General points concerning Fipio bus
The Fipio Bus
General
Fipio is a field bus which allows the decentralization of the inputs/outputs of a PLC station and its industrial peripheral devices nearest to the operational part.
Fipio bus is part of the WorldFIP product range from Schneider Automation S.A.S.
From a PLC station whose processor has a built-in Fipio link, the Fipio bus is used to connect 1 to
127 devices such as:
Momentum remote input/output modules (discrete, analog and counting modules),
TBX IP20 remote input/output modules (discrete and analog modules),
TBX IP65 and IP67 remote input/output modules (discrete modules),
XBT-F terminals,
Lexium, ATV 58 variable speed controllers,
Devices which conform to standard profiles,
Agent PLCs, PCs,
Inductel stations,
An AS-i gateway.
The Fipio field bus can be used in a single architecture (mono-station) or in a more complex architecture (multi-station) where several Fipio segments can be brought together by a local network at a higher level such as Fipway or Ethernet TCP_IP for example.
The Fipio protocol uses producer/consumer type exchanges and the bus is managed by a bus arbiter.
Manager PLC
A PLC station which has a built-in Fipio link is called a manager PLC
see page 30
.
Agent PLC
A PLC station with a PCMCIA card installed in a host slot is called an agent PLC
see page 32
14
35008155 12/2018
General points concerning Fipio bus
Main Characteristics
Structure
Nature
Topology
Access method
Communication
Privileged exchanges
Open field bus, conforming to World FIP and FIP standards.
Devices linked by chaining or branching.
Managed by a bus arbiter
By exchange of variables which can be accessed by the user in the form of Control Expert objects and X-Way datagrams.
Cyclical exchange of status variables and remote input/output commands
Transmission
Binary rate
Medium
1 Mb/s.
Shielded twisted pair (150 Ohms of characteristic impedance) or fiber optic.
Configuration
Number of connection points
Number of segments
128 logic connection points for whole architecture
15 maximum (in cascade format) using electrical or optical repeaters (14 maximum in cascade format).
Number of repeaters
PLC
Length
An electrical or optical repeater is required every 1000 meters or every 32 devices.
One manager PLC (connection point address 0).
Programming terminal One programming terminal (must be connected to connection point
63).
The length of a segment depends on its type of branches:
1000 meters maximum without repeater.
1500 meters maximum between the devices which are the furthest apart.
WARNING
UNEXPECTED EQUIPMENT OPERATION
You are advised against connecting/disconnecting elements from the Fipio bus while powered up as certain devices may then not restart.
Failure to follow these instructions can result in death, serious injury, or equipment damage.