PELLET STOVES
INSTALLATION AND USE MANUAL
2.6. CONNECTION TO THE FLUE PIPE
0,5 mt.
The flue pipe must have internal dimensions not larger than 20 x 20 cm, or diameter 20 cm. In the event of larger dimensions, or of the flue pipe being in poor condition (for example cracks, poor insulation, etc.), it is advisable to fit a stainless steel pipe of suitable diameter inside the flue pipe throughout its length, right up to the top.
Check with suitable instruments that there is a minimum draught of 10
Pa.
At the bottom of the flue pipe, provide an inspection cap to allow periodic checking and cleaning, which must be done annually.
Make a gas-tight connection to the flue pipe, using pipes and connectors as recommended by us.
You must ensure that a windproof cowl should be fitted which complies with the standards in force.
This type of connection ensures the evacuation of the fumes even in the event of a temporary power cut.
2.7. CONNECTION TO AN EXTERNAL FLUE WITH
INSULATED OR DOUBLE-WALL PIPE
The external fluepipe must have internal dimensions of minimum
10x10 cm or 10 cm diameter, and maximum 20x20 cm or 20 cm diameter.
Check with suitable instruments that there is a minimum draught of 10 Pa.
The only type of pipe which is permissible is insulated (double-walled) stainless steel, smooth on the inside, fixed to the wall. Flexible stainless steel pipe must not be used. At the bottom of the flue pipe, provide an inspection cap to allow periodic checking and cleaning, which must be
done annually. Make a gas-tight connection to the flue pipe, using pipes and connectors as recommended by us.
You must ensure that a windproof cowl should be fitted which complies with the standards in force.
This type of connection ensures the evacuation of the fumes even in the event of a temporary power cut.
2.8. CONNECTION TO THE FLUE PIPE
1) Windproof cowl
2) Flue pipe
3) Inspection
0,5 mt.
1) Windproof cowl
2) Flue pipe
3) Inspection
Chapter 2 page 14
1
2
3
1
2
3
For proper functioning, the connecting pipe between the stove and the chimney or flue duct must have a slope of not less than 3% in the horizontal stretches, the length of which must not exceed 2/3
metres, and the vertical distance between one tee connector and another (change of direction) must not be less than 1.5m.
Check with suitable instruments that there is a minimum draught of 10
Pa.
At the bottom of the flue pipe, provide an inspection cap to allow periodic checking and cleaning, which must be done annually.
Make a gas-tight connection to the flue pipe, using pipes and connectors as recommended by us.
You must ensure that a windproof cowl should be fitted which complies with the standards in force.
Theoretical notions for installation
0,5 mt.
2 - 3 mt. MAX
3-5 %
3
1
2
1) Windproof cowl
2) Flue pipe
3) Inspection