Wiring Main Circuit Terminals. Omron L7
Reklama
Reklama
Wiring Main Circuit Terminals
Applicable Wire Sizes and Crimp Terminals
Select the appropriate wires and crimp terminals using
Table 2.1
to
Table 2.3
. Refer to instruction manual
TOE-C726-2 for wire sizes for Braking Resistor Units and Braking Units.
Wire Sizes
Inverter
Model
CIMR
L7Z23P7
Table 2.1 200 V Class Wire Sizes
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
*1 mm
2
(AWG)
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M4 1.2 to 1.5
4
(12 to 10)
4
(12)
Wire Type
L7Z25P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M4 1.2 to 1.5
6
(10)
L7Z27P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M5 2.5
10
(8 to 6)
L7Z2011
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, PO, NO
M5
L7Z2015
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3, NO
B1, B2, PO
M6
M5
M6
L7Z2018
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3, NO
B1, B2, PO
M8
M5
M6
L7Z2022
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO
M8
M6
M8
L7Z2030
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO
M8
M6
M8
2.5
4.0 to 5.0
2.5
4.0 to 5.0
9.0 to 10.0
2.5
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
16
(6 to 4)
25 to 35
(3 to 1)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
50
(1 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
25
(4 to 2)
10
(8 to 6)
25
(4)
25 to 35
(3 to 2)
10 to 16
(8 to 6)
25
(4)
6
(10)
10
(8)
16
(6)
-
25
(4)
25
(3)
-
25
(4)
50
(1)
25
(4)
-
25
(4)
25
(3)
-
25
(4)
Power cables, e.g., 600 V vinyl power cables
2
2-
5
2
Inverter
Model
CIMR
L7Z2037
L7Z2045
L7Z2055
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO r/l1,
Δ/l2
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO r/l1,
Δ/l2
Terminal Symbol
R/L1, S/L2, T/L3, , 1, NO
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3, PO r/l1, Δ/l2
Terminal
Screws
Tightening
Torque
(N•m)
M10
M8
M10
M4
M10
M8
M10
M4
M12
M10
M8
M10
M4
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
70 to 95
(2/0 to 4/0)
Recommended
Wire Size
*1 mm
2
(AWG)
70
(2/0)
6 to 16
(10 to 4)
35 to 70
(2 to 2/0)
0.5 to 4
(20 to 10)
95
(3/0 to 4/0)
6 to 16
(10 to 4)
50 to 70
(1 to 2/0)
0.5 to 4
(20 to 10)
50 to 95
(1/0 to 4/0)
90
(4/0)
6 to 70
(10 to 2/0)
35 to 95
(3 to 4/0)
0.5 to 4
(20 to 10)
–
35
(2)
1.5
(16)
95
(3/0)
Wire Type
–
50
(1)
1.5
(16)
50 × 2P
(1/0
× 2P)
90
(4/0)
Power cables, e.g., 600 V vinyl power cables
–
50
(1/0)
1.5
(16)
*1. The wire size is valid for PVC insulated copper cable, 30° ambient temperature
Inverter
Model
CIMR
L7Z43P7
L7Z44P0
L7Z45P5
L7Z47P5
L7Z4011
Table 2.2 400 V Class Wire Sizes
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
M4
M4
M4
M4
M5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
2.5
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
*1 mm
2
(AWG)
2.5 to 4
(14 to 10)
4
(12)
2.5
(14)
2.5 to 4
(14 to 10)
4
(12)
2.5
(14)
4
(12 to 10)
2.5 to 4
(14 to 10)
6 to 10
(10 to 6)
6 to 10
(10 to 6)
4
(12)
2.5
(14)
6
(10)
4
(12)
10
(8)
6
(10)
Wire Type
Power cables, e.g., 600 V vinyl power cables
2-
6
Inverter
Model
CIMR
L7Z4015
L7Z4018
L7Z4022
L7Z4030
L7Z4037
L7Z4045
L7Z4055
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3, NO, PO
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3, NO
B1, B2, PO
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO, PO
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO, PO
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/T3,
R1/L11, S1/L21, T1/L31, NO
3, PO
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/T3,
R1/L11, S1/L21, T1/L31, NO
3, PO
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31, NO
3, PO
Terminal Symbol
Terminal
Screws
M5
M5
(M6)
M6
M5
M6
M6
M8
M6
M8
M8
M6
M8
M8
M6
M8
M8
M6
M8
*1. The wire size is valid for PVC insulated copper cable, 30° ambient temperature
Tightening
Torque
(N•m)
2.5
2.5
(4.0 to 5.0)
4.0 to 5.0
2.5
4.0 to 5.0
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
10 to 16
(8 to 4)
25 to 35
(4 to 2)
35 to 50
(2 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
50
(1 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
*1 mm
2
(AWG)
10
(8 to 6)
10
(8)
6 to 10
(10 to 6)
10 to 35
(8 to 2)
10
(8)
10 to 25
(8 to 4)
16
(6 to 4)
16 to 35
(6 to 2)
25
(4)
25 to 35
(4 to 2)
25 to 50
(4 to 1/0)
25
(4)
25
(4)
35
(2)
16
(6)
16
(6)
6
(10)
10
(8)
10
(8)
10
(8)
Wire Type
Power cables, e.g., 600 V vinyl power cables
-
25
(4)
50
(1)
25
(4)
35
(2)
-
-
25
(4)
2
2-
7
2
Recommended Crimp Terminal Sizes (Ring type)
Table 2.3 Crimp Terminal Sizes
Wire Cross Section (mm
2
)
Terminal Screws
0.5 - 1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
M5
M10
M12
M8
M10
M12
M10
M12
M6
M8
M10
M8
M6
M8
M6
M8
M4
M5
M6
M8
M4
M4
M4
M4
M5
M6
M8
A
620/4
630/4
630/4
650/4
650/4
101 R/5
101 R/6
101 R/8
102 R/5
102 R/6
102 R/8
103 R/5
*1
103 R/6
103 R/8
104 R/6
104 R/8
105 R/6
105 R/8
105 R/10
106 R/8
106 R/10
106 R/12
107 R/8
107 R/10
107 R/12
108 R/10
108 R/12
Crimp Terminal Type
Klauke y
B
1620/4
1620/4
1630/4
1650/4
1650/4
1650/5
1650/6
1650/8
1652/5
1652/6
1652/8
1653/5
1656/10
1656/12
1657/8
1657/10
1657/12
1658/10
1658/12
1653/6
1653/8
1654/6
1654/8
1655/6
1655/8
1655/10
1656/8
*1. Not applicable for L7Z2011
Select the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage.
Line voltage drop is calculated as follows:
JST
GS5-16
GS6-16
GS8-16
GS6-25
GS8-25
GS6-35
GS8-35
GS10-35
GS8-50
GS10-50
GS12-50
GS8-70
GS10-70
GS12-70
GS10-95
GS12-95
GS4-1
GS4-1
GS4-2.5
GS4-6
GS4-6
GS5-6
GS6-6
GS6-8
GS5-10
GS6-10
GS8-10
IMPORTANT
Line voltage drop (V) = 3 x wire resistance (
Ω
/km) x wire length (m) x current (A) x 10
-3
2-
8
Main Circuit Terminal Functions
Main circuit terminal functions are summarized according to terminal symbols in
. Wire the terminals correctly for the desired purposes.
Purpose
Main circuit power input
Inverter outputs
Table 2.4 Main Circuit Terminal Functions (200 V Class and 400 V Class)
Terminal Symbol
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
Model: CIMR-L7Z
200 V Class 400 V Class
23P7 to 2055 43P7 to 4055
2022 to 2055
23P7 to 2055
4022 to 4055
43P7 to 4055
DC bus terminals
1,
Braking Resistor Unit connection B1, B2
DC reactor connection
1, 2
Braking Unit connection
3,
Ground
Control Power Supply PO, NO
23P7 to 2055
23P7 to 2018
23P7 to 2018
2022 to 2055
23P7 to 2055
23P7 to 2055
43P7 to 4055
43P7 to 4018
43P7 to 4018
4022 to 4055
43P7 to 4055
43P7 to 4055
2
2-
9
2
Main Circuit Configurations
The main circuit configurations of the Inverter are shown in
B2
B1
+ 1
+
2
R/L1
S/L2
T/L3
-
Table 2.5 Inverter Main Circuit Configurations
200 V Class 400 V Class
CIMR - L7Z23P7 to 2018
CIMR - L7Z43P7 to 4018
U/T1
V/T2
W/T3
B2
B1
+
1
+ 2
R/L1
S/L2
T/L3
-
Power
Supply
Control
Circuit
Power
Supply
Control
Circuit
N0 P0
N0 P0
CIMR - L7Z2022,2030
+ 3
CIMR - L7Z4022 to 4055
+ 3
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
-
U/T1
V/T2
W/T3
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
-
N0
Power
Supply
P0
Control
Circuit
CIMR - L7Z2037 to 2055
+ 3
N0
Power
Supply
P0
Control
Circuit
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
r/l1
Δ 200/
l200
U/T1
V/T2
W/T3
N0
Power
Supply
P0
Control
Circuit
Note: Consult your Omron-Yaskawa Motion Control representative for using 12-phase rectification.
U/T1
V/T2
W/T3
U/T1
V/T2
W/T3
2-
10
Standard Connection Diagrams
Standard Inverter connection diagrams are shown in
. These are the same for both 200 V Class and
400 V Class Inverters. The connections depend on the Inverter capacity.
CIMR-L7Z23P7 to 2018 and 43P7 to 4018
3 Phase 200VAC or
400VAC
DC reactor
(optional)
Braking
Resistor
(optional)
+ 1 + 2
B1 B2
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
M
CIMR-L7Z2022, 2030, and 4022 to 4055
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
+ 3
R1/L11
S1/L21
T1/L31
-
U/T1
V/T2
W/T3
M
Be sure to remove the short-circuit bar before connecting the DC reactor.
CIMR-L7Z2037 to 2055
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
+ 3
R1/L11
S1/L21
T1/L31 r / l1
/ l2
-
U/T1
V/T2
W/T3
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
M
The DC reactor is built in.
2
Control power is supplied internally from the DC bus at all inverter models.
Fig 2.4 Main Circuit Terminal Connections
2-
11
2
Wiring the Main Circuits
This section describes wiring connections for the main circuit inputs and outputs.
Wiring Main Circuit Inputs
Consider the following precautions for the main circuit power supply input.
Installing Fuses
To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the table below.
Rated
Inverter Type Inverter Input
Current (A)
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
52
68
96
115
21
25
40
156
176
220
269
Voltage (V)
240
240
240
240
240
240
240
240
240
240
240
Table 2.6 Input Fuses
Fuse Selection
Current (A)
I
2 t (A
2 s)
80
100
130
150
30
40
60
180
240
300
350
82~220
220~610
290~1300
450~5000
1200~7200
1800~7200
870~16200
1500~23000
2100~19000
2700~55000
4000~55000
Selection Example (FERRAZ)
Model Rating I²t (A²s)
A60Q30-2
A50P50-4
A50P80-4
A50P80-4
A50P125-4
A50P150-4
A50P150-4
A50P200-4
A50P250-4
A50P300-4
A50P350-4
600V / 30A
500V / 50A
500V / 80A
500V / 80A
500V / 125A
500V / 150A
500V / 150A
500V / 200A
500V/ 250A
500V / 300A
500V / 350A
132
250
640
640
1600
2200
2200
4000
6200
9000
12000
43P7
44P0
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4055
10.2
13.2
17
22
32
41
49
58
78
96
115
154
480
480
480
480
480
480
480
480
480
480
480
480
30
50
60
70
15
20
25
80
100
125
150
200
34~72
50~570
100~570
100~640
150~1300
400~1800
700~4100
240~5800
500~5800
750~5800
920~13000
1500~13000
A60Q20-2
A60Q30-2
A60Q30-2
A60Q30-2
A70P50-4
A70P70-4
A70P80-4
A70P80-4
A70P100-4
A70P125-4
A70P150-4
A70P200-4
600V / 20A
600V / 30A
600V / 30A
600V / 30A
700V / 50A
700V / 70A
700V / 80A
700V / 80A
700V / 100A
700V / 125A
700V / 150A
700V / 200A
41
132
132
132
300
590
770
770
1200
1900
2700
4800
2-
12
Installing a Moulded-Case Circuit Breaker
If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3) it must be suitable for the Inverter.
•
•
The MCCB should have a capacity of 1.5 to 2 times of the inverter's rated current.
For the MCCB's time characteristics selection the inverter's overload protection (one minute at 150% of the rated output current) must be considered.
Installing an Earth Leakage Breaker
An earth leakage breaker which is able to detect all kinds of current should be used in order to ensure a safe earth leakage current detection.
•
•
If a special-purpose earth leakage breaker for Inverters is used, it should have an actuating current of at least 30 mA per Inverter.
If a standard earth leakage breaker is used, it should have an actuating current of 200 mA or more per
Inverter and a actuating time of 0.1 s or more.
Installing a Magnetic Contactor at the Input
If the power supply for the main circuit is shut off by a control circuit, a magnetic contactor can be used.
The following things should be considered:
•
•
The Inverter can be started and stopped by opening and closing the magnetic contactor on the primary side.
Frequently opening and closing the magnetic contactor may cause an Inverter fault. Do not exceed one power up per hour.
When the Inverter is operated using the Digital Operator, automatic operation cannot be performed after recovery from a power interruption.
Connecting Input Power Supply to the Terminal Block
The input power supply can be connected in any sequence to the terminals R, S or T on the terminal block; the input phase sequence is irrelevant to the output phase sequence.
Installing an Input AC Reactor
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or a phase advancing capacitor is switched nearby, an excessive peak current could flow through the input power circuit, causing an inverter damage. As a countermeasure an optional AC Reactor the inverter input or a DC reactor at the DC reactor connection terminals can be installed.
In order to fulfill the EN12015 an AC reactor has to be installed. Refer to
for the available reactors. The AC reactor has to be installed between the power supply and the EMC filter (like shown in
)
Power
Supply
L1
L2
L3
AC
Reactor
Filter
L7Z
Inverter
M
Fig 2.5 AC reactor installation
Installing a Surge Absorber
Always use a surge absorber or diode for inductive loads near the Inverter. Inductive loads include magnetic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
2
2-
13
2
Wiring the Output Side of the Main Circuit
The following precautions should be considered for the output circuit wiring.
Connecting the Inverter and Motor
The output terminals U/T1, V/T2 and W/T3 must be connected according to the motor lead wires U, V and W.
The motor should rotate forward with the forward run command. If not, two of the motor cable wires can be switched.
Never Connect a Power Supply to Output Terminals
A power supply must never be connected to the output terminals U/T1, V/T2, and W/T3. Otherwise the internal circuits of the Inverter will be damaged.
Never Short or Ground Output Terminals
If the output terminals are touched with bare hands or the output wires come into contact with the Inverter case, an electric shock or a short circuit may occur.
Do Not Use a Phase Advancing Capacitor
A phase advancing capacitor must never be connected to the inverter output circuit. The high-frequency components of the Inverter output may overheat and be damaged and may cause other parts to burn.
Using a Magnetic Contactor
A magnetic contactor (MC) between the Inverter and motor must not be turned ON or OFF during inverter operation. If the MC is turned ON during the Inverter is operation, a large inrush current will be created and the inverter’s over current protection may operate.
Ground Wiring
The following precautions should be considered for the ground connection.
•
•
Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100
Ω and that of the 400 V Inverter with a ground resistance of less than 10
Ω.
Ground wires should not be shared with other devices, such as welding machines or power tools.
•
•
A ground wire, that complies with technical standards on electrical equipment must be used. The length of the ground wire should be as low as possible.
Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
When more than one Inverter is used the ground wires should not be looped.
OK
NO
Fig 2.6 Ground Wiring
2-
14
Connecting a Braking Resistor and Braking Unit (CDBR)
A Braking Resistor and Braking Unit can be connected to the Inverter like shown in the
To prevent overheating of the braking unit/braking resistor, the inverter operation should be stopped when the overload contacts are operated.
200 V and 400 V Class Inverters with 3.7 to 18.5 kW Output Capacity
Braking Resistor
Inverter
Thermal overload relay contact
2
200 V and 400 V Class Inverters with 22 kW or higher Output Capacity
CDBR Braking Unit Braking Resistor
Inverter
Thermal overload relay contact
Thermal overload relay contact
Fig 2.7 Connecting the Braking Resistor and Braking Unit
2-
15
2
Connecting Braking Units in Parallel
When two or more Braking Units are connected in parallel the wiring and jumper settings must be done like
. There is a jumper for selecting whether each Braking Unit is to be a master or slave. “Mas-
ter” must be set for the first Braking Unit only, “Slave” must be set for all other Braking Units (i.e. from the second Unit onwards).
Thermal overload relay contact
Thermal overload relay contact
Thermal overload relay contact
Braking
Resistor
Braking
Resistor
Braking
Resistor
Inverter
Braking Unit #3
Braking Unit #2
2-
16
Braking Unit #1
Thermal overload relay contact
Thermal overload relay contact
Thermal overload relay contact
Fig 2.8 Connecting Braking Units in Parallel
Control Power Supply Connection
The controller of the Varispeed L7 can be supplied by an external voltage source during rescue operation using the twisted wires marked with P0 and N0. Upon shipment the wires are connected to the main circuit terminal
B1 (units up to 18.5 kW) or terminal +3 (units from 22 kW and above) and terminal -.
B2
B1 / + 3
L1
L2
L3
P0
N0
R/L1
S/L2
T/L3
-
Power Supply
Control circuit
Fig 2.9 Control Power Supply Connection
Please refer to
for details about rescue operation.
U/T1
V/T2
W/T3
Atsisiųsti