Wiring. Omron L7
જાહેરાત
જાહેરાત
2
Wiring
This chapter describes the terminals, main circuit terminal connections, main circuit terminal wiring specifications, control circuit terminals, and control circuit wiring specifications.
Connection Diagram ...........................................................2-2
Terminal Block Configuration..............................................2-4
Wiring Main Circuit Terminals .............................................2-5
Wiring Control Circuit Terminals .......................................2-17
EN81-1 Conform Wiring with One Motor Contactor..........2-21
Wiring Check.....................................................................2-23
Installing and Wiring Option Cards ...................................2-24
2
Connection Diagram
The connection diagram of the Inverter is shown in
When using the Digital Operator, the motor can be operated by wiring only the main circuits.
L1
3-phase power
380 to 480V
50/60Hz
L2
L3
PE
Magnetic
Contactor
Line
Filter
DC reactor to improve input power factor (optional)
Braking Resistor unit (optional)
Link
(+1)
L1(R)
L2(S)
(+2) (-)
B1
L3(T)
B2
U/T1
V/T2
W/T3
1
Motor
IM/PM
Multi function
Inputs
(Factory setting)
Forward run/stop
Reverse run/stop
Nominal Speed
Inspection Run
Intermediate Speed
Leveling Speed
Not used
Hardware Baseblock (note 3)
S1
S2
S3
S4
S5
S6
S7
BB
BB1
TA1
PG-X2
(Optional)
P
P
Voltage adjustment
Analog input
(Speed reference)
2kOhm
2kOhm
0 to 10 V
P
Input option cards
+24V, 8mA
SC
IP24V (24V)
CN5(NPN setting)
E(G)
+V Analog input power supply +15V, 20mA
A1
Master speed reference 0 to 10V
AC
0 V
2CN
PG
TA3
TA2
MA
MB
MC
A Pulse
B Pulse
Z Pulse
2
3
Pulse Monitor Output
RS-422
(100m or less)
Fault contact output
250VAC, max. 1A
30VDC, max. 1A
M1
M2
Brake Command
(Factory setting)
M3
M4
Contactor Control
(Factory setting)
Multi-function contact output
250VAC, max. 1A
30VDC, max. 1A
M5
M6
Inverter Ready
(Factory setting)
Optional control power supply input for Rescue
Operation to terminal B1 to terminal -
P0
N0
Control Power
Supply Input
3CN
Output option cards
Note:
1. Main circuit terminals are indicatied with double circles and
control circuit terminals are indicatied with a single circles
2. The CN5 factory setting is NPN
3. To enable the inverter both inputs, BB and BB1 must be closed. If only one of the inputs is closed, “BB” will be displayed in the operator panel and the inverter will not start.
1
Shielded wires
Twisted-pair wires
2
Fig 2.1 Connection Diagram (Model CIMR-L7Z43P7 Shown Above)
2-
2
Circuit Descriptions
Refer to the numbers indicated in
.
1
These circuits are hazardous and are separated from accessible surfaces by protective separation
2
These circuits are separated from all other circuits by protective separation consisting of double and reinforced insulation. These circuits may be interconnected with SELV
*
(or equivalent) or non-
SELV
*
circuits, but not both.
3
Inverters supplied by a four-wire-system source (neutral grounded)
These circuits are SELV
*
circuits and are separated from all other circuits by protective separation consisting of double and reinforced insulation. These circuits may only be interconnected with other SELV
*
(or equivalent) circuits.
Inverters supplied by a three-wire-system source (ungrounded or corner grounded)
These circuits are not separated from hazardous circuits other circuits by protective separation, but only with basic insulation. These circuits must not be interconnected with any circuits which are accessible, unless they are isolated from accessible circuits by supplemental insulation
* SELV (Safety Extra Low Voltage) circuits have no direct connection to the primary power and are supplied by a transformer or equivalent isolating device. The circuits are designed and protected, so that, under normal and single fault condition, its voltage does not exceed a safe value.
(See IEC 61010)
1. Control circuit terminals are arranged as shown below.
IMPORTANT
E(G)
SC SC SC BB +V A1 AC
S1 S2 S3 S4 S5 S6 S7 BB1
M5 M6
M3 M4
MA MB MC
M1
M2
E(G)
2. The output current capability of the +V terminal is 20 mA.
3. Main circuit terminals are indicated with double circles and control circuit terminals are indicated with single circles.
4. The wiring of the digital inputs S1 to S7 and BB is shown for the connection of contacts or NPN transistors (0V common and sinking mode). This is the default setting.
For the connection of PNP transistors or for using a 24V external power supply, refer to
5. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when connecting a DC reactor.
2
2-
3
2
Terminal Block Configuration
The terminal arrangements are shown in
and
Control circuit terminals
Control circuit terminals
Main circuit terminals
Charge indicator
Ground terminal
Fig 2.2 Terminal Arrangement (200 V/400 V Class Inverter of 3.7 kW)
Charge indicator
Main circuit terminals
Ground terminals
Fig 2.3 Terminal Arrangement (200 V/400 V Class Inverter of 22 kW or more)
2-
4
Wiring Main Circuit Terminals
Applicable Wire Sizes and Crimp Terminals
Select the appropriate wires and crimp terminals using
Table 2.1
to
Table 2.3
. Refer to instruction manual
TOE-C726-2 for wire sizes for Braking Resistor Units and Braking Units.
Wire Sizes
Inverter
Model
CIMR
L7Z23P7
Table 2.1 200 V Class Wire Sizes
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
*1 mm
2
(AWG)
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M4 1.2 to 1.5
4
(12 to 10)
4
(12)
Wire Type
L7Z25P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M4 1.2 to 1.5
6
(10)
L7Z27P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M5 2.5
10
(8 to 6)
L7Z2011
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M5
L7Z2015
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3, NO
B1, B2, PO
M6
M5
M6
L7Z2018
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3, NO
B1, B2, PO
M8
M5
M6
L7Z2022
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO
M8
M6
M8
L7Z2030
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO
M8
M6
M8
2.5
4.0 to 5.0
2.5
4.0 to 5.0
9.0 to 10.0
2.5
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
16
(6 to 4)
25 to 35
(3 to 1)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
50
(1 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
25
(4 to 2)
10
(8 to 6)
25
(4)
25 to 35
(3 to 2)
10 to 16
(8 to 6)
25
(4)
6
(10)
10
(8)
16
(6)
-
25
(4)
25
(3)
-
25
(4)
50
(1)
25
(4)
-
25
(4)
25
(3)
-
25
(4)
Power cables, e.g., 600 V vinyl power cables
2
2-
5
2
Inverter
Model
CIMR
L7Z2037
L7Z2045
L7Z2055
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO r/l1,
Δ/l2
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO r/l1,
Δ/l2
Terminal Symbol
R/L1, S/L2, T/L3, , 1, NO
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3, PO r/l1, Δ/l2
Terminal
Screws
Tightening
Torque
(N•m)
M10
M8
M10
M4
M10
M8
M10
M4
M12
M10
M8
M10
M4
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
70 to 95
(2/0 to 4/0)
Recommended
Wire Size
*1 mm
2
(AWG)
70
(2/0)
6 to 16
(10 to 4)
35 to 70
(2 to 2/0)
0.5 to 4
(20 to 10)
95
(3/0 to 4/0)
6 to 16
(10 to 4)
50 to 70
(1 to 2/0)
0.5 to 4
(20 to 10)
50 to 95
(1/0 to 4/0)
90
(4/0)
6 to 70
(10 to 2/0)
35 to 95
(3 to 4/0)
0.5 to 4
(20 to 10)
–
35
(2)
1.5
(16)
95
(3/0)
Wire Type
–
50
(1)
1.5
(16)
50 × 2P
(1/0
× 2P)
90
(4/0)
Power cables, e.g., 600 V vinyl power cables
–
50
(1/0)
1.5
(16)
*1. The wire size is valid for PVC insulated copper cable, 30° ambient temperature
Inverter
Model
CIMR
L7Z43P7
L7Z44P0
L7Z45P5
L7Z47P5
L7Z4011
Table 2.2 400 V Class Wire Sizes
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
M4
M4
M4
M4
M5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
2.5
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
*1 mm
2
(AWG)
2.5 to 4
(14 to 10)
4
(12)
2.5
(14)
2.5 to 4
(14 to 10)
4
(12)
2.5
(14)
4
(12 to 10)
2.5 to 4
(14 to 10)
6 to 10
(10 to 6)
6 to 10
(10 to 6)
4
(12)
2.5
(14)
6
(10)
4
(12)
10
(8)
6
(10)
Wire Type
Power cables, e.g., 600 V vinyl power cables
2-
6
Inverter
Model
CIMR
L7Z4015
L7Z4018
L7Z4022
L7Z4030
L7Z4037
L7Z4045
L7Z4055
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3, NO
B1, B2, PO
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO, PO
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO, PO
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/T3,
R1/L11, S1/L21, T1/L31, NO
3, PO
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/T3,
R1/L11, S1/L21, T1/L31, NO
3, PO
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO
Terminal Symbol
Terminal
Screws
M5
M5
(M6)
M6
M5
M6
M6
M8
M6
M8
M8
M6
M8
M8
M6
M8
M8
M6
M8
*1. The wire size is valid for PVC insulated copper cable, 30° ambient temperature
Tightening
Torque
(N•m)
2.5
2.5
(4.0 to 5.0)
4.0 to 5.0
2.5
4.0 to 5.0
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
10 to 16
(8 to 4)
25 to 35
(4 to 2)
35 to 50
(2 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
50
(1 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
*1 mm
2
(AWG)
10
(8 to 6)
10
(8)
6 to 10
(10 to 6)
10 to 35
(8 to 2)
10
(8)
10 to 25
(8 to 4)
16
(6 to 4)
16 to 35
(6 to 2)
25
(4)
25 to 35
(4 to 2)
25 to 50
(4 to 1/0)
25
(4)
25
(4)
35
(2)
16
(6)
16
(6)
6
(10)
10
(8)
10
(8)
10
(8)
Wire Type
Power cables, e.g., 600 V vinyl power cables
-
25
(4)
50
(1)
25
(4)
35
(2)
-
-
25
(4)
2
2-
7
2
Recommended Crimp Terminal Sizes (Ring type)
Table 2.3 Crimp Terminal Sizes
Wire Cross Section (mm
2
)
Terminal Screws
0.5 - 1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
M5
M10
M12
M8
M10
M12
M10
M12
M6
M8
M10
M8
M6
M8
M6
M8
M4
M5
M6
M8
M4
M4
M4
M4
M5
M6
M8
A
620/4
630/4
630/4
650/4
650/4
101 R/5
101 R/6
101 R/8
102 R/5
102 R/6
102 R/8
103 R/5
*1
103 R/6
103 R/8
104 R/6
104 R/8
105 R/6
105 R/8
105 R/10
106 R/8
106 R/10
106 R/12
107 R/8
107 R/10
107 R/12
108 R/10
108 R/12
Crimp Terminal Type
Klauke y
B
1620/4
1620/4
1630/4
1650/4
1650/4
1650/5
1650/6
1650/8
1652/5
1652/6
1652/8
1653/5
1656/10
1656/12
1657/8
1657/10
1657/12
1658/10
1658/12
1653/6
1653/8
1654/6
1654/8
1655/6
1655/8
1655/10
1656/8
*1. Not applicable for L7Z2011
Select the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage.
Line voltage drop is calculated as follows:
JST
GS5-16
GS6-16
GS8-16
GS6-25
GS8-25
GS6-35
GS8-35
GS10-35
GS8-50
GS10-50
GS12-50
GS8-70
GS10-70
GS12-70
GS10-95
GS12-95
GS4-1
GS4-1
GS4-2.5
GS4-6
GS4-6
GS5-6
GS6-6
GS6-8
GS5-10
GS6-10
GS8-10
IMPORTANT
Line voltage drop (V) = 3 x wire resistance (
Ω
/km) x wire length (m) x current (A) x 10
-3
2-
8
Main Circuit Terminal Functions
Main circuit terminal functions are summarized according to terminal symbols in
. Wire the terminals correctly for the desired purposes.
Purpose
Main circuit power input
Inverter outputs
Table 2.4 Main Circuit Terminal Functions (200 V Class and 400 V Class)
Terminal Symbol
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
Model: CIMR-L7Z
200 V Class 400 V Class
23P7 to 2055 43P7 to 4055
2022 to 2055
23P7 to 2055
4022 to 4055
43P7 to 4055
DC bus terminals
1,
Braking Resistor Unit connection B1, B2
DC reactor connection
1, 2
Braking Unit connection
3,
Ground
Control Power Supply PO, NO
23P7 to 2055
23P7 to 2018
23P7 to 2018
2022 to 2055
23P7 to 2055
23P7 to 2055
43P7 to 4055
43P7 to 4018
43P7 to 4018
4022 to 4055
43P7 to 4055
43P7 to 4055
2
2-
9
2
Main Circuit Configurations
The main circuit configurations of the Inverter are shown in
B2
B1
+ 1
+
2
R/L1
S/L2
T/L3
-
Table 2.5 Inverter Main Circuit Configurations
200 V Class 400 V Class
CIMR - L7Z23P7 to 2018
CIMR - L7Z43P7 to 4018
U/T1
V/T2
W/T3
B2
B1
+
1
+ 2
R/L1
S/L2
T/L3
-
Power
Supply
Control
Circuit
Power
Supply
Control
Circuit
N0 P0
N0 P0
CIMR - L7Z2022,2030
+ 3
CIMR - L7Z4022 to 4055
+ 3
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
-
U/T1
V/T2
W/T3
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
-
N0
Power
Supply
P0
Control
Circuit
CIMR - L7Z2037 to 2055
+ 3
N0
Power
Supply
P0
Control
Circuit
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
r/l1
Δ 200/
l200
U/T1
V/T2
W/T3
N0
Power
Supply
P0
Control
Circuit
Note: Consult your Omron-Yaskawa Motion Control representative for using 12-phase rectification.
U/T1
V/T2
W/T3
U/T1
V/T2
W/T3
2-
10
Standard Connection Diagrams
Standard Inverter connection diagrams are shown in
. These are the same for both 200 V Class and
400 V Class Inverters. The connections depend on the Inverter capacity.
CIMR-L7Z23P7 to 2018 and 43P7 to 4018
3 Phase 200VAC or
400VAC
DC reactor
(optional)
Braking
Resistor
(optional)
+ 1 + 2
B1 B2
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
M
CIMR-L7Z2022, 2030, and 4022 to 4055
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
+ 3
R1/L11
S1/L21
T1/L31
-
U/T1
V/T2
W/T3
M
Be sure to remove the short-circuit bar before connecting the DC reactor.
CIMR-L7Z2037 to 2055
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
+ 3
R1/L11
S1/L21
T1/L31 r / l1
/ l2
-
U/T1
V/T2
W/T3
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
M
The DC reactor is built in.
2
Control power is supplied internally from the DC bus at all inverter models.
Fig 2.4 Main Circuit Terminal Connections
2-
11
2
Wiring the Main Circuits
This section describes wiring connections for the main circuit inputs and outputs.
Wiring Main Circuit Inputs
Consider the following precautions for the main circuit power supply input.
Installing Fuses
To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the table below.
Rated
Inverter Type Inverter Input
Current (A)
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
52
68
96
115
21
25
40
156
176
220
269
Voltage (V)
240
240
240
240
240
240
240
240
240
240
240
Table 2.6 Input Fuses
Fuse Selection
Current (A)
I
2 t (A
2 s)
80
100
130
150
30
40
60
180
240
300
350
82~220
220~610
290~1300
450~5000
1200~7200
1800~7200
870~16200
1500~23000
2100~19000
2700~55000
4000~55000
Selection Example (FERRAZ)
Model Rating I²t (A²s)
A60Q30-2
A50P50-4
A50P80-4
A50P80-4
A50P125-4
A50P150-4
A50P150-4
A50P200-4
A50P250-4
A50P300-4
A50P350-4
600V / 30A
500V / 50A
500V / 80A
500V / 80A
500V / 125A
500V / 150A
500V / 150A
500V / 200A
500V/ 250A
500V / 300A
500V / 350A
132
250
640
640
1600
2200
2200
4000
6200
9000
12000
43P7
44P0
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4055
10.2
13.2
17
22
32
41
49
58
78
96
115
154
480
480
480
480
480
480
480
480
480
480
480
480
30
50
60
70
15
20
25
80
100
125
150
200
34~72
50~570
100~570
100~640
150~1300
400~1800
700~4100
240~5800
500~5800
750~5800
920~13000
1500~13000
A60Q20-2
A60Q30-2
A60Q30-2
A60Q30-2
A70P50-4
A70P70-4
A70P80-4
A70P80-4
A70P100-4
A70P125-4
A70P150-4
A70P200-4
600V / 20A
600V / 30A
600V / 30A
600V / 30A
700V / 50A
700V / 70A
700V / 80A
700V / 80A
700V / 100A
700V / 125A
700V / 150A
700V / 200A
41
132
132
132
300
590
770
770
1200
1900
2700
4800
2-
12
Installing a Moulded-Case Circuit Breaker
If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3) it must be suitable for the Inverter.
•
•
The MCCB should have a capacity of 1.5 to 2 times of the inverter's rated current.
For the MCCB's time characteristics selection the inverter's overload protection (one minute at 150% of the rated output current) must be considered.
Installing an Earth Leakage Breaker
An earth leakage breaker which is able to detect all kinds of current should be used in order to ensure a safe earth leakage current detection.
•
•
If a special-purpose earth leakage breaker for Inverters is used, it should have an actuating current of at least 30 mA per Inverter.
If a standard earth leakage breaker is used, it should have an actuating current of 200 mA or more per
Inverter and a actuating time of 0.1 s or more.
Installing a Magnetic Contactor at the Input
If the power supply for the main circuit is shut off by a control circuit, a magnetic contactor can be used.
The following things should be considered:
•
•
The Inverter can be started and stopped by opening and closing the magnetic contactor on the primary side.
Frequently opening and closing the magnetic contactor may cause an Inverter fault. Do not exceed one power up per hour.
When the Inverter is operated using the Digital Operator, automatic operation cannot be performed after recovery from a power interruption.
Connecting Input Power Supply to the Terminal Block
The input power supply can be connected in any sequence to the terminals R, S or T on the terminal block; the input phase sequence is irrelevant to the output phase sequence.
Installing an Input AC Reactor
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or a phase advancing capacitor is switched nearby, an excessive peak current could flow through the input power circuit, causing an inverter damage. As a countermeasure an optional AC Reactor the inverter input or a DC reactor at the DC reactor connection terminals can be installed.
In order to fulfill the EN12015 an AC reactor has to be installed. Refer to
for the available reactors. The AC reactor has to be installed between the power supply and the EMC filter (like shown in
)
Power
Supply
L1
L2
L3
AC
Reactor
Filter
L7Z
Inverter
M
Fig 2.5 AC reactor installation
Installing a Surge Absorber
Always use a surge absorber or diode for inductive loads near the Inverter. Inductive loads include magnetic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
2
2-
13
2
Wiring the Output Side of the Main Circuit
The following precautions should be considered for the output circuit wiring.
Connecting the Inverter and Motor
The output terminals U/T1, V/T2 and W/T3 must be connected according to the motor lead wires U, V and W.
The motor should rotate forward with the forward run command. If not, two of the motor cable wires can be switched.
Never Connect a Power Supply to Output Terminals
A power supply must never be connected to the output terminals U/T1, V/T2, and W/T3. Otherwise the internal circuits of the Inverter will be damaged.
Never Short or Ground Output Terminals
If the output terminals are touched with bare hands or the output wires come into contact with the Inverter case, an electric shock or a short circuit may occur.
Do Not Use a Phase Advancing Capacitor
A phase advancing capacitor must never be connected to the inverter output circuit. The high-frequency components of the Inverter output may overheat and be damaged and may cause other parts to burn.
Using a Magnetic Contactor
A magnetic contactor (MC) between the Inverter and motor must not be turned ON or OFF during inverter operation. If the MC is turned ON during the Inverter is operation, a large inrush current will be created and the inverter’s over current protection may operate.
Ground Wiring
The following precautions should be considered for the ground connection.
•
•
Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100
Ω and that of the 400 V Inverter with a ground resistance of less than 10
Ω.
Ground wires should not be shared with other devices, such as welding machines or power tools.
•
•
A ground wire, that complies with technical standards on electrical equipment must be used. The length of the ground wire should be as low as possible.
Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
When more than one Inverter is used the ground wires should not be looped.
OK
NO
Fig 2.6 Ground Wiring
2-
14
Connecting a Braking Resistor and Braking Unit (CDBR)
A Braking Resistor and Braking Unit can be connected to the Inverter like shown in the
To prevent overheating of the braking unit/braking resistor, the inverter operation should be stopped when the overload contacts are operated.
200 V and 400 V Class Inverters with 3.7 to 18.5 kW Output Capacity
Braking Resistor
Inverter
Thermal overload relay contact
2
200 V and 400 V Class Inverters with 22 kW or higher Output Capacity
CDBR Braking Unit Braking Resistor
Inverter
Thermal overload relay contact
Thermal overload relay contact
Fig 2.7 Connecting the Braking Resistor and Braking Unit
2-
15
2
Connecting Braking Units in Parallel
When two or more Braking Units are connected in parallel the wiring and jumper settings must be done like
. There is a jumper for selecting whether each Braking Unit is to be a master or slave. “Mas-
ter” must be set for the first Braking Unit only, “Slave” must be set for all other Braking Units (i.e. from the second Unit onwards).
Thermal overload relay contact
Thermal overload relay contact
Thermal overload relay contact
Braking
Resistor
Braking
Resistor
Braking
Resistor
Inverter
Braking Unit #3
Braking Unit #2
2-
16
Braking Unit #1
Thermal overload relay contact
Thermal overload relay contact
Thermal overload relay contact
Fig 2.8 Connecting Braking Units in Parallel
Control Power Supply Connection
The controller of the Varispeed L7 can be supplied by an external voltage source during rescue operation using the twisted wires marked with P0 and N0. Upon shipment the wires are connected to the main circuit terminal
B1 (units up to 18.5 kW) or terminal +3 (units from 22 kW and above) and terminal -.
B2
B1 / + 3
L1
L2
L3
P0
N0
R/L1
S/L2
T/L3
-
Power Supply
Control circuit
Fig 2.9 Control Power Supply Connection
Please refer to
for details about rescue operation.
U/T1
V/T2
W/T3
Wiring Control Circuit Terminals
Wire Sizes
For remote operation using analog signals, the control line length between the Analog Operator or operation signals and the Inverter should be less than 30 m. The controller wires should always be separated from main power lines or other control circuits in order to avoid disturbances.
It is recommended to use shielded twisted-pair wires and ground the shield for the largest area of contact between shield and ground.
The terminal numbers and the appropriate wire sizes are shown in
Table 2.7
.
Terminals
Table 2.7 Terminal Numbers and Wire Sizes (Same for all Models)
Terminal
Screws
Tightening
Torque
(N•m)
Possible Wire
Sizes mm
2
(AWG)
Recommended Wire
Size mm
2
(AWG)
AC, SC, A1, +V, S1, S2, S3,
S4, S5, S6, S7, BB, MA,
MB, MC, M1, M2, M3, M4,
M5, M6
E (G)
Phoenix type
M3.5
0.5 to 0.6
0.8 to 1.0
Solid wire
*1:
0.5 to 2.5
Stranded wire:
0.5 to 1.5
(26 to 14)
0.5 to 2.5
14)
(20 to
0.75
(18)
1.0
(12)
Wire Type
• Shielded, twisted-pair wire
• Shielded, polyethylene-covered, vinyl sheath cable
*1. Ferrules with plastic sleeves should be used for the signal lines to simplify wiring and improve reliability.
Ferrules for Signal Lines
Models and sizes of ferrules with plastic sleeves for the signal lines are shown in the following table.
Wire Size mm
2
(AWG)
0.25 (24)
0.5 (20)
0.75 (18)
1.5 (16)
2 (14)
Table 2.8 Ferrule Sizes
Model
AI 0.25 - 8YE
AI 0.5 - 8WH
AI 0.75 - 8GY
AI 1.5 - 8BK
AI 2.5 - 8BU d1
0.8
1.1
1.3
1.8
2.3
d2
2
2.5
2.8
3.4
4.2
L
12.5
14
14
14
14
Manufacturer
Phoenix Contact
2
Fig 2.10 Ferrule Sizes
2-
17
2
Control Circuit Terminal Functions
The functions of the control circuit terminals are shown in
. Use the appropriate terminals for the cor-
rect purposes.
Type No.
S1
S2
S3
S4
Digital input signals
S5
S6
S7
BB
BB1
*1
SC
Table 2.9 Control Circuit Terminals with default settings
Signal Name
Forward run/stop command
Reverse run/stop command
Nominal speed
Inspection Run
Intermediate speed
Leveling speed
Not used
Hardware baseblock
Hardware baseblock 1
Digital input common
–
–
Function
Forward run when ON; stopped when OFF.
Reverse run when ON; stopped when OFF.
Nominal speed when ON.
Inspection RUN when ON.
Intermediate speed when
ON.
Functions are selected by setting
H1-01 to H1-05.
Leveling speed when ON.
–
–
Signal Level
24 VDC, 8 mA
Photo-coupler
Analog input signals
+V
A1
AC
E(G)
15 V power supply
*2
15 V power supply for analog references
Frequency reference
Analog reference neutral
Shield wire, optional ground line connection point
0 to +10 V/100%
–
–
Brake command
(1NO contact)
Brake command when ON.
–
–
–
15 V
(Max. current: 20 mA)
0 to +10 V(20 k
Ω)
–
–
Digital output signals
M5
M6
MA
MB
MC
M1
M2
M3
M4
Contactor Control
(1NO contact)
Inverter Ready
(1NO contact)
Fault output signal (SPDT)
(1 Change over contact)
Contactor Control when ON
Inverter Ready when ON.
Multi-function contact outputs Relay contacts
Contact capacity:
1 A max. at 250 VAC
1 A max. at 30 VDC
*3
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
*1. This terminal is available on inverters with hardware SPEC B only. ( hardware version).
page 1-4, Inverter Specifications
describes how to find out the inverter
*2. Do not use this power supply for supplying any external equipment.
*3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in
Fig 2.11
.
Fig 2.11 Flywheel Diode Connection
Flywheel diode
External power: 30
VDC max.
Coil
1 A max.
The rating of the flywheel diode must be at least as high as the circuit voltage.
2-
18
Sinking/Sourcing Mode (NPN/PNP Selection)
The input terminal logic can be switched over between sinking mode (0-V common, NPN) and sourcing mode
(+24V common, PNP) by using the jumper CN5. An external power supply is also supported, providing more freedom in signal input methods.
Table 2.10 Sinking/Sourcing Mode and Input Signals
Internal Power Supply – Sinking Mode (NPN)
External Power Supply – Sinking Mode (NPN)
S1
S2
B1
SC
A1
B2 B3
A2 A3
CN5
IP24V
(+24V)
S1
S2
+
24 VDC
SC
A1
B1 B2 B3
A2 A3
CN5
IP24V
(+24V)
Internal Power Supply – Sourcing Mode (PNP) External Power Supply – Sourcing Mode (PNP)
2
S1
S2
SC
B1
A1
B2 B3
A2 A3
CN5
IP24V
(+24V)
S1
S2
-
24 VDC
SC
A1
B1 B2 B3
A2 A3
CN5
IP24V
(+24V)
2-
19
Control Circuit Terminal Connections
Connections to Inverter control circuit terminals are shown in
Fig 2.12
.
2
Multi function
Inputs
(Factory setting)
Forward run/stop
Reverse run/stop
Nominal Speed
Inspection Run
Intermediate Speed
Leveling Speed
Not used
Hardware Baseblock (note 2)
S6
S7
BB
BB1
S1
S2
S3
S4
S5
+24V, 8mA
SC
IP24V (24V)
CN5(NPN setting)
E(G)
Voltage adjustment
Analog input
(Speed reference)
2kOhm
2kOhm
0 to 10 V
P
+V
Analog input power supply +15V, 20mA
A1 Master speed reference 0 to 10V
AC
0 V
MA
MB
MC
Fault contact output
250VAC, max. 1A
30VDC, max. 1A
M1
M2
Brake Command
(Factory setting)
M3
M4
Contactor Control
(Factory setting)
M5
M6
Inverter Ready
(Factory setting)
Multi-function contact output
250VAC, max. 1A
30VDC, max. 1A
Note:
1. The CN5 factory setting is NPN
2. To enable the inverter both inputs, BB and BB1 must be closed. If only one of the inputs is closed, “BB” will be displayed in the operator panel and the inverter will not start.
INFO
Shielded wires
Twisted-pair wires
Fig 2.12 Control Circuit Terminal Connections
The base block circuit is a two channel circuit, i.e. always both channels (terminal BB and BB1) have to be enabled to enable the inverter output.
Generally the terminals BB and BB1 can be linked directly at the terminals. However, if an EN81-1 conform one motor contactor solution is required, the recommended BB and BB1 terminal wiring depends on the installation:
1. If the controller and inverter are mounted in the same cabinet the terminals BB and BB1 can be linked directly at the inverter terminal board. Only one wire from the controller to the inverter base block input is necessary.
2. If the inverter is mounted separated from the controller cabinet, two physically separated wires for the
BB and BB1 terminal should be used in order to keep redundancy in case of a fault of one of the signal lines.
2-
20
EN81-1 Conform Wiring with One Motor Contactor
In order to use the L7Z with one motor contactor instead of two while keeping compliance to the
EN81-1:1998, the following rules have to be followed:
•
The hardware base block function using the terminals BB and BB1 must be used to enable / disable the drive. The input logic must be PNP.
•
•
•
If the elevator safety chain is opened, the inverter output must be cut. This means that the base block signals at the terminals BB and BB1 must be opened, e.g. via an interposing relay.
The base block monitor function must be programmed for one of the multi-function outputs (H2- =
46/47). The regarding digital output contact must be implemented in the contactor supervision circuit of the controller in order to prevent a restart in case of an inverter base block or motor contactor malfunction.
All contactors must be conform to the EN81-1:1998, paragraph 13.2.
shows an EN81-1:1998 wiring example.
Fig 2.13 EN81-1 Conform Wiring with One Motor Contactor (Example)
2
Safety Chain
Circuit
Contactor Close
Command
Elevator Controller
Contactor Check
(Restart Permission)
K01
24VDC *1
K1
BB BB1
Up/Down; Speed selection; ...
Yaskawa
CIMR-L7xxxx
BB Monitor
(NC)
K2
M
The wiring rules and the wiring example are approved by the TUEV Sued, Germany. For more details please contact your OYMC sales representative.
2-
21
2
Control Circuit Wiring Precautions
The following precautions for wiring the control circuits must be considered.
•
•
Control circuit and main circuit wiring should be separated (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/
T2, W/T3, , 1, 2, and 3, PO, NO) and other high-power lines.
The wiring for control circuit terminals MA, MB, MC, M1, M2, M3, M4, M5, and M6 (contact outputs) should be separated from wiring to other control circuit terminals.
•
•
•
•
If an optional external power supply is used, it should be a UL Listed Class 2 power supply.
Twisted-pair or shielded twisted-pair cables should be used for control circuits to prevent operating faults.
The cable shields should be connected to the ground with the maximum contact area.
Cable shields have to be grounded on both cable ends.
2-
22
Wiring Check
Checks
Check all wiring after wiring has been completed. Do not perform continuity check on control circuits. Perform the following checks on the wiring.
•
•
Is all wiring correct?
Have no wire clippings, screws, or other foreign material been left?
•
•
Are all screws tight?
Are any wire ends contacting other terminals?
2
2-
23
Installing and Wiring Option Cards
2
Option Card Models and Specifications
Up to three option cards can be mounted simultaneously in the Inverter. Each of the three option board sockets on the controller card (A, C and D) can take up one option card like shown in
.
shows the available option cards and their specifications.
Card
PG speed control cards
Communications cards
PLC option card
Analog Input card
Analog Output Cards
Digital Output Cards
Table 2.11 Option Card Specifications
Model Specifications
PG-B2
PG-X2
Two phase (phase A and B), +12V inputs, max. response frequency: 50 kHz
Three phase (phase A, B, Z), line driver inputs
(RS422), max. response frequency: 300 kHz
PG-F2
3G3RV-PDRT2
SI-P1
SI-R1
SI-S1
S1-J
3G3RV-P10ST8-E
3G3RV-P10ST8-DRT-E
AI-14B
AO-08
AO-12
DO-08
DO-02C
Hiperfacey or EnDat 2.1 interface card
Intelligent DeviceNet option card
Option card for Profibus-DP fieldbus
Option card for InterBus-S fieldbus
Option card for CANOpen fieldbus
Option card for LONworks
PLC option card
PLC option card with DeviceNet communications port (Slave)
3 Channel analog input card
Signal level: -10 to 10 V or 0 to 10V
Resolution: 13 Bit + sign
2 channel analog output card
Signal level: 0 to 10 V
Resolution: 8 Bit
2 channel high resolution analog output card
Signal level: -10 to +10 V
Resolution: 11 Bit + sign
6 channel digital output card for monitoring the inverter status (fault, zero speed, running, etc.)
2 channel relay contact output
Mounting
Location
A
A
A
C
C
C
C
C
C
C
C
D
D
D
D
Installation
Before mounting an Option Card, remove the terminal cover and be sure that the charge indicator inside the
Inverter is OFF. After that, remove the Digital Operator/LED Monitor and front cover and mount the Option
Card.
Refer to documentation provided with the Option Card for the mounting instructions.
2-
24
Preventing C and D Option Card Connectors from Rising
After installing an Option Card into slot C or D, insert an Option Clip to prevent the side with the connector from rising. The Option Clip can be easily removed by holding onto the protruding portion of the Clip and pulling it out.
A Option Card mounting spacer hole
CN4
A Option Card connector
CN2
C Option Card connector
A Option Card mounting spacer
(Provided with A Option Card)
Option Clip
(To prevent raising of
C and D Option Card)
C Option Card mounting spacer
C Option Card
D Option Card
D Option Card mounting spacer
A Option Card mounting spacer
A Option Card
Fig 2.14 Mounting Option Cards
PG Speed Control Card Terminals and Specifications
PG-B2 Option Card
Input/Output Specifications
Terminal
TA1
TA2
TA3
No.
1
2
5
4
(E)
2
3
6
1
3
4
Table 2.12 PG-B2 I/O Specifications
Contents
Power supply for pulse generator
Specifications
12 VDC (±5%), 200 mA max.
0 VDC (GND for power supply)
H: +8 to 12 V (max. input frequency: 50 kHz)
Pulse input terminals phase A
GND pulse input phase A
H: +8 to 12 V (max. input frequency: 50 kHz)
Pulse input terminals phase B
GND pulse input phase B
Pulse monitor output terminals phase A
Open collector output, 24 VDC, 30 mA max.
Pulse monitor output terminals phase B
Shield connection terminal
Open collector output, 24 VDC, 30 mA max.
-
2
2-
25
2
Wiring the PG-B2 card
The following illustrations show wiring examples for the PG-B2 using the option cards power supply or an external power source for supplying the PG.
Three-phase 200
VAC (400 VAC)
Inverter
R/L1
S/L2
T/L3
Power supply +12 V
Power supply 0 V
Pulse input phase A
GND pulse input phase A
Pulse input phase B
GND pulse input phase B
Pulse monitor output phase A
Pulse monitor output phase B
Fig 2.15 PG-B2 Wiring Using the Option Cards Power Supply
2-
26
Fig 2.16 PG-B2 Wiring Using a 12 V External Power Supply
Precautions:
•
The length of the pulse generator's wiring must not be more than 100 meters.
•
The direction of rotation of the PG can be set in user parameter F1-05. The factory setting is A-phase leading in forward direction (motor shaft turning counterclockwise seen from motor shaft side).
Forward rotation of standard motor (PG)
Forward command
Motor output axis rotates counter-clockwise during Inverter forward command.
Rotation
(CCW)
A-phase
B-phase
The A-phase leads (CCW) when motor rotation is forward.
•
•
The pulse monitor output factor can be changed using parameter F1-05.
PG-X2 Option Card
Input/Output Specifications
Terminal
TA1
TA2
TA3
No.
1
2
3
3
4
5
10
1
2
6
7
(E)
7
8
9
4
5
6
Table 2.13 PG-X2 I/O Specifications
Contents
Power supply for pulse generator
Pulse input terminal phase A (+)
Pulse input terminal phase A (–)
Pulse input terminal phase B (+)
Pulse input terminal phase B (–)
Pulse input terminal phase Z (+)
Pulse input terminal phase Z (–)
Common terminal inputs
Pulse monitor output terminal phase A (+)
Pulse monitor output terminal phase A (–)
Pulse monitor output terminal phase B (+)
Pulse monitor output terminal phase B (–)
Pulse monitor output terminal phase Z (+)
Pulse monitor output terminal phase Z (–)
Common terminal monitor outputs
Shield connection terminal
*1. The 5V and 12V power supply should not be used at the same time.
–
–
Specifications
12 VDC (±5%), 200 mA max.
*1
0 VDC (GND for power supply)
5 VDC (±5%), 200 mA max.
*1
Line driver input (RS422 level)
(maximum input frequency: 300 kHz)
–
Line driver output (RS422 level output)
2
2-
27
2
Wiring the PG-X2 card
The following illustrations show wiring examples for the PG-X2 using the option cards power supply or an external power source for supplying the PG.
Three-phase
200 VAC
(400 VAC)
PG-X2
0V
+5 VDC
A+ Phase Input
A- Phase Input
B+ Phase Input
B- Phase Input
Z+ Phase Input
Z- Phase Input
P
P
P
A Phase Output
B Phase Output
Z Phase Output
Fig 2.17 PG-X2 Wiring Using the Option Cards Power Supply
2-
28
Fig 2.18 PG-X2 Wiring Using a 5 V External Power Supply
Precautions:
•
The length of the pulse generator's wiring must not be more than 100 meters.
•
•
The direction of rotation of the PG can be set in user parameter F1-05. The factory setting is A-phase leading in forward direction (motor shaft turning counterclockwise seen from motor shaft side).
PG-F2 Option Card
Supported Encoders
The PG-F2 option card can be used in combination with the following encoder types:
•
•
Hiperface y
: SRS60/70
EnDat 2.1: ECN1313, ECN113, ECN413
The maximum encoder speed shall not exceed 1200 min
-1
.
Input/Output Specifications
Terminal
TB1
TB2
TB3
TB4
No.
1
2
3
2
1
8
1
6
7
4
5
2
3
4
(E)
Table 2.14 PG-F2 I/O Specifications
Contents
Hiperface y
EnDat
Us 7-12V
5V U
P and U
P
sensor
Specifications
EnDat: 5VDC (±5%, max. 250 mA)
Hiperface y
: 8VDC (±5%, max. 150mA)
0V GND
REFSIN
0V U
N
and 0V sensor
B-
+SIN
REFCOS
+COS
DATA+
DATA-
-
-
Pulse monitor A+
B+
A-
A+
DATA
/DATA
CLOCK
/CLOCK
Pulse monitor A-
Pulse monitor B+
Pulse monitor B-
Shielded sheath connection terminal
Differential inputs
RS-485 Data channel,
Terminating resistance: 130 Ohm
Differential output, Clock frequency: 100 kHz
Open Collector Outputs max 24 VDC, 30 mA
Encoder Power Supply Voltage Selection
The encoder power supply voltage must be set according to the encoder type using switch S1 on the PG-F2 card. Using potentiometer RH1 the encoder power supply voltage can be fine adjusted. The switch S1 factory setting is OFF (EnDat is preselected). The encoder power supply is pre adjusted to 5.0~5.25V upon shipment.
2
S1
RH1
I
OFF
I: 8V (U
S
= 7.5 ~ 10.5 V), for HIPERFACE
OFF: 5V (U
S
= 5 V +-5%), for EnDat, (factory setting)
S1 = I: 7.5 ~ 10.5 V, for HIPERFACE
S1 = OFF: 4.85 ~ 6.5 V, for EnDat
(factory setting: 5.0 to 5.25V)
Fig 2.19 PG-F2 Encoder Power Supply Voltage Selection
2-
29
2
Wiring the PG-F2 Card
The following illustration shows PG-F2 option card wiring with Hiperface y
or EnDat 2.1 encoders.
Three-phase
200 VAC
(400 VAC)
HIPERFACE® or
EnDat Encoder
PM
PG-F2
TB3
TB2
1
2
TB1
1
4
5
2
3
6
7
8
TB4
A+ Phase Output
A- Phase Output
B+ Phase Output
B- Phase Output
( CLOCK)
( /CLOCK)
U
S
( U
P
and U
P sensor)
GND ( 0
V
UN and 0V sensor)
REFSIN ( B-)
P +SIN ( B+)
REFCOS ( A-)
+COS ( A+) P
Data+ ( DATA)
Data- ( /DATA)
P
Fig 2.20 PG-F2 Wiring (EnDat signal names in brackets)
Precautions:
•
The length of the pulse generator's wiring must not be more than 50m for the signal lines and 30m for the monitor output at terminal TB3.
•
The direction of rotation of the PG can be set in user parameter F1-05 (PG Rotation). The factory setting is A-phase/SIN leading in forward direction (motor shaft turning counterclockwise seen from the shaft side).
SIN
COS
Pulse A
Pulse B
•
•
The signal voltage levels must be within the following limits:
REFSIN (B-), REFCOS (A-) offset: 2.2 ~ 2.8 V
+SIN (B+), +COS (B-) peak-to-peak voltage 0.9 ~ 1.1 V
2-
30
Wiring the Terminal Blocks
Wire Sizes (Same for All PG-Card Models)
Terminal wire sizes are shown in
Table 2.15
. For the ferrule types refer to
Terminal
Pulse generator power supply
Pulse input terminal
Pulse monitor output terminal
Shield connection terminal
Table 2.15 Wire Sizes
Terminal
Screws
-
M3.5
Wire Thickness Wire Type
• max. 1.0 mm² for flexible wire
• max. 0.5 mm² for flexible wire with ferrules
• max. 1.5 mm² for solid wire
0.5 to 2.5 mm²
Shielded, twisted-pair wire
Shielded, polyethylenecovered, vinyl sheath cable
Tightening Torque
0.22 Nm
-
Wiring Precautions
Consider the following precautions for wiring.
•
Shielded twisted-pair wires must be used for signal lines. Use cables which are recommended by the encoder manufacturer only.
•
•
•
For the cable connection to the encoder connectors which are recommended by the encoder manufacturer should be used.
Ferrules should be used (refer to
).
The signal lines of the PG Speed Control Card should be separated from main power lines and other control circuits.
•
•
•
•
•
The shield must be connected (green grounding cable of the option card) to the ground terminal to prevent operational errors caused by noise.
The wire ends should not be soldered. Doing so may cause contact faults.
The PG cards power supply must not be used for anything other than the pulse generator (encoder). Using it for another purpose can cause malfunctions due to noise.
A separate power supply is required if the PG power supply consumption is higher than 200 mA. (If momentary power loss must be handled, use a backup capacitor or other method.)
The PG cards maximum input frequency must not be exceeded. The output frequency of the pulse generator can be calculated using the following formula.
f
PG (Hz) =
Motor speed at maximum output frequency (min
–1
)
60 x PG rating (p/rev)
2
2-
31
2
2-
32
ડાઉનલોડ કરો