32 System Description WAGO-I/O-SYSTEM 750

750-316/300-000 Fieldbus Coupler MODBUS RTU

3.6 Grounding

3.6.1 Grounding the DIN Rail

3.6.1.1 Framework Assembly

When setting up the framework, the carrier rail must be screwed together with the electrically conducting cabinet or housing frame. The framework or the housing must be grounded. The electrical connection is established via the screw. Thus, the carrier rail is grounded.

Ensure sufficient grounding is provided!

You must take care to ensure the flawless electrical connection between the carrier rail and the frame or housing in order to guarantee sufficient grounding.

3.6.1.2 Insulated Assembly

Insulated assembly has been achieved when there is constructively no direct ohmic contact between the cabinet frame or machine parts and the carrier rail.

Here, the earth ground must be set up via an electrical conductor in accordance with valid national safety regulations.

Recommendation

The optimal setup is a metallic assembly plate with grounding connection which is electrically conductive linked to the carrier rail.

The separate grounding of the carrier rail can be easily set up with the aid of the

WAGO ground wire terminals.

Table 10: WAGO Ground Wire Terminals

Order No. Description

283-609 1-conductor ground (earth) terminal block make an automatic contact to the carrier rail; conductor cross section: 0.2 mm² … 16 mm

2

Note : Also order the end and intermediate plate (283-320).