Fipio hardware implementation
TSX FPP 10 PCMCIA card Section 2.3
TSX FPP 10 PCMCIA card
Subject of this Section
This Section deals with the installation of a TSX FPP 10 PCMCIA card.
What Is in This Section?
This section contains the following topics:
Topic
Introduction
Description
Connection of the TSX FPP 10 card
Precautions to be taken when connecting PCMCIA card
Installation
Mounting Cards and Cables
Displaying operating state of PCMCIA cards
Visual Diagnostics for TSX FPP 10 PCMCIA Card
Consumption of PCMCIA card
Page
32
35008155 12/2018
Fipio hardware implementation
Introduction
General
Premium/Atrium PLC stations connect to communication networks, buses and links via PCMCIA communication cards.
The card to be connected is a metal unit whose dimensions comply with PCMCIA extended type
III format.
The PCMCIA card is installed in the host slot of the processor of Premium PLCs.
The PCMCIA card can also be used in devices which have a type III host slot, such as XBT terminals or third-party devices, such as PC compatible devices, for example.
Illustration:
NOTE: It is prohibited to connect PCMCIA cards when the power is switched on.
Definition
An agent PLC is a PLC with a connected PCMCIA card.
35008155 12/2018
33
Fipio hardware implementation
TSX FPP 10 card
The PCMCIA card used to connect a Premium/Atrium PLC station to a Fipio bus is the TSX FPP
10.
The PCMCIA card is installed, operated and maintained using Control Expert programming and operation software for all PLCs in the Premium/Atrium family.
34
35008155 12/2018
Fipio hardware implementation
Description
General
PCMCIA type III (extended) communication cards are built into a metal unit with the following dimensions:
Length: 85.5 mm
Width: 51 mm
Height: 10 mm
The front of the card is designed to display the operating status of communications as well as the physical connection to the network.
Mechanical configuration
The mechanical configuration of the card must be adapted by mounting a removable cover, depending on the type of installation desired:
Type of installation
Installation on a
Premium type processor.
Installation on an Atrium type processor.
Installation on a PC compatible device.
Configuration
Removable cover with wings. Screws are provided to fix it to the host module (marked 3 on illustration)
Removable cover with wings. Screws are provided to fix it to the
Atrium processor
(marked 2 on illustration).
Removable cover
(marked 1 on illustration).
Illustration
NOTE: The covers with wings, mounted on PCMCIA cards, prevent any accidental removal when switched on and guarantee that the card remains in good working order.
The two covers (1) and (3) are provided with the PCMCIA card. The cover (2) is provided with the
Atrium processor.
Connection to the network is achieved by connecting the link cable to the front of the card. A guidance system is used to prevent anything being mounted incorrectly.
The product reference label informs the user of the type of physical layer supported by the card.
35008155 12/2018
35
Fipio hardware implementation
Connection of the TSX FPP 10 card
General
The TSX FPP 10 PCMCIA card is connected to the Fipway bus using a connector such as a TSX
FP ACC 3 or TSX FP ACC 4.
To connect the PCMCIA card to the ACC3/ACC4 connector the user may use:
Either a 1 m cable, product reference TSX FP CG 010.
Or a 3 m cable, product reference TSX FP CG 030.
Items required for connecting a Premium/Atrium PLC to the remote inputs/outputs Fipio bus:
36
35008155 12/2018
Fipio hardware implementation
Precautions to be taken when connecting PCMCIA card
General
NOTICE
PCMCIA CARD DESTRUCTION
Cables (TSX FP CG 010/030) are to be connected and disconnected from the PCMCIA card only when the power is switched off
Failure to follow these instructions can result in equipment damage.
CAUTION
PCMCIA CARD DESTRUCTION
Power off the module before inserting or removing the PCMCIA card.
Failure to follow these instructions can result in injury or equipment damage.
When removing or inserting the card, the unit is not guaranteed to be operational.
The PCMCIA card must be equipped with a PLC version cover and be screwed into the reception
module before the power is switched on (see Mechanical configuration,
page 35
The ferrule, placed in direct contact with the PCMCIA card device, is used to drain electrical interference carried by the link cable braids.
35008155 12/2018
37
Fipio hardware implementation
Installation
Installation
The TSX FPP 10 card can only be installed in the host slot of processors. It cannot be installed in the module TSX SCM 21601
Application-specific channel and network connection
The installation of the card in the processor does not count as an application-specific channel or as a network connection.
38
35008155 12/2018
Fipio hardware implementation
Mounting Cards and Cables
PCMCIA Card Details
Illustration:
PCMCIA cards are made up of the following elements:
2
3
Number Designation
1 Equipped card
4
Body made of zamac
PCMCIA connector
Upper cover
5
6
Removable cover
Link cable with ferrule
Comments
Receives electronic components.
-
Connector with 20 connection points.
Houses the product reference label which shows the type of PCMCIA card
Ensures the card is displayed in its slot. The names of the two LEDs are printed on the front of the removable cover. This cover also allows the
PCMCIA card to be fastened to the processor.
The ferrule placed on the end of the cable nearest to the PCMCIA card prevents the cable being pinched by the removable cover. This ferule also eliminates the risk of causing a bending radius which can damage the quality of the link.
35008155 12/2018
39
Fipio hardware implementation
Assembly for TSX P57 1•4 to TSX P57 5•4 Processors
To assemble the transmission card for the processor or the TSX SCY 21601, first remove the cover which is screwed on the device and then follow the instructions below:
Step
1
2
3
4
5
Action
Connect the cable
Place the appropriate cover on the device, taking care to insert the ferrule in the slot provided in order to fix the cable to the card.
Screw on the cover.
Insert the card in the slot provided in the host device.
Screw in the card to stop it being moved when switched on, and to ensure it functions effectively.
Illustration
Assembly for TSX P57 5•4 Processors
To assemble the card in TSX P57 5•4 type processors, follow the instructions below:
Step
1
2
3
Action
Connect the cable.
Place the appropriate cover on the device, taking care to insert the ferrule in the slot provided in order to fix the cable to the card.
Screw on the cover.
Illustration
40
35008155 12/2018
Step
4
Action
Remove the plastic cover from the caddy.
Illustration
5 Guide the card into the caddy from an oblique angle using the 2 locating devices.
6 Slide the card into the caddy until it stops. The card is now firmly attached to the caddy.
7
8
Insert the assembly
(caddy and card) in the slot provided in the host device.
Screw in the card to stop it being moved when switched on, and to ensure it functions effectively.
35008155 12/2018
Fipio hardware implementation
41
Fipio hardware implementation
Displaying operating state of PCMCIA cards
General
Two diagnostics LEDs are located on the front of the card. They inform the user on the status of exchanges between the device supporting the PCMCIA card and related devices.
Illustration
Number Description
1 "ERR" Error LED (normally off) displays errors.
It is red
2 The "COM" communication LED displays line activity.
This LED is yellow
Diagram
42
35008155 12/2018
Fipio hardware implementation
Visual Diagnostics for TSX FPP 10 PCMCIA Card
General
Depending on their state, the LEDs of the PCMCIA card indicate the operating mode for communication, as well as the card diagnostics.
TSX FPP 10 card
State of LEDs:
ERR COM Meaning
Device switched off No dialog
Corrective actions
Check supply, card inoperational
Normal operation -
(1) Serious fault
Functional fault
Functional fault
Change the card
Check the configuration and the connection to the communication bus
Check the configuration
Key:
Off
On
Flashing
(1) = Indifferent state
35008155 12/2018
43
Fipio hardware implementation
Consumption of PCMCIA card
TSX FPP 10
Table of consumption:
Voltage
5 volts
Typical Current
280 mA
Maximum Current
330 mA
Power dissipation
1.65 W max.