WAGO-I/O-SYSTEM 750
750-316/300-000 Fieldbus Coupler MODBUS RTU
3.6.2 Grounding Function
System Description 33
The grounding function increases the resistance against electro-magnetic interferences. Some components in the I/O system have a carrier rail contact that dissipates electro-magnetic interferences to the carrier rail.
Figure 18: Carrier Rail Contact (Example)
Ensure sufficient grounding is provided!
You must take care to ensure the direct electrical connection between the carrier rail contact and the carrier rail.
The carrier rail must be grounded.
For information on carrier rail properties, see section “Mounting” > … > “Carrier
Rail Properties”.
The bottom CAGE CLAMP
® connectors of the supply modules enable optional connection of a field-side functional ground. This potential is made available to the I/O module arranged on the right through the spring-loaded contact of the three power contacts. Some I/O modules are equipped with a knife-edge contact that taps this potential. This forms a potential group with regard to functional ground with the I/O module arranged on the left.
Manual
Version 1.0.0
advertisement
Related manuals
advertisement
Table of contents
- 6 Notes about this Documentation
- 6 Validity of this Documentation
- 6 Copyright
- 7 Symbols
- 9 Number Notation
- 9 Font Conventions
- 10 Important Notes
- 10 Legal Bases
- 10 Subject to Changes
- 10 Personnel Qualifications
- 10 Provisions
- 11 Technical Condition of Specified Devices
- 12 Safety Advice (Precautions)
- 14 System Description
- 15 Manufacturing Number
- 16 Component Update
- 16 Storage, Assembly and Transport
- 17 Assembly Guidelines/Standards
- 18 Power Supply
- 18 Isolation
- 19 System Supply
- 19 Connection
- 20 Dimensioning
- 23 Field Supply
- 23 Connection
- 25 Fusing
- 28 Supplementary Power Supply Regulations
- 29 Supply Example
- 31 Power Supply Unit
- 32 Grounding
- 32 Grounding the DIN Rail
- 32 Framework Assembly
- 32 Insulated Assembly
- 33 Grounding Function
- 34 Shielding
- 34 General
- 34 Bus Cables
- 35 Signal Lines
- 35 WAGO Shield Connecting System
- 36 Device Description
- 39 Connectors
- 39 Device Supply
- 40 Fieldbus Connection
- 41 Display Elements
- 42 Operating Elements
- 42 Service Interface
- 43 Mode Selector Switch
- 49 Manual Configuration
- 52 Technical Data
- 52 Device Data
- 52 System Data
- 52 Connection Type
- 53 Climatic Environmental Conditions
- 53 Mechanical Strength acc. to IEC
- 54 Approvals
- 56 Standards and Guidelines
- 57 Mounting
- 57 Installation Position
- 57 Overall Configuration
- 59 Mounting onto Carrier Rail
- 59 Carrier Rail Properties
- 60 WAGO DIN Rail
- 60 Spacing
- 61 Mounting Sequence
- 62 Inserting and Removing Devices
- 63 Inserting the Fieldbus Coupler/Controller
- 63 Removing the Fieldbus Coupler/Controller
- 64 Inserting the I/O Module
- 65 Removing the I/O Module
- 66 Connect Devices
- 66 Data Contacts/Internal Bus
- 67 Power Contacts/Field Supply
- 69 Function Description
- 69 Startup of the Fieldbus Coupler
- 71 Process Data Architecture
- 71 Basic Setup
- 72 Example of an Input Process Image
- 73 Example of an Output Process Image
- 74 Process Data MODBUS RTU
- 75 Data Exchange
- 75 Memory Space
- 76 Addressing
- 76 Adressing the I/O Modules
- 79 Commissioning
- 80 Diagnostics
- 80 LED Signaling
- 81 Evaluating Fieldbus Status
- 82 Evaluating Node Status – I/O LED (Blink Code Table)
- 163 Figure 1: Fieldbus Node (Example)
- 164 Figure 2: Labeling on the Side of a Component (Example)
- 164 Figure 3: Example of a Manufacturing Number
- 167 Figure 4: Isolation for Fieldbus Couplers/Controllers (Example)
- 168 System Supply Module (right)
- 169 Couplers
- 174 Figure 8: Supply Module with Fuse Carrier (Example 750-610)