Ethernet Configuration Chapter 11
Ethernet Configuration
Introduction
This chapter describes how to configure the Ethernet network interface of the Modicon M258 Logic
Controller.
What Is in This Chapter?
This chapter contains the following sections:
Section
11.1
11.2
11.3
Ethernet Services
Firewall Configuration
Ethernet Optional Devices
Topic Page
EIO0000004135 09/2020
137
Ethernet Configuration
Ethernet Services Section 11.1
Ethernet Services
What Is in This Section?
This section contains the following topics:
Topic
Presentation
IP Address Configuration
Modbus TCP Client/Server
Web Server
FTP Server
FTP Client
SNMP
Page
138
EIO0000004135 09/2020
Ethernet Configuration
Presentation
Ethernet Services
The controller supports the following services:
Modbus TCP Server
Modbus TCP Client
Web Server
FTP Server
SNMP
Modbus TCP Slave Device
Ethernet Protocols
The controller supports the following protocols:
IP (Internet Protocol)
UDP (User Datagram Protocol)
TCP (Transmission Control Protocol)
ARP (Address Resolution Protocol)
ICMP (Internet Control Messaging Protocol)
IGMP (Internet Group Management Protocol)
Connections
This table shows the maximum number of connections:
Connection Type
Modbus Server
Modbus Client
EtherNet/IP Target
FTP Server
Web Server
Machine Expert Protocol (EcoStruxure Machine
Expert software, trace, Web visualization, HMI devices)
4
10
8
Maximum Number of Connections
8
8
16
EIO0000004135 09/2020
139
Ethernet Configuration
Each connection based on TCP manages its own set of connections as follows:
1. When a client tries to open a connection that exceeds the poll size, the controller closes the oldest connection.
2. If all connections are busy (exchange in progress) when a client tries to open a new one, the new connection is denied.
3. All server connections stay open as long as the controller stays in operational states ( RUNNING ,
STOPPED , HALT ).
4. All server connections are closed when leaving or entering operational states ( RUNNING ,
STOPPED , HALT ), except in case of power outage (because the controller does not have time to close the connections).
Services Available
With an Ethernet communication, the IEC VAR ACCESS service is supported by the controller.
With the IEC VAR ACCESS service, data can be exchanged between the controller and an HMI.
The NetWork variables service is also supported by the controller. With the NetWork variables service, data can be exchanged between controllers.
NOTE: For more information, refer to the EcoStruxure Machine Expert Programming Guide.
140
EIO0000004135 09/2020
Ethernet Configuration
IP Address Configuration
Introduction
There are different ways to assign the IP address to the added Ethernet interface of the controller:
Address assignment by DHCP server
Address assignment by BOOTP server
Fixed IP address
Post configuration file
has priority over the others.
. If a post configuration file exists, this assignment method
The IP address can also be changed dynamically through the:
Controller Selection tab in EcoStruxure Machine Expert
changeIPAddress function block
NOTE: If the attempted addressing method is unsuccessful, the link uses a default IP address
derived from the MAC address.
Carefully manage the IP addresses because each device on the network requires a unique address. Having multiple devices with the same IP address can cause unintended operation of your network and associated equipment.
WARNING
UNINTENDED EQUIPMENT OPERATION
Verify that there is only one master controller configured on the network or remote link.
Verify that all devices have unique addresses.
Obtain your IP address from your system administrator.
Confirm that the IP address of the device is unique before placing the system into service.
Do not assign the same IP address to any other equipment on the network.
Update the IP address after cloning any application that includes Ethernet communications to a unique address.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Verify that your system administrator maintains a record of assigned IP addresses on the network and subnetwork, and inform the system administrator of any configuration changes performed.
EIO0000004135 09/2020
141
Ethernet Configuration
Address Management
This diagram shows the different types of address systems for the controller:
142
NOTE: If a device programmed to use the DHCP or BOOTP addressing methods is unable to contact its respective server, the controller uses the default IP address. It repeats its request constantly.
The IP process restarts in the following cases:
Controller reboot
Ethernet cable reconnection
Application download (if IP parameters change)
DHCP or BOOTP server detected after a prior addressing attempt was unsuccessful.
EIO0000004135 09/2020
Ethernet Configuration
In the Devices tree, double-click Ethernet:
Ethernet Configuration
EIO0000004135 09/2020
143
Ethernet Configuration
This table describes the configured parameters:
Configured Parameters
Interface Name
Network Name
IP Address by DHCP
IP Address by BOOTP
Fixed IP Address
Ethernet Protocol
Transfer Rate
Description
Name for the network link.
Used as device name to retrieve IP address through
DHCP, maximum 15 characters.
IP address is obtained by DHCP server.
IP address is obtained by BOOTP server.
IP address, Subnet Mask, and Gateway Address are defined by the user.
Protocol type used (Ethernet 2 or IEEE 802.3)
NOTE: If you change the Ethernet Protocol, a power cycle is required before it will be recognized by the controller.
Speed and Duplex are in auto-negotiation mode.
Default IP Address
The IP address by default is 10.10.x.x.
The last two fields in the default IP address are composed of the decimal equivalent of the last two hexadecimal bytes of the MAC address of the port.
The MAC address of the port can be retrieved on the label placed on the front side of the controller.
The default subnet mask is Default Class A Subnet Mask of 255.0.0.0.
NOTE: A MAC address is written in hexadecimal format and an IP address in decimal format.
Convert the MAC address to decimal format.
Example: If the MAC address is 00.80.F4.01.80.F2, the default IP address is 10.10.128.242.
Address Classes
The IP address is linked:
to a device (the host)
to the network to which the device is connected
An IP address is always coded using 4 bytes.
The distribution of these bytes between the network address and the device address may vary.This distribution is defined by the address classes.
144
EIO0000004135 09/2020
Ethernet Configuration
The different IP address classes are defined in this table:
Address Class
Class A
Class B
Class C
Class D
Class E
1
1
1
1
Byte1
0
1
1
Network ID
0 Network ID
1
0
1
1
Network ID
0
1
Multicast Address
0
Byte 2
Host ID
Byte 3
Host ID
Byte 4
Host ID
Address reserved for subsequent use
Subnet Mask
The subnet mask is used to address several physical networks with a single network address. The mask is used to separate the subnetwork and the device address in the host ID.
The subnet address is obtained by retaining the bits of the IP address that correspond to the positions of the mask containing 1, and replacing the others with 0.
Conversely, the subnet address of the host device is obtained by retaining the bits of the IP address that correspond to the positions of the mask containing 0, and replacing the others with 1.
Example of a subnet address:
IP address
Subnet mask
192 (11000000)
255 (11111111)
Subnet address 192 (11000000)
1 (00000001)
255 (11111111)
1 (00000001)
17 (00010001)
240 (11110000)
16 (00010000)
11 (00001011)
0 (00000000)
0 (00000000)
NOTE: The device does not communicate on its subnetwork when there is no gateway.
Gateway Address
The gateway allows a message to be routed to a device that is not on the current network.
If there is no gateway, the gateway address is 0.0.0.0.
The gateway address must be defined on Ethernet_1 interface. The traffic to unknown networks is sent through this interface.
EIO0000004135 09/2020
145
Ethernet Configuration
Security Parameters
This table describes the different security parameters:
Security Parameters
Discovery protocol
FTP Server
Machine Expert protocol
Modbus Server
SNMP protocol
Web Server (HTTP)
WebVisualisation protocol
Description
This parameter deactivates Discovery protocol. When deactivated,
Discovery requests are ignored.
This parameter deactivates the FTP Server of the controller. When deactivated, FTP requests are ignored.
This parameter deactivates the Machine Expert protocol on Ethernet interfaces. When deactivated, every Machine Expert request from every device is rejected, including those from the UDP or TCP connection. Therefore, no connection is possible on Ethernet from a
PC with EcoStruxure Machine Expert, from an HMI target that wants to exchange variables with this controller from Controller Assistant.
This parameter deactivates the Modbus Server of the controller. When deactivated, every Modbus request to the controller is ignored.
This parameter deactivates the SNMP server of the controller. When deactivated, SNMP requests are ignored.
This parameter deactivates the Web Server of the controller. When deactivated, HTTP requests to the controller Web Server are ignored.
This parameter deactivates the Web visualization pages of the controller. When deactivated, HTTP requests to the logic controller
WebVisualisation protocol are ignored.
Default settings
Active
Inactive
Active
Inactive
Inactive
Active
Inactive
146
EIO0000004135 09/2020
Ethernet Configuration
Modbus TCP Client/Server
Introduction
Unlike Modbus serial link, Modbus TCP is not based on a hierarchical structure, but on a client/server model.
The Modicon M258 Logic Controller implements both client and server services so that it can initiate communications to other controllers and I/O devices, and to respond to requests from other controllers, SCADA, HMIs, and other devices. By default, Modbus Server functionality is not active.
Without any configuration, the embedded Ethernet port of the controller supports Modbus server.
The Modbus client/server is included in the firmware and does not require any programming action from the user. Due to this feature, it is accessible in RUNNING, STOPPED and EMPTY states.
Modbus TCP Client
The Modbus TCP client supports the following function blocks from the PLCCommunication library without any configuration:
ADDM
READ_VAR
SEND_RECV_MSG
SINGLE_WRITE
WRITE_READ_VAR
WRITE_VAR
For further information, refer to the Function Block Descriptions. See EcoStruxure Machine Expert
Modbus and ASCCII Read/Write Functions PLCCommunication Library Guide.
EIO0000004135 09/2020
147
Ethernet Configuration
Modbus TCP Server
The Modbus server supports the Modbus requests:
Function Function Code
Dec (Hex)
1 (1)
2 (2)
3 (3)
6 (6)
8 (8)
15 (F)
16 (10)
23 (17)
43 (2B)
–
–
–
–
–
–
Subfunction
Dec (Hex)
–
–
14 (E)
Read digital outputs (%Q)
Read digital inputs (%I)
Read holding register (%MW)
Write single register (%MW)
Diagnostic
Write multiple digital outputs (%Q)
Write multiple registers (%MW)
Read/write multiple registers (%MW)
Read device identification
NOTE: The embedded Modbus server only ensures time-consistency for a single word (2 bytes).
If your application requires time-consistency for more than 1 word, add and configure
a Modbus TCP Slave Device so that the contents of the %IW and %QW buffers are time-consistent in the associated IEC task (MAST by default).
Diagnostic Request
This table contains the data selection code list:
Data Selection Code (hex)
00
01
02
03
04
05 - 7E
7F
Description
Reserved
Basic Network Diagnostics
Ethernet Port Diagnostic
Modbus TCP/Port 502 Diagnostics
Modbus TCP/Port 502 Connection Table
Reserved for other public codes
Data Structure Offsets
148
EIO0000004135 09/2020
Ethernet Configuration
Web Server
Introduction
As standard equipment, the controller provides an embedded Web server with a predefined, builtin website. You can use the pages of the website for module setup and control as well as application diagnostics and monitoring. These pages are ready to use with a Web browser. No configuration or programming is required.
The Web server can be accessed by the web browsers listed below:
Google Chrome (version 65.0 or greater)
Mozilla Firefox (version 54 or greater)
Microsoft Internet Explorer (version 11 or greater)
The Web server is limited to 10 TCP connections
.
The Web server has full access to your application for reading and writing data and controlling the state of the controller. By enabling the Web server, you enable these functions. You can disable the Web server on an interface by deselecting the Web Server active parameter in the Ethernet
Configuration tab ( see page 143 ) .
The Web server is a tool for reading and writing data, and controlling the state of the controller, with full access to all data in your application. However, if there are security concerns over these functions, you must at a minimum assign a secure password to the Web Server or disable the Web server to help prevent unauthorized access to the application. By enabling the Web server, you enable these functions.
EIO0000004135 09/2020
149
Ethernet Configuration
The Web server allows you to monitor a controller and its application remotely, to perform various maintenance activities including modifications to data and configuration parameters, and change the state of the controller. Care must be taken to ensure that the immediate physical environment of the machine and process is in a state that will not present safety risks to people or property before exercising control remotely.
WARNING
UNINTENDED EQUIPMENT OPERATION
Configure and install the RUN/STOP input for the application, if available for your particular controller, so that local control over the starting or stopping of the controller can be maintained regardless of the remote commands sent to the controller.
Define a secure password for the Web Server and do not allow unauthorized or otherwise unqualified personnel to use this feature.
Ensure that there is a local, competent, and qualified observer present when operating on the controller from a remote location.
You must have a complete understanding of the application and the machine/process it is controlling before attempting to adjust data, stopping an application that is operating, or starting the controller remotely.
Take the precautions necessary to assure that you are operating on the intended controller by having clear, identifying documentation within the controller application and its remote connection.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: The Web server must only be used by authorized and qualified personnel. A qualified person is one who has the skills and knowledge related to the construction and operation of the machine and the process controlled by the application and its installation, and has received safety training to recognize and avoid the hazards involved. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this feature.
150
EIO0000004135 09/2020
Ethernet Configuration
Web Server Access
Access to the Web server is controlled by User Rights when they are enabled in the controller. For more information, refer to Users and Groups Tab Description
To access the Web server you must first connect to the controller with EcoStruxure Machine Expert or Controller Assistant and modify the default user password.
WARNING
UNAUTHORIZED DATA ACCESS
Secure access to the FTP/Web server using User Rights.
If you disable User Rights, disable the FTP/Web server to help prevent any unwanted or unauthorized access to data in your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
In order to change the password, go to Users and Groups tab of the device editor. For more information, refer to the EcoStruxure Machine Expert Programming Guide (see SoMachine,
Programming Guide) .
NOTE: The only way to gain access to a controller that has user access-rights enabled and for which you do not have the password(s) is by performing an Update Firmware operation. This clearing of User Rights can only be accomplished by using a USB key to update the controller firmware. In addition, you may clear the User Rights in the controller by running a script (for more information, refer to EcoStruxure Machine Expert Programming Guide memory, but restores the ability to access the Controller.
(see SoMachine,
Programming Guide) ) . This effectively removes the existing application from the controller
EIO0000004135 09/2020
151
Ethernet Configuration
Home Page Access
To access to the website home page shown in the following illustration, type in your navigator the
IP address of the controller, or 90.0.0.1 for a USB connection:
This figure shows the Web Server site login page:
This figure shows the home page of the Web Server site once you have logged in:
152
EIO0000004135 09/2020
Ethernet Configuration
NOTE: Schneider Electric adheres to industry best practices in the development and implemen tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
Limit the number of devices connected to a network to the minimum necessary.
Isolate your industrial network from other networks inside your company.
Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
Monitor activities within your systems.
Prevent subject devices from direct access or direct link by unauthorized parties or unauthen ticated actions.
Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Generic Menu Bar
The generic menu bar lets you access the main Web server pages.
The Web Server contains the following pages:
Menu
Home
Documentation
Page Description
Home
Home page of the controller Web server page.
Provides access to the tabs:
Monitoring
Diagnostics
Maintenance
Setup
References Link to the brand site.
EIO0000004135 09/2020
153
Ethernet Configuration
Home Page Menu Descriptions:
:
Menu
Monitoring
Diagnostics
Maintenance
Setup
Submenu
Controller Viewer
Description
Serial Number
Version (firmware, boot...)
Configuration status
Expansion Viewer
Shows the status of expansion modules.
Shows the module with module I/O values.
Oscilloscope
Displays 2 variables in the form of a recorder-type time chart.
Lets you display and modify controller variables.
Controller
Controller status
Ethernet status
Serial
Profibus
FTP
Serial line status
Profibus status
Link to the file system server ( /Usr , /bd0 and /Sys folders)
User Management
Lets you change user password and customize login message.
Users account management: allows you to remove all passwords from the controller and reset user
accounts to their default state.
Clone management: lets you include or exclude user access rights when cloning a controller.
Lets you set the Ethernet and serial line parameters.
Post configuration setup
EthernetIP configurations
Lets you set the EthernetIP configuration files.
The following submenu is visible in each tab:
Submenu
Info
Control
Description
Current Controller information
Reference
Device name
Running state
Allows you to Start or Stop the controller
154
EIO0000004135 09/2020
Ethernet Configuration
The Web server allows you to remotely monitor a controller and its application, and to perform various maintenance activities including modifications to data and configuration parameters, and change the state of the controller. Ensure that the immediate physical environment of the machine and process is in a state that will not present safety risks to people or property before exercising control remotely.
WARNING
UNINTENDED EQUIPMENT OPERATION
Configure and install the RUN/STOP input for the application, if available for your particular controller, so that local control over the starting or stopping of the controller can be maintained regardless of the remote commands sent to the controller.
Define a secure password for the Web Server and do not allow unauthorized or otherwise unqualified personnel to use this feature.
Ensure that there is a local, competent, and qualified observer present when operating on the controller from a remote location.
You must have a complete understanding of the application and the machine/process it is controlling before attempting to adjust data, stopping an application that is operating, or starting the controller remotely.
Take the precautions necessary to assure that you are operating on the intended controller by having clear, identifying documentation within the controller application and its remote connection.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: The Web server must only be used by authorized and qualified personnel. A qualified person is one who has the skills and knowledge related to the construction and operation of the machine and the process controlled by the application and its installation, and has received safety training to recognize and avoid the hazards involved. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this feature.
EIO0000004135 09/2020
155
Ethernet Configuration
Page Access
This table lists the necessary status of the controller to access different pages:
Menu
Home
Documentation
Monitoring
Diagnostics
Maintenance
Setup
Submenu
Home
References
Controller Viewer
Expansion Viewer
IO Viewer
Oscilloscope
Data parameters
Controller diagnostic
Ethernet diagnostic
Serial diagnostic
Profibus diagnostic
/Usr or /bd0
/Sys X
Post configuration setup X
EthernetIP configurations files
X
X
X
-
X
X
X
-
-
-
X
X
X
Controller State
EMPTY STOPPED
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
RUNNING
X
X
X
X
X
X
-
-
-
-
X
X
X
X
X
HALT
X
156
EIO0000004135 09/2020
Monitoring: Controller Viewer Submenu
The Controller Viewer submenu shows the controller status:
Ethernet Configuration
The Configuration status field can change depending on the controller reference visualized (a
TM258LF42DT in the previous screenshot) and can have the following status:
Configuration Status Description
No error No error detected on the corresponding element.
Error An error is detected on the corresponding element.
EIO0000004135 09/2020
157
Ethernet Configuration
Monitoring: Expansion Viewer Submenu
The Expansion Viewer submenu shows the expansion module status:
158
The following table describes each status code:
20
30
100
200
Status Code
0
10
11
201
202
Description
INACTIVE: module inactive
BOOT: boot state
FWDNLD: firmware download in progress
PREOP: basic initialization
OPERATE: register initialization
ACTIVE: module communication active
ERROR: an error has been detected
UNSUP: unsupported module
NOCFG: no configuration available
EIO0000004135 09/2020
Ethernet Configuration
Monitoring: Data Parameters
Monitoring Web Server Variables
To monitor Web server variables, you must add a Web Data Configuration object to your project.
Within this object, you can select all variables you want to monitor.
This table describes how to add a Web Data Configuration object:
Step
1
2
3
Action
Right click the Application node in the Applications tree tab.
Click Add Object → Web Data Configuration....
Result: The Add Web Data Configuration window is displayed.
Click Add.
Result: The Web Data Configuration object is created and the Web Data Configuration editor is open.
NOTE: As a Web Data Configuration object is unique for a controller, its name cannot be changed.
Web Data Configuration Editor
Click the Refresh button to be able to select variables, this action will display all the variables defined in the application.
EIO0000004135 09/2020
159
Ethernet Configuration
Select the variables you want to monitor in the web server:
160
NOTE: The variable selection is possible only in offline mode.
EIO0000004135 09/2020
Ethernet Configuration
Monitoring: Data Parameters Submenu
The Data Parameters submenu allows you to display and modify variable values:
Element
Add
Description
Adds a list description or a variable
Del Deletes a list description or a variable
Refresh period Refreshing period of the variables contained in the list description (in ms)
Refresh Enables I/O refreshing:
Gray button: refreshing disabled
Orange button: refreshing enabled
Load
Save
Loads saved lists from the controller internal Flash to the Web server page
Saves the selected list description in the controller ( /usr/web or /bd0/web directory)
NOTE: IEC objects ( %IW , %M ,...) are not directly accessible. To access IEC objects you must first group their contents in located registers (refer to Relocation Table
EIO0000004135 09/2020
161
Ethernet Configuration
Monitoring: IO Viewer Submenu
The IO Viewer submenu allows you to display and modify the current I/O values:
162
Element
Refresh
1000 ms
<<
>>
Description
Enables I/O refreshing:
Gray button: refreshing disabled
Orange button: refreshing enabled
I/O refreshing period in ms
Goes to previous I/O list page
Goes to next I/O list page
EIO0000004135 09/2020
Ethernet Configuration
Monitoring: Oscilloscope Submenu
The oscilloscope submenu can display up to 2 variables in the form of a recorder time chart:
Element
Reset
Refresh
Load
Save
Item0
Item1
Min
Max
Period(ms)
Description
Erases the memorization
Starts/stops refreshing
Loads parameter configuration of Item0 and Item1
Saves parameter configuration of Item0 and Item1 in the controller
Variable to be displayed
Variable to be displayed
Minimum value of the variable axis
Maximum value of the variable axis
Page refresh period in milliseconds
EIO0000004135 09/2020
163
Ethernet Configuration
Diagnostic: Controller Submenu
The Controller submenu displays information of the current status of the controller:
164
EIO0000004135 09/2020
Diagnostic: Ethernet Submenu
The Ethernet submenu displays Ethernet communication information:
Ethernet Configuration
The Reset Statistic button sets the Ethernet statistics to 0.
EIO0000004135 09/2020
165
Ethernet Configuration
Diagnostics: Serial Submenu
The Serial submenu displays the serial line communication information:
The Reset Statistics button sets the statistics of the serial connections to 0.
Diagnostics: Profibus Submenu
The Profibus submenu is available for controllers with PCI module. It displays the Profibus communication information:
166
EIO0000004135 09/2020
Ethernet Configuration
Maintenance Page
The Maintenance page provides access to the /usr , /bd0 and /sys folders of the controller flash
:
Index of /usr or /bd0 :
Index of /sys :
WARNING
UNINTENDED WEB SERVER AND CONTROLLER BEHAVIOR
Do not modify any of the files in the /usr and /sys directories.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000004135 09/2020
167
Ethernet Configuration
Setup: Post Conf Submenu
The Post Conf page allows you to update the PostConf
file saved on the controller:
168
Step
1
2
3
Action
Click Load.
Modify the parameters ( see page 239 )
.
Click Save.
NOTE: The new parameters will be considered at next Post Configuration file reading
.
EIO0000004135 09/2020
Ethernet Configuration
Setup: Ethernet IP configurations File Submenu
The file tree only appears when the Ethernet IP service is configured on the controller.
Index of /usr or /bd0 :
File
My Machine Controller.gz
My Machine Controller.ico
My Machine Controller.eds
Description
GZIP file
Icon file
Electronic Data Sheet file
Maintenance: User Management Submenu
The User Management submenu displays a screen that allows you to access two different actions:
User accounts management:
Allows you to manage user accounts management, removing passwords and returning the user accounts on the controller to default settings.
Click Disable to remove passwords on the controller.
Click OK on the window that appears to confirm. As a result:
Users no longer have to set and enter a password to connect to the controller.
FTP and HTTP connections accept anonymous user connections.
NOTE: The Disable button is only active if the current user has administrative privileges.
Click Reset to default to return the user accounts on the controller to their default setting state.
Click OK on the window that appears to confirm.
NOTE: Connections to FTP and HTTP are blocked until a new password is set.
EIO0000004135 09/2020
169
Ethernet Configuration
Clone management: allows you to control whether user rights are copied and applied to the target controller when cloning a controller with a USB key.
Click Exclude users rights to exclude copying user rights to the target controller when cloning a controller.
NOTE: By default, the users rights are excluded.
Click Include users rights to copy user rights to the target controller when cloning a controller. A popup prompts you to confirm copying the user rights. Click OK to continue.
170
EIO0000004135 09/2020
Ethernet Configuration
FTP Server
Introduction
Any FTP client installed on a computer that is connected to the controller (Ethernet or through USB port), without EcoStruxure Machine Expert installed, can be used to transfer files to and from the data storage area of the controller.
NOTE: Schneider Electric adheres to industry best practices in the development and implemen tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
Limit the number of devices connected to a network to the minimum necessary.
Isolate your industrial network from other networks inside your company.
Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
Monitor activities within your systems.
Prevent subject devices from direct access or direct link by unauthorized parties or unauthen ticated actions.
Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Make use of the security-related commands which provide a way to add, edit, and remove a user in the online user management of the target device where you are currently logged in.
The FTP server is deactivated by default.
FTP Access
Access to the FTP server is controlled by User Rights when they are enabled in the controller. For more information, refer to Users and Groups Tab Description
To access the FTP server you must first connect to the controller with EcoStruxure Machine Expert or Controller Assistant and modify the default user password.
Files Access
See File Organization ( see page 28 )
.
EIO0000004135 09/2020
171
Ethernet Configuration
FTP Client
Introduction
The FtpRemoteFileHandling library provides the following FTP client functionalities for remote file handling:
Reading files
Writing files
Deleting files
Listing content of remote directories
Adding directories
Removing directories
NOTE: Schneider Electric adheres to industry best practices in the development and implemen tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
Limit the number of devices connected to a network to the minimum necessary.
Isolate your industrial network from other networks inside your company.
Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
Monitor activities within your systems.
Prevent subject devices from direct access or direct link by unauthorized parties or unauthen ticated actions.
Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
For further information, refer to FtpRemoteFileHandling Library Guide.
172
EIO0000004135 09/2020
Ethernet Configuration
SNMP
Introduction
The Simple Network Management Protocol (SNMP) is used to provide the data and services required for managing a network.
The data is stored in a Management Information Base (MIB). The SNMP protocol is used to read or write MIB data. Implementation of the Ethernet SNMP services is minimal, as only the compulsory objects are handled.
SNMP Server
This table presents the supported server objects:
Object sysDescr
Description
Text description of the device
Access
Read
Value
SCHNEIDER M258 Fast Ethernet
TCP/IP
1.3.6.1.4.1.3833.1.7.36
sysObjectID Points to the product reference in the private MIB sysUpTime Time elapsed since the controller was last turned on sysContact Data item used to contact the manager of this node sysName Node administrative name sysLocation Physical location of the product sysService Indicates the type of service provided by this product
Read
Read
Read/Write -
-
Read/Write TM258LF42DT
Read/Write -
Read 79
The size of these character strings is limited to 50 characters.
The values written are saved to the controller via SNMP client tool software. The Schneider Electric software for this is ConneXview. ConneXview is not supplied with the controller or bus coupler. For more details, refer to www.schneider-electric.com.
EIO0000004135 09/2020
173
Ethernet Configuration
Firewall Configuration Section 11.2
Firewall Configuration
Introduction
This section describes how to configure the firewall of the Modicon M258 Logic Controller.
What Is in This Section?
This section contains the following topics:
Topic
Introduction
Dynamic Changes Procedure
Firewall Behavior
Firewall Script Commands
Page
174
EIO0000004135 09/2020
Ethernet Configuration
Introduction
Firewall Presentation
In general, firewalls help protect network security zone perimeters by blocking unauthorized access and permitting authorized access. A firewall is a device or set of devices configured to permit, deny, encrypt, decrypt, or proxy traffic between different security zones based upon a set of rules and other criteria.
Process control devices and high-speed manufacturing machines require fast data throughput and often cannot tolerate the latency introduced by an aggressive security strategy inside the control network. Firewalls, therefore, play a significant role in a security strategy by providing levels of protection at the perimeters of the network. Firewalls are an important part of an overall, system level strategy.
NOTE: Schneider Electric adheres to industry best practices in the development and implemen tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
Limit the number of devices connected to a network to the minimum necessary.
Isolate your industrial network from other networks inside your company.
Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
Monitor activities within your systems.
Prevent subject devices from direct access or direct link by unauthorized parties or unauthen ticated actions.
Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Firewall Configuration
There are three ways to manage the controller firewall configuration:
Static configuration
Dynamic changes
Application settings
Script files are used in the static configuration and for dynamic changes.
EIO0000004135 09/2020
175
Ethernet Configuration
Static Configuration
The static configuration is loaded at the controller boot.
The controller firewall can be statically configured by managing a default script file located in the controller. The path to this file is /usr/Cfg/FirewallDefault.cmd
.
Dynamic Changes
After the controller boot, the controller firewall configuration can be changed by the use of script files.
There are two ways to load these dynamic changes using:
A physical USB memory key.
A function block
in the application.
176
EIO0000004135 09/2020
Ethernet Configuration
Dynamic Changes Procedure
Using a USB Memory Key
This table describes the procedure to execute a script file from a USB memory key:
Step
1
2
3
Action
Create a valid script file
For example, name the script file
FirewallMaintenance.cmd
.
Load the script file on the USB memory key.
For example, load the script file in the usr/Cfg folder.
In the file Sys/Cmd/Script.cmd
, add a code line with the command
Firewall_install "/pathname/FileName"
For example, the code line is
Firewall_install "/bd0/usr/cfg/FirewallMaintenance.cmd"
4 Insert the USB memory key on the controller.
Using a Function Block in the Application
This table describes the procedure to execute a script file from an application:
Step
1
2
3
Action
Create a valid script file
For example, name the script file
FirewallMaintenance.cmd
.
Load the script file in the controller memory.
For example, load the script file in the usr/Syslog folder with FTP.
Use an ExecuteScript function block.
For example, the [SCmd] input is 'Firewall_install
"/usr/Syslog/FirewallMaintenance.cmd"'
EIO0000004135 09/2020
177
Ethernet Configuration
Firewall Behavior
Introduction
The firewall configuration depends on the action done on the controller and the initial configuration state. There are five possible initial states:
There is no default script file in the controller.
A correct script file is present.
An incorrect script file is present.
There is no default script file and the application has configured the firewall.
A dynamic script file configuration has already been executed.
No Default Script File
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is not configured. No protection is activated.
Firewall is configured according to the dynamic script file.
Firewall is not configured. No protection is activated.
Firewall is configured according to the application settings.
Default Script File Present
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is configured according to the default script file.
The whole configuration of the default script file is deleted.
Firewall is configured according to the dynamic script file.
Firewall is configured according to the default script file.
The dynamic script file is not taken into account.
The whole configuration of the application is ignored.
Firewall is configured according to the default script file.
Incorrect Default Script File Present
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is not configured. No protection is activated
Firewall is configured according to the dynamic script file.
Firewall is not configured. No protection is activated.
Firewall is configured according to the application settings.
178
EIO0000004135 09/2020
Ethernet Configuration
Application Settings with No Default Script File
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is configured according to the application settings.
The whole configuration of the application settings is deleted.
Firewall is configured according to the dynamic script file.
Firewall is configured according to the application settings. The dynamic script file is not taken into account.
The whole configuration of the previous application is deleted.
Firewall is configured according to the new application settings.
Execute Dynamic Script File Already Executed
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is configured according to the dynamic script file configuration (see note).
The whole configuration of the previous dynamic script file is deleted.
Firewall is configured according to the new dynamic script file.
Firewall is configured according to the previous dynamic script file configuration. The dynamic incorrect script file is not taken into account.
The whole configuration of the application is ignored
Firewall is configured according to the dynamic script file.
NOTE: If a USB memory key containing a cybersecurity script is plugged into the controller, booting is blocked. First remove the USB key to correctly boot the controller.
EIO0000004135 09/2020
179
Ethernet Configuration
Firewall Script Commands
Overview
This section describes how script files (default script files or dynamic script files) are written so that they can be executed during the booting of the controller or during a specific command triggered.
NOTE: The MAC layer rules are managed separately and have more priority over other packet filter rules.
Script File Syntax
The syntax of script files is described in Script Syntax Guidelines.
General Firewall Commands
The following commands are available to manage the Ethernet firewall of the M258 Logic
Controller:
Command
Firewall Enable
Firewall Disable
FireWall Eth1 Default Allow
FireWall Eth1 Default Reject
Description
Blocks the frames from the Ethernet interfaces. If no specific
IP address is authorized, it is not possible to communicate on the Ethernet interfaces.
NOTE: By default, when the firewall is enabled, the frames are rejected.
IP addresses can access the controller on the Ethernet interfaces.
Frames are accepted by the controller.
Frames are rejected by the controller.
NOTE: By default, if this line is not present, it corresponds to the command FireWall Eth1 Default Reject .
Specific Firewall Commands
The following commands are available to configure firewall rules for specific ports and addresses:
Command
Firewall Ethx
Allow IP •.•.•.•
Firewall Ethx
Reject IP •.•.•.•
Firewall Ethx
Allow IPs •.•.•.• to •.•.•.•
Range
• = 0...255
• = 0...255
• = 0...255
Description
Frames from the specified IP address are allowed on all port numbers and port types.
Frames from the specified IP address are rejected on all port numbers and port types.
Frames from the IP addresses in the specified range are allowed for all port numbers and port types.
180
EIO0000004135 09/2020
Ethernet Configuration
Command
Firewall Eth1
Reject IPs •.•.•.• to •.•.•.•
Range
• = 0...255
Firewall Eth1
Allow port_type port Y
Y = (destination port
)
Firewall Eth1
Reject port_type port Y
Y = (destination port
)
Description
Frames from the IP addresses in the specified range are rejected for all port numbers and port types.
Frames with the specified destination port number are allowed.
Frames with the specified destination port number are rejected.
NOTE: When IP forwarding is activated, rules with reject port only filter frames with current controller as destination. They are not applied for the frames routed by the current controller.
Frames with a destination port number in the specified range are allowed.
Firewall Eth1
Allow port_type ports Y1 to Y2
Y = (destination port
Firewall Eth1
Reject port_type ports Y1 to Y2
Y = (destination port
Firewall Eth1
Allow IP •.•.•.• on port_type port
Y
• = 0...255
Y = (destination port
Firewall Ethx
Reject IP •.•.•.• on port_type port
Y
• = 0...255
Y = (destination port
Firewall Ethx
Allow IP •.•.•.• on port_type ports
Y1 to Y2
• = 0...255
Y = (destination port
)
)
)
)
Firewall Ethx
Reject IP •.•.•.• on port_type ports
Y1 to Y2
• = 0...255
Y = (destination port
)
Firewall Ethx
Allow IPs
•1.•1.•1.•1 to
•2.•2.•2.•2 on port_type port Y
• = 0...255
Y = (destination port
)
Firewall Ethx
Reject IPs
•1.•1.•1.•1 to
•2.•2.•2.•2 on port_type port Y
• = 0...255
Y = (destination port
)
)
Frames with a destination port number in the specified range are rejected.
Frames from the specified IP address and with the specified destination port number are allowed.
Frames from the specified IP address and with the specified destination port number are rejected.
Frames from the specified IP address and with a destination port number in the specified range are allowed.
Frames from the specified IP address and with a destination port number in the specified range are rejected.
Frames from an IP address in the specified range and with the specified destination port number are allowed.
Frames from an IP address in the specified range and with the specified destination port number are rejected.
EIO0000004135 09/2020
181
Ethernet Configuration
Command
Firewall Ethx
Allow IPs
•1.•1.•1.•1 to
•2.•2.•2.•2 on port_type ports Y1 to Y2
Range
• = 0...255
Y = (destination port
)
Firewall Ethx
Reject IPs
•1.•1.•1.•1 to
•2.•2.•2.•2 on port_type ports Y1 to Y2
• = 0...255
Y = (destination port
)
Firewall Ethx
Allow MAC
••:••:••:••:••:••
• = 0...F
Firewall Ethx
Reject MAC
••:••:••:••:••:••
• = 0...F
Description
Frames from an IP address in the specified range and with a destination port number in the specified range are allowed.
Frames from an IP address in the specified range and with a destination port number in the specified range are rejected.
Frames from the specified MAC address ••:••:••:••:•• are allowed.
NOTE: When the rules to allow the MAC address are applied, only the listed MAC addresses can communicate with the controller, even if other rules are allowed.
Frames with the specified MAC address ••:••:••:••:•• are rejected.
Script Example
; Enable FireWall. All frames are rejected;
FireWall Enable;
; Allow frames on Eth1
FireWall Eth1 Default Allow;
; Block all Modbus Requests on all IP address
Firewall Eth1 Reject tcp port 502;
; Reject frames on Eth2
FireWall Eth2 Default Reject;
; Allow FTP active connection for IP address 85.16.0.17
FireWall Eth2 Allow IP 85.16.0.17 on tcp ports 20 to 21;
NOTE: Characters are limited to 200 per line, including comments.
182
EIO0000004135 09/2020
Ports Used
Protocol
EcoStruxure Machine Expert
FTP
HTTP
Modbus TCP
SNMP
NVL
EtherNet/IP
Destination Port Numbers
UDP 1740, 1741, 1742, 1743
TCP 1105
TCP 21, 20
TCP 80
TCP 502
UDP 161, 162
UDP Default value: 1202
UDP 2222
TCP 44818
Ethernet Configuration
EIO0000004135 09/2020
183
Ethernet Configuration
Ethernet Optional Devices Section 11.3
Ethernet Optional Devices
What Is in This Section?
This section contains the following topics:
Topic
Ethernet Manager
EtherNet/IP Device
Modbus TCP Slave Device
Page
184
EIO0000004135 09/2020
Ethernet Configuration
Ethernet Manager
Adding an Ethernet Manager
The controller supports the following Ethernet managers:
EthernetIP (for CIP Device)
ModbusTCP Slave Device
To add an Ethernet manager to your controller, select in the Hardware Catalog:
For an EthernetIP: EthernetIP
For a ModbusTCP: ModbusTCP Slave Device
Drag it to the Devices tree and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button
EIO0000004135 09/2020
185
Ethernet Configuration
EtherNet/IP Device
Introduction
This section describes the configuration of the EtherNet/IP Device (CIP) to the controller.
For further information about EtherNet/IP (CIP), refer to the www.odva.org website.
Adding an EtherNet/IP Device
See Adding an EtherNet Manager
EtherNet/IP Device Configuration
To configure the EtherNet/IP device parameters, double-click Ethernet → EthernetIP in the
Devices tree.
The following dialog box is displayed:
186
The EtherNet/IP configuration parameters are defined as:
Instance:
Number referencing the input or output Assembly.
Size:
Number of channels of an input or output Assembly.
The memory size of each channel is 2 bytes that stores the value of an %IWx or %QWx object, where x is the channel number.
EIO0000004135 09/2020
Ethernet Configuration
For example, if the Size of the Output Assembly is 20, it represents that there are 20 input channels (IW0...IW19) addressing %IWy...%IW(y+20-1), where y is the first available channel for the Assembly.
Element
Output Assembly
Input Assembly
Instance
Size
Instance
Size
Admissible Controller
Range
150...189
2...40
100...149
2...40
EcoStruxure Machine Expert
Default Value
150
20
100
20
EDS File Generation
You can generate an EDS file to facilitate configuring EtherNet/IP cyclic data exchanges.
To generate the EDS file:
Step
1
2
3
Action
In the Devices tree, right-click the EthernetIP node and choose the Export as EDS command from the context menu.
Modify the default file name and location as required.
Click Save.
NOTE: The Major Revision and Minor Revision objects in the EDS file are used to ensure uniqueness of the EDS file. The values of these objects do not reflect the actual controller revision level.
The EDS file is generated automatically in the "/usr/Eip" directory within the controller when an application is downloaded, or at start-up when a boot application exists, according to the parameters above.
NOTE: The EDS file is generated when the control network is working correctly on the controller
(cable connected and the IP address is acquired).
EIO0000004135 09/2020
187
Ethernet Configuration
EthernetIP Slave I/O Mapping Tab
Variables can be defined and named in the EthernetIP Slave I/O Mapping tab. Additional information such as topological addressing is also provided in this tab.
188
For further generic descriptions, refer to I/O Mapping Tab Description
.
EIO0000004135 09/2020
Ethernet Configuration
The table below describes the EthernetIP Slave I/O Mapping configuration:
Channel Type
WORD -
Default
Value
Description
Command word of controller outputs (%QW) Input IW0
IWxxx
Output QW0
QWxxx
WORD State of controller inputs (%IW)
The number of words depends on the size parameter configured in EtherNet/IP Device
Configuration
.
Output means OUTPUT from Originator controller (= %IW for the controller).
Input means INPUT from Originator controller (= %QW for the controller).
Connections on EtherNet/IP
To access a target device, open a connection (global name used by EtherNet/IP protocol level) which can include several sessions that send requests.
One explicit connection uses one session (a session is a TCP or UDP connection.
One I/O connection uses 2 sessions.
The following table shows the EtherNet/IP connections limitations:
Characteristic
Explicit connections
I/O connections
Connections
Sessions
Simultaneous requests
Maximum
8 (Class 3)
1 (Class 1)
8
16
32
EIO0000004135 09/2020
189
Ethernet Configuration
Profile
The controller supports the following objects:
Object class Class ID
1
1
Cat.
Number of
Instances
1
1
Identity Object
01 hex
02 hex
Connection Manager Object
04 hex
06 hex
File Object
37 hex
Modbus Object
44 hex
TCP/IP Interface Object
Ethernet Link Object
F5 hex
F6 hex
2
1
1
2
1
2
1
1
1
Effect on Interface Behavior
Supports the reset service
Explicit message connection
-
Defines I/O data format
-
Allows to exchange EDS file
TCP/IP configuration
Counter and status information
Identity Object (Class ID = 01 hex)
The following table describes the class attributes of the Identity Object:
2
3
Attribute ID
1
4
6
7
Access
Get
Get
Get
Get
Get
Get
Name
Revision
Data Type
UINT
Max Instances UINT
Number of
Instances
UINT
Optional
Instance
Attribute List
01h
01h
UINT, UINT [ ] 00h
UINT
Value Details
01h Implementation revision of the
Identity Object
The largest instance number
The number of object instances
07h
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes.
The largest class attributes value Max Class
Attribute
Max Instance
Attribute
UINT 07h The largest instance attributes value
190
EIO0000004135 09/2020
Ethernet Configuration
The following table describes the Class Services:
Service Code (hex) Name
01 Get Attribute All
0E Get Attribute Single
Description
Returns the value of all class attributes
Returns the value of the specified attribute
The following table describes the Instance Services:
Service Code (hex) Name
01 Get Attribute All
05
0E
Reset (1)
Get Attribute Single
Description
Returns the value of all class attributes
Initializes EtherNet/IP component (controller reboot)
Returns the value of the specified attribute
(1) Reset Service description:
When the Identity Object receives a Reset request, it:
determines whether it can provide the type of reset requested
responds to the request attempts to perform the type of reset requested
The Reset common service has one specific parameter, Type of Reset (USINT), with the following values:
Value
0
Type of Reset
Reboots the controller.
NOTE: This value is the default value if this parameter is omitted.
Reset Warm.
1
2 Not supported.
3...99
Reserved
100...199
Vendor specific
200...255
Reserved
The following table describes the Instance attributes:
2
3
Attribute ID
1
4
Access
Get
Get
Get
Get
Name
Vendor ID
Device type UINT
Product code UINT
Revision
Data Type Value
UINT 243h
Struct of
USINT,
USINT
-
0Eh
805h
Details
Schneider Automation ID
Controller
Controller product code
Product revision of the controller
Equivalent to the 2 low bytes of controller version
(1)
EIO0000004135 09/2020
191
Ethernet Configuration
Attribute ID
5
6
Access
Get
Get
Name
Status
Data Type Value
WORD (1) -
Serial number UDINT -
Details
See definition in the table below
Serial number of the controller
XX + 3 LSB of MAC address
Example: TM258LD42DT.
7 Get Product name Struct of
USINT,
STRING
-
1
2
Bit
0
3
4...7
(1) Mapped in a WORD:
MSB: minor revision (second USINT)
LSB: major revision (first USINT)
Example: 0205h means revision V5.2.
Status Description (Attribute 5):
8
9
10
Name
Owned
Reserved
Configured
Reserved
Extended Device
Status
Minor
Recoverable
Error
Minor
Unrecoverable
Error
Major
Recoverable
Error
-
Description
Unused
-
TRUE indicates the device application has been reconfigured.
0: self-testing or undetermined
1: firmware update in progress
2: at least one invalid I/O connection error detected
3: no I/O connections established
4: non-volatile configuration invalid
5: non recoverable error detected
6: at least one I/O connection in RUNNING state
7: at least one I/O connection established, all in idle mode
8: reserved
9...15: unused
TRUE indicates the device detected an error, which, under most circumstances, is recoverable.
This type of event does not lead to a change in the device state.
TRUE indicates the device detected an error, which, under most circumstances, is not recoverable.
This type of event does not lead to a change in the device state.
TRUE indicates the device detected an error, which requires the device to report an exception and enter into the HALT state.
This type of event leads to a change in the device state, but, under most circumstances, is recoverable.
192
EIO0000004135 09/2020
Ethernet Configuration
Bit
11
Name
Major
Unrecoverable
Error
12...15 Reserved -
Description
TRUE indicates the device detected an error, which requires the device to report an exception and enter into the HALT state.
This type of event leads to a change in the device state, but, under most circumstances, is not recoverable.
Message Router Object (Class ID = 02 hex)
The following table describes the class attributes of the Message Router Object:
Attribute ID
1
2
3
4
5
6
7
Access
Get
Get
Get
Get
Get
Get
Get
Name
Revision
Optional
Service
List
Max Class
Attribute
Max
Instance
Attribute
Data Type
UINT
Max
Instances
Number of
Instance
Optional
Instance
Attribute
List
UINT
UINT
Struct of UINT,
UINT [ ]
01h
20
UINT
UINT
UINT
Value Details
01h Implementation revision of the Message
Router Object
01h The largest instance number
00h
07h
119
The number of object instances
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes (from 100 to 119).
The number and list of any implemented optional services attribute (0: no optional services implemented)
The largest class attributes value
The largest instance attributes value
The following table describes the Class Services:
Service Code (hex) Name
01 Get Attribute All
0E Get Attribute Single
Description
Returns the value of all class attributes
Returns the value of the specified attribute
The following table describes the Instance Services:
Service Code (hex) Name
01 Get Attribute All
0E Get Attribute Single
Description
Returns the value of all class attributes
Returns the value of the specified attribute
EIO0000004135 09/2020
193
Ethernet Configuration
The following table describes the Instance attributes:
Attribute ID
1
2
100
101
102
103
104
Access Name
Get
Get
Get
Get
Get
Get
Get
Implemented Object
List
Number available
Total incoming Class1 packets received during the last second
Total outgoing Class1 packets sent during the last second
Total incoming Class3 packets received during the last second
Total outgoing Class3 packets sent during the last second
Total incoming unconnected packets received during the last second
Data Type
Struct of
UINT, UINT [ ]
UINT
UINT
UINT
UINT
UDINT
UINT
-
-
-
-
-
-
Value Description
Implemented Object list. The first 2 bytes contain the number of implemented objects. Each two bytes that follow represent another implemented class number.
This list contains the following objects:
Identity
Message Router
Assembly
Connection Manager
Parameter
File Object
Modbus
Port
TCP/IP
Ethernet Link
20h Maximum number of concurrent CIP (Class1 or
Class 3) connections supported
Total number of incoming packets received for all implicit (Class1) connections during the last second
Total number of outgoing packets sent for all implicit
(Class1) connections during the last second
Total number of incoming packets received for all explicit (Class 3) connections during the last second
Total number of outgoing packets sent for all explicit
(Class 3) connections during the last second
Total number of incoming unconnected packets received during the last second
194
EIO0000004135 09/2020
Attribute ID
105
106
107
108
109
110
111
112
113
114
EIO0000004135 09/2020
Access Name
Get Total outgoing unconnected packets sent during the last second
Get
Get
Get
Total incoming
EtherNet/IP packets received during the last second
Total outgoing
EtherNet/IP packets sent during the last second
Total incoming Class1 packets received
Data Type
UINT
UINT
UINT
UINT
Get Total outgoing Class1 packets sent
UINT
Get Total incoming Class3 packets received
UINT
Get
Get
Get
Get
Total incoming Class3 packets Invalid
Parameter Value
Total incoming Class3 packets Invalid Format
Total outgoing Class3 packets sent
Total incoming unconnected packets received
UINT
UINT
UINT
UINT
Ethernet Configuration
-
-
-
-
-
-
-
-
-
-
Value Description
Total number of outgoing unconnected packets sent during the last second
Total unconnected Class1 or
Class 3 packets received during the last second
Total unconnected Class1 or
Class 3 packets sent during the last second
Total number of incoming packets received for all implicit (Class1) connections
Total number of outgoing packets sent for all implicit
(Class1) connections
Total number of incoming packets received for all explicit (Class 3) connections. This number includes the packets that would be returned if an error had been detected (listed in the next two rows).
Total number of incoming
Class 3 packets that targeted a non-supported service/class/instance/attribu te/member
Total number of incoming
Class 3 packets that had an invalid format
Total number of packets sent for all explicit (Class 3) connections
Total number of incoming unconnected packets. This number includes the packets that would be returned if an error had been detected
(listed in the next two rows).
195
Ethernet Configuration
Attribute ID
115
116
117
118
119
Access Name
Get Total incoming unconnected packets
Invalid Parameter
Value
Data Type
UINT
Get
Get
Get
Get
Total incoming unconnected packets
Invalid Format
Total outgoing unconnected packets sent
Total incoming
EtherNet/IP packets
Total outgoing
EtherNet/IP packets
UINT
UINT
UINT
UINT -
-
-
-
-
Value Description
Total number of incoming unconnected packets that targeted a non-supported service/class/instance/attribu te/member
Total number of incoming unconnected packets that had an invalid format
Total number of all unconnected packets sent
Total unconnected, Class 1, or Class 3 packets received
Total unconnected, Class 1, or Class 3 packets sent
Assembly Object (Class ID = 04 hex)
The following table describes the class attributes of the Assembly Object:
2
3
4
Attribute ID
1
5
6
7
Access Name
Get Revision
Get
Get
Get
Get
Get
Get
Data Type
UINT
Max Instances UINT
Number of Instances UINT
Optional Instance
Attribute List
Struct of:
UINT
UINT [ ]
Optional Service List UINT
Max Class Attribute UINT
Max Instance Attribute UINT
1
4
Value Details
2 Implementation revision of the
Assembly Object
189
2
00h
The largest instance number
The number of object instances
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes.
The number and list of any implemented optional services attribute (0: no optional services implemented)
07h
04h
The largest class attributes value
The largest instance attributes value
196
EIO0000004135 09/2020
Ethernet Configuration
The following table describes the Class Services:
Service Code (hex) Name
0E Get Attribute Single
Description
Returns the value of the specified attribute
The following table describes the Instance Services:
Service Code (hex) Name
0E Get Attribute Single
10
18
19
Set Attribute Single
Get Member
Set Member
Description
Returns the value of the specified attribute
Modifies the value of the specified attribute
Reads a member of an Assembly object instance
Modifies a member of an Assembly object instance
Instances Supported
Output means OUTPUT from Originator controller (= %IW for the controller).
Input means INPUT from Originator controller (= %QW for the controller).
The controller supports 2 Assemblies:
Name
Controller Output (%IW)
Controller Input (%QW)
Instance Data Size
Configurable: must be between 100 and 149 2...40 words
Configurable: must be between 150 and 189 2...40 words
NOTE: The Assembly object binds together the attributes of multiple objects so that information to or from each object can be communicated over a single connection. Assembly objects are static.
The Assemblies in use can be modified through the parameter access of the network configuration tool (RSNetWorx). The controller needs to recycle power to register a new Assembly assignment.
The following table describes the Instance attributes:
Attribute ID
1
2
3
4
Access
Get
Get
Get/Set
Get
Name
Number of Member
Object List
Member List
Instance Data
Instance Data Size
Data Type
UINT
ARRAY of
Struct
ARRAY of
Byte
UINT
-
-
Value Description
2...40
Always 1 member for the controller
4...80
Array of 1 structure where each structure represents one member
Data Set service only available for Controller output
Size of data in byte
EIO0000004135 09/2020
197
Ethernet Configuration
Member list content:
Name
Member data size
Member path size
Member path
EPATH is:
Word
0
1
Value
2004 hex
24xx hex
2 30 hex
Data Type
UINT
UINT
EPATH -
6
Value
4...40
Type of Reset
Member data size in bits
Size of the EPATH (see table below)
EPATH to the Member
Semantic
Class 4
Instance xx where xx is the instance value (example: 2464 hex = instance
100).
Attribute 3
Connection Manager Object (Class ID = 06 hex)
The following table describes the class attributes of the Assembly Object:
Attribute ID
1
2
Access Name
Get Revision
Get
Data Type Value Details
UINT 2 Implementation revision of the
Connection Manager Object
UINT 189 The largest instance number
3 Get
Max
Instances
Number of
Instances
UINT 2 The number of object instances
198
EIO0000004135 09/2020
Ethernet Configuration
Attribute ID
4
6
7
Access Name
Get Optional
Instance
Attribute List
Get
Data Type Value Details
Struct of:
UINT
UINT [ ]
The number and list of the optional attributes. The first word contains the number of attributes to follow and each following word contains another attribute code.
Following optional attributes include:
total number of incoming connection open requests
the number of requests rejected because of the non-conforming format of the Forward Open the number of requests rejected because of insufficient resources the number of requests rejected because of the parameter value sent with the Forward Open the number of Forward Close requests received the number of Forward Close requests that had an invalid format the number of Forward Close requests that could not be matched to an active connection the number of connections that have timed out because the other side stopped producing, or a network disconnection occurred
UINT 07h The largest class attributes value
Get
Max Class
Attribute
Max
Instance
Attribute
UINT 08h The largest instance attributes value
The following table describes the Class Services:
Service Code (hex)
01
0E
Name
Get Attribute All
Get Attribute Single
Description
Returns the value of all class attributes
Returns the value of the specified attribute
EIO0000004135 09/2020
199
Ethernet Configuration
The following table describes the Instance Services:
Service Code (hex)
01
0E
4E
52
54
Name
Get Attribute All
Get Attribute Single
Forward Close
Unconnected Send
Forward Open
Description
Returns the value of all instance attributes
Returns the value of the specified attribute
Closes an existing connection
Sends a multi-hop unconnected request
Opens a new connection
The following table describes the Instance attributes:
Attribute ID
1
2
3
4
5
6
7
8
Access
Get
Get
Name
Open Requests
Data Type Value Description
UINT Number of Forward Open service requests received
Open Format Rejects UINT -
Get Open Resource
Rejects
ARRAY of
Byte
-
Number of Forward Open service requests which were rejected due to invalid format
Number of Forward Open service requests which were rejected due to lack of resources
Get Open Other Rejects UINT -
Get
Get
Get
Get
Close Requests
Close Format
Requests
Close Other
Requests
UINT
UINT
UINT
Connection Timeouts UINT -
-
-
-
Number of Forward Open service requests which were rejected for reasons other than invalid format or lack of resources
Number of Forward Close service requests received
Number of Forward Close service requests which were rejected due to invalid format
Number of Forward Close service requests which were rejected for reasons other than invalid format
Total number of connection timeouts that have occurred in connections controlled by this
Connection Manager
200
EIO0000004135 09/2020
Ethernet Configuration
File Object (Class ID = 37 hex)
The following table describes the class attributes of the File Object:
2
3
6
Attribute ID
1
7
32
Access
Get
Get
Get
Get
Get
Name
Revision
Max Instances
Number of Instances
Max Class Attribute
Data Type Value Details
UINT 1 Implementation revision of the
File Object
UINT
UINT
UINT
C9h
2
20h
The largest instance number
The number of object instances
Max Instance Attribute UINT 0Bh
The largest class attributes value
The largest instance attributes value
Get Instance List Returns information on all configured instances including
Instance Number, Instance
Name and Instance File Name
The following table describes the Class Services:
Service Code (hex) Name
0E Get Attribute Single
Description
Returns the value of the specified attribute
Instance Code
The File object provides download functionality for the EDS and EDS Icon files. The following instances of the File object are implemented:
Instance C8 hex returns an uncompressed version of the EDS text file. The instance name attribute is returned as "EDS and Icon Files". The file name attribute returns "M258xxx.eds"
where M258xxx is the exact reference of the controller. The contents of the EDS file are adjusted dynamically by the controller. The connection data sizes in the EDS file are adjusted to reflect the actual standard Assembly instance sizes.
Instance C9 hex returns a compressed version of the device EDS icon file. The instance name is returned as "Related EDS and Icon Files". The file name attribute returns "M258xxx.gz" where
M258xxx is the exact reference of the controller. This is zip encoded file containing only one file:
M258xxx.ico. The file is encoded with the ZLIB compression file format. ZLIB is a free, general purpose, legally unencumbered, loss-less compression library. The specifications are available from the Internet Engineering Task Force (http://www.ietf.org).
EIO0000004135 09/2020
201
Ethernet Configuration
The following table describes the Instance Services:
Service Code
(hex)
0E
4B
4F
Name Description
Get Attribute Single Returns the value of the specified instance attribute
Initiate Upload Start uploading process. Request contains the Maximum File Size the Client can accept on Upload. Response contains the actual File
Size, which will never be more than the Maximum File Size and the
Transfer Size, which is the number of bytes transferred with each
Upload Transfer request.
Upload Transfer Upload another section of file data. Request contains the Transfer
Number, which is incremented with each subsequent transfer.
Response contains the matching Transfer Number, Transfer Type,
File Data, and for the last transfer, the Checksum word. Transfer
Type indicates if this is the first, intermediate or last packet, if it is the only packet, or if the transfer should be aborted.
The following table describes the Instance Attributes:
Attribute ID
1
2
Access
Get
Get
Name
State
Data Type Value Description
USINT
Instance Name STRING -
One of the following:
0: non existent
1: file empty - file should not have any content until it is downloaded from the remote client. When set, File name,
Revision, Checksum and File Save
Flag values have no meaning, and
File Size is 0.
2: file loaded - file contents are preloaded by the application (file size >
0) or file data has been downloaded and stored into the non-volatile memory area
3: upload initiated
4: download initiated
5: upload in progress
6: download in progress
7: storing to non-volatile area is in progress
Unique Name assigned to the File Object
Instance. For the C8 hex instance, it is
"EDS and Icon Files". For the C9 hex instance, it is "Related EDS and Icon
Files".
202
EIO0000004135 09/2020
Ethernet Configuration
6
7
4
5
8
10
11
Attribute ID
3
9
Access
Get
Get
Get
Get
Get
Name
Instance
Format
Revision
File Name
File Revision
File Size
Data Type Value Description
UINT Revision number assigned for this instance by the application, to differentiate between different file formats.
STRING
USINT
UDINT
File Checksum UINT
-
-
-
Major
Minor
Unique name for File Storage
File Revision is updated every time file content is changed.
File Size in bytes
Get Invocation
Method
USINT -
Two’s complement of the 16 bit sum of all bytes
Defines what should happen after the file is downloaded. Possible options include:
0: No Action
2: Power Cycle, etc.
Get File Save
Parameters
BYTE -
Get
Get
File Type
File Encoding
Format
USINT
UINT -
-
If bit 1 is set, the file should be explicitly saved to non-volatile storage after download is complete.
0: Read/Write access
1: Read Only access
0: no encoding
1: encoded using ZLIB
Modbus Object (Class ID = 44 hex)
The Modbus object provides an additional method to access the Modbus table data. A single explicit request will either read or write 1 or more contiguous registers. An additional Pass-through service allows the user to specify an actual Modbus message data.
The following table describes the class attributes of the Modbus Object:
Attribute ID
1
Access
Get
Name
Revision
Data Type
UINT
Value Details
1 Implementation revision of the
Modbus Object
The following table describes the Class Services:
Service Code (hex) Name
0E Get Attribute Single
Description
Returns the value of the specified attribute
EIO0000004135 09/2020
203
Ethernet Configuration
Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:
Service Code
(hex)
4B
Name Description
4C
4E
4F
50
Read Digital Inputs
Read Coils
Returns the value of one or several contiguous Digital Input registers
Returns the value of one or several contiguous Coils
Read Holding Registers Returns the value of one or several contiguous Holding
Registers
Write Coils Updates the value of one or several contiguous Coils
Write Holding Registers Updates the value of one or several contiguous Holding
Registers
NOTE: The Read Register service requires 4 bytes of data: the first word contains the starting register address and the second word contains the number of registers to read. The Write service request requires the same 4 bytes, followed by the actual data.
The Modbus Pass-through service indicates a specific Modbus function. The translation function will not perform any Indian conversion on the request or response data. Both request and response contain 1 byte of the Modbus Function code followed by the Modbus message data, including a sub-function code if present.
TCP/IP Interface Object (Class ID = F5 hex)
This object maintains link specific counters and status information for an Ethernet 802.3 communications interface.
The following table describes the class attributes of the TCP/IP Interface Object:
2
3
Attribute ID
1
6
7
Access
Get
Get
Get
Get
Get
Name
Revision
Max Instances
Number of Instance
Max Class Attribute
Data Type
UINT
UINT
UINT
UINT
Max Instance Attribute UINT
1
1
Value Details
1 Implementation revision of the
TCP/IP Interface Object
The largest instance number
The number of object instances
07h
06h
The largest class attributes value
The largest instance attributes value
204
EIO0000004135 09/2020
Ethernet Configuration
The following table describes the Class Services:
Service Code (hex)
01
0E
Name
Get Attribute All
Get Attribute Single
Description
Returns the value of all class attributes
Returns the value of the specified attribute
Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:
Service Code (hex)
01
0E
Name
Get Attribute All
Get Attribute Single
Description
Returns the value of all instance attributes
Returns the value of the specified instance attribute
The following table describes the Instance Attributes:
Attribute ID
1
Access Name
Get Status
Data Type Value
DWORD Bit level
2
3
Get
Get
Configuration
Capability
Configuration
DWORD Bit level
DWORD Bit level
Description
0: The interface configuration attribute has not been configured.
1: The interface configuration contains a valid configuration.
2...15: Reserved.
0: BOOTP Client
1: DNS Client
2: DHCP Client
3: DHCP-DNS capable
4: interface configuration set table
All other bits are reserved and set to
0.
0: The interface configuration is valid.
1: The interface configuration is obtained with BOOTP.
2: The interface configuration is obtained with DHCP.
3: reserved
4: DNS Enable
All other bits are reserved and set to
0.
EIO0000004135 09/2020
205
Ethernet Configuration
Attribute ID
4
Access Name
Get Physical Link
5
6
Get
Get
Interface configuration
Host Name
Data Type Value
UINT
Padded
EPATH
UDINT
UDINT
UDINT
UDINT
UDINT
Path size
Path
IP Address -
Network
Mask
-
-
Logical segments identifying the physical link object. The path is restricted to one logical class segment and one logical instance segment. The maximum size is 12 bytes.
Gateway
Address
Primary
Name
-
Secondary
Name
Description
Number of 16 bits word in the element Path
STRING
STRING -
Default
Domain
Name
0: no secondary name server address has been configured.
Otherwise, the name server address shall be set to a valid Class A, B, or C address.
ASCII characters. Maximum length is
48 characters. Padded to an even number of characters (pad not included in length).
0: no Domain Name is configured
ASCII characters. Maximum length is
64 characters. Shall be padded to an even number of characters (pad not included in length).
0: no Host Name is configured
206
EIO0000004135 09/2020
Ethernet Configuration
Ethernet Link Object (Class ID = F6 hex)
This object provides the mechanism to configure a TCP/IP network interface device.
The following table describes the class attributes of the Ethernet Link Object:
2
3
Attribute ID
1
6
7
Access
Get
Get
Get
Get
Get
Name
Revision
Max Instances
Number of Instances
Max Class Attribute
Data Type
UINT
UINT
UINT
UINT
Max Instance Attribute UINT
1
1
Value Details
2 Implementation revision of the
Ethernet Link Object
The largest instance number
The number of object instances
07h
03h
The largest class attributes value
The largest instance attribute value
The following table describes the Class Services:
Service Code (hex) Name
01 Get Attribute All
0E Get Attribute Single
Description
Returns the value of all class attributes
Returns the value of the specified attribute
Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:
Service Code (hex) Name
01 Get Attribute All
10
0E
Set Attribute Single
Get Attribute Single
Description
Returns the value of all instance attributes
Modifies the value of the specified attribute
Returns the value of the specified instance attribute
EIO0000004135 09/2020
207
Ethernet Configuration
The following table describes the Instance Attributes:
Attribute ID
1
2
Access Name
Get
Data Type Value
Interface Speed UDINT -
Get Interface Flags DWORD Bit level
3 Get Physical
Address
ARRAY of
6 USINT
-
Description
Speed in Mbps (10 or 100)
0: link status
1: half/full duplex
2...4: negotiation status
5: manual setting / requires reset
6: local hardware error detected
All other bits are reserved and set to 0.
This array contains the MAC address of the product.
Format: XX-XX-XX-XX-XX-XX
208
EIO0000004135 09/2020
Ethernet Configuration
Modbus TCP Slave Device
Overview
This section describes the configuration of Modbus TCP Slave Device to the controller.
The Modbus TCP Slave Device is a privileged Modbus device on the network. It serves as a gateway for an external I/O scanner configured as the Modbus master, and allows this scanner to exchange data with the controller without interfering with the operation of the Modbus server on the controller. Essentially, the Modbus TCP Slave allows two Modbus masters to coexist and exchange data.
While the Modbus TCP Slave Device uses standard Modbus commands (3 h, 6 h, and so on), these commands do not have their standard meaning. As this device is acting as a gateway for an external I/O scanner (Modbus master), the schema where %IW registers are associated with inputs (read-only) and %QW registers are associated with outputs (read-write) is reversed when considered from the perspective of the external Modbus master.
For further information about Modbus TCP, refer to the www.odva.org
website.
Adding a Modbus TCP Slave Device
See Adding an Ethernet Manager
.
Modbus TCP Configuration
To configure the Modbus TCP Slave Device, double-click Modbus → Modbus TCP in the Devices tree.
This dialog box appears:
EIO0000004135 09/2020
209
Ethernet Configuration
Element
IP Master Address
TimeOut
Slave Port
Unit ID
Holding Registers (%IW)
Input Registers (%QW)
Description
IP address of the Modbus master
The connections are not closed on this address.
Timeout in 500 ms increments
NOTE: The timeout applies to the IP master Address unless the address is
0.0.0.0.
Modbus communication port (502)
Sends the requests to the Modbus TCP slave device (1...247), instead of to the embedded Modbus server (255).
Size of the %IW registers in bytes (2...40 bytes)
Size of the %QW registers in bytes (2...40 bytes)
Modbus TCP Slave Device I/O Mapping Tab
The I/Os are mapped to Modbus registers from the master perspective as follows:
%IWs are mapped from register 0 to n-1 and are R/W (n = Holding register quantity, each %IW
register is 2 bytes).
%QWs are mapped from register n to n+m -1 and are read only (m = Input registers quantity, each %QW register is 2 bytes).
Once a Modbus TCP Slave Device has been configured, Modbus commands sent to its Unit ID
(Modbus address) are handled differently than the same command would be when addressed to any other Modbus device on the network. For example, when the Modbus command 3 (3 hex) is sent to a standard Modbus device, it reads and returns the value of one or more registers. When this same command is sent to the Modbus TCP by the external I/O scanner.
Slave, it facilitates a read operation
The Modbus TCP Slave Device responds to a subset of the Modbus commands, but does so in a way that differs from Modbus standards, and with the purpose of exchanging data with the external
I/O scanner. The following Modbus commands are supported by the Modbus TCP slave device:
Function Code
Dec (Hex)
3 (3)
6 (6)
16 (10)
23 (17)
Other
Function Comment
Read holding register
Write single register
Allows the master to read %IW and %QW objects of the device
Allows the master to write %IW objects of the device
Write multiple registers Allows the master to write %IW objects of the device
Read/write multiple registers
Not supported
Allows the master to read %IW and %QW objects of the device and write %IW objects of the device
–
NOTE: Modbus requests that attempt to access registers above n+m-1 are answered by the 02 -
ILLEGAL DATA ADDRESS exception code.
210
EIO0000004135 09/2020
Ethernet Configuration
To link I/O objects to variables, select the Modbus TCP Slave Device I/O Mapping tab:
EIO0000004135 09/2020
211
Ethernet Configuration
Channel
Input
Output
IW0
...
IWx
QW0
...
QWy
Type
WORD
...
WORD
WORD
...
WORD
Description
Holding register 0
...
Holding register x
Input register 0
...
Input register y
The number of words depends on the Holding Registers (%IW) and Input Registers (%QW) parameters of the Modbus TCP tab.
NOTE: Output means OUTPUT from Originator controller (= %IW for the controller). Input means
INPUT from Originator controller (= %QW for the controller).
Bus Cycle Options
In the Modbus TCP Slave Device I/O Mapping tab, select the Bus cycle task to use:
Use parent bus cycle setting (the default),
MAST
An existing task of the project: you can select an existing task and associate it to the scanner.
For more information about the application tasks, refer to the EcoStruxure Machine Expert
Programming Guide.
NOTE: There is a corresponding Bus cycle task parameter in the I/O mapping editor of the device that contains the Modbus TCP Slave Device. This parameter defines the task responsible for refreshing the %IW and %QW registers.