Sending the measured value. Hydac PB ETS 4000 SAE J1939 E V03
Add to My manuals15 Pages
Hydac PB ETS 4000 SAE J1939 E V03 is a temperature transmitter that can be used for measuring the current fluid temperature using a 1kHz sample rate, ensuring high accuracy (<1°C) and high resolution (1/8 °C). It can also be used to measure the actual pressure value and convert temperature values into a linear process value. Additionally, it can send the current temperature values (fluid and device temperature) cyclically, within a range of 1 millisecond to 1 minute. The device has a CAN 2.0 B interface and operates according to the SAE-J1939 standard.
advertisement
![Sending the measured value. Hydac PB ETS 4000 SAE J1939 E V03 | Manualzz Sending the measured value. Hydac PB ETS 4000 SAE J1939 E V03 | Manualzz](http://s1.manualzz.com/store/data/065681124_1-70e074d2a85b76103c81514eb5a49739-360x466.png)
14 ETS 4000 SAE J1939 V03
3.5.2 Saving the settings
The changed settings will not automatically become persistent, which means, they will not be stored permanently. For this purpose, an extra storage process needs to be carried out explicitly. This is carried out by writing the string "save" into the Index 102.
Master
Index
(Byte 1) r/w
(Byte 2) dc
(Byte 3) ack
(Byte 4) (Byte 5)
Value ( "save“)
(Byte 6) (Byte 7) (Byte 8)
" s " 0x61 " v " 0x65
E Sensor
Index
(Byte 1) r/w
(Byte 2) dc
(Byte 3) ack
(Byte 4) (Byte 5) (Byte 6)
Value
(Byte 7) (Byte 8)
3.5.3 Reset to factory default settings
The settings can be reset to factory default settings at any time. For this purpose, the string
"load" must be written into Index 103.
Master
Index
(Byte 1) r/w
(Byte 2) dc
(Byte 3) ack
(Byte 4) (Byte 5)
Value ( "load“)
(Byte 6) (Byte 7) (Byte 8)
" l " 0x6F " a " 0x64
Sensor
Index
(Byte 1) r/w
(Byte 2) dc
(Byte 3) ack
(Byte 4) (Byte 5) (Byte 6)
Value
(Byte 7) (Byte 8)
3.5.4 Restart
A restart is carried out by briefly disconnecting ETS from the power supply. A restart can also be performed by writing the string "boot" into the index 104.
Master
Index
(Byte 1) r/w
(Byte 2) dc
(Byte 3) ack
(Byte 4) (Byte 5)
Value ( "boot")
(Byte 6) (Byte 7) (Byte 8)
" b " 0x6F " o " 0x74
4 Sending the measured value
Depending on the configuration, the ETS sends the current temperature via message. The configuration was described in the previous chapter. In addition to being sent cyclically, the measured value can also be requested by means of a "request" message, PGN 59904
(0x00EA00) at any time.
5 Miscellaneous
The Software Identification (version number) can be requested by means of a "request" message on PGN 65242 (0x00FEDA).
Edition: 2021-04-12 HYDAC ELECTRONIC GMBH Part no.: 670057
ETS 4000 SAE J1939 V03 15
HYDAC ELECTRONIC GMBH
Hauptstr. 27
D-66128 Saarbruecken
Germany
Web: www.hydac.com
E-mail: [email protected]
Tel.: +49 (0)6897 509-01
Fax.: +49 (0)6897 509-1726
HYDAC Service
For enquiries about repairs or alterations, please contact HYDAC Service.
HYDAC SERVICE GMBH
Hauptstr. 27
D-66128 Saarbruecken
Germany
Phone: +49 (0)6897 509-1936
Fax: +49 (0)6897 509-1933
Note
The information in this manual relates to the operating conditions and applications described. For applications and/or operating conditions not described please contact the relevant technical department.
If you have any questions or suggestions or encounter any problems of a technical nature, please contact your HYDAC representative.
E
Edition: 2021-04-12 HYDAC ELECTRONIC GMBH Part no.: 670057