- Home
- Domestic appliances
- Climate control
- Temperature & humidity sensors
- Elis
- FLONET FH30 Series
- User manual
advertisement
Project design, installation and service manual
Page 26 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
4.6 Thermal insulation
When installed in thermally insulated piping, to prevent unnecessary heat loss, the meter sensor is usually provided with thermal insulation too.
In such cases, the following rules need be observed:
•
Insulation shall be applied onto the meter sensor only;
•
Maximum surface temperature of the sensor, whether thermally insulated or not, shall not exceed the values given in Section 3.4;
• The maximum insulation thickness shall not exceed 40mm (the thermal conductivity coefficient λ
0.045 (Wm -1 K -1 ) at 50
C; see standard EN 13787);
D
≤
•
In the cases of compact meter version, the part connecting the meter sensor and transmitter shall always remain bare;
•
The transmitter shall be protected from additional heating (by direct sunshine or heat emanating from nearby equipment).
4.7 Flowmeter heating
In measuring fluids with sub-zero operational temperatures, or at ambient temperatures close to the specified minimum fluid temperatures, it is permitted to provide the meter sensor with thermal insulation and auxiliary heating system.
•
The sensor heating can be facilitated by electricity or a suitable heat-carrying medium supplied through a special piping system;
•
In cases of electric heating, it is recommended to use a regulated AC power source with current switching at zero.
5 ELECTRICAL CONNECTIONS
5.1 Transmitter
5.1.1 Terminal box
Terminals
L
N
PE
AC power source
95 to 250VAC, 45 to 65Hz
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
ELIS PLZEŇ a. s.
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 27 of 72
Terminals
C (+)
D ( –)
PE
DC power source
24V ± 20% (19.2 to 28.8VDC)
1
2
3
4
5
6
7
8
Terminals
−
+
−
+
Output signals
A
B
OUT1
OUT2
−I (H1)
+I (H2)
Functions
RS-485 MODBUS RTU
Binary output
Current output
The output and communication signals shall be connected to the target devices via shielded cables.
The cable shielding shall be connected at one end only, to the PE terminal, located on the terminal blocks.
5.1.2 Excitation circuit
Excitation current
Maximum voltage:
I = 200mA
Umax = 30V
5.1.3 Signal cables
The maximum length of the signal cables depends on the measured fluid conductivity and electric parameters of the cables themselves.
To eliminate risk of electromagnetic interference via the connecting cables, the transmitter shall be located as close as possible to the meter sensor.
The relationship between the measured fluid conductivity and the maximum length of the cables connecting the meter transmitter and sensor is shown in the following graph:
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 28 of 72
ELIS PLZEŇ a. s.
15 30 45 60 75 90 105 120 135 150
Cable length (m)
The above graph applies to sensor sizes up to DN80. For sizes in excess of DN80, the maximum cable length shown in the graph shall be derated as follows:
L
DNXX
=
L
DN80
× DN80
DNXX
(m) where L
DN80 is maximum cable length determined from the graph for sensor sizes up to DN80
L
DNXX
is maximum cable length for the given sensor size (in excess of DN80)
DNXX sensor size in excess of DN80
Distance between the sensor and transmitter not exceeding 10m:
Fixed connection of the signal cable conductors to the transmitter terminals
Cable parameters: R = 80 Ω/km (loop 2 × 80 Ω/km)
Distance between the sensor and transmitter 10 to 150m:
The signal cable end provided with a connector with the matching counter piece at the transmitter
Cable parameters: R Ω/km loop 2 × Ω/km
The signal cables are included in the product delivery scope. In their order, the customer shall specify the cable length.
The flowmeter is calibrated with the connecting signal cable in place. The customer shall not modify or exchange the cable; such action shall be reserved to the authorised service staff or the meter manufacturer.
The connecting cable shall be fixed in position. Should it be left free, changes in the cable capacity due to its movement might adversely affect the measurement accuracy, especially at low fluid flow velocities.
Cable extension or shortening is not permitted. Replacement of a damaged cable shall be arranged with the meter manufacturer.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
5.2 Sensor connection box
Page 29 of 72
Sensor connection box
Signal cable connection table – the sensor protection class IP 67/IP 68
Terminal Description Conductor colour
E2
E1
FE
SP+
SP −
FE
PE
Electrode E2
Electrode E1
Brown BN
White WH
Grounding electrode Blue BU (shielding for the conductor pair BN, WH)
Excitation winding Green GN
Excitation winding Yellow YE
Grounding electrode Blue BU (shielding for the conductor pair GN, YE)
Protection conductor Yellow and green GNYE (the cable shielding)
Cond c o s leadin o e minals SP and SP− may be connec ed o disconnected only with the transmitter power source switched off.
The sensor designed with protection class IP 68 has a fixed connection of the signal cable conductors to the sensor terminals. In production, the terminal box is sealed and the terminals embedded in an impregnation compound protecting the sensor from the ambient humidity. The other end of the cable is provided with a connector facilitating connection to the meter transmitter.
5.3 Power and information cables
In operating environments free of explosion risk, the power and information cable connections do not require any special arrangement. Applicable to the meter installation work are standard procedures known from conventional measurement and control systems. However, due attentional shall be paid to the applicable national regulations and standards.
The flowmeter does not include any integrated line circuit breaker. Unless the meter configuration includes a moveable power cord and plug, a separate power switch or circuit breaker shall be used (see the provisions of section 6.11.3.1 of standard EN 61010-1).
The protective conductor of the power supply cable to be connected to the PE terminal must be longer than the L and N conductors. The PE conductor must be disconnected as last if the power cable is removed from the bushing. This PE terminal is located at the bottom of the terminal box of the instrument box.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 30 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
5.4 Cable placement
To minimise the effect of electromagnetic interference, the cables connecting the sensor and the meter transmitter shall be laid at least 25cm away from the power cables of other electric equipment.
In selecting cable routes, attention shall be paid to the risk of thermal degradation of the cable insulation due to nearby technological heat sources. All cables shall be laid outside the thermal insulation layers on piping.
The cable glands shall be properly sealed and tightened with suitable tooling. To prevent cables from being pulled out of the glands, their position shall be mechanically fixed no further than 0.3m away from each gland.
Outside the gland , the cable shall be bent to form a “dripping loop” the straight length of about 30mm of the cable is led horizontally from the gland and then bent down to form a loop).
5.5 Power supply specifications
The electrical circuits of the transmitter forming part of a FLONET FH30xx flowmeter are designed as floating, insulated from the ground potential.
The FH30xx electromagnetic flowmeter can be delivered with either AC or DC power supply.
AC power supply
•
95 to 250VAC, 45 to 65Hz, 3VA max.
•
Internal fuse T 1.25A/250 V, 5 x 20 mm
DC power supply
•
24V ± 20% (19.2 to 28.8VDC), 3W max.
•
Internal fuse T 2A/250V, 5 x 20mm
Special attention shall be paid to the power supply arrangement in cases of an electromagnetic flowmeter installed in a piping system provided with cathodic protection.
For more detailed information, see Section 5.7. ( Grounding and potential equalising ) hereof.
In locations with strong electromagnetic interference (e.g. in the vicinity of frequency converters), it is recommended to include a filter in the power supply lines. The filter shall be installed as close as possible to the meter transmitter.
Filter parameters:
Rated voltage:
Rated current:
250V/50Hz
0.5A or higher
Attenuation characteristic: 10kHz 10 to 20dB
10MHz 40dB
5.6 Input and output connections
Outputs from the flowmeter of the type series FLONET FH30xx are not intrinsically safe.
5.6.1 Multifunction outputs OUT1, OUT2
Functions and parameters
•
Passive outputs: electrically insulated from the ground and other inputs and outputs
•
Open collector: Umax = 30V, Imax = 30mA
•
Status in cases of power cut:
•
Output operational modes: open o Frequency: Frequency range 0 to 10kHz, duty cycle 1:1 o Pulse: Maximum frequency 100Hz o Binary:
Selectable pulse number
Pulse length setting 1 to 999ms
Exceedance of set limit values of measured quantities
Permanently closed
No-error condition
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 31 of 72
ELIS PLZEŇ a. s.
The output parameters of the frequency output are influenced by the capacity of the connected cable.
When transmitting a frequency output signal with a value reaching up to 10 kHz over long distances, this negative effect on the quality of the transmitted signal at the evaluation point must be considered.
Multifunction outputs – selectable functions
•
Pulses/frequency for Q+
•
Pulses/frequency for Q –
•
Pulses/frequency for IQI
•
Q > Qmax
•
|Q| > Qmax
•
Output negation
Pulse number determination for the pulse output
Restrictive conditions in setting the pulse output parameters:
•
Maximum output frequency: f max
= 100Hz
•
The middle period between pulses M shall be equal to or wider than the pulse width P .
Breaching this condition will result in an error message.
It holds:
M
P
P + M = T f =
1
T
P
T
M
In selecting the pulse number, the following requirement shall be met:
Q max
≤ 3.6 × V × f max
(m 3 /h, l/imp, imp/s) where: Q … fluid flow rate
V … volume per one pulse
P … pulse length f … pulse output frequency
T … cycle length
(m
(l)
3
(s)
(Hz)
(s)
/hod)
The flowmeter software permits setting the V values in steps shown in the table below:
V (l)
0.001 0.01 0.1 1 10 100 1000 10000
The pulse length in cases of electronic determination of the fluid volume passed through the sensor is recommended to be set at P min
= 5ms, which meets the condition for f max
at the pulse output equal to 100Hz. In cases of electro-mechanical counters, P min
is usually set at 50ms, corresponding to the maximum frequency at the pulse output of 10Hz.
Example:
Assume that a user specified for their flowmeter of DN100 the maximum operating flow rate:
Q max
= 150 m 3 /h (Q max
= 41.66 l/s … v 5.3 m/s)
For the fluid volume corresponding to one pulse (of length 5ms, f max
100Hz) it holds:
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 32 of 72
ELIS PLZEŇ a. s.
V
V
Q max
3.
6 × f max
(l/pulse, m3/h, Hz)
0.416 (l/pulse)
By selecting the next higher pulse number from the above table (1 litre per pulse) the user will make sure that the pulse output frequency will not exceed (for the specified Q max of 150 m 3 /hour) the value of
100Hz and, at the same time, verify the selection of the pulse length (5ms). The user may choose the
V values other than those from the basic selection in the above table, e.g. 0,5 litres/pulse.
Passive output
FLONET FH30xx DATA PROCESSING SYSTEM
Imax = 30mA Uextmax =30 V
Assignment of terminals
Output Terminal
3 −
OUT1
OUT2
4
5
6
+
−
+
Shielded cables must be used to connect the output signals.
The shield is only connected on one side, namely the PE terminal located on the terminal board.
5.6.2 Current output 4 to 20mA
Functions and parameters
•
Passive current output electrically insulated from the ground and other inputs and outputs
•
Umax = 30V
•
Rzmin = 250
•
Programmable function: o Volume flow rate
•
Fixed current setting in the range of 4 to 20mA
In cases of power cut, the current output will preserve the last value prior to the power failure .
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 33 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
Passive output
FLONET FH30xx DATA PROCESSING SYSTEM
Imax = 20mA
Imin = 4mA
Selectable functions of the current output
•
Output −Q ... +Q
•
Output 0 ... |Q|
•
Fixed current 4 ... 20mA
Current for |Q|
Uextmax = 30V
Current loop resistance:
Rz =
Uext − 8
0.02
(
, V, A)
Rzmin = 250 Ω
Rzmax = 800 Ω
Current for −Q ... +Q
The flow rates corresponding to 4 or 20mA can be either positive or negative, and their mutual relationships can be either “greater than” or “lower than”. Therefore, the user may select any one of six possible functions of I out
vs. flow rate Q:
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
ELIS PLZEŇ a. s.
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 34 of 72
Shielded cables must be used to connect the output signals.
The shielding is only connected on one side, namely on the PE terminal, which is located on the terminal board.
5.6.3 Communication interfaces
5.6.3.1 Communication interface RS-485 MODBUS RTU
CONTROL AND DATA-PROCESSING SYSTEM OPERATION
Communication interface: RS-485 MODBUS RTU according to standard EN 61158, electrically insulated
PC requirements: Windows 7 or higher OS upgrade (Linux, iOS) with JAVA 8u40 or higher, the FLOSET 4.0 communication software installed
* .Flo configuration file
Connecting cable:
USB / RS-485 converter with connection cables
Type A according to EN 61158-2 (a twisted pair of conductors, 90% shielding)
Interconnection:
FH 30xx Bus conductor
1
2
PE
A
B
Shielding
Detailed instructions regarding application of the RS-485 MODBUS RTU communication interface can be found the manual:
Es 90684K Communication interface RS-485 MODBUS RTU
Electromagnetic flowmeters FLONET FH30xx and FLONEX FXx11x
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 35 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
5.7 Grounding and potential equalising
To guarantee correct operation of the FH30xx electromagnetic flowmeter, it is necessary to ensure that the potential of the measured fluid before and after the flowmeter, the reference meter potential and the
PE protection conductor be equalised with the ground potential at the meter installation site. For the equipment grounding and potential equalising, use Cu conductor of cross-section 4mm 2 .
The external PE terminal on the transmitter box shall be internally connected to the reference meter potential.
Electrically conductive piping
Flanges on the conductive piping shall be connected to the PE terminals on the sensor and transmitter housings and to the ground potential.
The bolted connections between the piping and sensor flanges cannot be taken for a reliable and satisfactory conductive connection. It is recommended to provide threaded holes on the flanges for a reliable bolted connection of the grounding/equalising conductor.
It is not recommended to place the grounding or equalising conductors under the heads of the main flange bolts; such connection may be subject to corrosion and adversely affect the measurement accuracy.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
ELIS PLZEŇ a. s.
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 36 of 72
Piping made of insulating materials or piping with insulating lining
In such cases, the requirement for the fluid potential equalisation shall be met by two grounding rings installed before and after the flowmeter. Each grounding ring shall be inserted between two sealing rings.
The grounding rings are not included among the standard meter accessories , but they can be ordered with the product. Regarding chemical stability and resistance with respect to the measured fluid, the grounding rings shall meet the same criteria as the measuring electrodes.
In the cases of remote meter version, the PE terminal on the meter sensor and the transmitter box shall be interconnected by a Cu conductor of cross-section 4mm 2 .
This connection shall not serve the purpose of potential equalisation with any other equipment or devices.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 37 of 72
ELIS PLZEŇ a. s.
Piping with cathodic protection
If an electromagnetic flowmeter is to be installed into piping with cathodic protection, it is necessary to ensure that all flowmeter parts be electrically insulated from the piping. At the same time, the meter power source shall be insulated from the power grid. To ensure the overall piping conductivity, the installed meter shall be bypassed by Cu conductor of cross-section 6 mm 2 (connected to the piping flanges before and after the flowmeter).
The fluid potential shall be equalised with the reference meter potential (the PE terminal potential) by means of grounding rings. The grounding rings shall also be insulated from the piping.
6 METER COMMISSIONING
6.1 Check on electrical connections
Prior to meter energising, check and make sure that:
•
The power network voltage complies with the specifications on the meter rating plate;
•
The power network is properly protected;
•
All terminals and electrical connections are properly tightened;
•
The installation cables are: o intact, o connected at their ends to the correct terminals in the flowmeter and the co-operating equipment, o secured against incidental excessive stress (pulling out of the respective glands), and
•
The meter grounding and potential equalising has been carried out as specified in the product manual.
6.2 Check on meter housing tightness
To attain the parameters of the equipment protection class referred to in Chapter 8 (METER
SPECIFICATIONS), the flowmeter installation shall be carried out in observance of the following directions:
•
Use only cables of external diameters corresponding to the sizes of the cable glands installed;
•
Form dripping loops on the cables;
•
Avoid meter installation position where the cable glands lead upwards;
•
Tighten properly all covers and lids on the meter housings.
Following every service action:
•
Check the condition (integrity and intactness) of all sealing elements and surfaces;
•
Using suitable tooling, tighten all cable glands and meter housing covers.
6.3 Check on the installed meter
The flowmeters are supplied calibrated with verified functions and parameters set according to the customer specifications.
Prior to the meter commissioning, inspect the meter installation site in reference to the requirements of
Section 4.4 above, and assess the possible adverse effects from the nearby technological equipment such as:
•
Undesirable meter warming by external heat sources;
•
Excessive temperature stress on cable insulation;
•
Vibrations and shocks in the piping, and others.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 38 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
6.4 Check on the meter operation conditions
Prior to filling the piping and the installed meter sensor with the fluid to be measured, make sure that the fluid parameters (temperature and pressure) are within the limits specified on the meter plate, and that any risk to life or health of personnel is excluded.
7 OPERATION
7.1 Meter energising
7.1.1 Display status
Upon turning the power on, all meter modules will undergo the initiation procedure. Following the display test, the basic screen format with the following data will be shown:
•
Current volume flow rate
(if an error is detected, an error code is displayed next to the current flow)
•
Aggregate fluid volume passed through the meter sensor in the positive direction;
•
Aggregate fluid volume passed through the meter sensor in the negative direction.
The bar chart at the top of the display shows the current flow rate related to the specified maximum flow rate.
Basic screen format
7.2 Front panel and control buttons
7.2.1 Display
The meter is provided with a colour OLED display of 128 x 64 pixels where all the measured quantities, flowmeter parameters and important user information can be visualised. The display control is facilitated by means of four optical buttons (optical reflex sensors).
7.2.2 Control button functions
Button locations with respect to the display
▲
1 ⃝
4
■■■■■■■■■■■■■■■■■■■
1,025
m3/h
45,34
- 25,1
1
⃝
ESC m 3
►
⃝
⃝
ENTER
2
3
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 39 of 72
ELIS PLZEŇ a. s.
Comments:
1
2
3
4
Optical buttons (optical reflex sensors)
Instantaneous flow rate
Item selected from MENU – DISPLAY, or error messages
Instantaneous flow rate in the form of a bar chart
Control button functions
Buttons ▲, ►, ENTER are actuated by a short touch with a finger on the button.
Button ESC is actuated by either a short (0.3s) or long (> 2s) touch with a finger.
▲ Moving in a menu to the next item above
Cyclic functions: Setting a numeric value 0 – 9 (increasing)
►
Change in sign +/-
Moving in a menu to the next item below
Moving the position mark (cursor) in setting numeric values
ENTER Confirmation of selected action
ESC Departure from current operation to the previous menu item without any parameter change
ESC 2 s Finger touch > 2s: return to the basic screen format
Actuated can be just one button at a time; the other buttons shall remain uncovered.
To press the button repeatedly, you must first zoom out the finger and then reinsert.
7.3 Flowmeter control
7.3.1 Manual control
Manual meter control and selection of menu items using optical buttons do not require any special skills; these functions are intuitive and user-friendly.
7.3.1.1 Basic screen
1,025 m3/h
45,34 m3
-
25,1
The basic screen always shows information on instantaneous flow rate (lines 1 and 2).
The remaining two lines are reserved for supplementary data the user may select from the menu
Display .
The meter is supplied with these two lines pre-set to show the aggregate flow volumes passed through the sensor in the positive and negative directions.
If the flowmeter diagnoses a condition that may adversely affect the meter's operation, an error code is displayed next to the instantaneous flow value in line 1. If there is a serious error that can significantly affect the accuracy of the measurement, zero is displayed in the instantaneous flow field (eg ADC failure, interrupted or short-circuit excitation, unfilled piping, strong electromagnetic interference, etc.).
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 40 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
Error and diagnostic messages
Error code
E00 No error
Error description
E01
E02
E03
E04
E05
E06
E07
E08
ADC range overflow
Step change in flow
Error reading / writing to memory
Other electronics block error
Warning - zero flow cannot be calibrated
Low current excitation
Short circuit in coil circuit
Information - zeroing in progress, not measuring
E09
E10
E11
E12
E13
E14
High resistance of measured medium
OUT1 output error
OUT2 output error
Information - IOUT out of range
The time is not set correctly
Overload flow Q4 exceeded
As long as you move in the control or parameter-setting menus, the display remains in the active mode (back-lighted).
The backlighting time can be set in the menu item Backlighting time . Deactivated display will automatically be activated upon touching any control button.
User password
To enter the Main menu from the Basic screen, actuate the ESC 2 s button and enter your user password.
The initial user password pre-set in production is 0000.
Changing the access password is possible only with the FLOSET 4.0 program via the RS-485
MODBUS RTU communication link.
To return to the Basic screen format actuate the ESC 2 s button.
Should no control button ( ▲, ►, ESC, ENTER ) be actuated during the recent three minutes, or should the specified backlighting time elapse before that, the display will return automatically to the Basic screen format.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Language
Page 41 of 72
ELIS PLZEŇ a. s.
7.3.1.2 Main menu
Electromagnetic flowmeter FLONET FH30xx
To move downward in the menu, use button ►
Displayed data
Current output
Output functions
Serial line
Date setting
Time setting
Volume resetting
Number of samples
Suppressed flow rate
Zero setting
Manufacturing data
To move upward in the menu, use button ▲
Factory setting
Simulated flow
The selected item will be shown in a highlighted window where it can be opened by actuating the ENTER control button. When scrolling up or down in the menu, always four neighbouring items will be shown.
The manufacturer supplies the flowmeter verified as to its functions, calibrated and with parameters set according to the customer’s order. If installed in the user’s technology in observance of the requirements specified in the product manual, the flowmeter will be ready for immediate operational start.
In cases where the user requires an accelerated procedure for the meter commissioning and setting of the meter parameters with respect to the given operational conditions and the cooperating higher-level control system, it suffices to set the parameters shown in bold print in the above list of the main menu items.
Detailed description of the meter control procedures is given in the manual:
Es 90686K Electromagnetic flowmeters of the type series FLONEX FXx11x and FLONET
FH30xx Meter control instructions
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
FLONET FH30xx control menu structure
Page 42 of 72
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 43 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
7.3.2
Remote meter control using the FLOSET 4.0 program
Flowmeters of the type series FLONET FH30xx are provided with the digital interface RS-485 MODBUS
RTU and interface HART ® .
Through an interface RS-485 and communication software FLOSET 4.0 the meter can be connected as subordinated equipment to a computer (a personal, notebook or tablet computer) with Windows 7 or higher OS upgrade (Linux, iOS) with JAVA 8u40 or higher.
FLOSET 4.0 is not included in the scope of delivery.
On request we can deliver:
• LOSE . software
• LOSE . software User Guide
• lowme e confi a ion da a * .flo
• USB S-485 converter with connection cables
Program FLOSET 4.0 makes it possible to:
•
read the measured quantities (volume flow rate and flow volumes passed through the meter sensor in both directions);
•
set the parameters of the measured quantities to be displayed (units and number of decimal positions);
•
set the multifunction output parameters (in the binary, pulse or frequency operational modes), and the current output parameters;
•
set the flowmeter language, date and time;
•
set the digital interface parameters;
•
set the data archiving parameters and read the archived data;
•
monitor extraordinary operational events and read the archived data on such occurrences.
7.3.2.1 Communication interface MODBUS RTU
The physical form of this interface consists of a serial line RS-485 of the following parameters:
•
Speed 300, 600,1200, 2400, 4800, 9600, 19200, 38400, 57600 Bd;
•
8 data bits, 1 stop bit;
•
No parity.
Detailed description of communication via interface RS485 MODBUS RTU is given in the manual:
Es 90664K Communication interface RS-485 MODBUS RTU
Electromagnetic flowmeters FLONET FH30xx and FLONEX FXx11x
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 44 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
8 TECHNICAL DATA
Basic information and parameters
Measurement principle The Faraday induction law
Minimum fluid conductivity 10 μS/cm, 20 μS/cm for demineralised water
Measured flow velocity range
Rated inner diameter of connected piping
Flowmeter design version
Measuring and grounding electrode materials
Measured fluid temperature
/ sensor lining material
0.025 to 10 m/s
DN15 to DN1200
NPS ½ “ to 24“
Compact
Remote
Standard:
•
Stainless steel 1.4571 (SR, HR, SPR)
•
Hastelloy C276 (PTFE, E-CTFE)
Optional:
•
Hastelloy C276
•
Titanium
•
Tantalum
•
Platinum and rhodium
Flanges Lining
SR
Temperature range
( C)
−20 to +80
HR
SPR
PTFE
E-CTFE
SR
HR
SPR
PTFE
E-CTFE
0 to +80
+5 to +80
−20 to +110
−20 to +110
−35 to +80
0 to +80
+5 to +80
−35 to +150
−35 to +120
Sensor design version
Grounding
Manufacturing materials
Surface finish
AC power supply
Sensor size
DN25 to DN1200
DN25 to DN1200
DN40 to DN1200
DN15 to DN1200
DN300 to DN1200
DN25 to DN1200
DN25 to DN1200
DN40 to DN1200
DN15 to DN1200
DN300 to DN1200
Flanged DN15 to DN1200
Wafer DN25 to DN200
On flanges
With grounding rings
Grounding electrode (DN25 to DN1200 for PTFE, HR, SR)
(DN40 to DN1200 for SPR)
(DN300 to DN1200 for E-CTFE)
Transmitter housing: pressure casting, Al alloy
Sensor connection box: pressure casting, Al alloy
Sensor: measuring tube – stainless steel 1.4301
Sensor flanges and casing: standard – carbon steel
optional – stainless steel 1.4301
Transmitter housing: powder paint
Sensor connection box: powder paint
Sensor flanges and casing: standard – polyurethane paint
All-stainless-steel sensor: shot blasting
95 to 250VAC, 45 to 65Hz, 3VA max.
Internal fuse: T 1.25 A/250 V, 5 x 20 mm
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 45 of 72
ELIS PLZEŇ a. s.
DC power supply
Magnetic field
Back-up battery
Operating environment
Protection class
Pressure loss
24V
± 20% (19.2 to 28.8 VDC) , 3W max.
Internal fuse: T 2A/250V, 5 x 20mm
Pulse unidirectional field
Selectable frequencies 1.56Hz; 3.125Hz; 6.25Hz;12.5Hz
CR2032
Free of explosion risk
Transmitter: IP 67, optional IP 68
Sensor: standard IP 67, optional IP 68 (remote meter version)
Negligible provided the sensor and connected piping are of the same inner diameter
30min Starting time
Functions and properties
Meter display
Control elements
Language
Physical units of displayed quantities
Functions
Zero insensitivity
Condition following power cut
Graphic backlighted OLED, 128 x 64 pixels
Optical reflex sensors actuated by touch across the front viewing window in the transmitter
Czech, English, Dutch, Spanish, Polish, French, Italiano, German,
Russian or Portuguese
Metric
US
Imperial
Bidirectional measurements of:
•
Volume flow rate
•
Aggregate fluid volume passed through the meter sensor
Communication with external equipment
Archiving of measured data and extraordinary operational events
Sensor flooding check
Selectable
Summary counters:
Meter configuration and setting:
No change
No change
Diagnostic and error messages: Stored
Multifunction outputs: Open
Current output The last value prior to the power cut retained
Process parameters
Fluid temperature
Pressure class
Compact meter version: standard −20
C to +70
C
optional −35
C to +70
C
Remote meter version: standard −20
C to +110
C
optional −35
C to +150
C
PN 40 (4.0MPa) for DN15 to DN50
PN 16 (1.6MPa) for DN65 to DN200
PN 10 (1.0MPa) for DN250 to DN700
PN 6 (0.6MPa) for DN800 to DN1200
Class 150 ASME B16.5 for NPS ½“ to 24“
≤ 2%
≤ 5%
Solid particle content
Gas content
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Storage temperature
Page 46 of 72
ELIS PLZEŇ a. s.
Environment
Ambient temperature
Electromagnetic flowmeter FLONET FH30xx
Standard: −20°C to +70°C, no condensation
Optional: −40°C to +70°C, no condensation
−10°C to +70
C, no condensation (for HR , SR, PTFE, E-CTFE)
+5°C to +70
C, no condensation (for SPR)
Measurement accuracy
Reference conditions
Measurement accuracy at reference conditions
See Chapter 9 (CALIBRATION)
Standard: Class 2 acc. to EN ISO 4064-1
Q
3
/Q
1
= 400
On request, for example:
±0.5% of the measured value for flow rate 5 to 100% Q
4
±0. % of the measured value for flow rate 10 to 100% Q
4
Outputs
1 × Current output 4 to 20mA
2 x Multifunctional output
Passive: electrically insulated from the ground and other outputs;
Uextmax = 30V, Uextmin = 8V, Rzmax = 800 Ω, Rzmin = 250
Communication interfaces
Passive: electrically insulated from the ground and other outputs;
Uextmax = 30V, Imax = 50mA
Open collector
Operational modes:
Frequency: frequency range 0 to 10kHz, duty cycle 1:1
Pulse: Maximum frequency 100Hz
Pulse length 1 to 999ms
Binary:
Selectable pulse number
Output negation
Exceeding limit values of measured quantities
Error messages
Output negation
•
RS-485 MODBUS RTU, electrically insulated from the ground and other outputs
Cables
Data and power cables
Signal cable for remote meter version
Communication cable
Cable glands
Common cables for application in measurement and regulation systems
Data cables: twisted pair of conductors, 90% shielding
Supplied with the meter:
•
Sensor version of IP 67: maximum cable length 150 m
•
Sensor version of IP 68: maximum cable length 150 m
Twisted pair of conductors with common shielding; bus-bar cable, type A according to standard EN 61158-2
Compact meter version:
•
Transmitter: 2 pcs of glands M20x1.5
Remote meter version:
•
Transmitter: 2 pcs of glands M20x1.5
Sensor connection box: 1 pc of gland M20x1
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Page 47 of 72
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
9 CALIBRATION
9.1 General
The flowmeter is supplied verified as to its functions, calibrated and with parameters set according to the customer’s requirements.
The measurement accuracy of the flowmeter in its standard form and configuration is guaranteed to meet the provisions of the international standard EN ISO 4064-1 : Water meters for cold drinking water and hot water .
Unless agreed otherwise with the customer, the flowmeters are calibrated using the frequency output 0
– 10kHz.
Upon special requirement and agreement with the flowmeter manufacturer, the meter calibration may be carried out using alternative, i.e. pulse or current outputs.
The guaranteed measurement accuracy parameters shall always be related to the type of output which was used for the meter calibration. The remaining two types of output are recommended to be used for measurements with accuracy lower by 1 to 2% compared to that associated with the calibrated output.
For inspection or comparison measurements at the customer’s premises, or metrological verification of the meter parameters, the same type of electric output as that used for the initial calibration at the manufacturing plant shall be selected. Such measurements shall be performed under specified reference conditions.
At such measurements it is important to connect the hydraulic meter section (the sensor) into the hydraulic circuit on the test stand using connection elements (flanges, threaded fittings, fittings used in food-processing lines or others) of the same type, size and design as found on the meter sensor, to prevent occurrence of hydraulic disturbances that might significantly affect the meter measurement accuracy.
9.2 Reference conditions
Measured fluid: water, temperature 22
C ± 4
Ambient temperature: 22
C ±
Electrical conductivity of the measured fluid > 300μS
Straight piping sections ≥ 10 before and 5 after the flowmeter
Minimum medium pressure at the meter output: 1 bar
Time for the meter temperature stabilisation: > 30min
The sensor to be centred, grounded and supplied with power as required by the product manual
The meter shall be set for zero flow rate
9.3 Measurement accuracy
9.3.1 Flowmeter FLONET FH30xx – standard measurement accuracy
The meter accuracy shall meet the requirements of standard EN ISO 4064-1 (Water meters for cold drinking water and hot water).
Definitions according to EN ISO 4064-1:
Q
4
Q
2
Q
3
= 1.25
Q
1
= 1.6
Q
4 flow rate for fluid flow velocity at the meter sensor of 10 m/s.
Q
1
flow rate for fluid flow velocity at the meter sensor of 0.025 m/s
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
ELIS PLZEŇ a. s.
Electromagnetic flowmeter FLONET FH30xx
Standard metrological parameters according to EN ISO 4064-1
6
4
2
0
-2
-4
-6
Q1 Q2 Q3
Page 48 of 72
Q4
Rated inner diameter
Flow rates Q
1
, Q
2
, Q
3
and Q
4
for various meter sizes
Overloading flow rate Q
4
Continuous flow rate Q
3
Transient flow rate Q
2
Minimum flow rate Q
1
DN (m 3 /h) (m 3 /h) (m 3 /h) (m 3 /h)
80
100
125
150
200
250
300
350
15
20
25
32
40
50
65
400
500
600
700
800
900
1000
1200
4 500
7 200
10 000
14 000
18 000
23 000
28 000
40 000
180
280
430
650
1 150
1 800
2 520
3 500
6.5
12
18
30
45
72
120
144
224
344
520
920
1 440
2 016
2 800
5
10
14
24
36
58
96
3 600
5 760
8 000
11 200
14 400
18 400
22 400
32 000
14.40
23.04
32.00
44.80
57.60
73.60
89.60
128.00
0.0208
0.0384
0.0576
0.0960
0.1440
0.2304
0.3840
0.5760
0.90
1.38
2.08
3.68
5.76
8.06
11.20
9.00
14.40
20.00
28.00
36.00
46.00
56.00
80.00
0.0130
0.0240
0.0360
0.0600
0.0900
0.1440
0.2400
0.3600
0.56
0.86
1.30
2.30
3.60
5.04
7.00
Measurement range Q
3
/Q
1
400
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
Project design, installation and service manual
Electromagnetic flowmeter FLONET FH30xx
Page 49 of 72
ELIS PLZEŇ a. s.
9.3.2 Flowmeter FLONET FH30xx – increased measurement accuracy
For zero flow-rate setting and reference conditions:
Relative error
±0.5%
±0. % of the measured value
Flow rate range
5 –100% Q
4
10 –100% Q
4 of the measured value
Upon agreement with the manufacturer, flowmeters may be supplied with other (optional) accuracy parameters.
10 METER DESIGN DETAILS
10.1 Transmitter
Transmitter C14.00/C15.00 is fitted in a box made of aluminium alloy with removable front and rear covers.
Behind the window in the front cover there is a backlighted OLED display of 128x64 pixels. The flowmeter control is facilitated by optical buttons (optical reflex sensors) actuated by touching the respective spots on the front window.
The transmitter terminals can be accessed upon removal of the solid rear cover. When closed, the lid position is secured by means of an Allen bolt.
External cables can be brought into the terminal compartment via two glands accommodated in threaded holes M20 x 1.5. Should the meter configuration or higher number of output signals require so, inserted in the cable gland can be a sealing insert with more holes to hold the required number of cables.
This sealing insert is not included among the standard meter accessories.
Located at the top of the transmitter box is a grounding bolt and a flat area intended for the flowmeter rating plate. The transmitter plate is attached to the rear cover on the transmitter housing.
The surface finish of the housing consists of powder paint coating.
The connections of the transmitter terminals are described in Chapter 5 (ELECTRICAL CONNECTIONS).
The transmitter for the compact meter version (including a sensor of protection class
IP67) is supplied with the signal cable attached.
The transmitter for the remote meter version (used in combination with a sensor of protection class IP 68) is provided with a connector for the signal cable connection. The other end of the signal cable is attached to the sensor where the terminals inside the hermetic connection box are embedded in an insulating compound.
10.2 Sensor
The induction sensor consists of a measuring tube made of non-magnetic steel with insulation lining, two measuring electrodes and, in some cases, one grounding electrode. Located outside the measuring tube is a winding the function of which is to generate electromagnetic field perpendicular to the measuring electrode axis. The excitation winding and measuring electrodes are protected by the sensor housing made of carbon or stainless steel. In its standard design version, the sensor is provided with flanges according to EN 1092-1 or ANSI B16.5. Upon agreement with the manufacturer, other types of flanges can be provided.
The sensor can also be supplied in all-stainless-steel design.
ELIS PLZE Ň a. s., Luční 425/15, 301 00 Plzeň, Czech Republic, phone.: +420 377 517 711, fax: +420 377 517 722 Es 90678K
advertisement
Related manuals
advertisement
Table of contents
- 5 BASIC INFORMATION
- 5 Application
- 6 Meter properties and functions
- 6 Important user information
- 6 Safety instructions
- 6 Liability
- 7 Product warranty
- 7 Representations and certificates
- 8 METER IDENTIFICATION
- 8 FLONET FH30xx flowmeter type designation
- 8 Scope of delivery
- 8 Compact meter version FLONET FH30x
- 8 Remote meter version FLONET FH30x
- 9 Associated documents
- 9 Flowmeter rating plates
- 9 Main meter plate
- 9 Transmitter plate
- 10 Sensor plate
- 10 METER DESIGN AND MATERIAL VERSIONS
- 10 Compact and remote meter versions
- 12 Operating pressure of the measured fluid
- 14 Sensor dimensions
- 16 Sensor lining
- 16 Electrode materials
- 17 Sensors for flowmeters FLONET FH30xx; review of sensor design and material versions
- 18 INSTALLATION
- 18 Taking over
- 18 Meter handling
- 18 Storage
- 19 Installation conditions
- 19 General principles
- 19 Straight piping sections
- 20 Suppression of the pump effects
- 21 Suppression of the effects of closing valves
- 21 Suppression of vibration effects
- 22 Piping stacks
- 22 Sensor flooding
- 22 Free discharge points
- 23 Tightening torque
- 26 Thermal insulation
- 26 Flowmeter heating
- 50 Cable gland sizes
- 50 Company seals
- 51 Dimensions and weight
- 51 Sensor
- 51 Flanges according to EN
- 52 Flanges according to ASME B
- 53 Wafer sensor
- 54 Transmitter
- 54 Transmitter for compact meter version
- 54 – sensor protection class IP
- 55 Sensor connection box
- 56 FLOWMETER FAULTS
- 56 General rules
- 56 Spare PC boards and components
- 56 Software and simulation devices
- 57 Fault identification
- 58 Meter repair procedures
- 61 MAINTENANCE
- 61 SERVICES
- 61 WARRANTY
- 61 Warranty services
- 62 Post-warranty services
- 63 ORDER NUMBER
- 70 ASSOCIATED DOCUMENTS AND STANDARDS
- 71 ANNEXES
- 71 Representation on meter decontamination