Fipio Agent
How to access the FIPIO Agent parameters via PCMCIA cards
Introduction
How to access the link
The creation of an application setting up FIPIO Agents requires the configuration of the communication channel of the PLC registered as an FIPIO Agent.
This operation describes how to access the configuration parameters of the FIPIO
Agent link via the PCMCIA TSX FPP card for Micro/Premium PLCs.
The following table shows the procedure for accessing the FIPIO link:
Step
1
2
Action
Access the communication channel configuration screen.
From the dropdown menu, select the communication channel CHANNEL 1
Example
CHANNEL 1
CHANNEL 1
CHANNEL 1
(No PCMCIA submodule)
MAST
3 Select one of the following PCMCIA cards from the dropdown menu: z TSX FPP 10 PCMCIA CARD FIPIO
Example
CHANNEL 1
CHANNEL 1 (No PCMCIA submodule)
(Link not configured) MAST
TSX SCP 114 PCMCIA CARD RS485 MP
TSX FPP 20 PCMCIA FIPWAY CARD
TSX FPP 200 PCMCIA FIPWAY CARD
TSX FPP 10 PCMCIA FIPIO CARD
TSX MBP 100 PCMCIA MODBUS+ CARD
TSX MDM 10 PCMCIA MODEM CARD
35013154.02 07/2208
367
Fipio Agent
FIPIO Agent configuration screen
Introduction
Illustration
This screen, split into two areas, is used to register the communication channel and to configure the necessary parameters for a FIPIO Agent link.
The screen dedicated to communication looks like this:
1
TSX 3722 [POSITION 00.0..1]
Configuration
Designation: PROCESSOR 37222
CHANNEL 1
CHANNEL 1
FIPIO AGENT
TSX FPP 10 PCMCIA FIPIO CARD
MAST
2
Connection Point Address
Table Start Address %MW 0
1
Elements and functions
This table describes the different areas that make up the configuration screen:
Address Zone
1 common
2 specific
Function
See (See : PL7 Micro/Junior/Pro ; Communication applications
; Volume 1).
is used to select and complete the following parameters: z z connection point address the beginning address of the table.
the beginning address of the table.
This parameter indicates the address of the table to be reserved for the periodic data exchanges between the bus manager and the FIPIO Agent.
The table has 64 words: z z
32 words for the inputs (%IW\p.2.c\m.i.r),
32 words for the outputs (%QW\p.2.c\m.i.r).
368
35013154.02 07/2208
Fipio Agent
25.3
Debugging Fipio Agents
FIPIO Agent debugging screen
Introduction
Illustration
This screen, split into two areas, is used to debug a FIPIO Agent.
The screen dedicated to debugging looks like this:
TSX 3722 [POSITION 00.0..1]
Debugging
Designation: PROCESSOR 37222 Version: 3.4
1
CHANNEL 1
CHANNEL 1
FIPIO
TSX FPP 10 PCMCIAFIPIO CARD
MAST
2
FIPIO function status
State of output %MW
Active
Active
Table addresses:
OUTPUT from: %MW300 to %MW331
INPUT from: %MW322 to %MW363
Access values via animation tables
DIAG...
DIAG...
Elements and functions
This table describes the different areas that make up the configuration screen:
Address Zone
1 common
2 specific
Function
See (See : PL7 Micro/Junior/Pro ; Communication applications
; Volume 1).
is used to access the debugging parameters of a FIPIO Agent.
No data can be accessed from this screen.
35013154.02 07/2208
369
Fipio Agent
25.4
Language objects associated with the Fipio
Agents
Introduction
Aim of this
Section
What's in this
Section?
This Section introduces the language objects associated with Fipio Agents.
This section contains the following topics:
Topic
Language objects in implicit exchange
Language object for explicit exchange
Explicit exchange management and reports
Language objects associated with configuration
Page
370
35013154.02 07/2208
Fipio Agent
Language objects in implicit exchange
Introduction
Bit objects
This page describes all the language objects for implicit exchange associated with the FIPIO communication agents that can be displayed or modified by the agent’s application program. (PL7 Micro/Junior/Pro ; Communication applications ;
Volume 1)
The table below shows the different bit objects for implicit exchange.
Object (1) Function
%Ixy.MOD.ERR Module error bit
%Ixy.i.ERR
Channel error bit
Meaning
This bit set to 1, indicates a module error (at least one of the channels is faulty,…)
This bit set to 1, indicates a line fault.
Key
(1) z z xy.i Address z x: corresponds to the rack number (-) y: corresponds to the module number (0/1) i: corresponds to the channel number (1)
Word objects The table below shows the different word objects for implicit exchange.
Object (1)
%IWxy.i.0
Function Meaning
Agent function status Byte 0: z = 16#01: IDLE function z z
= 16#02: RUN function
= 16 #03: STOP function
Strategy to be applied to outputs
Byte 1: z z z
= 16#01: safety
= 16#02: %MW value valid
= 16 #03: fallback
Key
(1) z z xy.i Address z x: corresponds to the rack number (-) y: corresponds to the module number (0/1) i: corresponds to the channel number (1)
35013154.02 07/2208
371
Fipio Agent
Language object for explicit exchange
Introduction
Word objects
This page describes all the language objects for explicit exchange associated with the FIPIO communication agents that can be displayed or modified by the application program. (See : PL7 Micro/Junior/Pro ; Communication applications ;
Volume 1)
The table below shows the different word objects for explicit exchange.
Object (1) Function
%MWxy.MOD.2
Module status
%MWxy.i.2
Standard channel status
Meaning z z z z z z z z x0 = 1: defective module x1 = 1: functional error (error between the processor and the module, adjustment or configuration error, …) x2 = 1: terminal block fault (not connected) x3 = 1: self-tests running x4 = 1: reserved x5 = 1: error in hardware or software configuration (the module present is not that declared in the configuration, the sub-modules are not compatible) x6 = 1: missing module x7 = 1: error in one of the sub-modules z z
Byte 0: z x0 = 1: input words are disabled when the manager is in RUN z x1 = 1: output words are disabled when the agent is in RUN z x4 = 1: internal error of TSX FPP 10 card or card z not yet started by the manager x5 = 1: configuration error (the configured data module is different from that present) x6 = 1: communication error on FIPIO x7 = 1: application error (%MW table overrun)
Byte 1: reserved
Key
(1) xy.i Address z z z x: corresponds to the rack number (-) y: corresponds to the module number (0/1) i: corresponds to the channel number (1)
372
35013154.02 07/2208
Fipio Agent
Explicit exchange management and reports
Introduction
Word objects
This page describes all the language objects that manage explicit exchanges. (See
: PL7 Micro/Junior/Pro ; Communication applications ; Volume 1)
The table below shows the different word objects for the management of explicit exchanges.
Object (1)
%MWxy.MOD.0
%MWxy.MOD.1
%MWxy.i.0
Function
Module exchanges in progress
Module report
Meaning z z z x0 = 1: reading status in progress x1 = 1: sending of command parameters to the communication module x2 = 1: sending of adjustment parameters to the communication module z z x1 = 0: command parameters received and accepted by the module x2 = 0: adjustment parameters received and accepted by the module
Channel exchanges in progress z z z x0 = 1: reading status in progress x1 = 1: sending of command parameters to the communication channel x2 = 1: sending of adjustment parameters to the communication channel
%MWxy.i.1
Channel report z z x1 = 0: command parameters received and accepted by the communication channel x2 = 0: adjustment parameters received and accepted by the communication channel
Key
(1) z z z xy.i address x: corresponds to the rack number (-) y: corresponds to the module number (0/1) i: corresponds to the channel number (1)
35013154.02 07/2208
373
Fipio Agent
Language objects associated with configuration
Introduction
Internal constants
This page describes all the configuration language objects associated with the
FIPIO communication agents that can be displayed by the agent application program.
The following table describes the internal constants:
Object Function
%KWxy.i.0
Type
%KWxy.i.1
Reserved
%KWxy.i.2
Connection point address
%KWxy.i.3
Table start address
Meaning
Byte 0 = 16#09: for the FIPIO Agent function
-
Byte 0 = 16#01 to 16#7F: corresponds to addresses
1 to 127
Byte 0: least significant byte of the address
Byte 1: most significant byte of the address
374
35013154.02 07/2208
Index
A
Accessible Functions
Accessing configuration
Accessing the configuration
Accessing the configuration screen
Accessing the debugging screen
Accessing the diagnostics screen, 311
Addressing
Adjustment mode
B
Bus properties
C
Characteristics
35013154.02 07/2008
Communication channel test
Communication function
Compatibility
compatibility
Configuration
Configuration access
Configuration Parameters
Configuration parameters
Configuration Screen
Configuration screen
A C
375
Index
configuring standard profiles, 336
D
Data exchange
Debug parameters
Debug screen
Debugging
Debugging Parameters
Debugging parameters
Debugging screen
debugging standard profiles, 342
Diagnostics
Driver
E
Error processing using the program, 298
Exchange management
376
Explicit exchange
Standard profiles (FIPIO), 353
F
G
General
I
Implicit Exchange
Implicit exchange
Standard profiles (FIPIO), 351
Input/output management
Introduction
L
Language objects
35013154.02 07/2008
M
Management of exchanges
Management parameters
O
Operating Mode
Operating mode
P
Performance
Programming
R
Read mode
Report
35013154.02 07/2008
S
Set-up
system objects
T
W
Write mode
X
X-WAY
Index
377
Index
378
35013154.02 07/2008
Preuzimanje
Reklama