advertisement
Installation and Operation Manual
AllSync Plus
®
Clocks
®
Part # P000018
Rev. 3
January 2013
AllSync Plus Clock Installation
& Operation Manual
2
American Time
140 3rd Street South, PO Box 707
Dassel, MN 55325-0707
Phone:
800-328-8996
Fax:
800-789-1882 american-time.com
© American Time
AllSync Plus Clock Installation
& Operation Manual
Table of Contents
Safety Precautions ........................................................................................................................................................ 4
Introduction 5
Installation ..................................................................................................................................................................... 6
Electrical Connections ............................................................................................................................................. 6
Plastic Surface Mount Clock Installation .................................................................................................................. 7
Metal Surface Mount Clock Installation ................................................................................................................... 9
Metal Round Double Dial Clock Installation ........................................................................................................... 10
Plastic Double Dial Clock Installation ..................................................................................................................... 12
Metal Square Double Dial Clock Installation .......................................................................................................... 13
AllSync Plus Startup Routine ................................................................................................................................. 14
General Operation ........................................................................................................................................................ 16
AllSync Plus accuracy ........................................................................................................................................... 16
Movement corrections .......................................................................................................................................... 16
Start Up Example Operation .................................................................................................................................. 17
Troubleshooting ........................................................................................................................................................... 18
Appendix A - AllSync Plus Clock Specifications ....................................................................................................... 20
AllSync Plus Flush Metal Case Specifications ........................................................................................................ 20
AllSync Plus Flush Plastic Case Specifications ...................................................................................................... 22
AllSync Plus Dual Motor Metal Case Specifications ............................................................................................... 24
AllSync Plus Dual Motor Plastic Case Specifications .............................................................................................. 26
AllSync Plus Surface & Double Dial Metal Case Specifications .............................................................................. 28
AllSync Plus Surface & Double Dial Plastic Case Specifications ............................................................................. 30
Appendix B - LED Indication ....................................................................................................................................... 32
Glossary ....................................................................................................................................................................... 34
© American Time
3
4
Safety Instructions
AllSync Plus Clock Installation
& Operation Manual
All wiring to AllSync Plus clock(s) and Master must be installed by qualified persons in conformance with applicable national and local electrical codes. Improper installation of this equipment can result in lethal electrical shock and fire.
Disconnect and lock out electrical power to AC clocks before wiring.
There are no user serviceable parts inside AllSync Plus clocks.
The AllSync Plus clock(s) should be installed in a location protected from:
•
Water, including condensation
•
Physical damage
General Operation
© American Time
AllSync Plus Clock Installation
& Operation Manual
Introduction
The AllSync Plus Clock Manual explains how to install AllSync Plus Clocks and understand their operation.
The American Time AllSync Plus clock is the second generation of the AllSync Chameleon clock. The AllSync Plus clock incorporates all of the first generation AllSync clock features with improved accuracy and 15 minutes of reserve power for short power outages.
© American Time
5
6
Installation
AllSync Plus Clock Installation
& Operation Manual
Electrical Connections
Warning:
To prevent electrical shock, do not apply electrical power to master, clock relays and clock wiring before completing all wiring connections.
The AllSync Plus clock can run off either 24vac/60 Hz or 120vac/60 Hz. To change between the two different supply voltages two jumpers must be set inside each clock. This setting is completed by American Time when your clock(s) are built according to the part number ordered.
General Operation
Correction
Run
Correction
Run
120V 120V
24V 24V
Caution:
Setting the AllSync Plus clock for 24vac and powering it with 120vac will damage the circuit board.
Red wire = Correction
Black wire = Run
White wire = Neutral
Green wire = Ground
© American Time
AllSync Plus Clock Installation
& Operation Manual
Installation
Plastic Surface Mount Clock Installation
Warning:
The AllSync Plus plastic surface mount clock should be mounted according to these instructions to meet
UL clock listing.
1. Remove the AllSync Plus clock, mounting bracket, and wiring harness
(if applicable) from the packaging.
2. Using UL approved wire nuts, make connections between flying leads and wiring inside electrical box. a. Black wire should be connected to hot (run) wire from the master. b. Red wire should be connected to the correction line from the master
clock.
c. White wire should be connected to the neutral line.
d. Green wire should be connected to earth ground.
Note: All wiring connections should be made in accordance to local and national electrical codes.
3. Bundle all wall wiring and female connector wiring inside back box and place mounting bracket over back box opening.
4. Attach mounting bracket to back box and wall, ribbed post up.
5. Secure bracket to wall using appropriate mounting screw and anchor for wall material. Screw and anchor are not included.
© American Time
7
8
Installation
AllSync Plus Clock Installation
& Operation Manual
Plastic Surface Mount Clock Installation (cont)
6. Make connection between clock and wall wiring using attached four conductor mating connectors.
7. Bundle wires inside clock bezel.
8. Slide keyhole hanger over ribbed hanging stem on mounting bracket
General Operation
9. Screw bottom portion of clock to mounting bracket
Note: Screw bottom portion of the clock to the point the screw bottoms out.
Do not over tighten.
Caution:
Over tightening may damage clock bezel. If the clock bezel begins to deform, cease tightening.
© American Time
AllSync Plus Clock Installation
& Operation Manual
Installation
Metal Surface Mount Clock Installation
Warning: The AllSync Plus metal surface mount clock should be mounted according to these instructions to meet UL clock listing.
1. Remove the AllSync Plus clock, mounting bracket, and wiring harness (if applicable) from the packaging.
2. Snap female (wall half) connector into mounting bracket.
3. Using UL approved wire nuts, make connections between flying leads and wiring inside electrical box.
a. Black wire should be connected to hot (run) wire from the master.
b. Red wire should be connected to the correction line from the
master clock.
c. White wire should be connected to the neutral line.
d. Green wire should be connected to earth ground.
Note: All wiring connections should be made in accordance to local and national electrical codes.
4. Bundle all wall wiring and female connector wiring inside back box and place mounting bracket over back box opening, bent side up.
5. Screw mounting bracket to electrical box.
6. Connect clock wiring using connector attached to clock.
7. Hang clock on mounting bracket and secure using screw through the top of the clock.
© American Time
9
Installation
AllSync Plus Clock Installation
& Operation Manual
Metal Round Double Dial Clock Installation
Warning:
The AllSync Plus metal double dial clock should be mounted according to these instructions to meet UL clock listing.
1. Remove the AllSync Plus clocks, double dial ring, wiring harnesses, backbox plate and plastic bushings from the packaging.
2. Insert plastic bushing into box plate to protect wires
General Operation
10
3. Thread back box wire harnesses through double dial ring base and box
plate.
4. Insert 1
1
/
2
" screws into either side of double dial ring. Thread both screws half way through ring using same threaded hole.
Note: ceiling mount screw location should be directly above ring base and wall mount screw location should be 90 degrees from base. (Wall mount shown).
© American Time
AllSync Plus Clock Installation
& Operation Manual
Installation
5. Attach mounting clips by threading the 1
1
/
4
" screws included through them in each of the three positions. Do not completely tighten, they should be loose at this point.
6. Using UL approved wire nuts, make connections between flying leads and wiring inside electrical box.
a. Black wire should be connected to hot (run) wire from the master.
b. Red wire should be connected to the correction line from the master clock.
c. White wire should be connected to the neutral line.
d. Green wire should be connected to earth ground.
Note: All wiring connections should be made in accordance to local and national electrical codes
7. Attach box plate to electrical box.
8. Attach double dial ring to box plate using acorn style nuts.
9. Hang one side of the double dial clock on mounting ring using protruding screw and connect clock wires to one of the wall ends.
Note: The knot in the wall side wire harness may block clock installation. By simply pulling it away from ring base about half an inch will provide adequate space to install both clock sides.
10. Connect remaining side of double dial clock to remaining wire harness wall end and hang on remaining screw.
11. Tighten mounting clips installed in step 5 to firmly secure both side of double dial clock.
© American Time
11
Installation
AllSync Plus Clock Installation
& Operation Manual
Plastic Double Dial Clock Installation
Warning:
The AllSync Plus plastic double dial clock should be mounted according to these instructions to meet UL clock listing.
1. Remove the AllSync Plus plastic double dial clock from packaging.
General Operation
2. Using UL approved wire nuts, make connections between flying leads and wiring inside electrical box. a. Black wire should be connected to hot (run) wire from the
master. b. Red wire should be connected to the correction line from the
master clock.
c. White wire should be connected to the neutral line.
d. Green wire should be connected to earth ground.
Note: All wiring connections should be made in accordance to local and national electrical codes
3. Remove box plate from double dial clock by removing acorn nuts at base of clock.
4. Bundle wires inside electrical box.
5. Attach box plate to electrical box.
6. Connect clock to box plate using acorn nuts removed in step 3.
12
© American Time
AllSync Plus Clock Installation
& Operation Manual
Installation
Metal Square Double Dial Clock Installation
Warning:
The AllSync Plus metal square double dial clock should be mounted according to these instructions to meet UL clock listing.
1. Remove the AllSync Plus square metal double dial clock from
packaging.
2. Remove box plate from clock by removing acorn nuts at the base of the clock. Pull wall wiring through plate hole and attach to electrical box.
3. Using UL approved wire nuts, make connections between flying leads
and wiring inside back box.
a. Black wire should be connected to hot (run) wire from the master.
b. Red wire should be connected to the correction line from the
master clock.
c. White wire should be connected to the neutral line.
d. Green wire should be connected to earth ground.
Note: All wiring connections should be made in accordance to local and national electrical codes
4. Bundle wires inside electrical box.
5. Connect clock to box plate using acorn nuts removed in step 2.
© American Time
13
Installation
AllSync Plus Startup Routine
AllSync Plus Clock Installation
& Operation Manual
14
LED
LED location on back of clock
General Operation
The AllSync Plus clocks operate differently from their fixed clock protocol mechanical counterparts and from the older AllSync clocks.
After power is initially supplied to the AllSync Plus clock run line the following will occur:
1. The clock will charge its internal backup power cell and undergo startup diagnostics.
Note: This may take from 1-9 minutes. During this charge period the clock will run through the start
up diagnostics indicated by the LED on the back of the clock and the clock hands will remain still.
2. The second hand will begin slow stepping (moving 1 second on the clock face for every 3 seconds real
time).
Note: This stage will last for approximately 3 minutes. While the second hand is slowly stepping the
LED on the back will flash green. The green flashing LED indicates the microprocessor is telling the
movement what time it is. The default time for the circuit board is 12:50. This is the time the
movement receives on startup and after extended power outages (greater than 15-20 minutes).
3. The clock will rapidly advance and the LED will turn solid red.
Note: The solid red LED indicates the clock circuit board has not received a 12 hour correction.
4. The clock will stop rapid advancement sometime between 12:50 and 1:15 as seen on the clock face
and begin running at the correct pace (1 tick per second).
Note: The rapid advancement of the hands may pause periodically for the clock to find its position.
Rapid advancement will continue shortly after the clock has completed its location check.
Note: Rapid advancement may last as long as 15 minutes. Total rapid advancement time depends on
hand location prior to startup.
5. When the time on the clock face reaches approximately 2:02, the clock hands will rapidly advance to
match the minutes on the master clock connected to it.
Note: If a master does not send a valid correction, the AllSync Plus clock cannot synchronize its minutes
to the master.
Note: The minute and second hands will be on time with the master after this rapid correction.
6. Approximately 5 minutes after the conclusion of the first 12 hour correction from the connected
master the AllSync Plus clock will rapidly advance to match the exact time on of the master (hour
hand will correct).
Note: The AllSync Plus clock is set up at the factory for clock code 01 (xx:57:54 – 8 second hourly
correction, 5:57:54 – 14 second 12 hour correction). If running a different clock protocol, the AllSync
Plus clock may require an additional 12 hour correction to recognize the different clock protocol. If this
is the case, allow 24 hours for the clock to synchronize.
© American Time
AllSync Plus Clock Installation
& Operation Manual
User Notes
© American Time
15
General Operation
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus accuracy
The AllSync Plus movement continually makes adjustments to its own internal clock. With each correction received from your master clock it will make an adjustment to match the time on the master. For this reason, the longer the AllSync clock is connected to your master the closer it will get to your master’s time. After approximately 2 days the AllSync Plus clock should be ±1 second to the master system clock.
Movement corrections
The AllSync Plus clock has two primary yet completely separate parts: the circuit board and the movement. The circuit board listens to your master and tells your movement, when asked, the time in its own language. The movement will ask for the time 4 times a day at 2am, 8am 2pm and 8pm. For this reason if your master time is changed, the AllSync Plus clock will not correct until it has both received a correction from the master and reached one of its four daily correction times.
Note: The AllSync Plus clock(s) starts its internal clock at 12:50 when power has been removed from it by more than about 25 minutes.
General Operation
16
© American Time
AllSync Plus Clock Installation
& Operation Manual
General Operation
Start Up Example Operation:
Note: This is an example of how the AllSync Plus clock will operate with an ATS master running clock code
01 and actual (master) plug in time at 9 am.
Timeline
0 minutes
25 minutes
Actual Time
(Master
Time)
Clock
Microcontroller
Time shown on clock
Description
Power is applied to clock at 9 am actual time with the clock displaying 3 o’clock.
The clock microcontroller starts counting at 12:50.
25 minutes after power has been applied clock face matches microcontroller time.
1 hour
Microcontroller updates its time using an hourly correction from master clock.
1 hour
10 minutes
Clock movement requests time from microcontroller.
1.5 hours
9 hours
1 minute
9.5 hours
Clock movement synchronizes with clock microcontroller.
Master clock sends a 12 hour correction out shortly before 6 o'clock. The microcontroller resets clock movement. Clock movement requests the time.
Clock movement has finished fast correction and is now on time with the master.
© American Time
17
Troubleshooting
AllSync Plus Clock Installation
& Operation Manual
18
LED
General Operation
Note: The LED indicator on the back of the AllSync Plus clock is intended for troubleshooting purposes.
AllSync Plus Clock not correcting the hour hand
• LED is solid green
º Wait for 8:00 or 2:00 on clock face
º Disconnect clock for 1 hour, reconnect and wait for 24 hours.
• LED is solid red
º Wait for 12 hour correction
Note: LED on back of clock will alternate red-green while master is sending it a correction.
º If AllSync Plus clock(s) have been moved from one clock protocol to another with identical
hourly correction it may not recognize the switch. Set master for synchronous style correction with
different hourly correction, then, if needed change clock protocol back (refer to your master clock
instructions for setting clock protocol).
AllSync Plus Clock Synchronized to the correct hour and seconds but minutes are off by less than
• LED is green
º Wait for 8:00 or 2:00 on clock face
Note: LED on back of clock will alternate red-green while master is sending it a correction.
o Clock may have been jarred during shipment. Remove crystal and move the minute hand to the
correct time. Contact American Time Technical support for assistance at 800-328-8996.
• LED is red
o Wait for 12 hour correction and clock to cross 8:00 or 2:00
o If AllSync Plus clock has been moved from one clock protocol to another with identical
hourly correction it may not recognize the switch. Set master for synchronous style correction
with different hourly correction, then if needed, change clock protocol back. Refer to your master
clock instructions for setting clock protocol.
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock not running with power applied
• LED not lit
Troubleshooting
o Verify master clock is wired and operating correctly
o Verify wiring to clock (check voltage using voltmeter)
o Contact American Time Technical support at
800-328-8996
Note: You may damage clock by changing power supply settings to 24vac and applying 120vac.
• LED lit or
o Wait for 30 minutes. The AllSync Plus clock requires a short period (up to 15 minutes) to charge its
backup power supply.
o Remove dust cover on the back of the clock and verify connection between circuit board and
movement.
© American Time
19
AllSync Plus Clock Specifications
AllSync Plus
®
Flush Metal Case
®
AllSync Plus Clock Installation
& Operation Manual
FEATURES
•
5 Year Warranty
• Microprocessor controlled movement
• 15 minutes of backup power (no batteries required)
• Accuracy to within ±1 second of a master clock
• Reduced power consumption
• Attractive modern design
• Heavy-duty construction
• All metal case
• Diagnostic LED
General Operation DESCRIPTION
The
american time
™
AllSync Plus clocks are provided in round or square metal cases with glass crystals and bold, black numerals and minute markers on a non-yellowing white dial. Stylish hour and minute hands are aluminum with a black finish and a red sweep second hand.
AllSync Plus clocks are designed to work with multiple master clocks and correction signals. This unit is programmed to identify the signal it receives from the master and operate as that style of clock. Changing clock operation from one style to another is as easy as unplugging the clock from one system and plugging it into another. If needed, changing the placement of 2 small jumpers on the circuit board can change the voltage required to run this clock from 120vac to 24vac or 24vac to 120vac. This clock provides 15 minutes of backup run power without the use of batteries. If a power outage should last longer than 15 minutes, the clock will synchronize to the master clock at the hourly and 12 hour correction cycles.
Correction Signals
Works on:
• Hourly correction: 7-9 seconds starting at the 57th minute and 54th second. 12 hour correction: 13-18 seconds starting at
5:57:54 (am and pm).
• Hourly correction: 24-28.5 seconds starting at the 0 minute and 0 second. 12 hour correction: 24-32 minutes starting at
6:00:00 (am and pm).
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 10 pulses of 94-96 seconds starting at 5:05:00 (am and pm) and repeating every 2 minutes.
• Hourly correction: 24-26 seconds starting at 0 minute and 0 second. 12 hour correction: 25 pulses of 24-26 seconds starting at 6:00:00 (am and pm) and repeating every 60 seconds.
• Hourly correction: 63-67 seconds starting at the 58th minute and 0 second. 12 hour correction: 14 pulses of 63-67 seconds starting at 5:06:00 (am and pm) and repeating every 2 minutes.
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 12 pulses of 63-67 seconds starting at 5:05:00 (am and pm) repeating every 90 seconds.
*Note:
When switching between these correction protocols, you must use a different correction protocol to complete the transition.
The AllSync Plus clock needs to distinguish between hourly corrections before it can change correction protocols internally.
20
140 3rd St. S, PO Box 707, Dassel, MN 55325
800-328-8996 • american-time.com
Page 1 of 2 PS03010 Rev H
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock Specifications
SPECIFICATIONS
• 24vac/60 Hz or 120vac/60 Hz
• Current draw: 24vac, 1 watt, .043 amps
120vac, 3 watts, .028 amps
Maximum operating voltage: 24vac setting = 40vac
120vac setting = 150vac
Minimum operating voltage: 24vac setting = 15vac
120vac setting = 50vac
GENERAL
Types of secondary clocks compatible with AllSync Plus:
Cincinnati
Dukane
Edwards
Faraday
WS*, *D-8, *D-10, *D-12 Series
24SS* Series, 240* Series
Honeywell
Lathem
National Time
Simplex
®
& IBM
*010 & *012 Series
2315*, 2316*, 2335*, 2336*, 2380*, 2382*, 2310*, 2320*, 2330*, 2313*, 2314*, 2333*,
1310 through 1431 Series and 2420* through 2431* Series
ST402A* Series
Type SS* Series
*EX-HH and *EX-LL Series
77* Series, 82* Series, 2310 – 92* Series, 6310 – 92* Series
*Indicates more numbers before or after.
ORDERING INFORMATION
Part # Description
U45BHAA?04 10" Rd Flush, Black Sand 120vac
U45BHBA?04 10" Rd Flush, Black Sand 24vac
U55BHAA?04 12" Rd Flush, Black Sand 120vac
U55GHAA?04 12" Rd Flush, Steel Gray 120vac
U55BHBA?04 12" Rd Flush, Black Sand 24vac
U55GHBA?04 12" Rd Flush, Steel Gray 24vac
U58BHAA?04 12" Sq Flush, Black Sand 120vac
U58BHBA?04 12" Sq Flush, Black Sand 24vac
U65BHAA?04 15" Rd Flush, Black Sand 120vac
U65BHBA?04 15" Rd Flush, Black Sand 24vac
BEZEL FINISHES
Black Sand=BH
Matte finish
Steel Gray=GH
Smooth satin finish 12" round only
Note:
Replace the ? in the part number with the number from the list below that will correspond with the system you’re replacing.
New flush mount installations require backboxes.
0 = Faraday
7 = 2-hook
1 = National
8 = Setco
5 = Simplex
®
9 = R&H (keyhole)
6 = Cincinnati/Edwards
For a plexiglass crystal, replace the BH or GH in the part number with BG or GG.
Steel flush mount
A
B
Steel
OUTSIDE DIMENSIONS
Round
“A” Dimensions:
11
1
⁄
4
" for 10" clocks
13
1
⁄
4
" for 12" clocks
16" for 15" clocks
“B” Dimensions:
1
5
⁄
8
" for 10", 12" & 15" clocks
B
Flush mount steel square
A
B
Surface mount steel square
OUTSIDE DIMENSIONS
Square (12" only)
“A” Dimensions:
12
5
⁄
8
" for 12" clocks
A
“B” Dimensions:
1
1
⁄
4
" for 12" clocks
B
At American Time, we continually strive to improve our products to meet our customers’ needs and to provide the best possible value. The above specifications are believed to be correct, are subject to change without notice and may otherwise vary from the above. Please call if you need verification of any specifications or the suitability of a particular product for a particular application.
© American Time
Page 2 of 2 PS03010 Rev H
21
AllSync Plus Clock Specifications
AllSync Plus
®
Flush Molded Case
®
AllSync Plus Clock Installation
& Operation Manual
FEATURES
•
5 Year Warranty
• Microprocessor controlled movement
• 15 minutes of backup power (no batteries required)
• Accuracy to within ±1 second of a master clock
• Reduced power consumption
• Attractive modern design
• Impact-resistant black plastic case
• Shatter-resistant polycarbonate crystal
• Diagnostic LED
General Operation
DESCRIPTION
The
american time
™
AllSync Plus clocks are provided in round only high impact black plastic cases with clear polycarbonate crystals and bold, black numerals and minute markers on a non-yellowing white dial. Stylish hour and minute hands are aluminum with a black finish and a red sweep hand. Other bezel colors available. Consult factory.
AllSync Plus clocks are designed to work with multiple master clocks and correction signals. This unit is programmed to identify the signal it receives from the master and operate as that style of clock. Changing clock operation from one style to another is as easy as unplugging the clock from one system and plugging it into another. If needed, changing the placement of 2 small jumpers on the circuit board can change the voltage required to run this clock from 120vac to 24vac or 24vac to 120vac. This clock provides 15 minutes of backup run power without the use of batteries. If a power outage should last longer than 15 minutes, the clock will synchronize to the master clock at the hourly and 12 hour correction cycles.
Correction Signals
Works on:
• Hourly correction: 7-9 seconds starting at the 57th minute and 54th second. 12 hour correction: 13-18 seconds starting at
5:57:54 (am and pm).
• Hourly correction: 24-28.5 seconds starting at the 0 minute and 0 second. 12 hour correction: 24-32 minutes starting at
6:00:00 (am and pm).
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 10 pulses of 94-96 seconds starting at 5:05:00 (am and pm) and repeating every 2 minutes.
• Hourly correction: 24-26 seconds starting at 0 minute and 0 second. 12 hour correction: 25 pulses of 24-26 seconds starting at 6:00:00 (am and pm) and repeating every 60 seconds.
• Hourly correction: 63-67 seconds starting at the 58th minute and 0 second. 12 hour correction: 14 pulses of 63-67 seconds starting at 5:06:00 (am and pm) and repeating every 2 minutes.
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 12 pulses of 63-67 seconds starting at 5:05:00 (am and pm) repeating every 90 seconds.
*Note:
When switching between these correction protocols, you must use a different correction protocol to complete the transition.
The AllSync Plus clock needs to distinguish between hourly corrections before it can change correction protocols internally.
22
140 3rd St. S, PO Box 707, Dassel, MN 55325
800-328-8996 • american-time.com
Page 1 of 2 PS03011 Rev J
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock Specifications
SPECIFICATIONS
• 24vac/60 Hz or 120vac/60 Hz
• Current draw: 24vac, 1 watt, .043 amps
120vac, 3 watts, .028 amps
GENERAL
Types of secondary clocks compatible with AllSync Plus:
Maximum operating voltage: 24vac setting = 40vac
120vac setting = 150vac
Minimum operating voltage: 24vac setting = 15vac
120vac setting = 50vac
Cincinnati
Dukane
Edwards
Faraday
Honeywell
Lathem
National Time
WS*, *D-8, *D-10, *D-12 Series
24SS* Series, 240* Series
*010 & *012 Series
2315*, 2316*, 2335*, 2336*, 2380*, 2382*, 2310*, 2320*, 2330*, 2313*, 2314*, 2333*,
1310 through 1431 Series and 2420* through 2431* Series
ST402A* Series
Type SS* Series
*EX-HH and *EX-LL Series
Simplex
®
& IBM 77* Series, 82* Series, 2310 – 92* Series, 6310 – 92* Series
*Indicates more numbers before or after.
ORDERING INFORMATION
Part # Description
U45BAAA?04 10" Rd Flush 120vac
U45BABA?04 10" Rd Flush 24vac
U55BAAA?04 12" Rd Flush 120vac
U55BABA?04 12" Rd Flush 24vac
U65BAAA?04 15" Rd Flush 120vac
U65BABA?04 15" Rd Flush 24vac
Note:
Replace the ? in the part number with the number from the list below that will correspond with the system you’re replacing.
New flush mount installations require backboxes.
0 = Faraday 1 = National
7 = 2-hook 8 = Setco
5 = Simplex
®
6 = Cincinnati/Edwards
9 = R&H (keyhole)
Flush mount plastic
A
B
Surface mount plastic
OUTSIDE
DIMENSIONS
FLUSH MOUNT
SIZE A
10"
B
9
7
⁄
8
" 1
3
⁄
8
"
12" 13
1
⁄
4
" 2"
15" 16" 2"
B
At American Time, we continually strive to improve our products to meet our customers’ needs and to provide the best possible value. The above specifications are believed to be correct, are subject to change without notice and may otherwise vary from the above. Please call if you need verification of any specifications or the suitability of a particular product for a particular application.
© American Time Page 2 of 2 PS03011 Rev J
23
AllSync Plus Clock Specificatios
AllSync Plus
®
Dual Motor
Metal Case
®
AllSync Plus Clock Installation
& Operation Manual
24
General Operation
FEATURES
•
5 Year Warranty
• UL/cUL Listed - 12" and 15" surface mount only
• Microprocessor controlled movement
• 15 minutes of backup power (no batteries required)
• Accuracy to within ±1 second of a master clock
• Reduced power consumption
• Attractive modern design
• Heavy-duty construction
• All metal case
• Diagnostic LED
DESCRIPTION
The
american time
™
AllSync Plus clocks are provided in round or square metal cases with glass crystals and bold, black numerals and minute markers on a non-yellowing white dial. Stylish hour and minute hands are aluminum with a black finish and a red sweep second hand.
The
american time
™
AllSync Plus clock is designed to work with multiple master clocks and correction signals. This unit is programmed to identify the signal it receives from the master and operate as that style of clock. Changing clock operation from one style to another is as easy as unplugging the clock from one system and plugging it into another. If needed, changing the placement of 2 small jumpers on the circuit board can change the voltage required to run this clock from
120vac to 24vac or 24vac to 120vac. This clock provides 15 minutes of backup run power without the use of batteries. If a power outage should last longer than 15 minutes, the clock will synchronize to the master clock at the hourly and 12 hour correction cycles.
Correction Signals
Works on:
• Hourly Correction: 28.75-35 seconds starting at the 59th minute and 30th second. 12 hour correction: 13 minutes and 52 seconds-18 minutes and 8 seconds starting at 5:12:00 (am and pm). Note: This protocol switches off the run line during the hourly correction.
ORDERING INFORMATION
Part # Description
U45BHGA404 10" Rd Surface
U45BHGA?04 10" Rd Flush
U54BHGA404 12" Rd Surface
U55BHGA?04 12" Rd Flush
U57BHGA404 12" Sq Surface
U58BHGA?04 12" Sq Flush
U64BHGA404 15" Rd Surface
U65BHGA?04 15" Rd Flush
120vac
120vac
120vac
120vac
120vac
120vac
120vac
120vac
U53BHGA204 12" Rd Double dial wall 120vac
U52BHGA204 12" Rd Double dial ceiling 120vac
U51BHGA204 12" Sq Double dial wall 120vac
U50BHGA204 12" Sq Double dial ceiling 120vac
Part # Description
U45BHHA404 10" Rd Surface
U45BHHA?04 10" Rd Flush
U54BHHA404 12" Rd Surface
U55BHHA?04 12" Rd Flush
U57BHHA404 12" Sq Surface
U58BHHA?04 12" Sq Flush
U64BHHA404 15" Rd Surface
U65BHHA?04 15" Rd Flush
U53BHHA204 12" Rd Double dial wall 24vac
U52BHHA204 12" Rd Double dial ceiling 24vac
U51BHHA204 12" Sq Double dial wall 24vac
U50BHHA204 12" Sq Double dial ceiling 24vac
24vac
24vac
24vac
24vac
24vac
24vac
24vac
24vac
U63BHGA204 15" Rd Double dial wall 120vac
U62BHGA204 15" Rd Double dial ceiling 120vac
U63BHHA204 15" Rd Double dial wall 24vac
U62BHHA204 15" Rd Double dial ceiling 24vac
Note:
Replace the ? in the part number with the number from the list below that will correspond with the system you’re replacing.
New flush mount installations require backboxes.
0 = Faraday
7 = 2-hook
1 = National
8 = Setco
5 = Simplex
®
6 = Cincinnati/Edwards
9 = R&H (keyhole)
Also available in Steel Gray. Replace the BH in part number with GH - i.e. U54BHGA404 to U54GHGA404
140 3rd St. S, PO Box 707, Dassel, MN 55325
800-328-8996 • american-time.com
Page 1 of 2
PS03046 Rev G
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock Specifications
SPECIFICATIONS
• 24vac/60 Hz or 120vac/60 Hz
• Current draw: Single dial:
24vac, 1 watt, .043 amps
120vac, 3 watts, .028 amps
Double dial:
24vac, 2 watt, .086 amps
120vac, 6 watts, .056 amps
Maximum operating voltage: 24vac setting = 40vac
120vac setting = 150vac
Minimum operating voltage: 24vac setting = 15vac
120vac setting = 50vac
GENERAL
Types of secondary clocks compatible with AllSync Plus:
American Time X* Series
Standard
™
Electric CR & GRC 109106 through 109155 Series and 105047 through 105066 Series
*Indicates more numbers before or after.
Steel flush mount
Steel surface mount
BEZEL
FINISHES
Black Sand=BH
Matte finish
Steel Gray=GH
Smooth satin finish
12" round only
Wall mount round steel double dial
B
A
Flush mount steel square
A
B
A
B
Wall mount steel square double dial mechanical
A
B
Ceiling mount round steel double dial
B
Surface mount steel square
A
B
A
Ceiling mount steel square double dial mechanical
OUTSIDE DIMENSIONS
“A” Dimensions: Surface
11
1
⁄
4
" for 10" clocks
13
1
⁄
4
" for 12" clocks
16
1
⁄
4
" for 15" clocks
“B” Dimensions: Surface
2
1
⁄
4
" for 10", 12" & 15" clocks
“A” Dimensions: Flush
11
1
/
4
" for 10" clocks
13
1
⁄
4
" for 12" clocks
16" for 15" clocks
“B” Dimensions: Flush
1
5
⁄
8
" for 10", 12" & 15" clocks
“A” Dimensions: Double dial
13
1
⁄
4
" for 12"clocks
16
1
⁄
4
" for 15" clocks
“B” Dimensions: Double dial
16
7
⁄
8
" for 12"clocks
19
7
⁄
8
" for 15" clocks
OUTSIDE DIMENSIONS
Square (12" only)
“A” Dimensions: Surface
12
5
⁄
8
" for 12" clocks
“B” Dimensions: Surface
3
1
⁄
4
" for 12" clocks
“A” Dimensions: Flush
12
5
⁄
8
" for 12" clocks
“B” Dimensions: Flush
1
1
⁄
4
" for 12" clocks
“A” Dimensions: Double dial
12
5
⁄
8
" for 12" clocks
“B” Dimensions: Double dial
17
1
⁄
8
" for 12" clocks
A
B
B
Double dial mounting requires a 4" square electrical box in the wall or ceiling.
A
At American Time, we continually strive to improve our products to meet our customers’ needs and to provide the best possible value. The above specifications are believed to be correct, are subject to change without notice and may otherwise vary from the above. Please call if you need verification of any specifications or the suitability of a particular product for a particular application.
Steel square double dial profile
© American Time
Page 2 of 2 PS03046 Rev G
25
C
AllSync Plus Clock Specifications
AllSync Plus
®
Dual Motor
Molded Case
®
AllSync Plus Clock Installation
& Operation Manual
FEATURES
•
5 Year Warranty
• UL/cUL Listed - 12" surface mount only
• Microprocessor controlled movement
• 15 minutes of backup power (no batteries required)
• Accuracy to within ±1 second of a master clock
• Reduced power consumption
• Attractive modern design
• Impact-resistant black plastic case
• Shatter-resistant safety crystal
• Diagnostic LED
26
General Operation
DESCRIPTION
The
american time
™
AllSync Plus clocks are provided in
round only high impact black plastic cases with clear polycarbonate crystals and bold, black numerals and minute markers on a non-yellowing white dial. Stylish hour and minute hands are aluminum with a black finish and a red sweep hand. Other bezel colors available. Consult factory.
The
american time
™
AllSync Plus clock is designed to work with multiple master clocks and correction signals. This unit is programmed to identify the signal it receives from the master and operate as that style of clock. Changing clock operation from one style to another is as easy as unplugging the clock from one system and plugging it into another. If needed, changing the placement of 2 small jumpers on the circuit board can change the voltage required to run this clock from
120vac to 24vac or 24vac to 120vac. This clock provides 15 minutes of backup run power without the use of batteries. If a power outage should last longer than 15 minutes, the clock will synchronize to the master clock at the hourly and 12 hour correction cycles.
Correction Signals
Works on:
• Hourly Correction: 28.75-35 seconds starting at the 59th minute and 30th second. 12 hour correction: 13 minutes and 52 seconds-18 minutes and 8 seconds starting at 5:12:00 (am and pm). Note: This protocol switches off the run line during the hourly correction.
ORDERING INFORMATION
U44BAGA904 10" Rd Surface 120vac
U45BAGA?04 10" Rd Flush 120vac
Description
U44BAHA904 10" Rd Surface 24vac
U45BAHA?04 10" Rd Flush 24vac
U54BAGA304 12" Rd Surface 120vac
U55BAGA?04 12" Rd Flush 120vac
U54BAHA304 12" Rd Surface 24vac
U55BAHA?04 12" Rd Flush 24vac
U53BAGA204 12" Rd Double dial wall 120vac
U52BAGA204 12" Rd Double dial ceiling 120vac
Note:
Double dial mounting requires a 4" square electrical box in the wall or ceiling.
Surface clocks have a molded in hanger in the plastic cases.
U53BAHA204 12" Rd Double dial wall 24vac
U52BAHA204 12" Rd Double dial ceiling 24vac
12" surface clocks come complete with security bracket
Replace the ? in the part number with the number from the list below that will correspond with the system you’re replacing.
New flush mount installations require backboxes.
0 = Faraday 1 = National
7 = 2-hook 8 = Setco
5 = Simplex
®
6 = Cincinnati/Edwards
9 = R&H (keyhole)
140 3rd St. S, PO Box 707, Dassel, MN 55325
800-328-8996 • american-time.com
Page 1 of 2 PS03047 Rev G
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock Specifications
SPECIFICATIONS
• 24vac/60 Hz or 120vac/60 Hz
• Current draw: Single dial:
24vac, 1 watt, .043 amps
120vac, 3 watts, .028 amps
Double dial:
24vac, 2 watt, .086 amps
120vac, 3 watts, .056 amps
Maximum operating voltage: 24vac setting = 40vac
120vac setting = 150vac
Minimum operating voltage: 24vac setting = 15vac
120vac setting = 50vac
GENERAL
Types of secondary clocks compatible with AllSync Plus:
American Time X* Series
Standard
™
Electric CR & GRC 109106 through 109155 Series and 105047 through 105066 Series
*Indicates more numbers before or after.
Flush mount plastic
A
A
OUTSIDE DIMENSIONS
Surface
Flush
SIZE A B
Flush mount plastic
10" 9
7
⁄
8
" 1
3
⁄
8
"
12" 13
1
⁄
4
" 2"
Surface
SIZE A B
10" 10
3
⁄
8
" 2
1
⁄
2
"
12" 13
1
⁄
4
" 2
1
⁄
2
"
A
Surface mount plastic
A
B
Double Dial
SIZE A B C
12" 13
1
⁄
4
" 15" 8
5
⁄
8
"
Double Dial 12" only
Wall mount plastic double dial
B
Ceiling mount plastic double dial
B
A
B
B
A
Plastic double dial profile
C
At American Time, we continually strive to improve our products to meet our customers’ needs and to provide the best possible value. The above specifications are believed to be correct, are subject to change without notice and may otherwise vary from the above. Please call if you need verification of any specifications or the suitability of a particular product for a particular application.
Page 2 of 2 PS03047 Rev G
© American Time
27
AllSync Plus Clock Specifications
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus
®
Surface and Double Dial Metal Case
®
General Operation
FEATURES
•
5 Year Warranty
• UL Listed - 12" and 15" round, surface mount only
• Microprocessor controlled movement
• 15 minutes of backup power (no batteries required)
• Accuracy to within ±1 second of a master clock
• Reduced power consumption
• Attractive modern design
• Heavy-duty construction
• All metal case
• Diagonostic LED
• Optional plexiglass crystal available
DESCRIPTION
The
american time
™
AllSync Plus clocks, with are provided in round or square metal cases with glass crystals and bold, black numerals and minute markers on a non-yellowing white dial. Stylish hour and minute hands are aluminum with a black finish and a red sweep second hand.
The
american time
™
AllSync Plus clock is designed to work with multiple master clocks and correction signals. This unit is programmed to identify the signal it receives from the master and operate as that style of clock. Changing clock operation from one style to another is as easy as unplugging the clock from one system and plugging it into another. If needed, changing the placement of 2 small jumpers on the circuit board can change the voltage required to run this clock from 120vac to 24vac or
24vac to 120vac. This clock provides 15 minutes of backup run power without the use of batteries. If a power outage should last longer than 15 minutes, the clock will synchronize to the master clock at the hourly and 12 hour correction cycles.
Correction Signals
Works on:
• Hourly correction: 7-9 seconds starting at the 57th minute and 54th second. 12 hour correction: 13-18 seconds starting at
5:57:54 (am and pm).
• Hourly correction: 24-28.5 seconds starting at the 0 minute and 0 second. 12 hour correction: 24-32 minutes starting at 6:00:00
(am and pm).
•
*Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 10 pulses of 94-96 seconds starting at 5:05:00 (am and pm) and repeating every 2 minutes.
• Hourly correction: 24-26 seconds starting at 0 minute and 0 second. 12 hour correction: 25 pulses of 24-26 seconds starting at
6:00:00 (am and pm) and repeating every 60 seconds.
• Hourly correction: 63-67 seconds starting at the 58th minute and 0 second. 12 hour correction: 14 pulses of 63-67 seconds starting at 5:06:00 (am and pm) and repeating every 2 minutes.
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 12 pulses of 63-67 seconds starting at 5:05:00 (am and pm) repeating every 90 seconds.
*Note:
When switching between these correction protocols, you must use a different correction protocol to complete the transition. The
AllSync Plus clock needs to distinguish between hourly corrections before it can change correction protocols internally.
28
140 3rd St. S, PO Box 707, Dassel, MN 55325
800-328-8996 • american-time.com
Page 1 of 2 PS03058 Rev D
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock Specifications
SPECIFICATIONS
• 24vac/60 Hz or 120vac/60 Hz
• Current draw: Single dial:
24vac, 1 watt, .043 amps
120vac, 3 watts, .028 amps
Double dial:
24vac, 2 watts, .086 amps
Maximum operating voltage: 24vac setting = 40vac
110vac setting = 150vac
Minimum operating voltage: 24vac setting = 15vac
110vac setting = 50vac
BEZEL
FINISHES
GENERAL
120vac, 6 watts, .056 amps
Types of secondary clocks compatible with AllSync Plus:
Cincinnati
Dukane
Edwards
Faraday
WS*, *D-8, *D-10, *D-12 Series
24SS* Series, 240* Series
*010 & *012 Series
2315*, 2316*, 2335*, 2336*, 2370*, 2372*, 2380*, 2382*, 2311*, 2320*, 2331*, 2314*,
1310 through 1431 Series and 2420* through 2431* Series
ST402A* Series Honeywell
Lathem
National Time
Type SS* Series
*EX-HH and *EX-LL Series
Simplex
®
& IBM 77* Series, 82* Series, 2310 – 92* Series, 6310 – 92* Series
*Indicates more numbers before or after.
ORDERING INFORMATION
Part # Description
U54BHAA404 12" Rd Surface 120vac
U54BHBA404 12" Rd Surface 24vac
U57BHAA404 12" Sq Surface 120vac
U57BHBA404 12" Sq Surface 24vac
Black Sand=BH
Matte finish
Steel Gray=GH
12" round only
Smooth satin finish
Part # Description
U53BHAA204 12" Rd Double dial wall 120vac
U53BHBA204 12" Rd Double dial wall 24vac
U52BHAA204 12" Rd Double dial ceiling 120vac
U52BHBA204 12" Rd Double dial ceiling 24vac
U64BHAA404 15" Rd Surface 120vac
U64BHBA404 15" Rd Surface 24vac
Notes: Replace the BH (Black Sand) in the part # with GH for a Steel Gray case. 10" & all square available in Black Sand only.
For a plexiglass crystal, replace the BH or GH in the part number with BG or GG. 10" & all square available in Black Sand only.
U51BHAA204 12" Sq Double dial wall 120vac
U51BHBA204 12" Sq Double dial wall 24vac
U50BHAA204 12" Sq Double dial ceiling 120vac
U50BHBA204 12" Sq Double dial ceiling 24vac
U63BHAA204 15" Rd Double dial wall 120vac
U63BHBA204 15" Rd Double dial wall 24vac
U62BHAA204 15" Rd Double dial ceiling 120vac
U62BHBA204 15" Rd Double dial ceiling 24vac
Steel flush mount
Flush mount steel square
A
A
B
B
Steel surface mount
Wall mount round steel double dial
Ceiling mount round steel double dial
A
OUTSIDE DIMENSIONS
Round
“A” Dimensions:
11
1
⁄
4
" for 10" clocks
13
1
⁄
4
" for 12" clocks
16
1
⁄
4
" for 15" clocks
“B” Dimensions:
2
1
⁄
4
" for 10", 12" & 15" clocks
B
A
B
A
B
Surface mount steel square
Wall mount steel square double dial mechanical
Ceiling mount steel square double dial mechanical
A
Square (12" only)
“A” Dimensions:
12
5
⁄
8
"
“B” Dimensions:
3
1
⁄
4
"
A
B
B
B
A
Double dial mounting requires a 4" square electrical box in the wall or ceiling.
Steel square double dial profile
At American Time, we continually strive to improve our products to meet our customers’ needs and to provide the best possible value. The above specifications are believed to be correct, are subject to change without notice and may otherwise vary from the above. Please call if you need verification of any specifications or the suitability of a particular product for a particular application.
Page 2 of 2 PS03058 Rev D
© American Time
29
C
AllSync Plus Clock Specifications
AllSync Plus
®
Surface and Double Dial
Molded Case
®
AllSync Plus Clock Installation
& Operation Manual
FEATURES
•
5 Year Warranty
• UL Listed - 12" surface mount only
• Microprocessor controlled movement
• 15 minutes of backup power (no batteries required)
• Accuracy to within ±1 second of a master clock
• Reduced power consumption
• Attractive modern design
• Impact-resistant black plastic case
• Shatter-resistant polycarbonate crystal
• Diagnostic LED
General Operation
DESCRIPTION
The
american time
™
AllSync Plus clocks are provided in round only high impact black plastic cases with clear polycarbonate crystals and bold, black numerals and minute markers on a non-yellowing white dial. Stylish hour and minute hands are aluminum with a black finish and a red sweep hand. Other bezel colors available. Consult factory.
The
american time
™
AllSync Plus clock is designed to work with multiple master clocks and correction signals. This unit is programmed to identify the signal it receives from the master and operate as that style of clock. Changing clock operation from one style to another is as easy as unplugging the clock from one system and plugging it into another. If needed, changing the placement of 2 small jumpers on the circuit board can change the voltage required to run this clock from
120vac to 24vac or 24vac to 120vac. This clock provides 15 minutes of backup run power without the use of batteries. If a power outage should last longer than 15 minutes, the clock will synchronize to the master clock at the hourly and 12 hour correction cycles.
Correction Signals
Works on:
• Hourly correction: 7-9 seconds starting at the 57th minute and 54th second. 12 hour correction: 13-18 seconds starting at
5:57:54 (am and pm).
• Hourly correction: 24-28.5 seconds starting at the 0 minute and 0 second. 12 hour correction: 24-32 minutes starting at
6:00:00 (am and pm).
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 10 pulses of 94-96 seconds starting at 5:05:00 (am and pm) and repeating every 2 minutes.
• Hourly correction: 24-26 seconds starting at 0 minute and 0 second. 12 hour correction: 25 pulses of 24-26 seconds starting at 6:00:00 (am and pm) and repeating every 60 seconds.
• Hourly correction: 63-67 seconds starting at the 58th minute and 0 second. 12 hour correction: 14 pulses of 63-67 seconds starting at 5:06:00 (am and pm) and repeating every 2 minutes.
• *Hourly correction: 54-56 seconds starting at the 58th minute and 5th second. 12 hour correction: 12 pulses of 63-67 seconds starting at 5:05:00 (am and pm) repeating every 90 seconds.
*Note:
When switching between these correction protocols, you must use a different correction protocol to complete the transition.
The AllSync Plus clock needs to distinguish between hourly corrections before it can change correction protocols internally.
30
140 3rd St. S, PO Box 707, Dassel, MN 55325
800-328-8996 • american-time.com
Page 1 of 2 PS03059 Rev D
© American Time
AllSync Plus Clock Installation
& Operation Manual
AllSync Plus Clock Specifications
SPECIFICATIONS
• 24vac/60 Hz or 120vac/60 Hz
• Current draw: Single dial:
24vac, 1 watt, .043 amps
120vac, 3 watts, .028 amps
Double dial:
24vac, 2 watts, .086 amps
120vac, 6 watts, .056 amps
Maximum operating voltage: 24vac setting = 40vac
120vac setting = 150vac
Minimum operating voltage: 24vac setting = 15vac
120vac setting = 50vac
GENERAL
Types of secondary clocks compatible with AllSync Plus:
Cincinnati
Dukane
Edwards
Faraday
Honeywell
Lathem
National Time
WS*, *D-8, *D-10, *D-12 Series
24SS* Series, 240* Series
*010 & *012 Series
2315*, 2316*, 2335*, 2336*, 2370*, 2372*, 2380*, 2382*, 2311*, 2320*, 2331*, 2314*,
1310 through 1431 Series and 2420* through 2431* Series
ST402A* Series
Type SS* Series
*EX-HH and *EX-LL Series
Simplex
®
& IBM 77* Series, 82* Series, 2310 – 92* Series, 6310 – 92* Series
*Indicates more numbers before or after.
ORDERING INFORMATION
Part # Description
U44BAAA904 10" Rd Surface 120vac
U44BABA904 10" Rd Surface 24vac
Part # Description
U64BAAA304 15" Rd Surface 120vac
U64BABA304 15" Rd Surface 24vac
U54BAAA304 12" Rd Surface 120vac
U54BABA304 12" Rd Surface 24vac
U53BAAA204 12" Rd Double dial wall 120vac
U53BABA204 12" Rd Double dial wall 24vac
U52BAAA204 12" Rd Double dial ceiling 120vac
U52BABA204 12" Rd Double dial ceiling 24vac
U63BAAA204 15" Rd Double dial wall 120vac
U63BABA204 15" Rd Double dial wall 24vac
U62BAAA204 15" Rd Double dial ceiling 120vac
U62BABA204 15" Rd Double dial ceiling 24vac
Note:
Double dial mounting requires a 4" square electrical box in the wall or ceiling.
Surface clocks have a molded in hanger double dial
Flush mount plastic
Surface mount plastic
OUTSIDE DIMENSIONS
Surface
SIZE A B C
10" 10
3
⁄
8
" 2
1
⁄
2
" N/A
12" 13
1
⁄
4
" 2
1
⁄
2
" N/A
15" 16" 2
1
⁄
2
" N/A
Double Dial (12" & 15" only)
12" 13
1
⁄
4
" 15" 8
5
⁄
8
"
15" 16" 19
1
/
4
" 8
5
⁄
8
"
Wall mount plastic double dial
B
Ceiling mount plastic double dial
A
Note: 12" surface mount clocks include security bracket.
Plastic double dial profile
A
A
A
B
A
B
B
B
A
C
At American Time, we continually strive to improve our products to meet our customers’ needs and to provide the best possible value. The above specifications are believed to be correct, are subject to change without notice and may otherwise vary from the above. Please call if you need verification of any specifications or the suitability of a particular product for a particular application.
Plastic double dial profile
© American Time
Page 2 of 2 PS03059 Rev D
31
C
Appendix B - LED Indication
AllSync Plus Clock Installation
& Operation Manual
Note: LED indicator can be found on the back of the AllSync Plus clock on the side of the dust cover as indicated by the decal, or refer to picture on page 19.
Normal Operation:
Flashing Green (0.5 sec. ON – 0.5 sec OFF) = Microprocessor is sending an update to the movement.
Note: The movement requests the time from the circuit board after startup and at 2am, 8am, 2pm and 8pm as seen on the clock. During this request the circuit board will send the time to the movement. Each request will last approximately 3 minutes.
Flashing Red (0.5 sec. ON – 0.5 sec OFF) = Incorrect DIP switch settings or clock error.
General Operation
Note: If the LED is flashing red settings in the clock may be incorrect. Contact American Time Technical support for assistance at
800-328-8996.
Alternating Red and Green (0.5 sec Red – 0.5 sec. Green) = AllSync Plus circuit board receiving correction signal from master.
Both colors OFF 1 sec. = At the top of each minute the AllSync Plus clock LED will turn off at the 00 sec. and continue with normal operation at 01 sec.
Note: After the clock has had sufficient time to synchronize (the LED will remain green and the movement has crossed 8:00 or 2:00 on its face) this LED flashing off should match the second hand on the clock passing the top of the minute.
Continuous Red = Power is on and the AllSync Plus circuit board has not received a 12 hour correction in last 15 hours.
Note: If the AllSync Plus clock is installed in a clock system running a correction protocol different than 01
(factory) or its previously recognized protocol, it may require more than one 12 hour correction to adjust its internal clock. In this case the LED will remain red after one 12 hour correction.
Continuous Green = Power is on and the AllSync Plus circuit board has received at least one 12 hour correction in the last 15 hours.
32
© American Time
AllSync Plus Clock Installation
& Operation Manual
Startup diagnostics routine
1. 5 sec. – solid red only
2. 1 sec. – OFF
3. 1 sec. – Green (DIP Switch 1 ON) or Red (DIP Switch 1 OFF)
Or
4. 1 sec. – OFF
5. 1 sec. – Green (DIP Switch 2 ON) or Red (DIP Switch 2 OFF)
Or
6. 1 sec. – OFF
Appendix B - LED Indication
7. 1 sec. – Green (DIP Switch 3 ON) or Red (DIP Switch 3 OFF)
Or
8. 1 sec. – OFF
9. 1 sec. – Green (DIP Switch 4 ON) or Red (DIP Switch 4 OFF)
Or
10. 2 sec. – OFF
11. Continue with normal operation
Note: For normal operation all DIP switches should be on or green during the startup diagnostics.
Note: If the circuit board has not received power for over 30 minutes it may cycle through the startup diagnostics several times while the power cell is charging.
© American Time
33
Glossary
AllSync Plus Clock Installation
& Operation Manual
General Operation
Clock Protocol - A specific time and duration of a set of correction pulses sent from a master clock to synchronize a clock system. Through the development of clock systems many different clock system manufacturers designed their own clock protocols. For this reason clocks cannot generally move from one system to another unless the system has the same clock protocol. The AllSync Plus clock is designed to recognize many different clock protocols.
Cold Start - AllSync Plus operational state in which power is applied for the first time or after the clock has not had power for a sufficient amount of time to drain it to the point it resets its internal processor.
LED - Light Emitting Diode - Indicator light on the back of the AllSync Plus clock.
Master Clock - In a clock system, a device that acts as the source of time. The master clock transmits the time to any number of secondary (or slave) clocks.
Movement - The inner mechanism of an analog clock that moves the clock’s hands.
Secondary Clock - Also known as a slave clock, this is a clock that synchronizes its timekeeping to that of a connected master clock.
Synchronization - The process of bringing two clocks or time sources into phase so their difference is zero. In the case of a timekeeping system, time synchronization takes place between the master clock and all secondary clocks.
34
© American Time
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 6 Electrical Connections
- 7 Plastic Surface Mount Clock Installation
- 9 Metal Surface Mount Clock Installation
- 10 Metal Round Double Dial Clock Installation
- 12 Plastic Double Dial Clock Installation
- 13 Metal Square Double Dial Clock Installation
- 14 AllSync Plus Startup Routine
- 16 AllSync Plus accuracy
- 16 Movement corrections
- 17 Start Up Example Operation
- 20 AllSync Plus Flush Metal Case Specifications
- 22 AllSync Plus Flush Plastic Case Specifications
- 24 AllSync Plus Dual Motor Metal Case Specifications
- 26 AllSync Plus Dual Motor Plastic Case Specifications
- 28 AllSync Plus Surface & Double Dial Metal Case Specifications
- 30 AllSync Plus Surface & Double Dial Plastic Case Specifications