Draining the machine and an externally closed application

General

-

Before draining the unit, the heat transfer fluid should be at ambient temperature

(approx. 20 °C). If not, let the machine run with a set point of approx. 20 °C for a few minutes until the thermal fluid is at a safe temperature.

-

Connect one end of a suitable drain hose to the drain of the unit (8), and place the other end into a suitable container (make sure the hose and container materials are compatible with the heat transfer fluid being used.

Draining

-

Open the drain valve (4) if available.

-

The heat transfer fluid should flow through the pump case, and drain port into the container.

-

Disconnect the hose from the unit’s outlet (1).

-

Disconnect the hose from the inlet to the unit (2).

-

Leave the temperature control device open to dry out for some time (without sealing caps and open drain valve (4).

Changing heat transfer fluid / internal cleaning

-

After emptying the unit as described in the chapter Draining the machine and an externally closed application depending on the thermal fluid, it is possible that remnants of the oil remain in the machine.

-

Connect a short hose between the inlet (2) and outlet (1) of the unit.

-

When having used silicon oils as thermal fluid, use a suitable solvent (e.g.

Mucasol) to clean the internal components such as pump housing, reservoir, etc.

Depending on the amount of contamination, it may be necessary to drain the solvent off, and repeat the procedure a number of times with clean solvent.

-

Afterwards, leave the temperature control device stand for some time (open all drain valves and have the connections opened).

23

advertisement

Key Features

  • Advanced functionality with programmer and interface
  • Compact design with small footprint
  • High cooling capacity of 1.8 kW
  • Temperature range from -20 to 120 °C
  • Natural refrigerant for environmentally friendly operation

Related manuals

Frequently Answers and Questions

What is the temperature range of the MPC UC015w?
The MPC UC015w has a temperature range from -20 to 120 °C.
What is the cooling capacity of the MPC UC015w?
The MPC UC015w has a cooling capacity of 1.8 kW.
What type of refrigerant does the MPC UC015w use?
The MPC UC015w uses a natural refrigerant for environmentally friendly operation.