Hydac PB ETS 4000 SAE J1939 E V03 is a temperature transmitter that can be used for measuring the current fluid temperature using a 1kHz sample rate, ensuring high accuracy (<1°C) and high resolution (1/8 °C). It can also be used to measure the actual pressure value and convert temperature values into a linear process value. Additionally, it can send the current temperature values (fluid and device temperature) cyclically, within a range of 1 millisecond to 1 minute. The device has a CAN 2.0 B interface and operates according to the SAE-J1939 standard.
advertisement
![Carry out configuration. Hydac PB ETS 4000 SAE J1939 E V03 | Manualzz Carry out configuration. Hydac PB ETS 4000 SAE J1939 E V03 | Manualzz](http://s1.manualzz.com/store/data/065681124_1-70e074d2a85b76103c81514eb5a49739-360x466.png)
E
12
3.3 Carry out configuration
ETS 4000 SAE J1939 V03
Before the settings can be changed the ETS must be set to its editing mode. The changed settings must then be stored and a restart needs to be carried out. Please see chapter "commands" below.
To read and write the settings, the master sends a message with the parameter group number 61184 to the ETS's address. ETS responds by the same parameter group number and sends an acknowledge code.
In case of reading requests the requested data are sent with the code.
3.4 Message data structure
The content of the messages is listed in the following table:
Byte Content
0
1
2
Setting index r/w, 0=read, 1=write
Sub index of the configuration (0 if no sub index is used)
3 Acknowledge, see remarks
4-7 Data LittleEndian
For entries in which a sub index is used, i.e. 59 (status channel) a sub index has to be set in order to inquire the channel.
5
6
7
8
9
10
11
12
1
2
3
4
The acknowledge code is always 0 with regard to the messages sent by the master. In the response of the ETS the acknowledge code means:
Ack-Code Description
0 Ok
Parameters read only
Value too high
Value too low
Index does not exist
Error while saving parameters
Error while restoring parameters
Invalid r/w Byte (i.e. >1)
Parameters write only
Invalid data
Processor occupied
Error while accessing the hardware
Sub index does not exist
Edition: 2021-04-12 HYDAC ELECTRONIC GMBH Part no.: 670057