- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Honeywell
- AUTOMATIC CONTROL SI Edition
- User manual
Bibliography. Honeywell AUTOMATIC CONTROL SI Edition
Add to My manuals512 Pages
Honeywell AUTOMATIC CONTROL SI Edition is the latest and greatest in automatic control for commercial buildings. It is packed with features that will help you to optimize your building's performance and save energy. With this device, you can:
advertisement
SMOKE MANAGEMENT FUNDAMENTALS
Another consideration in zone pressurization is that bringing in outdoor air at low temperatures can cause serious freeze damage. Provision should be made to prevent damage when using outdoor air, such as providing emergency preheat and minimizing the quantity of outdoor air used.
Testing of smoke control strategies should include not only verification of acceptable pressures but also confirmation that interaction with other systems creates no problems, such as excessive door pull in a stairwell pressurization system (refer to American with Disabilities Act).
Typical Operation for Zone Pressurization System (Fig. 6):
1. Smoke detector(s) initiate alarm in specific zone.
2. System switches to smoke control mode as determined in remote control panel.
3. System turns on pressurization fans if not already on.
4. System allows pressurization fans to continue running if supply duct smoke detector is not in alarm or manual override is not activated.
5. System enables damper operation as appropriate for smoke control mode.
6. Operator verifies operation as appropriate (e.g., action of differential pressure switch).
7. Operator cancels smoke control mode as long as initiating panel is not in alarm and FSCS is not in manual override.
complex system to modulate dampers or fans at multiple injection points (Fig. 9) in response to differential pressure measurements at these points.
STAIRWELL
ROOF
LEVEL
BAROMETRIC
PRESSURE
DAMPER
C5151
Fig. 8. Stairwell Pressurization with Barometric
Pressure Damper to Vent to the Outside.
ROOF
LEVEL
STAIRWELL
EXTERIOR
WALL
OUTDOOR
AIR
INTAKE
STAIRWELL PRESSURIZATION CONTROL
The objective of stairwell pressurization is to provide an acceptable environment within a stairwell, in the event of a fire, to furnish an egress route for occupants and a staging area for firefighters. On the fire floor, a pressure difference must be maintained across the closed stair tower door to ensure that smoke infiltration is limited. Also, adequate purging must be provided to limit smoke density caused by temporary door openings on the fire floor.
To ensure proper stairwell pressurization system design, a means should be included to modulate either the supply or the exhaust/relief dampers. Also, a means should be included to provide multiple supply injection points at a minimum of every three floors (unless design analysis can justify a greater spacing) to provide uniform pressurization.
According to NFPA 92A, Recommended Practice for Smoke
Control Systems, the intake of supply air should be isolated from smoke shafts, roof smoke and heat vents, and other building openings that might expel smoke from the building in a fire. Wind shields should be considered at fan intakes.
Open-loop control of pressurization is seldom acceptable because of significant pressure differences caused by door openings. Closed loop or modulation provides the ability to control pressurization within acceptable limits. Closed loop control can be as simple as a barometric pressure damper
(Fig. 8) to relieve pressure at the top of a stairwell or a more
MODULATING
DAMPER
(4 PLACES)
DUCT
SHAFT
DUCT
CENTRIFUGAL
FAN
C5152
Fig. 9. Stairwell Pressurization with Modulating Dampers and Multiple Injection Points to Regulate Pressure.
Testing of stairwell pressurization systems should be conducted with agreed on conditions including:
— Number and location of doors held open
— Outside pressure conditions known
— Maximum door pull force allowed
Typical Operation for Stairwell Pressurization (Fig. 6):
1. Any fire alarm initiates smoke control mode.
2. System turns on pressurization fans.
3. System allows pressurization fans to continue running if supply duct smoke detector is not in alarm or manual override is not activated.
180 ENGINEERING MANUAL OF AUTOMATIC CONTROL
advertisement
Key Features
- Control all aspects of your building's HVAC system from a single location
- Monitor and adjust temperature, humidity, and ventilation levels
- Create custom control programs to meet your specific needs
- Integrate with other building systems, such as lighting and security
- Access your system remotely via the internet
Related manuals
Frequently Answers and Questions
What are the benefits of using Honeywell AUTOMATIC CONTROL SI Edition?
How easy is it to use Honeywell AUTOMATIC CONTROL SI Edition?
How much does Honeywell AUTOMATIC CONTROL SI Edition cost?
advertisement
Table of contents
- 99 Series 40 Control Circuits
- 101 Series 80 Control Circuits
- 102 Series 60 Two-Position Control Circuits
- 105 Series 60 Floating Control Circuits
- 106 Series 90 Control Circuits
- 113 Motor Control Circuits
- 128 Introduction
- 128 Definitions
- 130 Typical System
- 130 Components
- 137 Electronic Controller Fundamentals
- 138 Typical System Application
- 139 Microprocessor-Based/DDC Fundamentals
- 141 Introduction
- 141 Definitions
- 142 Background
- 142 Advantages
- 143 Controller Configuration
- 144 Types of Controllers
- 145 Controller Software
- 150 Controller Programming
- 153 Typical Applications
- 159 Introduction
- 159 Definitions
- 161 Abbreviations
- 162 Indoor Air Quality Concerns
- 172 Indoor Air Quality Control Applications
- 178 Bibliography
- 180 Introduction
- 180 Definitions
- 181 Objectives
- 181 Design Considerations
- 183 Design Priniples
- 186 Control Applications
- 189 Acceptance Testing
- 189 Leakage Rated Dampers
- 190 Bibliography
- 191 Building Management System Fundamentals
- 192 Introduction
- 192 Definitions
- 193 Background
- 194 System Configurations
- 197 System Functions
- 204 Integration of Other Systems
- 209 Air Handling System Control Applications
- 211 Introduction
- 211 Abbreviations
- 212 Requirements for Effective Control
- 214 Applications-General
- 215 Valve and Damper Selection
- 216 Symbols
- 217 Ventilation Control Processes
- 219 Fixed Quantity of Outdoor Air Control
- 231 Heating Control Processes
- 236 Preheat Control Processes
- 243 Humidification Control Process
- 244 Cooling Control Processes
- 251 Dehumidification Control Processes
- 254 Heating System Control Process
- 256 Year-Round System Control Processes
- 269 ASHRAE Psychrometric Charts
- 271 Building Airflow System Control Applications
- 273 Introduction
- 273 Definitions
- 274 Airflow Control Fundamentals
- 288 Airflow Control Applications
- 298 References
- 299 Chiller, Boiler, and Distribution System Control Applications
- 303 Introduction
- 303 Abbreviations
- 303 Definitions
- 304 Symbols
- 305 Chiller System Control
- 335 Boiler System Control
- 343 Hot and Chilled Water Distribution Systems Control
- 382 High Temperature Water Heating System Control
- 388 District Heating Applications
- 403 Individual Room Control Applications
- 405 Introduction
- 416 Unitary Equipment Control
- 432 Hot Water Plant Considerations
- 437 Introduction
- 437 Definitions
- 441 Valve Selection
- 446 Valve Sizing
- 456 Introduction
- 456 Definitions
- 457 Damper Selection
- 466 Damper Sizing
- 471 Damper Pressure Drop
- 472 Damper Applications
- 475 Introduction
- 475 Conversion Formulas and Tables
- 482 Electrical Data
- 485 Properties of Saturated Steam Data
- 486 Airflow Data
- 488 Moisture Content of Air Data
- 494 Application
- 494 Equipment
- 494 Controllers
- 494 Actuators
- 495 Operation
- 495 General
- 495 Bridge Circuit Theory
- 495 Basic Bridge Circuit
- 495 Bridge Circuit in Balanced Condition
- 495 Bridge Circuit on Increase in Controlled Variable
- 496 Bridge Circuit on Decrease in Controlled Variable
- 496 Bridge Circuit with Limit Controls
- 497 Bridge Circuit with Low-Limit Control
- 497 Bridge Circuit with High-Limit Control
- 498 Control Combinations
- 498 Low-Limit Control
- 498 High-Limit Control
- 499 Two-Position Limit Control
- 499 Manual and Automatic Switching
- 499 Closing the Actuator with a Manual Switch
- 499 One Thermostat to Another
- 499 Reversing for Heating and Cooling Control
- 500 One Actuator to Another
- 500 Unison Control
- 500 Manual Minimum Positioning of Outdoor Air Damper
- 501 Step Controllers
- 501 Application
- 501 Equipment
- 501 Starters
- 501 Contactors and Relays
- 502 Operation
- 502 Momentary Start-Stop Circuit
- 502 Hand-Off-Auto Start-Stop Circuit
- 503 Momentary Fast-Slow-Off Start-Stop Circuit
- 504 Control Combinations