The IODDT Type T_GEN_MOD Applicable to All Modules. Schneider Electric Premium and Atrium Using EcoStruxure™ Control Expert - Fipio Bus
जाहिरात
जाहिरात
Fipio language objects
The IODDT Type T_GEN_MOD Applicable to All Modules Section 9.2
The IODDT Type T_GEN_MOD Applicable to All Modules
Details of the Language Objects for the IODDT of Type T_GEN_MOD
At a Glance
All Premium PLC modules have an associated IODDT of type T_GEN_MOD .
Observations
In general, the meaning of the bits is given for bit status 1. In specific cases an explanation is given for each status of the bit.
Not all bits are used.
List of Objects
The table below presents the objects of the IODDT:
Standard symbol
MOD_ERROR
EXCH_STS
STS_IN_PROGR
EXCH_RPT
STS_ERR
MOD_FLT
MOD_FAIL
CH_FLT
BLK
CONF_FLT
NO_MOD
EXT_MOD_FLT
MOD_FAIL_EXT
CH_FLT_EXT
BLK_EXT
Type
BOOL
INT
BOOL
INT
BOOL
INT
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Access Meaning
R Module error bit.
Module exchange control word.
Reading of module status words in progress.
Exchange report word.
Error when reading status words of the module.
Module internal error word.
Internal fault, module unserviceable.
Faulty channel(s).
Terminal block fault.
Address
%I\2.e\0.m.MOD.ERR
%MW\2.e\0.m.MOD.0
%MW\2.e\0.m.MOD.0.0
%MW\2.e\0.m.MOD.1
%MW\2.e\0.m.MOD.1.0
%MW\2.e\0.m.MOD.2
%MW\2.e\0.m.MOD.2.0
%MW\2.e\0.m.MOD.2.0
%MW\2.e\0.m.MOD.2.2
Hardware or software configuration error.
%MW\2.e\0.m.MOD.2.5
Module missing or inoperative.
%MW\2.e\0.m.MOD.2.6
%MW\2.e\0.m.MOD.2.7
Internal error word of the module (Fipio extension only).
Internal fault, module unserviceable (Fipio extension only).
%MW\2.e\0.m.MOD.2.8
Faulty channel(s) (Fipio extension only).
%MW\2.e\0.m.MOD.2.9
Terminal block fault (Fipio extension only). %MW\2.e\0.m.MOD.2.10
35008155 12/2018
159
Fipio language objects
Standard symbol
CONF_FLT_EXT
NO_MOD_EXT
Type
BOOL
BOOL
Access Meaning
R Hardware or software configuration fault
(Fipio extension only).
R Module missing or inoperative (Fipio extension only).
Address
%MW\2.e\0.m.MOD.2.13
%MW\2.e\0.m.MOD.2.14
160
35008155 12/2018
Premium and Atrium Using EcoStruxure™ Control Expert
Standard profiles
35008155 12/2018
Fipio communication standard profiles Chapter 10
Fipio communication standard profiles
Subject of this Chapter
This chapter introduces devices compatible with the standard communication profiles for use with the Fipio bus and its services.
What Is in This Chapter?
This chapter contains the following sections:
Section
10.1
10.2
10.3
10.4
Topic
Introduction to standard Fipio communication profiles
Configuration of the Fipio bus standard profiles
Debugging the Fipio bus standard profiles
Language objects associated with the Fipio bus standard profiles
Page