SECTION 3
Data Setting Console Operation
This section provides the basic operating procedures of the Data Setting Console including parameter settings and displays.
3-4-1 Table of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-2 How to Display and Set Parameter Data . . . . . . . . . . . . . . . . . . . . .
21
Operating Procedure
Section 3-1
3-1 Operating Procedure
After preparing the CPU Unit, follow the procedure below to use the Temperature Control Unit.
1,2,3...
1.
Set the switches on the front and rear panels according to the operating conditions. (Refer to
Set SW2-2 under the display cover to the OFF position to enable data setting from the Data Setting Console.
2.
Mount to Rack.
Turn OFF the PC power supply before mounting or dismounting the C200H on the Rack.
3.
Connect the input wiring. (Refer to
.)
The 24-VDC power supply must be connected. The Data Setting Console will not operate unless the 24-VDC power supply is connected. The sensors can be connected immediately before the system is tested.
4.
Connect the Data Setting Console. (Refer to
5.
Turn ON the 24-VDC power supply and the PC power supply.
Set the CPU Unit to PROGRAM mode.
6.
Set data from the Data Setting Console. (Refer to the rest of this section.)
Under either one of the following conditions (i.e., when control is stopped), the bank number can be changed to set data using the Data Setting Console.
• When SW203-5 on the rear panel is set to ON (to stop temperature control in PROGRAM mode) and the CPU Unit is set to PROGRAM mode.
• When the Stop Bit (word n+2, bit 06 for loop 1 and bit 04 for loop 2) is
ON.
In all other cases, the executed bank number (default value = 1) is displayed and the bank number cannot be changed from the Data Setting
Console. Change the executed bank number with a user program or with a device, such as the Programming Console.
7.
Test operation and adjust data. (Refer to the rest of this section.)
Connect the output wiring and turn on the heater power to start the test operation. Monitor the control conditions and adjust the data until the required control is achieved.
8.
Create the user programs. (Refer to
SECTION 4 PC Memory Allocation and Programming
Create the user programs for data setting, monitoring, and switching the bank number, as required. Set SW2-2 under the display cover to the ON position to enable data setting from the CPU Unit.
9.
Start operation.
22
Data Flow
3-2 Data Flow
Section 3-2
The data flow in the Temperature Control Unit is shown in the diagram below.
If SW2-2 is ON
Write
Temperature
Control Unit
I/O bus
Read
CS-series or
C200H CPU
Unit
Read Write If SW2-2 is OFF
Data Setting
Console
Data Settings from Data
Setting Console
The read operation and setting the executed bank number are possible from a user program or from a device, such as the Programming Console, regardless of the ON/OFF setting of SW2-2.
Data written from the Data Setting Console and data written with the
EEPROM write commands when SW2-1 (switching memory contents) is set to Normal are written to the Temperature Control Unit EEPROM and are consequently retained when the power supply is turned OFF.
Data written with RAM write commands when SW2-1 (switching memory contents) is set to Normal, the SP value set when SW2-1 (switching memory contents) is set to Fixed and executed bank number settings made from the CPU
Unit are written directly to RAM and are not saved to EEPROM. This data is lost when the power supply is turned OFF.
Set SW2-2 under the display cover to the OFF position to enable data setting from the Data Setting Console.
While Temperature Control Unit is in control operation, all data can be set using the specified executed bank number (default value = 1).
Change the executed bank number with a user program or with a device, such as the Programming Console. The executed bank number cannot be changed from the Data Setting Console.
Under either one of the following conditions (i.e., when control is stopped), the bank number can be changed to set data using the Data Setting Console.
• When SW203-5 on the rear panel is set to ON (to stop temperature control in the PROGRAM mode) and the CPU Unit is set to PROGRAM mode.
23
Nomenclature and Features
Section 3-3
• When the Stop Bit (word n+2, bit 06 for Loop 1 and bit 04 for Loop 2) is
ON.
3-3 Nomenclature and Features
3-3-1 Nomenclature
Front View Side View
Data display
Operation indicators
Display for Cam
Positioner
Cover
Display Key
(With cover open)
Level Key
Down Key
Up Key
Operation keys
Select parameters
Set data
Switch Loops
Loop Key
Temperature Control Unit connector
Connecting cable (sold separately)
C200H-CN225 (2 m)
C200H-CN425 (4 m)
Panel mounting bracket
(Refer to
Appendix D Dimensions for details about panel mounting.)
Rear View
The bottom row of the operation keys have upper and lower labels. The upper labels apply to Temperature Control Unit operation. The lower labels are for the Cam Positioner Unit.
Two display sheets are supplied: one for the Temperature Control Unit and one for the Cam Positioner Unit. If the Data Setting Console is to be used with the Temperature Control Unit only, stick the display sheet for the Temperature
Control Unit.
24
Nomenclature and Features
Section 3-3
3-3-2 Features
Data Display
Name Function
PV (Process Value) Displays the PV or the parameter symbol selected with the
Level or Display Key (Refer to next page).
SV (Set Value) Displays the SV or setting/monitored data corresponding to the parameter symbol selected with the Level, Display or Loop
Keys and indicated in the PV display. Displays the SP when the PV is indicated in the PV display.
BK (Bank Number) Displays the executed bank number. Displays the bank number of the displayed data when temperature control is interrupted. (See note.)
Note Temperature control is interrupted when SW203-5 on the rear panel is set to
ON and also the CPU Unit is set to PROGRAM mode, or when the Stop Bit
(word n+2, bit 06 for loop 1 and bit 04 for loop 2) is ON.
Operation Indicators
Name Function
LOOP2
OUT (Output)
Indicates whether the displayed settings relate to Loop 1 or Loop
2. Press the Loop Key and hold down for approximately 2 seconds to switch between Loop 1 and Loop 2.
Indicator OFF:Loop 1
Indicator ON: Loop 2
Turns ON when the output is ON for transistor output or voltage output types.
AT (Auto-tuning) Blinks at approximately 1 second intervals during auto-tuning.
These indicators relate to the currently displayed loop.
HB (Heater
Burnout)
Turns ON to indicate a heater burnout alarm.
ALM1 (Alarm) Turns ON to indicate the temperature is in the alarm range set with Alarm SV 1
(upper- and lower-limit alarm). Refer to the following page.
Display Patterns
Note The Data Setting Console will not operate unless a 24-VDC power supply is connected to the Temperature Control Unit input terminals.
Display Pattern 1 Display Pattern 2
Process value
Executed bank number or displayed bank number
Indicator OFF: Loop 1
Indicator ON: Loop 2
Set point
Executed bank number or displayed bank number
Indicator OFF: Loop 1
Indicator ON: Loop 2
Parameter symbol
SV (Set value)
Monitored value
Execution status
25
Parameter Displays and Settings
Operation Keys
Name
Level Key
Display Key
Loop Key
Up Key
Down Key
Section 3-4
Function
The parameter items are divided into three display groups (Refer to display levels 0 to 2 on the next page). Press this key to switch from one group to another. The display levels automatically cycle in the sequence 0 –> 1 –> 2 –> 0 when the key is held down for approximately 2 seconds.
Press this key to select the required parameter from the selected display level 0 to 2 (Refer to table below).
The parameters cycle automatically when the key is held down.
Press this key for approximately two seconds to switch between
Loop 1 and Loop 2.
Press this key to increment SV.
The SV increment continuously while the key is held down. The
SV display blinks when the value reaches its maximum limit.
Press this key to decrement an SV.
The SV decreases continuously while the key is held down. The
SV display blinks when the value reaches its minimum limit.
3-4 Parameter Displays and Settings
3-4-1 Table of Parameters
0
Display level
Parameter
Set point
1
Bank number
Alarm SV 1 (see note 4)
Alarm SV 2 (see note 4)
Input shift value
Proportional band
(see note 1)
Integral (reset) time (see note 1)
Derivative (rate) time (see note 1)
SP lower limit
SP upper limit
Display symbol
Write Read Loop no.
Bank no.
Data range
---
Yes Yes Yes Yes SP lower limit to
SP upper limit
Default value Page
0
°
C
bk
See note 5
Yes Yes No 1 to 8 1
al-1
Yes Yes Yes Yes Alarm mode 0
°
C
al-2
Yes Yes Yes Yes
TC 1, 4, 5:
0
°
to 9999
°
C
Other TCs:
–999
°
to 9999
°
C
0
°
C
Pt 1, 4, 5:
0.0
°
to 999.9
°
C
Other Pts:
–99.9
°
to 999.9
°
C
in-5
Yes Yes Yes Yes –99.9
°
to 999.9
°
C 0.0
°
C
p
Yes Yes Yes Yes 0.0
°
to 999.9
°
C 40.0
°
C
i d sl-l sl-h
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
0 to 9999 s
0 to 9999 s
240 s
40 s
Sensor measuring range lower limit to (SP upper limit – 1 digit)
(Sensor measuring range lower limit + 1 digit) to
SP upper limit
TC: –200
°
C
Pt: –99.9
°
C
TC: 1,300
°
C
Pt: 450.0
°
C
26
Parameter Displays and Settings
Section 3-4
1
Display level
Parameter
Control period
(see note 1 and 3)
Hysteresis (see note 2)
Alarm hysteresis
(see note 4)
Heater current monitor (see note 3)
Heater burnout current (see note 3)
2
Display symbol
Write Read Loop no.
Bank no.
cp
Yes Yes Yes No
Data range
1 to 99 s
hys hysa ct hb o
Yes
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
0.0
°
to 999.9
°
C
Default value Page
20 s
0.8
°
C
0.0
°
to 999.9
°
C 0.2
°
C
0.0 to 5.5 A ---
0.0 to 5.0
0.0: No heater burnout detection, alarm signal OFF
0.0 A
5.0: No heater burnout detection, alarm signal ON
0.0% to 100.0% ---
Control output variable monitor
Auto-tuning start/ stop (see note 1)
Copy bank
Sensor-type monitor
Alarm 1 mode
Alarm 2 mode
at bcpy in-t alt1 alt2
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
No
No
---
---
0 to 9
0 to 9
Mode for Alarm
SV 1/2 (0: no alarm)
---
---
Setting for
SW202
2
2
Note
Yes: Possible.
No: Not possible or not required.
1.
Only when PID control with feed-forward circuitry is selected
2.
Only when ON/OFF control is selected.
3.
Does not apply to current output.
4.
Does not apply when Alarm Mode = 0
5.
Under either one of the following conditions (i.e., when control is stopped), the bank number can be changed to set data using the Data Setting Console.
• When SW203-5 on the rear panel is set to ON (to stop temperature control in the PROGRAM mode) and the CPU Unit is set to PRO-
GRAM mode.
• When the Stop Bit (word n+2, bit 06 for loop 1 and bit 04 for loop 2) is
ON.
In all other cases, the executed bank number (default value = 1) is displayed and the bank number cannot be changed from the Data Setting
Console. Change the executed bank number with a user program or with a device, such as the Programming Console.
6.
Thermocouple = TC
Platinum Resistance Thermometer = Pt
27
Parameter Displays and Settings
3-4-2 How to Display and Set Parameter Data
PV and SV (Display Level 0)
Section 3-4
PV Process value (monitored every 500 ms)
SV
Currently set set value. Units:
°
C or
°
F. The SV can be changed from this display.
Valid SV Range
Set the SV in the range between the SV lower limit and the SV upper limit.
Error Display
When a sensor error occurs, one of the codes below and the detected temperature blink alternately in the PV display.
ser1 ser2
Temperature is out of the range: (sensor measurement range
±
10%FS).
That is, 10%FS below the lower limit or 10%FS above the upper limit.
Includes broken or incorrect sensor wiring.
ser1 : Loop 1; ser2 : Loop 2
serr
Abnormality in the cold junction compensating circuit. Applies to thermocouple type only.
SP Lower Limit (Display Level 1)
PV SP lower limit parameter symbol
SV
Currently set SV lower limit. Units:
°
C or
°
F.
The SV lower limit can be changed from this display.
When the sensor type is set with SW202 on the rear of the Unit, the SV lower limit is automatically set to the measuring range lower limit of the selected sensor, as shown below. However, the SP lower limit cannot be changed if the current SV lies inside the sensor measuring range.
Default values TC: –200
°
C
Pt: –99.9
°
C
Change the set limit, if required. Set the lower limit in the following range:
Sensor measuring range lower limit to (SP upper limit – 1 digit)
The SV and “----” blink alternately on the display if the SP lower limit is set outside the limit defined above to indicate that the value is out-of-range. Reset the SP lower limit inside the permitted range.
SP Upper Limit (Display Level 1)
PV SP upper limit parameter symbol
SV
Currently set SV upper limit. Units:
°
C or
°
F.
The SV upper limit can be changed from this display.
When the sensor type is set with SW202 on the rear of the Unit, the SV upper limit is automatically set to the measuring range upper limit of the selected sensor, as shown below. However, the SP upper limit cannot be changed if the current SV lies inside the sensor measuring range.
Default values TC: 1300
°
C
Pt: 450.0
°
C
Change the set limit, if required. Set the upper limit in the following range:
(Sensor measuring range lower limit + 1 digit) to SP upper limit
28
Parameter Displays and Settings
Section 3-4
The SV and “----” blink alternately on the display if the SP upper limit is set outside the limit defined above to indicate that the value is out-of-range. Reset the SP upper limit inside the permitted range.
Alarms SV 1 and SV 2 (Display Level 0)
PV
SV
Alarm 1/2 parameter symbol
Currently set alarm value. Units: C or F. The setting can be changed from this display. The alarm mode is set with the Alarm 1/2 Mode parameter described on the following page.
Two alarm SVs can be set for each loop and bank.
Alarm 1 and Alarm 2 Modes (Display Level 2)
PV
Alarm 1/2 Mode parameter symbol
SV
Currently set alarm mode.
The setting can be changed from this display.
Two alarm modes can be set for each loop.
Alarm
Mode
Alarm Type
0
Alarm Range
SP
0 No alarm
1 Upper- and lower-limit alarm x x
7
8
9
5
6
2
3
4
Upper-limit alarm
Lower-limit alarm
Upper- and lower-limit range alarm
Upper- and lower-limit alarm with standby sequence
Upper-limit alarm with standby sequence
Lower-limit alarm with standby sequence
Absolute-value upper-limit alarm
Absolute-value lower-limit alarm x x x x x x x x x x
29
Parameter Displays and Settings
Section 3-4
About the Standby Sequence
Select the standby sequence to avoid an alarm output immediately after power is turned ON where the value is in the alarm range. The standby sequence recognizes that the value is out of the alarm range and then outputs an alarm when the value enters the alarm range once more.
Lower Limit Alarm with Standby Sequence
Hysteresis
OFF point
Standby sequence cancel point
Alarm SV
0
°
C
Alarm output
The standby sequence is restarted in the following situations.
• When SV is changed.
• When executed bank number is changed.
• When alarm mode is changed.
• When PC power supply is turned ON.
• When restart flag is set ON.
• When PROGRAM mode is switched to MONITOR or RUN while the control interrupt is set (SW203-5 is ON).
• When the Stop Bit (word n+2, bit 06 or 04) goes OFF.
Alarm Hysteresis (Display Level 1)
PV
Alarm hysteresis parameter symbol
SV
Current setting. Units:
°
C or
°
F.
The setting can be changed from this display.
A hysteresis band is provided to prevent chattering of the alarm output when the alarm output is turned from ON to OFF.
Hysteresis bandwidth Hysteresis bandwidth
ON
OFF
ON
OFF
Input Input
Alarm SV Alarm SV
The alarm output is OFF if the process value lies within the hysteresis band when the Unit is turned on.
Heater Burnout Current (Display Level 1)
PV
SV
Heater burnout current parameter symbol
Currently set heater burnout current value. Units:
Amperes (A).
The setting can be changed from this display.
30
Parameter Displays and Settings
Section 3-4
Set the heater burnout current value in the range shown in the table below.
Refer to Appendix C Heater Burnout Detection for more details about the alarm SVs.
0.0
No heater burnout detection. Alarm signal OFF.
0.1 to 4.9
Within heater burnout current SV range.
5.0
No heater burnout detection. Alarm signal ON.
Heater Current Monitor (Display Level 1)
PV
SV
Heater current monitor parameter symbol
Currently set heater current value. Units: Amperes (A).
If the current exceeds 5.5 A, a CT Input Overflow error occurs and
BBBB is displayed.
Input Shift Value (Display Level 0)
PV
SV
Input shift value parameter symbol
Currently set input shift value. Units:
°
C or
°
F. The setting can be changed from this display.
If the displayed temperature value differs from the actual temperature value due to the sensor position or some other conditions, set the input shift value such that the correct temperature is displayed.
Control Period (Display Level 1)
PV Control period parameter symbol
SV
Currently set control period. Units: Seconds (s). The setting can be changed from this display.
The control period is the time required to complete one transistor output or voltage output ON/OFF cycle.
ON
OFF
ON time
Control period
Control Output Variable Monitor (Display Level 2)
PV
SV
Control output variable monitor parameter symbol
Current control output variable. Units: percentage (%).
The relationship between the control output variable and control period is defined by the formula below:
ON time
Control output variable (%) = x 100
Control period
The control output variable during ON/OFF control (when SW203-1 on the rear panel is ON) is ON = 100% and OFF = 0%.
31
Parameter Displays and Settings
Hysteresis (Display Level 1)
Section 3-4
PV Hysteresis parameter symbol
SV
Currently set hysteresis value. Units:
°
C or
°
F. The setting can be changed from this display.
Hysteresis is an operating band provided for ON/OFF operation to prevent output chattering (repeated ON/OFF switching) and eliminate noise influences.
Hysteresis
ON
OFF
SV
Hysteresis is applied in the following situations.
• When ON/OFF control is selected (SW203-1 is ON).
• When PID control with feed-forward circuitry (SW203-1 is OFF) and P
(proportional band) is 0.
Bank Number (Display Level 0)
PV
SV
Bank number parameter symbol
Currently set bank number.
During control operation: Executed bank number (default value = 1)
Control operation interrupted: Currently displayed bank number
Changing the Settings
The bank number can be changed from the Data Setting Console in the following situations.
• When the CPU Unit is set to PROGRAM mode and SW203-5 on the rear panel is set to ON to interrupt temperature control.
• When the Stop Bit (word n+2, bit 06 for loop 1 or bit 04 for loop 2) is ON.
When the above conditions are not met, the executed bank number cannot be changed from the Data Setting Console and the executed bank number
(default value = 1) is displayed. Change the executed bank number with a user program or with a device, such as the Programming Console.
Copy Bank (Display Level 2)
Copies the data, except for the SV (set value) data, from bank number 1 to banks 2 to 8.
PV
SV
Execute bank copy Bank being copied Bank copy completed
32
Parameter Displays and Settings
Sensor-type Monitor (Display Level 2)
PV
SV
Section 3-4
Sensor-type monitor parameter symbol
Sensor type currently set with SW202 on the rear panel. Number refers to the following if a platinum resistance thermometer is used:
0: JPt (OFF), 1: Pt (ON)
Auto-tuning Start/Stop (Display Level 2)
PV
AT
AT indicator blinks
SV
AT start Process value (PV)
Set point (SP)
AT executing
To interrupt, press the Level and Display Keys again to display at . When at appears, press the Up Key. On interrupt, the at display disappears and the process value is displayed.
Auto-tuning operates only when SW203-1 on the rear panel is set to OFF to enable PID control with feed-forward circuitry. When auto-tuning is completed, the AT indicator stops blinking and the P, I, and D data is written to EEPROM.
If necessary, the P, I, and D data can be changed as described in the following.
Proportional Band (Display Level 0)
PV
SV
Proportional Band parameter symbol
Currently set Proportional Band. Units:
°
C or
°
F. The setting can be changed from this display.
Integral (Reset) Time (Display Level 0)
PV
SV
Integral time parameter symbol
Currently set integral time. Units: second. The setting can be changed from this display.
Derivative (Rate) Time (Display Level 0)
PV
SV
Derivative time parameter symbol
Currently set derivative time. Units: second. The setting can be changed from this display.
33