- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Honeywell
- AUTOMATIC CONTROL SI Edition
- User manual
Hot Water Plant Considerations. Honeywell AUTOMATIC CONTROL SI Edition
Add to My manuals512 Pages
Honeywell AUTOMATIC CONTROL SI Edition is the latest and greatest in automatic control for commercial buildings. It is packed with features that will help you to optimize your building's performance and save energy. With this device, you can:
advertisement
INDIVIDUAL ROOM CONTROL APPLICATIONS
In some hea t pumps, a minim um of f timer pr events a compr essor r estar t for thr ee to five min utes. After shutdo wn, heat pump operation must not resume until pressures equalize between the suction and disc har ge sides of the compr essor. Shor t cycling the hea t pump ma y result in compr essor dama ge.
A two-sta ge, high-speed compr essor can pr ovide ca pacity contr ol for maxim um hea t pump ef ficiency. The r oom ther mosta t contr ols the indi vidual compr essor sta ges. The ther mosta t second stage contr ols the auxiliar y heat (for air -sour ce heat pumps) and compr essor sta ge two. When the outdoor ther mosta t contact c loses as outdoor temper atur e falls to its setpoint, the auxiliar y heat ener gizes with the compr essor (F ig. 38).
THERMOSTAT
STAGE 1
STAGE 2
HEAT PUMP
POWER
OUTDOOR AIR
THERMOSTAT
AUXILIARY
HEAT C3023
Fig. 38. Heat Pump Staging.
Defrost cycling is typicall y used w hen outdoor temper atur es are below 7
°
C, because the outdoor coil may operate below freezing and frost can form on the coil when the unit is in the heating mode. Frost inhibits airflow through the heat pump and degrades unit perf ormance . To remove the fr ost, the hea t pump momentar ily switches to the cooling mode . Hot g as fr om the compressor is directed to the outdoor coil, and the frost melts.
Typicall y the unit c ycles ever y 90 min utes for four to eight minutes to defrost. Instead of time-initiated defrost, some models use demand defr ost, which cycles to the cooling mode by measur ing chang es in the airf low acr oss the outdoor coil.
CONTROL LOOPS
Hea t pumps can use a v ar iety of methods to c hang e betw een cooling and hea ting, including a tw o-position r oom ther mosta t and man ual c hang eover.
Assuming automa tic chang eover betw een hea ting and cooling, on a r ise in space temper atur e, a tw o-position r oom ther mosta t senses the temper atur e rise and c ycles the hea t pump in the cooling mode . When space temper atur e falls below the deadband , the fir st sta ge of hea ting c ycles the compr essor in the hea ting mode . A fur ther dr op in space temper atur e br ings on additional thermostat heating stages to turn on supplemental electric resistance heaters.
In some hea t pumps, the c hang eover v alve cycles with the compressor in either the heating or cooling mode. In others, the chang eover valve remains in the hea ting or cooling position as long as space temperature is in the appropriate range.
Wher e a centr al water plant pr ovides hea ting/cooling sour ce water f or the hea t pumps, water contr ol is often pr ovided to conser ve water w hen the hea t pump c ycles off and w hen the water temper atur e is excessive for the load . Valves ma y be refrigerant pressure (may be furnished with the heat pump) or temper atur e contr olled. Temper atur e contr olled valves must close when the compr essor is of f, but m ust ha ve a minim um open position anytime the heat pump operates in order to keep water f low acr oss the water sensor .
Heat pump system controls must be carefully coordinated with the hea t pump man ufactur er and the w ater plant system
(on air -to-water hea t pumps).
422 ENGINEERING MANUAL OF AUTOMATIC CONTROL
INDIVIDUAL ROOM CONTROL APPLICATIONS
INDIVIDUAL ROOM CONTROL AUTOMATION
On automa ted jobs with a g r aphic BMS , ATUs ar e usuall y shown on a f loor plan similar to F igur e 39.
The Figur e 39 example sho ws a graphic of the souther n half of a floor with 30 VAV boxes and their associa ted space temper atur es. Selecting an y VAV box would pr oduce a g raphic of tha t bo x, similar to those pr eviously shown in this section, and all specif ied da ta suc h as space temper atur e setpoints, minimum and maximum airflow setpoints, etc.
ELEVATOR
LOBBY
V = VAV BOX
V
23.7
V
23.7
V
23.7
V
23.7
V
23.7
MEN
V
23.7
23.7
V
23.7
V
V
23.7
V
23.7
V
23.7
V
23.7
V
23.7
V
23.7
23.7
V
V
23.7
23.7
V
V
23.7
23.7
V
23.7
V
23.7
V
23.7
V 23.7
V
V
23.7
23.7
V
23.7
V
V
23.7
23.7
V
V
23.7
V
23.7
V
23.7
TENTH FLOOR SOUTH
Fig. 39. ATU System Floor Plan Graphic
M10532
ENGINEERING MANUAL OF AUTOMATIC CONTROL
423
INDIVIDUAL ROOM CONTROL APPLICATIONS
HOT WATER PLANT CONSIDERATIONS
See Chiller , Boiler, and Distr ibution System Contr ol
Applica tions section f or ad ditional inf orma tion on hot w ater system control.
Because unit v entila tor s have lar ge OA damper s in close pr oximity to the w ater coils, the hot w ater pump should r un anytime the O A temper atur e is less than fr eezing, independent of hot water temper atur e.
Unit ventila tor and f an coil unit hot w ater temper atur es should be r eset based upon the O A temper atur e to ma tch the hot w ater temper atur e to the load . This allows much smoother contr ol, and k eeps adequa te water v elocities in the hot w ater coils if modula ting valves ar e used. Dual schedules ar e recommended with signif icantl y war mer w ater pr ovided dur ing unoccupied per iods to aid in the con vection and w ar m-up ef for ts. A tr iple water temper atur e schedule ma y be consider ed wher e the convection mode has a higher w ater temper atur e than w ar mup or occupied modes. The setpoint shift betw een modes should be r amped o ver a 20 to 30 min ute dur ation.
The hot w ater pump should also r un dur ing unoccupied periods on a drop in room temperature to about 16
°
C. In this mode the coils will act as a r adia tor and ad d hea t to the b uilding per imeter without r unning the unit v entila tor f ans.
Unit Ventila tor s and f an coil units and their associa ted hea ting and cooling plants should be started by a global optimum start pr ogram with the O A damper c losed until occupanc y time .
424 ENGINEERING MANUAL OF AUTOMATIC CONTROL
SMOKE MANAGEMENT FUNDAMENTALS
ENGINEERING
INFORMATION
ENGINEERING MANUAL OF AUTOMATIC CONTROL
425
426 ENGINEERING MANUAL OF AUTOMATIC CONTROL
advertisement
Key Features
- Control all aspects of your building's HVAC system from a single location
- Monitor and adjust temperature, humidity, and ventilation levels
- Create custom control programs to meet your specific needs
- Integrate with other building systems, such as lighting and security
- Access your system remotely via the internet
Related manuals
Frequently Answers and Questions
What are the benefits of using Honeywell AUTOMATIC CONTROL SI Edition?
How easy is it to use Honeywell AUTOMATIC CONTROL SI Edition?
How much does Honeywell AUTOMATIC CONTROL SI Edition cost?
advertisement
Table of contents
- 99 Series 40 Control Circuits
- 101 Series 80 Control Circuits
- 102 Series 60 Two-Position Control Circuits
- 105 Series 60 Floating Control Circuits
- 106 Series 90 Control Circuits
- 113 Motor Control Circuits
- 128 Introduction
- 128 Definitions
- 130 Typical System
- 130 Components
- 137 Electronic Controller Fundamentals
- 138 Typical System Application
- 139 Microprocessor-Based/DDC Fundamentals
- 141 Introduction
- 141 Definitions
- 142 Background
- 142 Advantages
- 143 Controller Configuration
- 144 Types of Controllers
- 145 Controller Software
- 150 Controller Programming
- 153 Typical Applications
- 159 Introduction
- 159 Definitions
- 161 Abbreviations
- 162 Indoor Air Quality Concerns
- 172 Indoor Air Quality Control Applications
- 178 Bibliography
- 180 Introduction
- 180 Definitions
- 181 Objectives
- 181 Design Considerations
- 183 Design Priniples
- 186 Control Applications
- 189 Acceptance Testing
- 189 Leakage Rated Dampers
- 190 Bibliography
- 191 Building Management System Fundamentals
- 192 Introduction
- 192 Definitions
- 193 Background
- 194 System Configurations
- 197 System Functions
- 204 Integration of Other Systems
- 209 Air Handling System Control Applications
- 211 Introduction
- 211 Abbreviations
- 212 Requirements for Effective Control
- 214 Applications-General
- 215 Valve and Damper Selection
- 216 Symbols
- 217 Ventilation Control Processes
- 219 Fixed Quantity of Outdoor Air Control
- 231 Heating Control Processes
- 236 Preheat Control Processes
- 243 Humidification Control Process
- 244 Cooling Control Processes
- 251 Dehumidification Control Processes
- 254 Heating System Control Process
- 256 Year-Round System Control Processes
- 269 ASHRAE Psychrometric Charts
- 271 Building Airflow System Control Applications
- 273 Introduction
- 273 Definitions
- 274 Airflow Control Fundamentals
- 288 Airflow Control Applications
- 298 References
- 299 Chiller, Boiler, and Distribution System Control Applications
- 303 Introduction
- 303 Abbreviations
- 303 Definitions
- 304 Symbols
- 305 Chiller System Control
- 335 Boiler System Control
- 343 Hot and Chilled Water Distribution Systems Control
- 382 High Temperature Water Heating System Control
- 388 District Heating Applications
- 403 Individual Room Control Applications
- 405 Introduction
- 416 Unitary Equipment Control
- 432 Hot Water Plant Considerations
- 437 Introduction
- 437 Definitions
- 441 Valve Selection
- 446 Valve Sizing
- 456 Introduction
- 456 Definitions
- 457 Damper Selection
- 466 Damper Sizing
- 471 Damper Pressure Drop
- 472 Damper Applications
- 475 Introduction
- 475 Conversion Formulas and Tables
- 482 Electrical Data
- 485 Properties of Saturated Steam Data
- 486 Airflow Data
- 488 Moisture Content of Air Data
- 494 Application
- 494 Equipment
- 494 Controllers
- 494 Actuators
- 495 Operation
- 495 General
- 495 Bridge Circuit Theory
- 495 Basic Bridge Circuit
- 495 Bridge Circuit in Balanced Condition
- 495 Bridge Circuit on Increase in Controlled Variable
- 496 Bridge Circuit on Decrease in Controlled Variable
- 496 Bridge Circuit with Limit Controls
- 497 Bridge Circuit with Low-Limit Control
- 497 Bridge Circuit with High-Limit Control
- 498 Control Combinations
- 498 Low-Limit Control
- 498 High-Limit Control
- 499 Two-Position Limit Control
- 499 Manual and Automatic Switching
- 499 Closing the Actuator with a Manual Switch
- 499 One Thermostat to Another
- 499 Reversing for Heating and Cooling Control
- 500 One Actuator to Another
- 500 Unison Control
- 500 Manual Minimum Positioning of Outdoor Air Damper
- 501 Step Controllers
- 501 Application
- 501 Equipment
- 501 Starters
- 501 Contactors and Relays
- 502 Operation
- 502 Momentary Start-Stop Circuit
- 502 Hand-Off-Auto Start-Stop Circuit
- 503 Momentary Fast-Slow-Off Start-Stop Circuit
- 504 Control Combinations