Introduction to Fipio communication. Schneider Electric Premium and Atrium Using EcoStruxure™ Control Expert - Fipio Bus
விளம்பரம்
விளம்பரம்
General
Introduction to Fipio communication Section 3.1
Introduction to Fipio communication
Addressing of Remote Module Language Objects on a FIPIO Bus
At a Glance
The addressing of the main bit and word objects of remote modules on the Fipio bus is performed on a geographical basis. That means that it depends on:
The connection point,
The type of module (base or extended),
The channel number.
Illustration
Addressing is defined in the following way:
Syntax
The table below describes the different elements that make up addressing.
Family
Symbol
Object type I
Q
Element Values
% -
-
-
M
K -
-
-
Meaning
Image of the physical input of the module.
Image of the physical output of the module.
This information is exchanged automatically for each cycle of the task to which they are attached.
Internal variable
This read or write information is exchanged at the request of the project.
Internal constant
This configuration information is available as read only.
50
35008155 12/2018
General
Family
Format (size)
Module/channel address and connection point
Rack No.
Module No.
Channel No.
r m c
Element Values
X b e
W
D
F
-
16 Bit
32 Bit
32 Bit
Meaning
Boolean
For Boolean objects the X can be omitted.
Single length.
Double length.
Floating point. The floating point format used is the IEEE Std 754-1985 standard (equivalent to IEC 559).
2 Bus number.
1 to 127 Connection point number.
Channel data No. d
0
0 or 1
0 to 999 or MOD
0 to 999 or ERR
Virtual rack number:
0: base module, 1: extension module.
MOD: channel reserved for managing the module and parameters common to all the channels.
ERR: Used to read a module or channel fault.
35008155 12/2018
51
General
Examples
The table below shows some examples of addressing objects.
Object
%MW\2.1\0.0.5.2
%I\2.1\0.0.7
%Q\2.1\0.1.2
Meaning
Status word at rank 2 of the image bit of input 5 of the remote input base module situated at connection point 1 on the Fipio bus.
Image bit of input 7 of remote input base module situated at connection point 1 on the Fipio bus.
Image bit of output 2 of the remote output extension module situated at connection point 1 on the Fipio bus.
%I\2.2\0.0.MOD.ERR Fault information for Momentum module situated at connection point 2 on the Fipio bus.
%I\2.3\0.0.0.ERR
Fault information for channel 0 of Magelis module situated at connection point 3 on the Fipio bus.
52
35008155 12/2018