When using the closed cover cap, there is no pressure compensation of the measuring cell any more� This results in measurement deviations caused by:

• fluctuations of the atmospheric pressure

• pressure fluctuations inside the unit in case of temperature fluctuations

(Δ 10 K ≤ 30 mbar).

6 Electrical connection

The unit must be connected by a qualified electrician�

The national and international regulations for the installation of electrical equipment must be adhered to�

Voltage supply according to EN 50178, SELV, PELV�

► Disconnect power�

► Connect the unit as follows:

OUT1 positive switching OUT1 negative switching

Pin 1

Pin 3

Ub+

Ub-

Pin 4 (OUT1) • Binary switching output pressure monitoring

Pin 2 (OUT2) • Analogue output for system pressure

Core colours of ifm sockets:

1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black)

14