3.3 Carry out configuration

ETS 4000 SAE J1939 V03

Before the settings can be changed the ETS must be set to its editing mode. The changed settings must then be stored and a restart needs to be carried out. Please see chapter "commands" below.

To read and write the settings, the master sends a message with the parameter group number 61184 to the ETS's address. ETS responds by the same parameter group number and sends an acknowledge code.

In case of reading requests the requested data are sent with the code.

3.4 Message data structure

The content of the messages is listed in the following table:

Byte Content

0

1

2

Setting index r/w, 0=read, 1=write

Sub index of the configuration (0 if no sub index is used)

3 Acknowledge, see remarks

4-7 Data LittleEndian

For entries in which a sub index is used, i.e. 59 (status channel) a sub index has to be set in order to inquire the channel.

5

6

7

8

9

10

11

12

1

2

3

4

The acknowledge code is always 0 with regard to the messages sent by the master. In the response of the ETS the acknowledge code means:

Ack-Code Description

0 Ok

Parameters read only

Value too high

Value too low

Index does not exist

Error while saving parameters

Error while restoring parameters

Invalid r/w Byte (i.e. >1)

Parameters write only

Invalid data

Processor occupied

Error while accessing the hardware

Sub index does not exist

Edition: 2021-04-12 HYDAC ELECTRONIC GMBH Part no.: 670057