Ethernet Configuration
Web Server
Introduction
As standard equipment, the controller provides an embedded Web server with a predefined, builtin website. You can use the pages of the website for module setup and control as well as application diagnostics and monitoring. These pages are ready to use with a Web browser. No configuration or programming is required.
The Web server can be accessed by the web browsers listed below:
Google Chrome (version 65.0 or greater)
Mozilla Firefox (version 54 or greater)
Microsoft Internet Explorer (version 11 or greater)
The Web server is limited to 10 TCP connections
.
The Web server has full access to your application for reading and writing data and controlling the state of the controller. By enabling the Web server, you enable these functions. You can disable the Web server on an interface by deselecting the Web Server active parameter in the Ethernet
Configuration tab ( see page 143 ) .
The Web server is a tool for reading and writing data, and controlling the state of the controller, with full access to all data in your application. However, if there are security concerns over these functions, you must at a minimum assign a secure password to the Web Server or disable the Web server to help prevent unauthorized access to the application. By enabling the Web server, you enable these functions.
EIO0000004135 09/2020
149
Ethernet Configuration
The Web server allows you to monitor a controller and its application remotely, to perform various maintenance activities including modifications to data and configuration parameters, and change the state of the controller. Care must be taken to ensure that the immediate physical environment of the machine and process is in a state that will not present safety risks to people or property before exercising control remotely.
WARNING
UNINTENDED EQUIPMENT OPERATION
Configure and install the RUN/STOP input for the application, if available for your particular controller, so that local control over the starting or stopping of the controller can be maintained regardless of the remote commands sent to the controller.
Define a secure password for the Web Server and do not allow unauthorized or otherwise unqualified personnel to use this feature.
Ensure that there is a local, competent, and qualified observer present when operating on the controller from a remote location.
You must have a complete understanding of the application and the machine/process it is controlling before attempting to adjust data, stopping an application that is operating, or starting the controller remotely.
Take the precautions necessary to assure that you are operating on the intended controller by having clear, identifying documentation within the controller application and its remote connection.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: The Web server must only be used by authorized and qualified personnel. A qualified person is one who has the skills and knowledge related to the construction and operation of the machine and the process controlled by the application and its installation, and has received safety training to recognize and avoid the hazards involved. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this feature.
150
EIO0000004135 09/2020
Ethernet Configuration
Web Server Access
Access to the Web server is controlled by User Rights when they are enabled in the controller. For more information, refer to Users and Groups Tab Description
To access the Web server you must first connect to the controller with EcoStruxure Machine Expert or Controller Assistant and modify the default user password.
WARNING
UNAUTHORIZED DATA ACCESS
Secure access to the FTP/Web server using User Rights.
If you disable User Rights, disable the FTP/Web server to help prevent any unwanted or unauthorized access to data in your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
In order to change the password, go to Users and Groups tab of the device editor. For more information, refer to the EcoStruxure Machine Expert Programming Guide (see SoMachine,
Programming Guide) .
NOTE: The only way to gain access to a controller that has user access-rights enabled and for which you do not have the password(s) is by performing an Update Firmware operation. This clearing of User Rights can only be accomplished by using a USB key to update the controller firmware. In addition, you may clear the User Rights in the controller by running a script (for more information, refer to EcoStruxure Machine Expert Programming Guide memory, but restores the ability to access the Controller.
(see SoMachine,
Programming Guide) ) . This effectively removes the existing application from the controller
EIO0000004135 09/2020
151
Ethernet Configuration
Home Page Access
To access to the website home page shown in the following illustration, type in your navigator the
IP address of the controller, or 90.0.0.1 for a USB connection:
This figure shows the Web Server site login page:
This figure shows the home page of the Web Server site once you have logged in:
152
EIO0000004135 09/2020
Ethernet Configuration
NOTE: Schneider Electric adheres to industry best practices in the development and implemen tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
Limit the number of devices connected to a network to the minimum necessary.
Isolate your industrial network from other networks inside your company.
Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
Monitor activities within your systems.
Prevent subject devices from direct access or direct link by unauthorized parties or unauthen ticated actions.
Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Generic Menu Bar
The generic menu bar lets you access the main Web server pages.
The Web Server contains the following pages:
Menu
Home
Documentation
Page Description
Home
Home page of the controller Web server page.
Provides access to the tabs:
Monitoring
Diagnostics
Maintenance
Setup
References Link to the brand site.
EIO0000004135 09/2020
153
Ethernet Configuration
Home Page Menu Descriptions:
:
Menu
Monitoring
Diagnostics
Maintenance
Setup
Submenu
Controller Viewer
Description
Serial Number
Version (firmware, boot...)
Configuration status
Expansion Viewer
Shows the status of expansion modules.
Shows the module with module I/O values.
Oscilloscope
Displays 2 variables in the form of a recorder-type time chart.
Lets you display and modify controller variables.
Controller
Controller status
Ethernet status
Serial
Profibus
FTP
Serial line status
Profibus status
Link to the file system server ( /Usr , /bd0 and /Sys folders)
User Management
Lets you change user password and customize login message.
Users account management: allows you to remove all passwords from the controller and reset user
accounts to their default state.
Clone management: lets you include or exclude user access rights when cloning a controller.
Lets you set the Ethernet and serial line parameters.
Post configuration setup
EthernetIP configurations
Lets you set the EthernetIP configuration files.
The following submenu is visible in each tab:
Submenu
Info
Control
Description
Current Controller information
Reference
Device name
Running state
Allows you to Start or Stop the controller
154
EIO0000004135 09/2020
Ethernet Configuration
The Web server allows you to remotely monitor a controller and its application, and to perform various maintenance activities including modifications to data and configuration parameters, and change the state of the controller. Ensure that the immediate physical environment of the machine and process is in a state that will not present safety risks to people or property before exercising control remotely.
WARNING
UNINTENDED EQUIPMENT OPERATION
Configure and install the RUN/STOP input for the application, if available for your particular controller, so that local control over the starting or stopping of the controller can be maintained regardless of the remote commands sent to the controller.
Define a secure password for the Web Server and do not allow unauthorized or otherwise unqualified personnel to use this feature.
Ensure that there is a local, competent, and qualified observer present when operating on the controller from a remote location.
You must have a complete understanding of the application and the machine/process it is controlling before attempting to adjust data, stopping an application that is operating, or starting the controller remotely.
Take the precautions necessary to assure that you are operating on the intended controller by having clear, identifying documentation within the controller application and its remote connection.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: The Web server must only be used by authorized and qualified personnel. A qualified person is one who has the skills and knowledge related to the construction and operation of the machine and the process controlled by the application and its installation, and has received safety training to recognize and avoid the hazards involved. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this feature.
EIO0000004135 09/2020
155
Ethernet Configuration
Page Access
This table lists the necessary status of the controller to access different pages:
Menu
Home
Documentation
Monitoring
Diagnostics
Maintenance
Setup
Submenu
Home
References
Controller Viewer
Expansion Viewer
IO Viewer
Oscilloscope
Data parameters
Controller diagnostic
Ethernet diagnostic
Serial diagnostic
Profibus diagnostic
/Usr or /bd0
/Sys X
Post configuration setup X
EthernetIP configurations files
X
X
X
-
X
X
X
-
-
-
X
X
X
Controller State
EMPTY STOPPED
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
RUNNING
X
X
X
X
X
X
-
-
-
-
X
X
X
X
X
HALT
X
156
EIO0000004135 09/2020
Monitoring: Controller Viewer Submenu
The Controller Viewer submenu shows the controller status:
Ethernet Configuration
The Configuration status field can change depending on the controller reference visualized (a
TM258LF42DT in the previous screenshot) and can have the following status:
Configuration Status Description
No error No error detected on the corresponding element.
Error An error is detected on the corresponding element.
EIO0000004135 09/2020
157
Ethernet Configuration
Monitoring: Expansion Viewer Submenu
The Expansion Viewer submenu shows the expansion module status:
158
The following table describes each status code:
20
30
100
200
Status Code
0
10
11
201
202
Description
INACTIVE: module inactive
BOOT: boot state
FWDNLD: firmware download in progress
PREOP: basic initialization
OPERATE: register initialization
ACTIVE: module communication active
ERROR: an error has been detected
UNSUP: unsupported module
NOCFG: no configuration available
EIO0000004135 09/2020
Ethernet Configuration
Monitoring: Data Parameters
Monitoring Web Server Variables
To monitor Web server variables, you must add a Web Data Configuration object to your project.
Within this object, you can select all variables you want to monitor.
This table describes how to add a Web Data Configuration object:
Step
1
2
3
Action
Right click the Application node in the Applications tree tab.
Click Add Object → Web Data Configuration....
Result: The Add Web Data Configuration window is displayed.
Click Add.
Result: The Web Data Configuration object is created and the Web Data Configuration editor is open.
NOTE: As a Web Data Configuration object is unique for a controller, its name cannot be changed.
Web Data Configuration Editor
Click the Refresh button to be able to select variables, this action will display all the variables defined in the application.
EIO0000004135 09/2020
159
Ethernet Configuration
Select the variables you want to monitor in the web server:
160
NOTE: The variable selection is possible only in offline mode.
EIO0000004135 09/2020
Ethernet Configuration
Monitoring: Data Parameters Submenu
The Data Parameters submenu allows you to display and modify variable values:
Element
Add
Description
Adds a list description or a variable
Del Deletes a list description or a variable
Refresh period Refreshing period of the variables contained in the list description (in ms)
Refresh Enables I/O refreshing:
Gray button: refreshing disabled
Orange button: refreshing enabled
Load
Save
Loads saved lists from the controller internal Flash to the Web server page
Saves the selected list description in the controller ( /usr/web or /bd0/web directory)
NOTE: IEC objects ( %IW , %M ,...) are not directly accessible. To access IEC objects you must first group their contents in located registers (refer to Relocation Table
EIO0000004135 09/2020
161
Ethernet Configuration
Monitoring: IO Viewer Submenu
The IO Viewer submenu allows you to display and modify the current I/O values:
162
Element
Refresh
1000 ms
<<
>>
Description
Enables I/O refreshing:
Gray button: refreshing disabled
Orange button: refreshing enabled
I/O refreshing period in ms
Goes to previous I/O list page
Goes to next I/O list page
EIO0000004135 09/2020
Ethernet Configuration
Monitoring: Oscilloscope Submenu
The oscilloscope submenu can display up to 2 variables in the form of a recorder time chart:
Element
Reset
Refresh
Load
Save
Item0
Item1
Min
Max
Period(ms)
Description
Erases the memorization
Starts/stops refreshing
Loads parameter configuration of Item0 and Item1
Saves parameter configuration of Item0 and Item1 in the controller
Variable to be displayed
Variable to be displayed
Minimum value of the variable axis
Maximum value of the variable axis
Page refresh period in milliseconds
EIO0000004135 09/2020
163
Ethernet Configuration
Diagnostic: Controller Submenu
The Controller submenu displays information of the current status of the controller:
164
EIO0000004135 09/2020
Diagnostic: Ethernet Submenu
The Ethernet submenu displays Ethernet communication information:
Ethernet Configuration
The Reset Statistic button sets the Ethernet statistics to 0.
EIO0000004135 09/2020
165
Ethernet Configuration
Diagnostics: Serial Submenu
The Serial submenu displays the serial line communication information:
The Reset Statistics button sets the statistics of the serial connections to 0.
Diagnostics: Profibus Submenu
The Profibus submenu is available for controllers with PCI module. It displays the Profibus communication information:
166
EIO0000004135 09/2020
Ethernet Configuration
Maintenance Page
The Maintenance page provides access to the /usr , /bd0 and /sys folders of the controller flash
:
Index of /usr or /bd0 :
Index of /sys :
WARNING
UNINTENDED WEB SERVER AND CONTROLLER BEHAVIOR
Do not modify any of the files in the /usr and /sys directories.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000004135 09/2020
167
Ethernet Configuration
Setup: Post Conf Submenu
The Post Conf page allows you to update the PostConf
file saved on the controller:
168
Step
1
2
3
Action
Click Load.
Modify the parameters ( see page 239 )
.
Click Save.
NOTE: The new parameters will be considered at next Post Configuration file reading
.
EIO0000004135 09/2020
Ethernet Configuration
Setup: Ethernet IP configurations File Submenu
The file tree only appears when the Ethernet IP service is configured on the controller.
Index of /usr or /bd0 :
File
My Machine Controller.gz
My Machine Controller.ico
My Machine Controller.eds
Description
GZIP file
Icon file
Electronic Data Sheet file
Maintenance: User Management Submenu
The User Management submenu displays a screen that allows you to access two different actions:
User accounts management:
Allows you to manage user accounts management, removing passwords and returning the user accounts on the controller to default settings.
Click Disable to remove passwords on the controller.
Click OK on the window that appears to confirm. As a result:
Users no longer have to set and enter a password to connect to the controller.
FTP and HTTP connections accept anonymous user connections.
NOTE: The Disable button is only active if the current user has administrative privileges.
Click Reset to default to return the user accounts on the controller to their default setting state.
Click OK on the window that appears to confirm.
NOTE: Connections to FTP and HTTP are blocked until a new password is set.
EIO0000004135 09/2020
169
Ethernet Configuration
Clone management: allows you to control whether user rights are copied and applied to the target controller when cloning a controller with a USB key.
Click Exclude users rights to exclude copying user rights to the target controller when cloning a controller.
NOTE: By default, the users rights are excluded.
Click Include users rights to copy user rights to the target controller when cloning a controller. A popup prompts you to confirm copying the user rights. Click OK to continue.
170
EIO0000004135 09/2020