Type
Li-Ion
Li-Ion
Li-Ion
Nominal Voltage
(V)
750
750
750
Voltage Range (V)
700-950
700-950
700-950
Start-up Voltage (V) 720
720
720
Number of Battery
Inputs
1
1
1
Max. Continuous
Charging Current
(A)
33.3
40.0
40.0
Max. Continuous
Discharging
Current (A)
36.7
44.1
44.1
Max. Charging
Power (kW)
25
30
30
Max. Discharging
Power (kW)
27.5
33
33
Max. Input Power
(kW)
50
60
60
Max. Input Voltage
(V)*1
1000
1000
1000
Technical Data
Battery Side
PV Side
240
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
MPPT Operating
Voltage Range
(V)*2
120~950
120~950
120~950
MPPT Voltage
Range at Nominal
Power (V)
400~850
450~850
450~850
Start-up Voltage (V) 150
150
150
Nominal Input
Voltage (V)
750
750
750
Max. MPPT
Current(A)
21/21/42/42
21/21/42/42
21/21/42/42
Max. MPPT Short
Circuit Current (A)
26/26/52/52
26/26/52/52
26/26/52/52
Number of MPPTs
4
4
4
Number of Strings
per MPPT
1/1/2/2
1/1/2/2
1/1/2/2
Rated Power (kW)
25
29.999
30
Max. Power (kW)
25
29.999
30
Rated Apparent
25
Power to Grid (kVA)
29.999
30
Rated Apparent
Power from Grid
(kVA)
25
29.999
30
Max. Apparent
25
Power to Grid (kVA)
29.999
30
AC Side (On-Grid)
241
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Max. Apparent
Power from Grid
(kVA)
55.2
55.2
55.2
Nominal Voltage
(V)
220/380, 230/400,
3L/N/PE
220/380, 230/400,
3L/N/PE
220/380, 230/400,
3L/N/PE
Voltage Range (V)
180~260
(According to local
standard)
180~260
(According to local
standard)
180~260
(According to local
standard)
Nominal Frequenc
y (Hz)
50/60
50/60
50/60
Frequency Range
(Hz)
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
Rated Current
to Grid (A)
37.9 at 380V
36.3 at 400V
45.5 at 380V
43.5 at 400V
45.5 at 380V
43.5 at 400V
Rated Current
fromGrid (A)
37.9 at 380V
36.3 at 400V
45.5 at 380V
43.5 at 400V
45.5 at 380V
43.5 at 400V
Max. Current to
Grid (A)
37.9 at 380V
36.3 at 400V
45.5 at 380V
43.5 at 400V
45.5 at 380V
43.5 at 400V
Max. Current from
Grid (A)
80.0
80.0
80.0
Max. Output Fault
Current (Peak and
Duration) (A)
125@4μs
125@4μs
125@4μs
Inrush Current
(Peak and
Duration) (A)
32.3@5ms
32.3@5ms
32.3@5ms
Power Factor
0.8 leading ... 0.8
lagging
0.8 leading ... 0.8
lagging
0.8 leading ... 0.8
lagging
242
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
THDi
<3%
<3%
<3%
Maximum Output
Overcurrent
Protection (A)
125
125
125
Type of Voltage
a.c.
a.c.
a.c.
Rated Output
Apparent Power
(kVA)
25
30
30
Max. Output
Apparent Power
(kVA)
Off-grid: 27.5(45.0,
10s),
on-grid:55.2
Off-grid: 33(45.0,
10s),
on-grid: 55.2
Off-grid: 33(45.0,
10s),
on-grid:55.2
Nominal Output
Voltage (V)
220/380, 230/400,
3L/N/PE
220/380, 230/400,
3L/N/PE
220/380, 230/400,
3L/N/PE
Nominal Output
Frequency (Hz)
50/60
50/60
50/60
Frequency Range
(Hz)
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
Rated Output
Current (A)
37.9 at 380V
36.3 at 400V
45.5 at 380V
43.5 at 400V
45.5 at 380V
43.5 at 400V
Max. Output
Current (A)*3
Off-grid: 50.0,
on-grid: 80
Off-grid: 50.0,
on-grid: 80
Off-grid: 50.0,
on-grid: 80
Max. Output Fault
Current (Peak and
Duration) (A)
125@4μs
125@4μs
125@4μs
Inrush Current
(Peak and
Duration) (A)
32.3@5ms
32.3@5ms
32.3@5ms
Back-up Side
243
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Maximum
Overcurrent
Protection (A)
125
125
125
THDv (@Linear
Load)
<3%
<3%
<3%
On/Off-grid
Switching
Time(ms)
<4
<4
<4
Max. Efficiency
98.20%
98.20%
98.20%
European
Efficiency
97.40%
97.40%
97.40%
Max. Battery to AC
Efficiency
98.00%
98.00%
98.00%
PV String Current
Monitoring
Integrated
Integrated
Integrated
PV Insulation
Resistance
Detection
Integrated
Integrated
Integrated
Residual Current
Monitoring
Integrated
Integrated
Integrated
PV Reverse Polarity
Protection
Integrated
Integrated
Integrated
Battery Reverse
Polarity Protection
Integrated
Integrated
Integrated
Anti-islanding
Protection
Integrated
Integrated
Integrated
Efficiency
Protection
244
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
AC Overcurrent
Protection
Integrated
Integrated
Integrated
AC Short Circuit
Protection
Integrated
Integrated
Integrated
AC Overvoltage
Protection
Integrated
Integrated
Integrated
DC Switch
Integrated
Integrated
Integrated
DC Surge
Protection
Type II(Type I+II
optional)
Type II(Type I+II
optional)
Type II(Type I+II
optional)
AC Surge
Protection
Type II
Type II
Type II
Rapid Shutdown
Optional
Optional
Optional
AFCI
Optional
Optional
Optional
Remote Shutdown
Integrated
Integrated
Integrated
Operating
Temperature
Range (℃)
-35~+60
-35~+60
-35~+60
Operating
Environment
Indoor/Outdoor
Indoor/Outdoor
Indoor/Outdoor
Relative Humidity
0~100%
0~100%
0~100%
Max. Operating
Altitude (m)
4000 (>2000
derating)
4000 (>2000
derating)
4000 (>2000
derating)
Cooling Method
Smart Fan Cooling
Smart Fan Cooling
Smart Fan Cooling
User Interface
LED, WLAN+APP
LED, WLAN+APP
LED, WLAN+APP
General Data
245
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Communication
with BMS
CAN
CAN
CAN
Communication
RS485,
WiFi+LAN+Bluetoot
h,
4G+Bluetooth(Opti
onal)
RS485,
WiFi+LAN+Bluetoot
h,
4G+Bluetooth(Opti
onal)
RS485,
WiFi+LAN+Bluetoot
h,
4G+Bluetooth(Opti
onal)
Communication
Protocols
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Modbus-RTU,
Modbus-TCP
Weight (kg)
38
38
38
Dimension
(W×H×D mm)
800*340*270
800*340*270
800*340*270
Noise Emission
(dB)
≤45
≤45
≤45
Topology
Non-isolated
Non-isolated
Non-isolated
Self-consumption
at Night (W)
≤10
≤10
≤10
Ingress Protection
Rating
IP66
IP66
IP66
DC Connector
MC4, VACONN
Terminal
MC4, VACONN
Terminal
MC4, VACONN
Terminal
AC Connector
VACONN Terminal
VACONN Terminal
VACONN Terminal
Environmental
Category
4K4H
4K4H
4K4H
Pollution Degree
IV
IV
IV
Overvoltage
Category
DC II / AC III
DC II / AC III
DC II / AC III
246
Technical Data
GW25K-ETA-G20
GW29.999K-ETAG20
GW30K-ETA-G20
Protective Class
I
I
I
Storage
Temperature (℃)
-40~+70
-40~+70
-40~+70
Battery: C
Battery: C
Battery: C
PV: C
PV: C
AC: C
AC: C
Com: A
Com: A
Com: A
Mounting Method
Wall/Floor
Mounted
Wall/Floor
Mounted
Wall/Floor
Mounted
Active Antiislanding Method
SMS(Slip-mode
frequency) +AFD*4
SMS(Slip-mode
frequency) +AFD*4
SMS(Slip-mode
frequency) +AFD*4
Type of Electrical
Supply System
three phase
three phase
three phase
Country of
Manufacture
China
China
China
PV: C
The Decisive
Voltage Class (DVC) AC: C
Certification
Grid Standard
Safety Regulation
Please refer to the official website
EMC
*1: When the input voltage ranges from 950V to 1000V, the inverter will enter the
standby mode, and the voltage returns to950V to enter the normal operation state.
*2: Please refer to the user manual for the MPPT Voltage Range at nominal Power.
*3: The Max. Output Current in off-grid operation accounts for a three-phase
maximum 150% unbalanced capability.
*4: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with
Positive Feedback.
247
9.2 Battery Technical Data
Technical Data
Rated Energy (kWh)
Usable Energy (kWh)*1
GW5.1-BAT- GW8.3-BAT- GW5.1-BAT- GW8.3-BATD-G20
D-G20
D-G21
D-G21
5.12
8.32
5.12
8.32
5
8
5
8
LFP (LiFePO4)
Battery Type
Operating Voltage Range
(V) (single phase system)
350~550
Operating Voltage Range
(V) (three phase system)
700~950
Max. Input Current
(System) (A)
12
19
12
19
Max. Output Current
(System) (A)
13.2
21
13.2
21
Max. Input Power
(System) (kW)*2
5
8
5
8
Max. Output Power
(System) (kW)*2
5
8
5
8
Peak.Output Power
(System) (kW)*2
7.5 @10s
12 @10s
7.5 @10s
12 @10s
Charging Temperature
Range (°C)
-18~55
2~55
Discharging Temperature
Range (°C)
-20~55
-20~55
Relative Humidity
5-95%
Max. Operating Altitude
(m)
4000
248
Technical Data
GW5.1-BAT- GW8.3-BAT- GW5.1-BAT- GW8.3-BATD-G20
D-G20
D-G21
D-G21
Noise Emission (dB)
≤29
Communication
CAN
Weight (kg)
57.5±1
79±1
Dimensions (W×H×D mm)
Optional Function
Configuration
57.5±1
79±1
800*326*270
heating
/
Ingress Protection
IP66
Storage Temperature (℃)
-20 ~55
12 months (-20℃~35℃)
Max. Storage time
6 months (35℃~45℃)
Scalability
6 pcs
Mounting Method
Floor stacked / Wall-mounted
≥6000 (25±2℃, 0.5C, 90%DOD, 70%EOL)
Cycle Life
Country of Manufacture
Safety
Standard
and
EMC
Certification
Transportati
on
China
IEC62619, IEC60730,
EN62477,IEC63056,IEC62040,CE, CEC, VDE2510
CE, RCM
UN38.3 ADR
*1: Test conditions, 100% DOD (cell 2.85~3.6V voltage range), 0.2P charge &
discharge at 25±2 °C for battery system at the beginning of life. Usable energy is
defined by its initial design value. Actual available energy may vary depending on
charge/discharge rate, environmental conditions (e.g. temperature), transport and
storage factors.
249
*2: Max. Input Power /Max. Output Power/Peak.Output Power derating will occur
related to Temperature and SOC.
9.3 Smart Meter Technical Data
9.3.1 GM330
technical parameter
voltage range L-L (Vac)
voltage range L-N (Vac)
Nominal Frequency (Hz)
CT ratio
GM330
Three-phase, Split-phase,
Single-phase
172~817
100~472
50/60
nA:5A
Communication Method
RS485
Communication Distance
(m/ft)
1000/3280
voltage/current
Active Energy
Reactive Energy
Dimensions (WxHxD mm/in)
Class 0.5
Class 0.5
Class 1
72x85x72/2.83x3.35×2.83
Housing
4-module
Weight (g/lb)
Mounting Method
240/0.53
DIN Rail
User Interface
4 LEDs, Reset Button
Power Consumption (W)
≤5
IP Rating
Operating Temperature
Range (℃/°F)
Storage Temperature Range
(℃/°F)
Relative Humidity (noncondensing)
IP20
Supported Grid Type
Measurement
Range
Communication
Parameters
Accuracy
Parameters
General
Parameters
Environmental
Parameters
250
-30~+70/-22~+158
-30~70/-22~+158
0~95%
technical parameter
Max. Operating Altitude
(m/ft)
Certification
Parameters
Certificates
GMK330
Measurement Range
Supported Grid Types
1P2W/3P3W/3P4W
Operating voltage (Vac)*
3P4W:90~264 L-N
3P3W:90~264 L-L
Frequency (Hz)
50/60
CT ratio
120A: 40mA
200A: 50mA*
Number of CTs
3
Accuracy Parameters
voltage/current
Class 0.5
Active Energy
Class 0.5
Reactive Energy
Class 1
Communication Parameters
Communication Method
RS485
Communication Distance
(m)
1000
3000/9842
UL1741/ANSI
9.3.2 GMK330
model
GM330
General Parameters
Dimensions (W*H*D mm)
72*85*72
Housing
4-module
251
model
GMK330
Weight (g)
240
Mounting Method
DIN Rail
User Interface
4 LEDs, Reset Button
Power Consumption (W)
<5
Environmental Parameters
IP Rating
IP20
Operating Temperature
Range (℃)
-30-+70
Storage Temperature Range
-30-+70
(℃)
Relative Humidity (noncondensing)
0-95%
Max. Operating Altitude (m)
3000
*Supports 1.1 times rated voltage connection.
*The standard CT for the meter has been uniformly changed to the 120A:40mA
specification. Meters equipped with CTs of the 200A:50mA specification will no longer
be sold after June 2026.
9.4 Smart Dongle Technical Data
9.4.1 WiFi/LAN Kit-20
technical parameter
Output Voltage (V)
Power Consumption (W)
Communication Interface
Ethernet
Communication Wireless
Parameters
Bluetooth
WiFi/LAN Kit-20
5
≤2
USB
10M/100Mbps Auto-negotiation
IEEE 802.11 b/g/n @2.4 GHz
Bluetooth V4.2 BR/EDR and Bluetooth
LE Standard
252
technical parameter
Mechanical
Dimensions (W×H×D
Parameters
mm)
Weight (g)
Ingress Protection
Rating
Mounting Method
Operating Temperature Range (℃)
Storage Temperature Range (℃)
Relative Humidity
Max. Operating Altitude (m)
WiFi/LAN Kit-20
48.3*159.5*32.1
82
IP65
USB Port Plug and Play
-30~+60
-40~+70
0-95%
4000
253
10 Appendix
10.1 FAQ
10.1.1 How to conduct auxiliary detection for smart meters/CT?
The meter detection function can detect whether the meter CT is connected correctly
and the current operating status of the meter and CT.
1. Navigate to the detection page via [Home] > [Settings] > [Meter/CT Auxiliary
Detection].
2. Click Start Detection, wait for the detection to complete, and then view the
detection results.
10.1.2 How to Upgrade the Device Version
Through firmware information, you can view or upgrade:
The inverter's DSP version, ARM version, communication module software version,
battery's BMS version, DCDC version, etc.
• Prompt Upgrade:
When the user opens the App, an upgrade prompt pops up on the home page. The
user can choose whether to upgrade. If they choose to upgrade, they can complete
the upgrade by following the on-screen instructions.
• Regular Upgrade:
Go to [Home] > [Settings] > [Firmware Information] to enter the firmware
information viewing interface.
Click "Check for Updates". If a new version is available, complete the upgrade by
following the on-screen instructions.
• Forced Upgrade:
The App pushes upgrade information. The user must upgrade according to the
prompts; otherwise, the App cannot be used. Complete the upgrade by following the
254
on-screen instructions.
Inverter Software Version Upgrade
• The inverter supports software upgrade via a USB drive.
• Before using a USB drive to upgrade the device, please contact the after-sales
service center to obtain the software upgrade package and upgrade method.
10.2 Abbreviations
Abbreviation
Ubatt
Ubatt,r
Ibatt,max (C/D)
EC,R
UDCmax
UMPP
IDC,max
ISC PV
PAC,r
Sr (to grid)
Smax (to grid)
Sr (from grid)
Smax (from grid)
UAC,r
fAC,r
IAC,max(to grid)
IAC,max(from
grid)
English Description
Battery Voltage Range
Nominal Battery Voltage
Max. Charging Current
Max. Discharging Current
Rated Energy
Max.Input Voltage
MPPT Operating Voltage
Range
Max. Input Current per MPPT
Max. Short Circuit Current per
MPPT
Nominal Output Power
Nominal Apparent Power
Output to Utility Grid
Max. Apparent Power Output
to Utility Grid
Nominal Apparent Power
from Utility Grid
Max. Apparent Power from
Utility Grid
Nominal Output Voltage
Nominal AC Grid Frequency
Max. AC Current Output to
Utility Grid
Max. AC Current From Utility
Grid
255
Chinese Description
Battery voltage range
Nominal battery voltage
Max. charging/discharging
current
Rated energy
Max. Input Voltage
MPPT voltage range
Max. input current per MPPT
string
Max. short-circuit current per
MPPT string
Nominal output power
Nominal Apparent Power
Output to Utility Grid
Max. Apparent Power Output
to Utility Grid
Nominal apparent power
purchased from utility grid
Max. apparent power
purchased from utility grid
Nominal output voltage
Nominal AC Grid Frequency
Max. AC Current Output to
Utility Grid
Max. Current from Grid
Abbreviation
P.F.
IAC,max
UAC,r
English Description
Power Factor
Back-up Nominal apparent
power
Max. Output Apparent Power
(VA)
Max. Output Apparent Power
without Grid
Max. Output Current
Nominal Output Voltage
fAC,r
Nominal Output Freqency
Sr
Smax
Toperating
IDC,max
UDC
UDC,r
UAC
UAC,r
Toperating
Pmax
PRF
PD
PAC,r
F (Hz)
ISC PV
Udcmin-Udcmax
UAC,rang(L-N)
Usys,max
Haltitude,max
PF
THDi
Operating Temperature
Range
Max. Input Current
Input Voltage
DC Power Supply
Power Supply/AC Power
Supply
Power Supply/Input Voltage
Range
Operating Temperature
Range
Max Output Power
TX Power
Power Consumption
Power Consumption
Frequency
Max. Input Short Circuit
Current
Range of input Operating
Voltage
Power Supply Input Voltage
Max System Voltage
Max. Operating Altitude
Power Factor
Total Harmonic Distortion of
Current
256
Chinese Description
Power Factor
Off-grid nominal apparent
power
Max. Apparent Power to Grid
Max. Current to Grid
Max. output voltage
Nominal output voltage
frequency
Operating Temperature Range
Max. input current
Input voltage
DC input
Input voltage range/AC input
Input voltage range/AC input
Operating Temperature Range
Maximum Power
Transmit power
Power consumption
Power consumption
Frequency
Max. input short-circuit current
Operating Voltage range
Adapter input voltage range
Max. system voltage
Max. operating altitude
Power Factor
Current harmonic distortion
Abbreviation
Voc
Anti PID
PID Recovery
English Description
Total Harmonic Distortion of
Voltage
Commercial & Industrial
Smart Energy Management
System
Maximum Power Point
Tracking
Potential-Induced
Degradation
Open-Circuit Voltage
Anti-PID
PID Recovery
PLC
Power-line Commucation
THDv
C&I
SEMS
MPPT
PID
Modbus TCP/IP
Modbus RTU
SCR
UPS
ECO mode
TOU
ESS
PCS
RSD
EPO
SPD
ARC
DRED
RCR
AFCI
GFCI
Modbus Transmission Control
/ Internet Protocol
Modbus Remote Terminal
Unit
Short-Circuit Ratio
Uninterruptable Power Supply
Economical Mode
Time of Use
Energy Stroage System
Power Conversion System
Rapid shutdown
Emergency Power Off
Surge Protection Device
zero injection/zero export
Power Limit / Export Power
Limit
Demand Response Enabling
Device
Ripple Control Receiver
AFCI
Ground Fault Circuit
Interrupter
257
Chinese Description
Voltage harmonic distortion
Commercial & Industrial
Smart Energy Management
System
Maximum power point tracking
Potential-induced degradation
open-circuit voltage
Anti-PID
PID Recovery
Power-line carrier
communication
Modbus over TCP/IP
Modbus over serial link
Short-circuit ratio
Uninterruptible power supply
Economic Mode
Time of use
energy storage system
Power conversion system
Rapid Shutdown
Emergency Poweroff
Lightning protection
Power Limit
Demand response enabling
device
AFCI DC arc-fault protection
GFCI
Abbreviation
RCMU
FRT
HVRT
LVRT
EMS
BMS
BMU
BCU
SOC
SOH
SOE
SOP
SOF
SOS
DOD
English Description
Residual Current Monitioring
Unit
Fault Ride Through
High Voltage Ride Through
Low Voltage Ride Through
Energy Management System
Battery Management System
Battery Measure Unit
Battery Control Unit
State of Charge
State of Health
State Of Energy
State Of Power
State Of Function
State Of Safety
Depth of discharge
Chinese Description
Residual current monitoring
unit
Fault ride-through
High voltage ride-through
Low voltage ride-through
Energy management system
Battery management system
Battery measurement unit
Battery control unit
State of charge
State of health
State of energy
State of power
State of function
State of safety
depth of discharge
10.3 Explanation of Terms
• Definition of Overvoltage Categories
Overvoltage Category I: Equipment connected to circuits where measures are
taken to limit transient overvoltages to a suitably low level.
Overvoltage Category II: Energy-consuming equipment supplied from a fixed
electrical installation. This category includes appliances, portable tools, and other
household and similar loads. If special requirements for reliability and suitability
of such equipment exist, Overvoltage Category III applies.
Overvoltage Category III: Equipment in fixed electrical installations where
special requirements for reliability and suitability must be met. This includes
switching devices in fixed installations and industrial equipment permanently
connected to fixed electrical installations.
Overvoltage Category IV: Equipment used at the origin of the electrical
installation. This includes meters and primary overcurrent protection devices,
etc.
• Definition of Damp Location Categories
○
○
○
○
258
Environmental
Parameters
Temperature
Range
Humidity Range
Level
3K3
4K2
4K4H
0~+40℃
-33~+40℃
-33~+40℃
5% to 85%
15% to 100%
4% to 100%
• Definition of Environmental Categories:
Outdoor Inverter: Ambient air temperature range from -25°C to +60°C, suitable
for Pollution Degree 3 environments.
Indoor Type II Inverter: Ambient air temperature range from -25°C to +40°C,
suitable for Pollution Degree 3 environments.
Indoor Type I Inverter: Ambient air temperature range from 0°C to +40°C,
suitable for Pollution Degree 2 environments.
• Definition of Pollution Degree Categories
Pollution Degree 1: No pollution or only dry, non-conductive pollution.
○
○
○
○
○
○
○
Pollution Degree 2: Normally only non-conductive pollution occurs. Temporary
conductivity caused by condensation must be expected occasionally.
Pollution Degree 3: Conductive pollution occurs, or dry non-conductive pollution
becomes conductive due to condensation.
Pollution Degree 4: Persistent conductive pollution occurs, for example, due to
conductive dust, rain, or snow.
10.4 Battery SN Code Meaning
The 11th to 14th digits of the product SN code represent the production time code.
The production date in the above image is 2023-08-08
• The 11th and 12th digits are the last two digits of the production year, e.g., 2023 is
represented as 23;
259
• The 13th digit is the production month, e.g., August is represented as 8;
Details are as follows:
Month
Jan-Sep
Oct
Nov
Dec
Month Code
1~9
A
B
C
• The 14th digit is the production date, e.g., the 8th day is represented as 8;
Numbers are preferred for representation, e.g., 1~9 represent the 1st to 9th days,
A represents the 10th day, and so on. Among them, the letters I and O are not used
to avoid confusion. Details are as follows:
Production Day
1
2
3
4
5
6
7
8
9
Code
1
2
3
4
5
6
7
8
9
Production Date
10
11
12
13
14
15
16
17
18
Code
A
B
C
D
E
F
G
H
J
Production Date
21
22
23
24
25
26
27
28
29
Code
M
N
P
Q
R
S
T
U
V
260
11 Contact Information
GoodWe Technologies Co., Ltd.
90 Zijin Road, Suzhou New District, China
400-998-1212
www.goodwe.com
[email protected]
261
">