Hardware Implementation for Fipio Bus. Schneider Electric Premium and Atrium Using EcoStruxure™ Control Expert - Fipio Bus
Reklam
Reklam
Premium and Atrium Using EcoStruxure™ Control Expert
Fipio Hardware Implementation
35008155 12/2018
Hardware Implementation for Fipio Bus Part II
Hardware Implementation for Fipio Bus
35008155 12/2018
19
Fipio Hardware Implementation
20
35008155 12/2018
Premium and Atrium Using EcoStruxure™ Control Expert
Fipio hardware implementation
35008155 12/2018
Introduction to and implementation of Fipio bus devices Chapter 2
Introduction to and implementation of Fipio bus devices
Subject of this Chapter
This Chapter introduces the different Fipio bus architectures and the implementation of devices.
What Is in This Chapter?
This chapter contains the following sections:
Section
2.1
2.2
2.3
2.4
2.5
Topic
Introduction to Fipio bus architectures
Master Fipio communication built into processors
TSX FPP 10 PCMCIA card
TSX FPC 10 module
TSX FPP 20 PCMCIA card
Page
35008155 12/2018
21
Fipio hardware implementation
Introduction to Fipio bus architectures Section 2.1
Introduction to Fipio bus architectures
Subject of this Section
This Section introduces some different Fipio bus architectures.
What Is in This Section?
This section contains the following topics:
Topic
Architecture of Fipio bus with connection auxiliaries (IP20)
Architecture of Fipio Bus with Connection Auxiliaries (IP65)
Architecture of Fipio bus with Connection Auxiliaries (IP67)
Fipio Architecture with OZD FIP G3
Page
22
35008155 12/2018
Fipio hardware implementation
Architecture of Fipio bus with connection auxiliaries (IP20)
At a Glance
The architecture below shows the Fipio bus and the different devices (IP20) of which it is composed.
Description
The following table shows the devices on the bus:
6
7
8
4
5
2
3
Number Product reference
1 TSX FP CA/CRxxx
TSX FP CCxxx
TSX FP CE030
TSX FP ACC7
TSX FP ACC3 or TSX FP ACC4 or TSX FP ACC14
9
TSX FP ACC2
TSX FP ACC12
TSX FP ACC6
TSX FP ACC8
TBX BLP 01
Description
Trunk cable
Drop cable
Connection cable for terminals and PCs
Line terminator
Branching devices
Connector for daisy-chaining or branching
Connector for Premium PLC
Electrical repeater or fiber optic repeater if fiber optic link used
Connector for connecting TBXs
The Fipio reference manual (TSX DR FIP) specifies the characteristics of each device.
35008155 12/2018
23
Fipio hardware implementation
Architecture of Fipio Bus with Connection Auxiliaries (IP65)
At a Glance
The architecture below shows the Fipio bus and the different devices (IP65) of which it is composed.
24
35008155 12/2018
Fipio hardware implementation
Description
The following table shows the devices on the bus:
9
10
11
6
7
4
5
8
2
3
Number
1
Reference Description
TSX FP CA/CR••• Trunk cable
TSX FP CC•••
TSX FP CE030
Branch cable
Connection cable for terminals and PCs
TSX FP ACC7
TSX FP ACC4
TSX FP ACC2
TSX FP ACC12
TSX FP ACC6
TSX FP ACC8
Line terminator
Branching device
Connector for daisy-chaining or branching
Connector for Premium PLC
Electrical repeater or fiber optic repeater if fiber optic link used
TBX BLP 10
TBX FP ACC10
TSX FP CF•••
Connector for connecting IP 65 TBXs
Branching device
Remote power supply cable
The Fipio reference manual (TSX DR FIP) specifies the characteristics of each device.
35008155 12/2018
25
Fipio hardware implementation
Architecture of Fipio bus with Connection Auxiliaries (IP67)
Illustration
The diagram below shows the possible architectures which may be used to connect IP67 sealed
I/O modules, as well as the accessories used, to the Fipio bus.
26
A Branch head.
B IP67 branch.
35008155 12/2018
Fipio hardware implementation
Description
The following table presents the various accessories that make it possible to assemble the desired configuration whilst observing all the operating constraints of the Fipio bus.
Number Part Number
1 TSX EF ACC 99
2
3
4
5
6
7
8
9
TSX EF CF 01
TSX EF CM 01
TSX EF CF 03
TSX EF CM 03
TSX EF CT 03
TSX EF CF 02
TSX FP ACC 2 or
TSX FP ACC 12
TSX EF ACC 2••• and
TSX EF ACC 2••••
Type of connection Description
Branch box.
This IP65 branch box can be used to perform 3 functions:
Connection of a 24 VDC power supply,
Creation of an IP67 branch,
Connection of a programming terminal.
IP67 female connector, type
M23.
IP67 male connector, type
M23.
IP67 female connector, type 7/8"
(24 VDC power supply).
IP67 female solder connector with M23-type ring,
6 contacts for Fipio bus connection and 24 VDC power supply. This type of independent connector is designed to be fitted to one end of TSX FP CA/CC/CP•00/CR cables.
IP67 male solder connector with M23-type ring, 6 contacts for Fipio bus connection and 24 VDC power supply. This type of independent connector is designed to be fitted to one end of TSX FP CA/CC/CP•00/CR cables.
7/8" type IP67 female screw connector, 5 contacts for Fipio bus connection and 24 VDC power supply. This type of connector is designed to be used for connecting the
24 VDC power supply of TSX ESF/EMF output or mixed modules and/or of the TSX EF ACC 99 branch box. The maximum authorized current in each contact on the connector is 8 A.
7/8" type IP67 male screw connector, 5 contacts for linked connection using the TSX EF CT 03 T connector, designed to supply the preactuators with 24 VDC.
IP67 male connector, type 7/8"
(24 VDC power supply).
T connector (for linking 24 VDC power supply).
IP67 female connector, type
M23.
SUB-D 9 type female connector.
IP67 compoundfilled Fipio cable for linking of modules.
7/8" type IP67 T connector, 5 contacts for linking the 24 V power supply of the preactuators. The maximum authorized current for each contact on this connector is 8 A.
M23, type IP67 female threaded solder connector,
6 contacts for extending Fipio TSX FP CA/CC/CP•00/CR cables.
SUB-D type connectors with 9 contacts for Fipio/Fipway connection to PLCs. Can be used for linked or branched connection (90° high or low output, 45° high or low output).
Main compound-filled cable of a predefined length, 150 Ω twisted shielded pair, and a 1.5 mm female/female connector.
2
power supply pair.
Equipped with an M23 male connector and an M23 double
35008155 12/2018
27
Fipio hardware implementation
Number Part Number
10 TSX FP CP •00
11
12
13
14
15
TSX FP CC •00
TSX FP CA •00
TSX EF ACC 7
TSX FP ACC 7
TSX FP CG 0•0
Type of connection Description
IP67 Fipio cable
(1 cable pair,
2 1.5 mm 2 power supply conductors, in 100 m or 500 m).
Main IP67, Fipio cable, 150 Ω twisted shielded pair, and a
1.5 mm 2 power supply pair (Ø 9.5 mm). Free wire ends to be fitted with IP 67 M23 type TSX EF CF 01/02 and
TSX EF CM 01 solder connectors.
Fipio branch cable
(2 pairs, in 100 m or
500 m).
Fipio link cable
(1 pair, in 100 m,
200 m or 500 m).
Branch cable, 150 Ω double shielded twisted pair (Ø 8 mm) for standard environments and building interiors. Free wire ends to be fitted with IP67 M23 type TSX CF 01/02 and
TSX CM 01 soldered connectors.
Main cable, one 150 Ω shielded twisted pair (Ø 8 mm) for standard environments and building interiors. Free wire ends to be fitted with IP 67 M23 type TSX EF CF 01/02 and
TSX EF CM 01 solder connectors.
IP67 M23 type line terminator.
Line terminator
PLC or programming terminal link cable
IP67 M23 type line terminator, to be positioned, depending on use, at one or both ends of the section (male type for direct connection).
IP20 line terminator (batch of 2), to be positioned, depending on use, at one or both ends of the section.
Branch connection cable for TSX FP 10/20 PCMCIA interface card for Premium, FT 2000 terminal and PCcompatible PLCs. This cable allows a PLC or a programming terminal to be connected to a
TSX EF ACC 99 branch box.
Other Accessories
The following table shows the other accessories available.
Part Number
XZ-LG 101
XZ-LG 102
170 XTS 050 00
Type of connection
Identification labels.
IP67 sealing plugs.
IP67 sealing plug.
Description
Strip of 10 additional identification labels (a strip is already supplied with each module).
Batch of 10 M12 sealing plugs for unused I/O connectors. Each module is supplied with two plugs.
Sealing plug for M23 connector.
28
35008155 12/2018
Fipio Architecture with OZD FIP G3
Description
Example of a Fipio architecture:
Fipio hardware implementation
Most Schneider products which operate on the Fipio bus can be connected to the OZD FIP G3 transceiver:
As Fipio manager devices:
Premium: processors with an integrated FIPIO link: TSX P57•54 and TSX PCXI57 354 programmed with Control Expert (version V1.1 or later).
As Fipio bus agent devices:
TBX equipped with an LEP 030 communication module
Magelis XBT equipped with a TSX FPP 10 card
PC equipped with a TSX FPC 10 or PCMCIA FPP20 ISA card
Momentum
TSX Micro TSX 372• and TSX Premium TSX/PMX/PCX 57 equipped with a TSX FPP 010
card
Third-party devices which conform to the standard Fipio profiles defined in the FipConnect connection program.
NOTE: TSX FP ACC6 and TSX FP ACC8M repeaters are not compatible with architectures using
OZD FIP G3 transceivers.
NOTE: Fipio configurations in WorldFip mode are excluded from these architectures.
NOTE: The TSX DM OZD 01 manual gives all the characteristics of HIRSCHMANN OZD FIP G3 transceivers.
35008155 12/2018
29
Fipio hardware implementation
Master Fipio communication built into processors Section 2.2
Master Fipio communication built into processors
Built-in Fipio Link on Premium/Atrium Processors
General
Some Premium (see Premium and Atrium using EcoStruxure™ Control Expert, Processors, racks and power supply modules, Implementation Manual) and Atrium (see Premium and Atrium using
EcoStruxure™ Control Expert, Processors, racks and power supply modules, Implementation
Manual) processors have a built-in master Fipio link which makes it possible to connect the PLC station to a Fipio bus.
Illustration:
30
35008155 12/2018
Fipio hardware implementation
Connecting to Fipio Bus
The processor has a SUB-D 9-pin connector which is used to connect it to the Fipio bus using a
TSX FP ACC12 connector.
Illustration:
NOTE: The master Fipio link built into processors should not be taken into account when counting the station channels.
35008155 12/2018
31
Fipio hardware implementation
TSX FPP 10 PCMCIA card Section 2.3
TSX FPP 10 PCMCIA card
Subject of this Section
This Section deals with the installation of a TSX FPP 10 PCMCIA card.
What Is in This Section?
This section contains the following topics:
Topic
Introduction
Description
Connection of the TSX FPP 10 card
Precautions to be taken when connecting PCMCIA card
Installation
Mounting Cards and Cables
Displaying operating state of PCMCIA cards
Visual Diagnostics for TSX FPP 10 PCMCIA Card
Consumption of PCMCIA card
Page
32
35008155 12/2018
Fipio hardware implementation
Introduction
General
Premium/Atrium PLC stations connect to communication networks, buses and links via PCMCIA communication cards.
The card to be connected is a metal unit whose dimensions comply with PCMCIA extended type
III format.
The PCMCIA card is installed in the host slot of the processor of Premium PLCs.
The PCMCIA card can also be used in devices which have a type III host slot, such as XBT terminals or third-party devices, such as PC compatible devices, for example.
Illustration:
NOTE: It is prohibited to connect PCMCIA cards when the power is switched on.
Definition
An agent PLC is a PLC with a connected PCMCIA card.
35008155 12/2018
33
Fipio hardware implementation
TSX FPP 10 card
The PCMCIA card used to connect a Premium/Atrium PLC station to a Fipio bus is the TSX FPP
10.
The PCMCIA card is installed, operated and maintained using Control Expert programming and operation software for all PLCs in the Premium/Atrium family.
34
35008155 12/2018
Fipio hardware implementation
Description
General
PCMCIA type III (extended) communication cards are built into a metal unit with the following dimensions:
Length: 85.5 mm
Width: 51 mm
Height: 10 mm
The front of the card is designed to display the operating status of communications as well as the physical connection to the network.
Mechanical configuration
The mechanical configuration of the card must be adapted by mounting a removable cover, depending on the type of installation desired:
Type of installation
Installation on a
Premium type processor.
Installation on an Atrium type processor.
Installation on a PC compatible device.
Configuration
Removable cover with wings. Screws are provided to fix it to the host module (marked 3 on illustration)
Removable cover with wings. Screws are provided to fix it to the
Atrium processor
(marked 2 on illustration).
Removable cover
(marked 1 on illustration).
Illustration
NOTE: The covers with wings, mounted on PCMCIA cards, prevent any accidental removal when switched on and guarantee that the card remains in good working order.
The two covers (1) and (3) are provided with the PCMCIA card. The cover (2) is provided with the
Atrium processor.
Connection to the network is achieved by connecting the link cable to the front of the card. A guidance system is used to prevent anything being mounted incorrectly.
The product reference label informs the user of the type of physical layer supported by the card.
35008155 12/2018
35
Fipio hardware implementation
Connection of the TSX FPP 10 card
General
The TSX FPP 10 PCMCIA card is connected to the Fipway bus using a connector such as a TSX
FP ACC 3 or TSX FP ACC 4.
To connect the PCMCIA card to the ACC3/ACC4 connector the user may use:
Either a 1 m cable, product reference TSX FP CG 010.
Or a 3 m cable, product reference TSX FP CG 030.
Items required for connecting a Premium/Atrium PLC to the remote inputs/outputs Fipio bus:
36
35008155 12/2018
Fipio hardware implementation
Precautions to be taken when connecting PCMCIA card
General
NOTICE
PCMCIA CARD DESTRUCTION
Cables (TSX FP CG 010/030) are to be connected and disconnected from the PCMCIA card only when the power is switched off
Failure to follow these instructions can result in equipment damage.
CAUTION
PCMCIA CARD DESTRUCTION
Power off the module before inserting or removing the PCMCIA card.
Failure to follow these instructions can result in injury or equipment damage.
When removing or inserting the card, the unit is not guaranteed to be operational.
The PCMCIA card must be equipped with a PLC version cover and be screwed into the reception
module before the power is switched on (see Mechanical configuration,
page 35
The ferrule, placed in direct contact with the PCMCIA card device, is used to drain electrical interference carried by the link cable braids.
35008155 12/2018
37
Fipio hardware implementation
Installation
Installation
The TSX FPP 10 card can only be installed in the host slot of processors. It cannot be installed in the module TSX SCM 21601
Application-specific channel and network connection
The installation of the card in the processor does not count as an application-specific channel or as a network connection.
38
35008155 12/2018
Fipio hardware implementation
Mounting Cards and Cables
PCMCIA Card Details
Illustration:
PCMCIA cards are made up of the following elements:
2
3
Number Designation
1 Equipped card
4
Body made of zamac
PCMCIA connector
Upper cover
5
6
Removable cover
Link cable with ferrule
Comments
Receives electronic components.
-
Connector with 20 connection points.
Houses the product reference label which shows the type of PCMCIA card
Ensures the card is displayed in its slot. The names of the two LEDs are printed on the front of the removable cover. This cover also allows the
PCMCIA card to be fastened to the processor.
The ferrule placed on the end of the cable nearest to the PCMCIA card prevents the cable being pinched by the removable cover. This ferule also eliminates the risk of causing a bending radius which can damage the quality of the link.
35008155 12/2018
39
Fipio hardware implementation
Assembly for TSX P57 1•4 to TSX P57 5•4 Processors
To assemble the transmission card for the processor or the TSX SCY 21601, first remove the cover which is screwed on the device and then follow the instructions below:
Step
1
2
3
4
5
Action
Connect the cable
Place the appropriate cover on the device, taking care to insert the ferrule in the slot provided in order to fix the cable to the card.
Screw on the cover.
Insert the card in the slot provided in the host device.
Screw in the card to stop it being moved when switched on, and to ensure it functions effectively.
Illustration
Assembly for TSX P57 5•4 Processors
To assemble the card in TSX P57 5•4 type processors, follow the instructions below:
Step
1
2
3
Action
Connect the cable.
Place the appropriate cover on the device, taking care to insert the ferrule in the slot provided in order to fix the cable to the card.
Screw on the cover.
Illustration
40
35008155 12/2018
Step
4
Action
Remove the plastic cover from the caddy.
Illustration
5 Guide the card into the caddy from an oblique angle using the 2 locating devices.
6 Slide the card into the caddy until it stops. The card is now firmly attached to the caddy.
7
8
Insert the assembly
(caddy and card) in the slot provided in the host device.
Screw in the card to stop it being moved when switched on, and to ensure it functions effectively.
35008155 12/2018
Fipio hardware implementation
41
Fipio hardware implementation
Displaying operating state of PCMCIA cards
General
Two diagnostics LEDs are located on the front of the card. They inform the user on the status of exchanges between the device supporting the PCMCIA card and related devices.
Illustration
Number Description
1 "ERR" Error LED (normally off) displays errors.
It is red
2 The "COM" communication LED displays line activity.
This LED is yellow
Diagram
42
35008155 12/2018
Fipio hardware implementation
Visual Diagnostics for TSX FPP 10 PCMCIA Card
General
Depending on their state, the LEDs of the PCMCIA card indicate the operating mode for communication, as well as the card diagnostics.
TSX FPP 10 card
State of LEDs:
ERR COM Meaning
Device switched off No dialog
Corrective actions
Check supply, card inoperational
Normal operation -
(1) Serious fault
Functional fault
Functional fault
Change the card
Check the configuration and the connection to the communication bus
Check the configuration
Key:
Off
On
Flashing
(1) = Indifferent state
35008155 12/2018
43
Fipio hardware implementation
Consumption of PCMCIA card
TSX FPP 10
Table of consumption:
Voltage
5 volts
Typical Current
280 mA
Maximum Current
330 mA
Power dissipation
1.65 W max.
44
35008155 12/2018
Fipio hardware implementation
TSX FPC 10 module Section 2.4
TSX FPC 10 module
Description
General
The TSX FPC 10 module can be used for connecting the following devices to the Fipio bus:
FTX 517 workstations
CCX 77/87 supervision terminals any machine fitted with an ISA bus
The module is the same shape as a half-format PC extension card.
It is connected to the Fipio bus via a TSX FP CE030 cable and a TSX FP ACC3, TSX FP ACC4 or TBX FP ACC10 branching device
35008155 12/2018
45
Fipio hardware implementation
TSX FPP 20 PCMCIA card Section 2.5
TSX FPP 20 PCMCIA card
Description
General
The TSX FPP 20 card is used to connect a programming terminal to a PLC station via the Fipio bus.
The card can also be used to connect a Premium/Atrium PLC station to a Fipway network.
The programming terminal must have a type III (extended) PCMCIA slot.
To install the card, see the manual entitled Fipway Communication.
46
35008155 12/2018
İndir
Reklam